The impact of distributed generation to the lightning protection of modern distribution lines

Similar documents
Lightning performance of a HV/MV substation

Lightning overvoltage and protection of power substations

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Electric Stresses on Surge Arrester Insulation under Standard and

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

High voltage engineering

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

ABSTRACTS of SESSION 6

New Modeling of Metal Oxide Surge Arresters

Lightning Flashover Rate of an Overhead Transmission Line Protected by Surge Arresters

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Lightning Performance of Transmission Lines with Tall Sections

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

ABSTRACT 1 INTRODUCTION

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

X International Symposium on Lightning Protection

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

SURGE PROPAGATION AND PROTECTION OF UNDERGROUND DISTRIBUTION CABLES

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

Lightning Performance Improvement of 115 kv and 24 kv Circuits by External Ground in MEA s Distribution System

Simplified Approach to Calculate the Back Flashover Voltage of Shielded H.V. Transmission Line Towers

ABSTRACT 1.0 INTRODUCTION LIST OF SYMBOLS

Modeling insulation in high-voltage substations

The Effect of Lightning Parameters on Induced Voltages Caused by Nearby Lightning on Overhead Distribution Conducting Line.

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Utility System Lightning Protection

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Power Quality and Reliablity Centre

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Tab 8 Surge Arresters

Ferroresonance Experience in UK: Simulations and Measurements

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Influence Of Lightning Strike Location On The Induced Voltage On a Nearby Overhead Line

Comparison between Different InstallationLocations of Surge Arresters at Transmission Line Using EMTP-RV

The Many Uses of Transmission Line Arresters

OVERVOLTAGE PROTECTION OF POLE MOUNTED DISTRIBUTION TRANSFORMERS

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Fig.1. Railway signal system

In power system, transients have bad impact on its

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Analysis of Arrester Energy for 132kV Overhead Transmission Line due to Back Flashover and Shielding Failure

Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Insulation Co-ordination For HVDC Station

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

Modeling for the Calculation of Overvoltages Stressing the Electronic Equipment of High Voltage Substations due to Lightning

CVVOZE Power Laboratories (CVVOZEPowerLab)

Effective Elimination Factors to the Generated Lightning Flashover in High Voltage Transmission Network

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Shunt Reactor Switching

150 kj Compact Capacitive Pulsed Power System for an Electrothermal Chemical Gun

Computation of Lightning Impulse Backflashover Outages Rates on High Voltage Transmission Lines

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

High Voltage Induced By Transmission Lines Due To Lightning Case Study

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

Electrical Power and Energy Systems

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

Tab 2 Voltage Stresses Switching Transients

Introduction EMC. Filter parameters. Definition of EMC / EMI. X-Capacitor. Sources of EMI. Coupling mechanism. Y-Capacitor.

Comparison of metal oxide surge arrester models in overvoltage studies

Sensitivity Analysis of Maximum Overvoltage on Cables with Considering Forward and Backward Waves

Investigation on the Performance of Different Lightning Protection System Designs

GIS Disconnector Switching Operation VFTO Study

Electric Power Systems Research

Harmonic filter design for electrified railways

FERRORESONANCE SIMULATION STUDIES USING EMTP

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

The Role of the Grounding System in Electronics Lightning Protection

In order to minimise distribution (11 and 22 kv) feeder breaker

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

HIGH VOLTAGE Insulation Coordination

Evaluating the Response of Surge Arresters

MARCEL A. ARAÚJO, ROGÉRIO A. FLAUZINO, OURESTE E. BATISTA, LUCAS A. MORAES

CONTENTS. 1. Introduction Generating Stations 9 40

Journal of Applied Research and Technology 15 (2017)

Overvoltage Protection of Light Railway Transportation Systems

Transcription:

