Considerations and Recommendations for the Harmonisation of Under Frequency Loadshedding Schemes in Multi Zone Meshed Grids

Similar documents
Digital Object Identifier: /PTC URL:

EH2741 Communication and Control in Electric Power Systems Lecture 2

SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011

P5 Policy 5: Emergency Operations

CHARACTERISTIC NUMBERS OF PRIMARY CONTROL IN THE ISOLATED ESTONIAN POWER SYSTEM

OPERATIONAL RESERVE AD HOC TEAM REPORT

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

VOLTAGE STABILITY OF THE NORDIC TEST SYSTEM

ESB National Grid Transmission Planning Criteria

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

A Topology-based Scheme for Adaptive Underfrequency Load Shedding

Reliability Guideline: Generating Unit Operations During Complete Loss of Communications

P5 Policy 5: Emergency Operations

Combination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network

Low Frequency Demand Disconnection Summary

Network Code for HVDC Connections and DC-connected Power Park Modules Requirement Outlines

Use of the Power System Outlook (PSO) and SMART 1 Programs to View PSLF Dynamic Simulation Data Files

INCIDENTS CLASSIFICATION SCALE METHODOLOGY

Post-Event Analysis of a Compound Event in the ERCOT System Using Synchrophasor Data

Transmission Interconnection Requirements for Inverter-Based Generation

Fault Ride Through Principles. and. Grid Code Proposed Changes

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Frequency response White paper

The Coupling of Voltage and Frequecncy Response in Splitting Island and Its Effects on Load-shedding Relays *

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Phasor-based wide area monitoring in the South African power system

ITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

SCIENCE & TECHNOLOGY

Under-Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

Real-time Monitoring of Power Oscillations and Modal Damping in the European ENTSO-E System

each time the Frequency is above 51Hz. Continuous operation is required

Influence of Wind Generators in Voltage Dips

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Keeping it up to Speed Off-Nominal Frequency Operations. CETAC 2018 San Ramon

Islanding Detection Method Based On Impedance Measurement

Master s thesis report

Controlled Islanding Followed by Load Shedding Based on Rate of Frequency Decline

EE 742 Chapter 9: Frequency Stability and Control. Fall 2011

Using Synchrophasors for Frequency Response Analysis in the Western Interconnection. Bonneville Power Administration -- WECC JSIS Chair

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

Automatic connection/reconnection and admissible rate of change of active power

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Parameters related to voltage issues

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Generation and Load Interconnection Standard

FREQUENCY and VOLTAGE, ranges and durations

Deleted: 9 4 anuary ... [1] Deleted: much more. Formatted ... [2] Formatted Table. Formatted: Indent: Left: 0.06 cm

The EU Network Code on Requirements for Generators A Summary

Anti-IslandingStrategyforaPVPowerPlant

Integration of Variable Renewable Energy

Study on the Improvement of the Special Protection Scheme (SPS) in the Korean power system

RfG Implementation Fault Ride Through

The Role of Effective Parameters in Automatic Load-Shedding Regarding Deficit of Active Power in a Power System

NVESTIGATIONS OF RECENT BLACK-

The Value of Frequency Keeping and Governor Response to New Zealand

Use of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission Systems

Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing

Modle 6 : Preventive, Emergency and Restorative Control. Lecture 29 : Emergency Control : An example. Objectives. A simple 2 machine example

SOLID-STATE TRANSFORMERS

System Protection Schemes in Power Network based on New Principles

A Review of Adaptive Under Frequency Load Shedding Scheme on Islanded Distribution System Using MATLAB/SIMULINK

Facilitating Bulk Wind Power Integration Using LCC HVDC

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Low Frequency Local mode Oscillations in NER Grid, Validation using Model based analysis and Mitigation

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

Geoff Brown & Associates Ltd

MEASUREMENT OF VOLTAGE INSTABILITIES CAUSED BY INVERTERS IN WEAK GRIDS

ELEMENTS OF FACTS CONTROLLERS

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Generation and Load Interconnection Standard

Wind Power Facility Technical Requirements CHANGE HISTORY

A Novel Control Approach for Microgrids Islanded Operation - Load Step Pre-announcement and Bang-Bang Control

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction

FREQUENTLY ASKED QUESTIONS

Stability Issues of Smart Grid Transmission Line Switching

Table of Contents. Introduction... 1

WSAT Online Tool for Assessment of Secure Level of Wind Generation on the System

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

Step-Response Tests of a Unit at Atatürk Hydro Power Plant and Investigation of the Simple Representation of Unit Control System

Forward Looking Frequency Trends Technical Brief ERS Framework 1 Measures 1, 2, and 4: Forward Looking Frequency Analysis

Revision 24 of Issue 3 of the Grid Code has been approved by the Authority for implementation on 19 th November 2007.

