DSP-Based Simple Technique for Synchronization of 3 phase Alternators with Active and Reactive Power Load Sharing

Similar documents
CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads

CHAPTER-III MODELING AND IMPLEMENTATION OF PMBLDC MOTOR DRIVE

Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC)

Speed control of sensorless BLDC motor with two side chopping PWM

CHAPTER 4 FUZZY BASED DYNAMIC PWM CONTROL

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [Chakradhar et al., 3(6): June, 2014] ISSN:

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Abstract: PWM Inverters need an internal current feedback loop to maintain desired

Type of loads Active load torque: - Passive load torque :-

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

POWER- SWITCHING CONVERTERS Medium and High Power

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

Extraction of Extreme Power and Standardize of Voltage and Frequency under Varying Wind Conditions

Simulation of Solar Powered PMBLDC Motor Drive

EXPERIMENTAL INVESTIGATION OF THE ROLE OF STABILIZERS IN THE ENHANCEMENT OF AUTOMATIC VOLTAGE REGULATORS PERFORMANCE

Simulation of Advanced ELC with Synchronous Generator for Micro Hydropower

Modeling of Single Stage Grid-Connected Buck-Boost Inverter for Domestic Applications Maruthi Banakar 1 Mrs. Ramya N 2

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

CONCLUSIONS AND SCOPE FOR FUTURE WORK

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

Enhancement of Power Quality in Distribution System Using D-Statcom

Control of Power Converters for Distributed Generation

Chapter 10: Compensation of Power Transmission Systems

Design, Implementation, and Dynamic Behavior of a Power Plant Model

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Feed-Forward System Control for Solid- State Transformer in DFIG

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Using dspace in the Shunt Static Compensators Control

Fuzzy Logic Controller on DC/DC Boost Converter

Digital Control of MS-150 Modular Position Servo System

Project Proposal. Low-Cost Motor Speed Controller for Bradley ECE Department Robots L.C.M.S.C. By Ben Lorentzen

DSPIC based Low Cost and Efficient Digitized Feedback Loop for DC-DC Converter

Performance Comparison of Sensor and Sensorless Active Damping LCL Filter for Grid Connected of Wind Turbine

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

CHAPTER 6 CURRENT REGULATED PWM SCHEME BASED FOUR- SWITCH THREE-PHASE BRUSHLESS DC MOTOR DRIVE

To Study The MATLAB Simulation Of A Single Phase STATCOM And Transmission Line

Speed Feedback and Current Control in PWM DC Motor Drives

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

SVPWM Based Speed Control of Induction Motor with Three Level Inverter Using Proportional Integral Controller

MODELING AND CONTROL OF DISTRIBUTED ENERGY SYSTEMS DURING TRANSITION BETWEEN GRID CONNECTED AND STANDALONE MODES. A Dissertation.

Performance of DVR under various Fault conditions in Electrical Distribution System

Courseware Sample F0

TABLE OF CONTENTS CHAPTER NO. TITLE PAGE NO. LIST OF TABLES LIST OF FIGURES LIST OF SYMBOLS AND ABBREVIATIONS

SPEED SYNCHRONIZATION OF MASTER SLAVE D.C. MOTORS USING MICROCONTROLLER, FOR TEXTILE APPLICATIONS

Power Factor Correction of Three Phase Induction Motor

Linear vs. PWM/ Digital Drives

Analysis of Voltage Source Inverters using Space Vector PWM for Induction Motor Drive

Generator Operation with Speed and Voltage Regulation

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

Frequency Variable Three Phase Inverter Connected to PWM to Control the Induction Motor

645 P a g e. the quantity of compensate current needed accordingly. Fig. 1. Active powers filter with load current detection.