Energy Syst (2016) 7:357 364 DOI 10.1007/s12667-015-0175-3 ORIGINAL PAPER The impact of distributed generation to the lightning protection of modern distribution lines Vasiliki Vita 1 Lambros Ekonomou 1 Christos A. Christodoulou 2 Received: 9 October 2015 / Accepted: 3 November 2015 / Published online: 17 November 2015 Springer-Verlag Berlin Heidelberg 2015 Abstract The distributed generation (DG) has become very popular in recent years mainly due to their high efficiency, their benefits to distribution networks (e.g., improvement of voltage profiles and load factor, reduction of power losses, delivery of backup power, elimination of system upgrades, etc.) and their low emissions. On the other hand the continuous installation of DGs has raised several different issues that need to be considered. Lightning constitutes one of the main factors of failures in distribution lines and therefore the lightning performance of modern distribution lines with DGs is one of the issues that needs to be further studied. The lightning protection of the lines and the reduction or elimination of faults are mainly based on the protection measures undertaken by the electric utilities. In this work the impact of DG to the lightning protection of distribution lines is studied through extensive simulations that consider different factors that influence the efficiency of the protection systems and the developed overvoltages. The paper aims to contribute in the more effective lightning protection of modern distribution lines. Keywords Distributed generation Distribution lines Surge arresters Grounding resistance Simulation B Lambros Ekonomou lambros.ekonomou.1@city.ac.uk 1 Department of Electrical and Electronic Engineering, City University London, Northampton Square, London EC1V 0HB, UK 2 Department of Electrical & Computer Engineering, Democritus University of Thrace, 12 Vasillisis Sofias St, 671 00 Xanthi, Greece

358 V. Vita et al. 1 Introduction The configuration of the traditional electrical supply system has changed prominently over the last two decades when distributed generation (DG) power plants were reintroduced into the construction of the electricity network. The concept of DG, which can be traced back to the early 1900s, is based on small scale power plants that are connected to the electricity system close to consumers. DG has the potential to reduce emissions and increase the dependence on alternative energy sources, participating with this way in energy diversification. It also helps to deliver backup power during times of increased electricity demand, avoiding the investment in large power plants and transmission lines, having also as a result the reduction of the transmission and distribution power losses. Furthermore DG improves voltage profiles and the load factor, which minimizes the number of required voltage regulators, capacitors and their ratings and maintenance costs. These benefits however are counterbalanced by impacts on the distribution network since the integration of DG in it is not straightforward. The integration of DG into the distribution network and the larger penetration of renewable energy sources result in network connection issues as well as power system regulation and balancing issues. In addition DG increases the complexity of selective protection coordination resulting in conflicts in the normal operation of the existing networks. Major issues constitute also the distribution network stability with the DG to be able to remain synchronized after a major fault and the elimination of unintended islanding since this is of paramount importance for the general public, maintenance personnel and installed equipment. Finally the installation of DG influences significantly the lightning performance of distribution lines resulting in a higher lightning failure rate. Lightning strokes and switching surges are the main factors of power supply interruptions and equipment damages and malfunctions. Shield wires, surge arresters and increased insulation levels are the most used protective means, in order to secure the reliability of the system and reduce the overvoltage faults [1]. Han, Seo and Kim analysed the lightning overvoltages according to the location of overhead ground wires [2], while Bhattarai et al investigated the protection of wood pole distribution lines using surge arresters [3].In [4] the effect of grounding resistance and shield wire size in the lightning performance of distribution lines was studied. Similarly in [5] was studied the effect of grounding resistance and the pole topology. A statistical method that quantifies the effects of line parameters, soil resistivity, shielding of nearby objects and lightning crest current distribution on the lightning performance of distribution lines is presented in [6] having obtained results that are in close consistency with field data. Finally Araujo et al studied the performance of a distribution lines protection system, against lightning overvoltages, in the presence of DG and of concepts of smart grids providing interesting results and conclusions [7]. In the current paper studies related to direct lightning strokes on distribution lines connected with DG are presented. The installation of surge arresters, their installation position and the distribution line s grounding resistance were considered in the conducted sensitivity analysis. The conclusions of this work aim to contribute in the more effective lightning protection and the reduction of the lightning failure rate of modern distribution lines connected with DG power plants.

