OIL-IMMERSED ARC-SUPPRESSION COILS

Similar documents
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

Basic Principles and Operation of Transformer

TECHNICAL SPECIFICATION FOR POWER TRANSFORMER

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Introduction. Centrado leading-edge transformer. Introduction

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

SOUTHERN ELECTRICITY SUPPLY COMPANY OF ODISHA LIMITED (SOUTHCO UTILITY)

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

SECTION TRANSFORMERS

Industrial Applications

ELETTROMECCANICA. Since english OIL IMMERSED DISTRIBUTION TRANSFORMERS

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

nical catalogue Tech

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

General Electricity Company of Libya

Substation transformers

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

Liquid-Filled Transformers

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Arc Suppression Coils

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

Mechanical Design. Brian Brinson Mechanical Design Manager.

HOW TO SAFE GUARD THE TRANSFORMER..???

POWER TRANSFORMERS CATALOGUE

CAST RESIN DRY TRANSFORMER

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

EE059: Transformer Operation, Maintenance, Diagnosis & Testing

K Factor Power Transformers

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

THREE-PHASE DISTRIBUTION TRANSFORMERS

Cast resin transformers HARMONY TM

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Distribution transformers Part 2 Ground mounted transformers not closecoupled

PPC TECHNICAL SPECIFICATION D/ NCMD / THREE-PHASE DISTRIBUTION TRANSFORMERS

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Transformers Contents Page

TRANSFORMER OPERATIONAL. Principles, Selection & Troubleshooting

Oil-immersed Transformers

Pomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers

INTERNATIONAL STANDARD

TECHNICAL DATA TYPE CMD OIL-IMMERSED ON-LOAD TAP CHANGER

(

Power transformers for Network, Rectifiers, Furnace

Transformers handling and transport

DESIGNED MANUFACTURED TESTED

DISTRIBUTION TRANSFORMER kv

OIL TRANSFORMER HV/LV

DISTRIBUTION TRANSFORMER 11 / kv

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation

S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

Distribution Transformers

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

MODERN POWER TRANSFORMER PRACTICE BIBLIOGRAPHY

SYRIAN ARAB REPUBLIC MINISTRY OF ELECTRICITY PUBLIC ESTABLISHMENT FOR DISTRIBUTION THE ELECTRICITY (PEDE) SPECIFICATIONS FOR

PUBLIC POWER CORPORATION ENGINEERING & CONSTRUCTION OF TRANSMISSION PROJECTS DEPARTMENT

Prolific Systems & Technologies Pvt. Ltd. CORE DETAILS. CENTRE Figure - II L-2 X Y Wt-2

SPECIFICATION No SS-88/5 630 kva, 30 / 0.4 kv THREE-PHASE TRANSFORMERS WITH ON-LOAD TAP CHANGER

CONTENTS. 1. Introduction Generating Stations 9 40

Capacitive voltage transformers

Single & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

Transformer Protection

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

TRANSFORMER TECHNOLOGY GPT

Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers

Distribution and Power Transformers

EE188: Transformer Design, Construction, Testing & Maintenance

DISTRIBUTION TRANSFORMERS

Tesar s.r.l. Installation and maintenance manual. Installation, use and maintenance. Manual. Page :1\20

Capacitive voltage transformers

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

Distribution Transformers. The most comprehensive range of solutions for distribution transformer applications

1ZSC AAJ en, Rev. 1. Vacuum on-load tap-changers, type VUBB Technical guide

Onsite Mobile AC High Voltage Test System

PES & IAS NY Chapter And NY LMAG June 23 rd, 2015

POWER TRANSFORMERS TMPNG-SESH SERIES FOR OIL PUMPS ENERGY OF YOUR FUTURE

SGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

T S 15KVA 1PH 240/480 Transformer

Basic principles and operation of a transformer

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

UNIFIED FACILITIES GUIDE SPECIFICATIONS

POWER/DISTRIBUTION TRANSFORMER PERFORMANCE EVALUATION.

7. INSPECTION AND TEST PROCEDURES

1ZSE en, Rev. 6. On-load tap-changers, type UBB Technical guide

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Transcription:

ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department Tel.: +48 24 285 18 53, Fax: +48 24 285 47 53 marketing@ftz.pl Technical Department Tel.: +48 24 285 47 85, Fax: +48 24 285 46 31 technika@ftz.pl Quality Management Department Tel.: +48 24 285 48 31, Fax: +48 24 285 47 45 kontrola@ftz.pl Logistics Office Tel.: +48 24 285 47 52, Fax: +48 24 285 46 30 logistyka@ftz.pl OIL-IMMERSED ARC-SUPPRESSION COILS 100-4000 kva 1-37 kv