Simulation based study of Maximum Power Point Tracking and Frequency Regulation for Stand-alone Solar Photovoltaic Systems

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Investigation of D-Statcom Operation in Electric Distribution System

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

IN MANY industrial applications, ac machines are preferable

Improved direct torque control of induction motor with dither injection

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

Modeling & Simulation of PMSM Drives with Fuzzy Logic Controller

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

RAPID CONTROL PROTOTYPING FOR ELECTRIC DRIVES

A Switched Boost Inverter Fed Three Phase Induction Motor Drive

CURRENT FOLLOWER APPROACH BASED PI AND FUZZY LOGIC CONTROLLERS FOR BLDC MOTOR DRIVE SYSTEM FED FROM CUK CONVERTER

Modeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

User Guide Introduction. IRMCS3043 System Overview/Guide. International Rectifier s imotion Team. Table of Contents

Improved Active Power Filter Performance for Renewable Power Generation Systems

SUPERCONDUCTING MAGNETIC ENERGY

Volume 1, Number 1, 2015 Pages Jordan Journal of Electrical Engineering ISSN (Print): , ISSN (Online):

VOLTAGE HARMONIC CONTROL OF WEAK UTILITY GRID THROUGH DISTRIBUTED ENERGY SYSTEMS. A Thesis. Presented to

Speed Control of BLDC Motor Using FPGA

Bimal K. Bose and Marcelo G. Simões

DC SERVO MOTOR CONTROL SYSTEM

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

CHAPTER-5 DESIGN OF DIRECT TORQUE CONTROLLED INDUCTION MOTOR DRIVE

Microcontroller Based Closed Loop Speed and Position Control of DC Motor

Swinburne Research Bank

User Guide IRMCS3041 System Overview/Guide. Aengus Murray. Table of Contents. Introduction

CHAPTER 4 PI CONTROLLER BASED LCL RESONANT CONVERTER

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

A Model Based Digital PI Current Loop Control Design for AMB Actuator Coils Lei Zhu 1, a and Larry Hawkins 2, b

Laboratory Investigation of Variable Speed Control of Synchronous Generator With a Boost Converter for Wind Turbine Applications

Volume I Issue VI 2012 September-2012 ISSN

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Compensation for Neutral Point Potential in Three-Level Inverter by using Motor Currents

Modelling of Five-Level Inverter for Renewable Power Source

SIMULATION AND EVALUATION OF A PHASE SYNCHRONOUS INVERTER FOR MICRO-GRID SYSTEM

Levels of Inverter by Using Solar Array Generation System

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Power Factor Correction Input Circuit

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Transcription:

DSP-Based Simple Technique for Synchronization of 3 phase Alternators with Active and Reactive Power Load Sharing M. I. Nassef (1), H. A. Ashour (2), H. Desouki (3) Department of Electrical and Control Engineering, Arab Academy for Science & Technology, Alexandria, Egypt. E-mail: nassef@ieee.org (1), hashour@aast.edu (2), hdesouki@aast.edu (3) Abstract Automatic coupling of 3 phase synchronous alternators to infinite bus AC grid has been discussed and studied, analytically and practically as a case study, to deepen concept of distributed alternators control. The paper introduces an experimental setup for alternator synchronization with active and reactive power control scheme, as a laboratory guide to be followed by engineers in real power stations or in distributed generation. Through Matlab Simulink simulation analysis and practical results based on digital signal processor, the proposed prototype setups have been evaluated for different operation scenarios. Index Terms Alternator, DSP, experimental, load sharing, power control, synchronization. III. SIMULATION The proposed system is simulated according to single line diagram of Fig. 1 and consists of a three-phase alternator that should be synchronized and tied with a three-phase infinite bus AC grid of voltage (V AG ). In between, there is a three-phase load that will show the effectiveness of the active and reactive power controller over load sharing. Other peripherals have been used such as a controller to synchronize alternator to grid as in Fig. 2 and power control blocks to control active and reactive power over the alternator as seen in Fig. 3. I. INTRODUCTION The improvements of the conventional AC grid were exercised on its power quality [1], improved distribution and more robust protection and management schemes [2]. However, the concept of the conventional AC grid is still intact, such as a 3 phase synchronous alternator to be coupled with an AC grid with recent distributed generation (DG) systems [3]. For the investigated system, DC voltage choppers [4] have been used for controlling the field of the alternator and its speed to control both reactive and active power [5][6]. Such setup requires pulse width modulation (PWM) and feedback signals from the alternator [7], which have been monitored and managed with a Texas Instruments digital signal processor (EZ-DSP 28335), using least number of sensors. II. AUTOMATIC SYNCHRONIZATION WITH ACTIVE AND REACTIVE POWER CONTROL Analytically, active power (P) control is performed by manipulating the power angle (), which is the phase shift between AC grid (V AG ) and alternator voltage (V A ) signals; hence current is injected through line reactance (X) in unity power factor mode (UPF); using (1): Fig. 1. Single line diagram. In Fig. 2, two AC voltage transducers have been used to get a voltage signal over the AC grid and the alternator. Signals have been analyzed into a magnitude; and into angle using a phase locked loop simulation block (PLL). Both magnitudes and angles are compared to get an error value necessary for the field and speed controllers over the alternator, in order to synchronize it with grid. (1) Concerning analytical reactive power (Q) control, it adopts the idea of voltage magnitude control wherever reactive power level needs to be modified. Such concept is performed according to (2): (2) Simulation analysis using Matlab Simulink has been carried out to verify the control algorithm defined by the flow chart depicted in Fig. 7 for all modes of operation. Fig. 2. Synchronizing unit simulation.