The impact of distributed generation to the lightning... 359 2 System configuration The distribution line is consisting of unshielded wooden poles of 9.2 m height with average span length of 70 m. The wooden poles and the conductors geometries are shown in Fig. 1. Data from a real distribution line of nominal voltage of 20 kv (phase phase, rms) has been used as a case study. The distribution line uses porcelain insulators of basic insulation level of 125 kv. The characteristics of the three horizontally placed phase conductors are: Al, 3 95 mm 2,R line = 0.215 /km and X line = 0.334 /km. The distribution line that has a total length of 8 km is represented by distributed parameters based on the Bergeron s traveling wave method. The lossless distribution line is characterized by two values: the surge impedance Z and the wave propagation speed v given by Eqs. (1) and (2). Z = L C (1) 1 v = (2) LC where: L is the per-unit length inductance, and C is the per-unit length capacitance. In order to improve the lightning performance of the line, surge arresters are installed in various positions of the system. In general, surge arresters are installed between phase and earth and lead the current of the overvoltage to the ground. In normal operation of the electric network they present high resistance (M ) and during overvoltages they behave like conductors. The main electric characteristics of a surge arrester are [8 10]: (a) Continuous operating voltage the maximum permissible rms power frequency voltage that may be applied continuously between the arrester terminals. (b) Rated voltage the maximum permissible rms value of power frequency voltage between arrester terminals at which is designed to operate correctly under temporary overvoltages. (c) Residual voltage the peak value of the voltage that appears between the terminals of an arrester during the passage of the discharge current through it. (d) Energy withstand capability the maximum level of energy injected into the arrester at which it can still cool back down to its normal operating temperature. The IEEE Working Group 3.4.11 [11] proposed the model of Fig. 2 for a surge arrester. The model includes the non-linear resistances A 0 and A 1, separated by a R L filter. For slow front surges the filter impedance is low and the non-linear resistances are in parallel. For fast front surges filter impedance becomes high, and the current flows through the non-linear resistance A o. L 0 is associated with magnetic fields in the vicinity of the arrester. R 0 stabilizes the numerical integration and C represents the terminal-to-terminal capacitance. The equations for the above parameters are given as follows [11 13]: L 1 = (15 d)/n µh (3)

360 V. Vita et al. Fig. 1 Unshielded wooden pole of a typical 20 kv distribution line A B C Α (-1.15, 9.2), Β (0.35, 9.2), C (1.15, 9.2) Fig. 2 The IEEE model [11] Lo L1 Ro C Ao R1 A1 Table 1 Surge arrester characteristics Maximum continuous operating voltage 19.5 kv Rated voltage 24 kv Nominal discharge current 10 ka Maximum residual voltage (8/20 µs, 10 ka) 67 kv Energy capability 60 kj R 1 = (65 d)/n (4) L 0 = (0.2 d)/n µh (5) R 0 = (100 d)/n (6) C = (100 n)/d pf (7) where d is the length of arrester column in meters and n is the number of parallel columns of metal-oxide disks. In Table 1 are shown the characteristics of the 20 kv surge arrester that is used in the examined distributed line. The grounding resistance of the line is modeled as a lumped resistor, the wooden poles are modeled by a parallel combination of a resistor and a capacitor, while the insulators were modeled as voltage-dependent flashover switches [7,14]. The distributed generation power plants are considered as synchronous generators connected to the distribution network by transformers.

The impact of distributed generation to the lightning... 361 Finally the injected to the distribution line lightning current was modeled as a double exponential waveform, with peak magnitude of 15 ka, rise time 1.2 µs and time-to-half value of 50 µs. 3 Simulation results The impact of DG to the lightning protection of modern distribution lines has studied through extensive simulations that have performed using MATLAB Simulink. The simulation model of the under study distribution line connected with three DG units is shown in Fig3. The examined distribution line has been divided in four segments with length of 2 km each, in order to be defined different positions (A, B, C, D, E) along the line s length. At these positions surge arresters were installed and the developed overvoltages for each position were calculated. Simulated lightning discharges were applied at position A. Each one of the three DG units connected at points A, C and E were generated active power of 100 kw [15]. Simulations were conducted to the distribution line for each one of the six scenarios presenting in Table 2, in relation to the distribution line s grounding resistance that was varying from 1 to 60 Ohms. The obtained overvoltages at each one of the five different positions are shown in Figs. 4, 5, 6, 7, and 8. Based on the obtained results it can be observed that in cases where no arresters were installed on the distribution line, the variation of the grounding resistance had no effect in the developed overvoltages. This was something that was expected since the poles A segment 1 B segment 2 C segment 3 D segment 4 2km 2km 2km 2km E DG DG DG Fig. 3 Simulation model of distribution line with DG Table 2 Simulation scenarios 1 denotes the installation of equipment, 0 denotes the absence of equipment No. Surge arrester position DG unit position A B C D E A B C 1 0 0 0 0 0 0 0 0 2 1 0 1 0 1 0 0 0 3 1 1 1 1 1 0 0 0 4 0 0 0 0 0 1 1 1 5 1 0 1 0 1 1 1 1 6 1 1 1 1 1 1 1 1

362 V. Vita et al. Fig. 4 Developed overvoltage at position A in relation to grounding resistance Fig. 5 Developed overvoltage at position B in relation to grounding resistance Fig. 6 Developed overvoltage at position C in relation to grounding resistance

The impact of distributed generation to the lightning... 363 Fig. 7 Developed overvoltage at position D in relation to grounding resistance Fig. 8 Developed overvoltage at position E in relation to grounding resistance were made of wood, there were no active (under voltage) parts of the line connected to earth and the line was unshielded. However the overvoltages were attenuated as the distance from the lightning hit point was increased. The installation of surge arresters in all available positions (i.e., the closer installation) has shown that the developed overvoltages were reduced, although not significantly. Nevertheless the use of arresters in the examined distribution line is necessary since the overvoltages exceed the value of the basic insulation level of the line. Finally based on the obtained results has been proven that the presence of DG power plants affects the magnitude of the developed overvoltages, something that must be taken into account in the lightning protection of the modern distribution lines.