Applications Arc-suppression coils are designed for compensation of ground fault current in power network and are installed in power substations between ground and, in the case of star connection, the neutral point of power transformer or, in the case of delta connection, the neutral point of earthing transformer. The 1U terminal of operating winding should be connected with the neutral point terminal 1N of power or earthing transformer, and the 1N terminal of suppressing coil should be connected to earth. The additional winding terminals are located on the cover and marked with 2U - 2N respectively. The additional winding is used for forcing of current active component for selective operation of protecting devices. In the condition of short-circuit between phase line and ground the compensating current flows through the arc suppressing coil. The current-voltage characteristics of coils is very close to a straight line; this is very important in operation. On the cover the bushings of current transformer S1-S2 are also located. Operating conditions The arc suppression coils in standard version are designed for operation in the conditions of moderate climate. Maximum installation height for the reactor: 1000 m a.s.l. Operating place: Ambient temperature range: Open space or the room with sufficient ventilation; atmosphere free of dust and chemically active or explosive gases. -25 C up to +40 C (248 K up to 313 K), average annual temperature not exceeding +20 C (293 K). Rated frequency: 50 Hz Current regulation and operating time values are specified in the table below: Position of tap changer Compensating current expressed in % of rated current Operating time, hours 1 100 2 2 87.5 4 3 75 8 4 continuous 62.5 operation 5 50 continuous

operation NOTE: Coils in special versions meeting other requirements are available on request. Design Reactor cores: Reactor windings: Regulation: Tanks: Made of cold-rolled transformer plates covered with inorganic insulating material. The windings of reactors are made of electrolytic copper. The windings are wound from round wire with enamel insulation or shaped wire with paper insulation. Between individual windings the oil channels are provided that ensure the necessary oil circulation and suitable cooling. The windings are pressed by clamping bolts which eliminate vibrations during operation. Both the design and fixing structure of windings ensure very good dielectric strength and high resistance against lightning surges and very good short-circuit strength. To avoid overvoltages, the earthing diagram for all structural elements of suppressing coils was drawn up. For current regulations used tap changer, which is located inside tank. Tap changer manual drive is located on the cover. Adjustment of parameters can be changed by selecting of desired taps after de-energizing of the reactor. Each tap of the tap changer is equipped with locking mechanism. Tanks are made of steel. Tanks are made in the form of welded steel structure reinforced with stiffening members which ensure the required level of mechanical strength. The heat generated during operation is carried away by radiators made of sheet steel and fixed to tank jacket or by corrugated walls. The tank is equipped with the undercarriage with adjustable wheels that can be positioned for longitudinal and transversal travel. Main specifications of arc suppression coils: Frequency: 50 Hz Regulation of current in 5 steps Voltage: 500 V ±10% Additional winding dimensioned for the current of 500 A

Operating time: 10 seconds

International standards and requirements: PN-EN 60076-6 - Power transformers. Reactors PN-EN 60076-2 - Power transformers. Temperature rise for liquid-immersed transformers PN-EN 60076-1 - Power transformers. General requirements Specifications: Compensa ting power System voltage Voltage Compensating current Item Type kva V V A 1. DGOe 275/15 273 15750 9093 30-15 2. DGOe 365/15 364 15750 9093 40-20 3. DGOe 545/15 546 15750 9093 60-30 4. DGOe 730/15 727 15750 9093 80-40 5. DGOe 1090/15 1091 15750 9093 120-60 6. DGOe 1640/15 1637 15750 9093 180-90 7. DGOe 2180/15 2180 15750 9093 240-120 8. DGOe 365/20 364 21000 12124 30-15 9. DGOe 485/20 485 21000 12124 40-20 10. DGOe 730/20 727 21000 12124 60-30 11. DGOe 970/20 970 21000 12124 80-40 12. DGOe 1455/20 1455 21000 12124 120-60 13. DGOe 1940/20 1940 21000 12124 160-80 NOTE: The suppressing coil can be made for the voltage complying with the standard: 6, 10, 15, 20kV or other (from the range of 1-37kV). It is also possible to built the arc suppression coils equipped with: - connector bushings; - accessories (connector heads, transformer terminals, anti-vibration pads and so on).

Dimensional drawing : 1. Suppression coil winding bushing 2. Additional winding bushings 3. Current transformer bushings 4. Tap changer manual drive 5. Buchholz relay BF 25/6 6. Drain valve and oil test valve 7. Earthing terminals 8. Adjustable undercarriage 9. Rating plate 10. Dehumidifier 11. Maximum reading thermometer R3/4 12. Oil drain from conservator 13. Oil conservator 14. Conservator oil filling cap 15. Oil filling cap on the cover 16. Corrugated-wall tank 17. Suppression coil lifting lugs 18. Lugs for fixing of the suppression coil for transportation 19. Oil level indicator Ø100 Approximate dimensions: Item Type A B C H mm mm mm mm 1. DGOe 275/15 1470 1125 1370 2100 2. DGOe 365/15 1470 1125 1370 2100 3. DGOe 545/15 1470 1125 1370 2100 4. DGOe 730/15 1470 1185 1370 2100 5. DGOe 1090/15 1715 1185 1370 2350 6. DGOe 1640/15 1715 1185 1370 2350 7. DGOe 2180/15 1715 1185 1370 2350 8. DGOe 365/20 1470 1125 1370 2100 9. DGOe 485/20 1470 1125 1370 2100 10. DGOe 730/20 1470 1185 1370 2100 11. DGOe 970/20 1470 1185 1370 2100 12. DGOe 1455/20 1715 1185 1370 2350 13. DGOe 1940/20 1715 1185 1370 2350 NOTE: The manufacturer reserves the right to change specifications presented in the catalogue and resulting from technical progress.