After synchronization, power controller takes charge of further actions, like sharing load power with the AC grid or injecting the AC grid with active and/or reactive power when needed. The controller requires an extra AC current transducer, installed on alternator output, to be used for active and reactive power calculation, necessary for controller feedback as in Fig. 3. V. EXPERIMENTAL VALIDATION AND RESULTS This section will discuss the main components that have been used to get an experimental setup; which is required for validating the concept of power control and loading sharing. A. Algorithm and program Fig. 3. Active and reactive power controller simulation. Both of the synchronizing unit and the power controller follows the algorithm explained in Fig. 7, as it would be practically applied and programmed to the Texas Instruments DSP. In order to synchronize the alternator to AC grid and control its active and reactive power, control blocks have been created for such purpose as in Fig. 8, in order to be downloaded into the DSP. The control algorithm that such control blocks follow is shown in Fig. 7 where feedback signals are digitally filtered, conditioned and used for the control scheme. IV. SIMULATION RESULTS The alternator used in setup and in simulation has 4 poles, so it is driven to rotate at 1500 RPM, in order to be synchronized with a 50 Hz AC grid as seen in Fig. 4. Fig. 4. Grid versus alternator frequency. Fig. 5 shows the alternator operating in UPF as a current of 2.269 A (1500 W at 220 V ) is supplied to a standalone load before synchronization action; while in Fig. 6, after synchronization, current supplied by alternator is increased to 4.539 A (3000 W at 220 V ) as the alternator contributes for load sharing with the AC grid as well, reducing the AC grid load burden. Fig. 5. Alternator supplies load. Fig. 6. Alternator supplies load and inject active power to AC grid. Fig. 7. DSP program flowchart. Control blocks have the same structure as simulation program of section III and as seen in Fig. 1, because simulation was already based on practical setup considerations, to get corresponding simulation and practical results for proof of concept. Both of simulation and practical validation follow the algorithm shown in Fig. 7. Fig. 8 explains that the DSP has an analog to digital converter (ADC) which produces digital values for AC grid voltage and current, same for alternator. Also a digital reference value for active and reactive power set by external analog knobs. All of these digital values for voltage and currents are converted back to analog then processed by the PLLs into two separate values, voltage magnitude and phase shift. Voltage magnitudes and phase shifts of alternator and grid are used first for synchronization then for active and reactive power control. These magnitudes and phase shifts are used as compare signals for the PI controllers.