364 V. Vita et al. 4 Conclusions The paper presents the simulations that have been conducted in a distribution line connected with DG power plants in order to study the impact of DG to the lightning protection of modern distribution lines. Real data from a typical distribution line has been used in this work. Factors that influence significantly the efficiency of the protection systems and the developed overvoltages such as: the installation of surge arresters, the surge arresters installation position and the distribution line s grounding resistance were considered in the simulations. The obtained results can be very useful to electric utilities and researchers in an effort to upgrade/modify the existing lightning protection methods to include the presence of distributed generation. References 1. IEEE Std 1410-2010: IEEE Guide for improving the lightning performance of electric power overhead distribution lines (2011) 2. Han, J., Seo, H.C.,Kim, C.H.: Analysis of lightning overvoltage according to the location of overhead ground wire in Korea distribution system. In: IEEE Vehicle Power and Propulsion Conference (VPPC), Seoul, Korea 1274 1276 (2012) 3. Bhattarai, R., Harid, N., Griffiths, H., Haddad, A.: Application of surge arresters for lightning protection of 33kV wood pole distribution lines. In: 20 th International Conference and Exhibition on Electricity Distribution, Prague, Czech Republic, Paper 0947 (2009) 4. Thanasaksiri, T.: Improving the lightning performance of overhead distribution lines. In: IEEE Region 10 Conference TENCON 2004 3, 369 372 (2004) 5. Cabral, R.J., Gazzana, D.S., Leborgne, R.C., Bretas, A.S., Dias, G.A.D., Tello, M.: Analysis of distribution lines performance against lightning using ATP-EMTP. in: 2012 International Symposium on Electromagnetic Compatibility (EMC EUROPE), Rome (2012) 6. Mikropoulos, P.N., Tsovilis, T.E.: Statistical method for the evaluation of the lightning performance of overhead distribution lines. IEEE Trans. Dielectr. Electr. Insul. 20(1), 202 211 (2013) 7. Araujo, M.A., Flauzino, R.A., Batista, O.E., Moraes, L.A., Martins, C.H.R.: Protection of the distribution lines with distributed generation against lightning overvoltages in the context of smart grids: World Congress on Sustainable Technologies (WCST), London, 36 41 (2013) 8. Hinrichsen, V.: Metal-Oxide Surge Arresters, Fundamentals, 1st edn. Siemens, Berlin (2001) 9. Lee, B.H., Kang, S.M.: A new on-line leakage current monitoring system of ZnO surge arresters. Mater. Sci. Eng. 119(1), 13 18 (2005) 10. Christodoulou, C.A., Perantzakis, G., Spanakis, G.E., Karampelas, P.: Evaluation of lightning performance of transmission lines protected by metal oxide surge arresters using artificial intelligence techniques. Energy Syst. 3(4), 379 399 (2012) 11. IEEE working group 3.4.11: Modeling of metal oxide surge arresters. IEEE Trans. Power Deliv. 7(1), 302 309 (1992) 12. Christodoulou, C.A., Vita, V., Ekonomou, L., Chatzarakis, G.E., Stathopulos, I.A.: Application of Powell s optimization method to surge arrester circuit models parameters. Energy 35(8), 3375 3380 (2010) 13. Christodoulou, C.A., Ekonomou, L., Mitropoulou, A.D., Vita, V., Stathopulos, I.A.: Surge arresters circuit models review and their application to a Hellenic 150 kv transmission line. Simul. Model. Pract. Theory 18(6), 836 849 (2010) 14. Cabral, R.J., Gazzana, D.S., Leborgne, R.C., Bretas, A.S., Dias, G.A.D., Tello, M.: Improvement of an overhead distribution feeder performance against lightning considering the wire-guard protection and new grounding arrangements. In: 30th International Conference on Lightning Protection, Vienna, Austria (2012) 15. Lazarou, S., Vita, V., Karampelas, P., Ekonomou, L.: A power system simulation platform for planning and evaluating distributed generation systems based on GIS. Energy Syst. 4(4), 379 391 (2013)