Parameters related to frequency stability

LFC/AGC Nordic and European perspective. Exchange of balancing services international workshop Jan 2011 Whitley Gjerde

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

System Protection and Control Subcommittee

1

NPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements

Annex: HVDC Code comments

Transmission System Phase Backup Protection

Integration of Wind Generation into Weak Grids

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

P3 Policy 3: Operational Security

G. KOEPPL Koeppl Power Experts Switzerland

Transcription:

21, rue d Artois, F-75008 PARIS http : //www.cigre.org INNOVATION FOR SECURE AND EFFICIENT TRANSMISSION GRIDS CIGRÉ Belgium Conference Crowne-Plaza Le Palace Brussels, Belgium March 12-14, 2014 Considerations and Recommendations for the Harmonisation of Under Frequency Loadshedding Schemes in Multi Zone Meshed Grids S. DE BOECK, D. VAN HERTEM KU Leuven Belgium SUMMARY Historically defence plans and more specifically load shedding schemes, have always been designed nationally. After the severe disturbance in Europe in 2006, it became clear that the schemes used in the different control zones were not aligned. As a consequence there was an uneven distribution of the load shed in the different zones. A first step in achieving a more unified approach to withstand a large under frequency incidents has, been taken by ENTSO-E. But starting from policy 5 concerning emergency operations, it became clear that still a lot of variation to the proposed scheme is possible. This can be variations in the amount of load shed in each step, the frequency settings at which the shedding takes place and total amount of load that is shed at 48Hz. An overview of the different schemes used in Western Europe in 2006 is given and a comparison is made with some of the scheme currently in use. Starting from this comparison, the question rises of how these schemes would interact. To investigate the consequences of different approaches in designing an under frequency load shedding schemes in an interconnected system, simulations on a two zone system have been performed. From the different combinations simulated, it became clear that different approaches not necessarily lead to a higher total amount of load shed, but that the shedding is more located in specific zones. A unified approach results in similar amounts of load shed but more evenly spread over the zones. It should also be noted that this harmonisation does not imply that exactly the size for the steps or frequency setting for the tripping of the relay should be used. As this could result in a big load disconnection which in turn could lead to an overcompensation. Therefore the band around the linear scheme proposed by ENTSO-E should be defined more clearly. Also the minimum total amount of load that should be shed at 48 Hz should be defined. KEYWORDS Harmonisation, Under Frequency, Load shedding scheme, Multi Zone, Policy 5 Steven.deboeck@esat.kuleuven.be Dirk.vanhertem@esat.kuleuven.be The research leading to these results has received funding from the European Union Seventh Framework Programme under grant agreement n o 283012