The control strategy is built on simple closed loop control scheme with feedback, and the error signal is what decides the control actions, with a PI controller. The DSP works on producing a PWM signal over the two chopper circuits, which one control the alternator speed while the other controls field voltage; hence the active and reactive power of the alternator and its tie line power flow with AC grid. Feed forward control has been introduced to provide more dynamic and simpler control scheme. Feed forward is a term describing an element or pathway within a control system which passes a controlling signal from a source in its external environment, which is in this case a constant digital number. This constant number (i.e. ref. speed = 13000 in Fig. 8 is corresponding to the sampling number required by the DSP PWM block in order to control the DC/DC step down chopper which by its turn control DC motor speed, up to 1500 RPM, which is the speed for a 4 pole AC alternator to generate a 50 Hz power signal. Certainly such number isn t exact all time due to variable electric and physical characteristics of the IGBT and the DC motor (temperature, dv/dt, mechanical friction, etc ); here comes the advantage of feed forward control that works continuously on adding or subtracting to 13000 samples to stabilize the speed at 1500 RPM, which means an active power control as well since it is related to speed control. The value of feed forward control is produces by the power PI controller. There are three PI controllers, one for the active power control (speed control) which gets its error signal from comparing active power knob with alternator feedback current magnitude. The second PI is for field control, only used for synchronization at first then works only afterwards on providing a fixed field signal. It gets its error signal from comparing the AC grid and alternator voltage magnitudes. The third PI is for reactive power control, and it works sideby-side with the field PI controller by adding or subtracting over its fixed field signal (another feed forward control) in order to produce the desired field coil current, suitable for the desired reactive power. The reactive power PI controller gets its error signal by comparing the alternator current phase shift with the reactive power knob reference value. There are differences found between the proportional and integral gains (K P and K I ) of the previously discussed PI controllers - in case of practical and simulation studies - due to electric and physical characteristics that have been discussed earlier. These values are demonstrated in the following table I. Fig. 8. DSP program. Table I PI CONTROLLERS PARAMETERS FOR SIMULATION SOFTWARE AND PRACTICAL SETUP. PI Controller Simulation parameters Practical parameters K P K I K P K I Speed (active power) 7 15 12 16 Field 7 15 39 64 Reactive power 3 8 14 18 B. Experimental validation An experimental setup based on a synchronous alternator has been utilized to validate the concept of active and reactive control for load sharing over an AC grid, as shown in Fig. 9.a. A complete control setup based on DSP has been designed and implemented as shown in Fig. 9.b. It should be noted that a diesel engine has been substituted with a high inertia (flywheel) DC motor, with implemented variable speed chopper based armature drive circuit has been utilized for speed control of the alternator (hence the active power), while another excitation field control chopper circuit has been used for reactive control. (a) Power setup with motored AC alternator, AC grid and load. Sensors (Volt) Control knobs contactor Sensors (Amp) DC/DC Choppers DSP (b) Control setup with chopper and sensor circuits. Fig. 9. Overall practical setup for alternator with AC grid.