1. Introduction Historically defence plans have always been designed nationally, due to the importance of the electricity grid to the nation s economy and as the interconnection to neighbouring states were only limited. A part of this defence plan is the under frequency load shedding scheme (UFLS), intended to protect the system against a collapse caused by a frequency instability. As the European continental power system is synchronous and strongly interconnected, a contingency in one control zone can have a considerable impact in the other zones of the system. Therefore a uniform approach is preferred for the design of this under frequency protection scheme. ENTSO-E has done a first step in achieving this, by writing recommendations for the design of these UFLS schemes in policy 5: emergency situations. These recommendations are not binding and they still allow a lot of freedom in determining the set point for the under frequency load shedding relays. Therefore the actual implemented schemes of the different transmission system operators are quite different (Figure 2). This was clearly illustrated during the emergency situation taken place on the 4 th of November 2006[1]. During this event the European continental power system was split in three parts. The western part had a shortage of generation, which resulted in an under frequency situation. As a consequence the under frequency load shedding scheme was activated and protected the system from a full collapse. During the analysis of the event it became clear that not every control zone contributed by the same amount to protect the system. The amounts of load shed vary between 0.1% in Switzerland and 19% in Portugal, which is a considerable difference. Table 1 Load shed during 2006 UCTE Disturbance [1] 2. Recommendations made by ENTSO-E In Figure 1, the by ENTSO-E recommended load shedding scheme is displayed [2,4]. At the frequency of 49 Hz, it is recommended to shed at least 5% of the load. The percentage for the step size refers to the annual winter peak consumption (annual cold spell; ACS). This is the consumption on a specific day in January. Though most of the time the actual load is lower than this winter peak consumption. Therefore also the actual amount of load shed in a specific step can be significantly lower than the actual previsioned disconnected load in the load shedding scheme. It is also allowed to do the first step of the shedding scheme already at 49,2 Hz. If the frequency drops further below 49 Hz, then a linear stepwise disconnection is recommended by this scheme. The suggested scheme takes steps of 10% such that at 48 Hz, 50% of the load has been shed. Though the transmission system operator is free in determining the exact amount of load shed in each of these steps according to its own simulations and needs. Usually the steps vary between 5 and 10%. If the steps become smaller than 5%, then the possibility exists that there is no load connected on the feeder behind the under frequency relay. This reduces the responds to stabilize the system frequency. As a consequence, the following steps will be activated. But this can result in an uneven contribution by different zones if different schemes are being used. Also the maximum step size has to be limited, to not cause an over compensation or any dynamic instabilities. It is also recommended that the TSOs adapt their load shedding plan in order to take the additional loss of generation into account. These are usually small embedded generation units such as wind turbines, combined heat and power generation units and photovoltaic panels that will disconnect before the load shedding scheme is activated. 3. The Different Schemes: Theoretical and in Reality Within the ENTSO-E RG CE framework described above, still a lot of variation is possible. The different types of possible schemes, are given by the different curves in Figure 1.

Curve A, can be seen as a late load shedding scheme. This means that in the first steps of the load shedding scheme, close to 49Hz, a relative small amount of load will be shed compared with the size of the steps closer to 48Hz. This type of scheme is not favourable to cope with large frequency instabilities as it allows a fast decay of the frequency and will only act on the last moment. Therefore the risk exists that the relays will act to late and full system collapse will occur. A positive effect of the late scheme is, that it can reduce the amount of affected customers in the case of a frequency instability that has a minimum frequency just below 49 Hz, as the first steps of this scheme have a smaller size. Though this advantage does not equipoise the risk of system collapse in case of large frequency instabilities. In an interconnected system, a system operator could use this approach to reduce the impact of large contingencies on his own customers while relying on the neighbouring TSOs to resolve the instability. But it is more likely that a transmission system operator ends up with such a scheme unintentionally. As the size of the steps are determined based on the ACS, the actual amount of load shed in the first stages of the load shedding scheme can be considerably lower, for example during the night. Or in some countries even more, if the event occurs on a moment with a significant amount of energy generated by embedded renewable energy sources. The embedded generation units are mainly connected on feeders with a lot of residential consumption, which are mostly the low priority feeders. Figure 1 Proposed scheme by ENTSO-E and curves of possible schemes [2] A second scheme is the linear load shedding scheme. This is given by the curve B in Figure 1. In this scheme, the size of each step will remain the same. So if the frequency drops below 49 Hz during an event, then the amount of load shed will increase linearly with the depth of the frequency dip. This scheme is also proposed by ENTSO-E, as it is not the optimal scheme, but has an adequate effect on limiting both very large, as limited under frequency deviations. Though, as already explained above, the risk exist that you end up in a late shedding scheme unintentionally, as the exact amount of load that can be shed depends on the moment on which the event is taking place. The third scheme that is considered here, curve C, is the early shedding scheme. In this scheme the size of the first steps, close to 49 Hz, will be larger than the size of the steps closer to 48 Hz. This means that a larger amount of the load will be shed at the beginning of the scheme compared to the amount of load that will be shed at the end of the scheme. The advantage of this scheme is, that it is very adequate to cope with very large under frequency instabilities. As it will slow down the frequency decay very quickly and as such cause the frequency to stabilize much faster than a late or linear shedding scheme. The disadvantage of this scheme is, that in the case of smaller frequency instability events (minimum frequency close to 49 Hz), more load will be disconnected than necessary. The cost of this action can thus be higher than strictly necessary. But this has to be put in perspective with the number of activations of the scheme. An early shedding scheme is already used by some TSOs to take into account the extra disconnection of small embedded generation units, such as small cogeneration, wind and photovoltaic units. Though, the size of the first steps should also not be made to large, to avoid the possibility of overcompensating and causing an over frequency problem.

Figure 2 gives an overview of some of the under frequency load shedding schemes which were implemented in Western Europe 1 in 2006. These schemes show a similar trend. All the TSOs start the load shedding at 49 Hz. Below 49 Hz the shedding takes place at different set points. This is not necessarily bad, as it causes a certain smoothing of the load shedding at the system level compared to synchronized steps at a certain frequency in all zones. But it is clear that the step size used in each control zone is different. The step size varies from 3% to 20%. Most of the schemes depicted here use a quasi-linear scheme. TSO2 and TSO3 use the same frequency setting, but use a different step size. As a result TSO2 will always shed more load than TSO3. TSO4 and TSO1 use the same step size, but use a different trip frequency. As a result TSO4 will always shed before TSO1. What is important to notice is that at 48Hz the total amount of load shed varies between 40 and 60%. Also one TSO would only have shed 8% at 48 Hz. After the disturbance many of the TSOs did change their load shedding schemes in line with policy 5 of ENTSO-E. In the framework of the itesla project, a survey concerning the load shedding schemes has been done. From this, it became clear that still a lot of variation exists. The size of the steps can still be changing from 5 to 20%, and still not all the schemes lead to a shedding of 50% of the load at 48Hz. On the left in Figure 3 three schemes currently used in Europe, are shown. Not all of these schemes start shedding load at 49Hz. Next to that it is clear that the steps used are not of the same size. Also the amount of load shed at 48 Hz varies between 25 and 70%. On the right side it is clear that there is an uneven distribution between the different zones. For example at 49Hz TSO1 sheds 5%, TSO2 20% and TSO3 0%. The contribution of TSO1 is therefore one fifth of the total % shed. 49,1 TSO1 TSO2 TSO3 TSO4 TSO5 TSO6 48,9 48,7 48,5 48,3 48,1 Frequency stting relays 47,9 47,7 Figure 2 Example of load shedding schemes in Europe in 2006 [1] 90 80 70 60 50 40 30 20 10 0 47,5 % Load shed in control zone Figure 3 Left: 3 schemes in Europe. Right: relative contribution if these schemes in one system

Figure 4 Two zone test system based on Eurostag Tutorial example 4 [3] 4. The Network and the Simulations To simulate the interactions of the different schemes a full dynamic model of a network is needed. To identify the global effects of the combination of different schemes on different zones, a network consisting of two zones is proposed. Subsequently the results for the combinations of different schemes on this network will be discussed. The network used for this analysis is based on the multi-area network used in the tutorial of EUROSTAG5.1. The one zone network consists of 4 areas with conventional generation. The area C has been modified. In this area three generators have been connected to the NHVCEQ bus through a step up transformer. Two of these generators are coal fired power plants (1000MW) and one is a nuclear power plant (1000MW). There are also coal fired units in zones A and B: a 1100 MW generator connected in area A and a 500MW and 200MW generator in area B. All of the generators are equipped with a governor and an AVR. No gas fired units or intermittent generation units have been modelled here. The loads are connected in the areas A, B and C. In area A and B, they are of the impedance type, while the load in area C is modelled as a constant power load. In each zone, 3800MW of load is connected. In all the areas 50% of the loads are equipped with under frequency load shedding relays. This one zone network has been doubled and interconnected by two lines, to create a two zone system. Line 1 connects the busses NHVC2 -NHVA23 and line 2 connects the busses NHVB1-NHVC21. Because of these connections, there is a flow from zone one to zone two over line 1 and from zone two to zone one over line 2. During the simulations the combinations of the different load shedding schemes, given in the Figure 5, are tested on this network. These schemes are similar to the schemes described in Figure 1 and are also labelled as late, linear and early. For the early, linear and late scheme the frequency settings are the same. Below a frequency of 48,1 Hz, 50% of the load will be shed for all the schemes. The outage of multiple generation units (2550MW), connected to the bus NHVEQ, is simulated to represent a large frequency deviation. This contingency could occur in the case of a double bus bar fault.