C. Experimental results Fig. 10 shows the practical results of the alternator trying to synchronize with the grid, making its output voltage, phase angle and frequency measured same as grid. From Fig. 10.a to Fig. 10.d, the alternator output voltage is getting closer to AC grid voltage. 1 2 1 2 (a) Grid (1) and alternator (2) volts out of phase. (b) Grid and alternator are getting in phase. Finally, Fig. 13 shows the ability of the active power controller on load sharing between alternator and AC grid. The upper yellow signal is the alternator output current (I A ), that s in middle (blue) is the AC grid current (I G ) and the lower velvet signal is AC resistive load current (I L ), which has been increased three times to show system ability on load sharing, general performance and dynamics [8]. Fig. 13.a is a case of no load, so the alternator output current is all injected to AC grid, which explains why their current signals are opposite. Fig. 13.b is a case where the load took all the alternator active power output, leaving the AC grid no current to take. Finally, Fig. 13.c shows that the AC load power is doubled, which means that the alternator cannot supply it alone. Current is withdrawn from AC grid to compensate the difference. It would be noticed by having all three currents in phase. 1 2 (c) Field PI controller minimizing (d) Grid and alternator voltages phase shift. synchronized (V AG ). Fig. 10. Steps to minimize phase shift between grid and alternator voltages. (a) All current injected to grid (no load). (b) Load requires full alternator current, none to grid. All of the following figures are taken directly from oscciloscope, where signal in yellow is alternator grid synchronized voltage (V AG ) and blue is alternator output current (I A ). Fig. 11.a and Fig. 11.b are the same case of the simulated results given in Fig. 5 and Fig. 6 respectively, where the alternator is supplying active power to load only as in Fig. 11.a and then asked to produce more, in order to be injected to the AC grid as in Fig. 11.b. (c) Load sharing case: current from both alternator and grid to load. Fig. 13. Alternator & grid sharing AC load. From the obtained results, it s to be observed that automatic synchronization of the alternator has been achieved with the capability of active and power control and load sharing. VI. CONCLUSION (a) Alternator supplies load only. (b) Alternator supplies load and grid. Fig. 11. Active power control. The reactive power controller is able to produce and inject reactive power to AC grid at different levels, it can withdraw reactive power as seen in Fig. 12.a or it can produce reactive power as seen in Fig. 12.b. Reactive power controller operation is based on feedback phase shift of alternator output current, referred to V AG. In this paper, a simple yet effective technique for digital synchronization of an alternator to the grid has been presented. Moreover, the technique enabled control over active and reactive power delivered to the grid through the alternator. The presented results illustrate the system operation over wide range of references ensuring the stability of the system. The simplicity of the algorithm, low cost hardware requirements and results reveal the novelty and effectiveness of the proposed system. Further investigation into increasing synchronization speed and using switching filters for alternator field can be considered for achieving a much more effective system in the future investigation. VII. REFERENCES (a) Alternator absorbs reactive power. (b) Alternator produces reactive power. Fig. 12. Alternator reactive power control. [1] Hozouri. A. and Sharaf AM., "A FACT based voltage stabilization and harmonic reduction scheme for a SMIB system," International Conference on Energy, Automation, and Signal (ICEAS), pp.1-5, 28-30. Dec. 2011.

[2] M. I. Nassef, H. A. Ashour and H. Desouki, "Battery-less hybrid micro-grid power management using bi-directional three phase power converter," IEEE First International Conference on DC Microgrids (ICDCM), Atlanta, GA, 2015, pp. 19-25. [3] Huang H. and Chang L., "Energy-flow direction control of grid-connected IGBT inverters for wind energy extraction," Canadian Conference on Electrical and Computer Engineering, pp. 535-539, Vol. 1. 2000. [4] Yuhta A.; Keiju M.; Hasegawa M., "Discussions on various chopper circuits for power factor corrections," 2013 IEEE International Symposium on Industrial Electronics (ISIE), pp.1-6. 28-31 May 2013. [5] Hadi Saadat, power system analysis, 3 rd ed., Vol.1 PSA publishing, 2010, pp. 527-566. [6] Khan H.A.; Bargiev P.; Sreeram V., Iu H.H.C., Fernando T.L. and Mishra Y., "Active and reactive power control of synchronous generator for the realization of a virtual power plant," IECON 2012-38th Annual Conference on IEEE Industrial Electronics Society, pp.1204-1210. 25-28 October 2012. [7] Huang H. and Chang L., "Energy-flow direction control of grid-connected IGBT inverters for wind energy extraction," Canadian Conference on Electrical and Computer Engineering, pp. 535-539, Vol. 1. 2000. [8] Abdalla Omar H., Al-Badwawi R., Al-Hadi Hilal S., Al-Riyami Hisham A. and Al-Nadabi A., "Steady-State and Dynamic Performance of Oman Transmission System with Diesel-Engine Driven Distributed Generation," Universities' Power Engineering Conference (UPEC), Proceedings of 2011 46th International, pp.1-6. 5-8 September 2011.