early 5 lin5 Late5 Early10 Lin10 Late10 60 40 20 0 48,6 48,1 49 48,5 Figure 5 Left a five step shedding scheme and right a ten step shedding scheme 60 40 20 0 48 The results are given in Table 2. The name of the different cases consists of two parts. The first part represents the scheme used in control zone one, while the second part represents the scheme used in control zone two. For example linlate means that in control zone one a linear scheme is being used, while in control zone two a late shedding scheme is being used. Firstly, consider all the schemes to consist of 5 load shedding steps. Based on different schemes in different zones, different results are obtained. From Table 2, it can be seen that in the case one of the two TSOs uses a late shedding scheme while the other uses the linear scheme (linlate) or both use the late shedding approach (latelate), that more load shedding steps will need to be activated to stabilize the system compared to a linear scheme in both systems (linlin). As a consequence at least the same total amount of load will be shed. In the combination linlate, an additional step is activated compared to the linlin case. This means that also customers with a higher priority will be disconnected, which causes a higher impact of the event. One can also notice that for this linlate case the contributions to mitigate the frequency Table 2 Simulation results for the combinations of schemes imbalance are not divided equally between the two zones. In this case, control zone one disconnects 50% more load compared to zone two. And because one of the two zones uses this late approach also the maximum frequency drop will be deeper. The linlate case can thus results in more load to be shed than strictly necessary. For the case that the two zones use the early approach, the frequency instability will be corrected much faster, and the time to reach the minimum frequency is considerably lower. But slightly more load has been shed compared to the linlin case. In the case that zone two uses the early approach and zone one the linear, the load shed in each zone is clearly unbalanced. Zone two will disconnect 10% more load than zone one. Also the frequency dip is smaller. Making use of more load shedding steps, reduces overcompensation (ex. linlate 5 steps and linlate 10 steps) and for some events the total amount of load shed can even be smaller. Though one should take care that

there is no overlap between the actual opening of the switch gear of a certain load shedding step and the activation of the next load shedding step. It should also be noticed that between the moment of triggering the relay and opening of the switchgear there is a time period that can be up to 350ms. This time period depends on the relay, the communication between relay and switchgear and the actual opening of the switchgear. Therefore a minimum difference between two consecutive under frequency load shedding steps should be respected. An often used minimum value is 0.1 Hz between two steps. Overall it can be seen that when different zones use the same approach, less load will be shed to stabilize the system. For the earlylate case the total load shed was lower but there was a very uneven distribution what could cause high priority customers in zone one to be disconnected, while the other zone was affected much less. It can also be seen that increasing the number of steps in the scheme will generally reduce the risk of overcompensation. 5. Considerations and recommendations Generally using the same approach in all the systems gives better results. The amount of load shed in total is limited and the amount of load shed in each zone is more or less equal. So the burden is spread more equally over all the zones, which causes the priority ranking of customers to be respected. Generally an early approach will cause a smaller frequency dip but more load could be disconnected than a late approach. Using a different approach in each control zone often results in more load to be disconnected. But it always results in an uneven distribution of the load shedding between the different zones. Therefore the zone that will activate at the highest frequency settings, will activate a larger part of its scheme. And as such will have more affected customers. To minimize the possibility to end up in this unwanted situation. The allowed deviations of step size, and as such closely linked the number of steps, should be reduced. This should be done through a further harmonization towards the linear scheme, specific grid codes or through a change of the regulatory framework. One should of course keep in mind that it remains impossible to know the exact amount of load that will be connected during an event. But by harmonizing the design of the scheme, the real deviations from the linear scheme can be kept limited. As in many countries the DSO is responsible for the final implementation of the scheme, the communication between both TSOs amongst each other and between TSO and DSO is crucial in facilitating this harmonisation. Finally it should be noted that the amount of load connected to the system is continuously changing depending on the season, moment during the day,.. And these load patterns will do so even more under the impulse of embedded generation and local storage. Now the relays are updated ad hoc, but updating these relays settings in function of the season, moment of the day, or as a function of a predicted amount of renewable generation, could ameliorate the effectiveness of the scheme. Though with the current relays it is often not possible to do such fast changes of the settings. A first step in the harmonisation could be the periodic (every X years) aligning of the schemes between TSOs. 6. REFERENCES [1] UCTE, Final Report System Disturbance on 4 November 2006, UCTE, Tech. Rep., 2007.[Online]. Available: https://www.entsoe.eu/search?q=final+report+system+disturbance [2] ENTSO-E, Operations handbook policy 5: Emergency operations, ENTSO-E, Tech. Rep.,2012.[Online]. Available: https://www.entsoe.eu/publications [3] Tractebel Engineering & RTE, 2013, Eurostag tutorial [4] ENTSO-E, Technical Background and Recommendations for Defence Plans in the Continental Europe Synchronous Area ENTSO-E, Tech. Rep. 2010.[Online]. Available: https://www.entsoe.eu/publications/system-operations-reports/continental-europe/