Earth Mat Design for a 66kv Substation

Similar documents
DESIGN OF SUBSTATION GROUNDING IN A TWO LAYER EARTH STRUCTURE (A CASE STUDY OF 132KV SUBSTATION)

Industrial and Commercial Power Systems Topic 7 EARTHING

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-II) OVERHEAD NETWORK GROUNDING. Rev. 01

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

Earthing of Electrical Devices and Safety

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Keywords: Absolute potential, grounding system software, ETAP , Ground potential rise (GPR), Step and Touch Potentials

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD (PART-I) UNDERGROUND NETWORK GROUNDING. Rev. 01

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

kv AC substation

Grounding for Power Quality

HV Substation Earthing Design for Mines

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

ABSTRACT 1 INTRODUCTION

AC Voltage- Pipeline Safety and Corrosion MEA 2015

EPR Safety Mat Modelling & Field Testing Summary Report

THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

6B.6 Substation Grounding

Underground System Design TADP 547

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

The Potential Gradient of Ground Surface according to Shapes of Mesh Grid Grounding Electrode using Reduced Scale Model

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

SDCS-03 DISTRIBUTION NETWORK GROUNDING CONSTRUCTION STANDARD GROUNDING RESISTANCE MEASUREMENTS AND IMPROVEMENT

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

High Voltage Pylon Earth Measurements

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

Safety Issues Caused by High Earth Resistance and Identifying Them Using Instruments

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Outdoor Installation 2: Lightning Protection and Grounding

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Grounding and Lightning arrestors

FAQ ON EARTHING STANDARDS 16/08/2018

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Agenda. Earthing of Telecom Installations using Single Point Earthing. Reference Documents. How many earths? Earthing Issue...

VI 3 - i TABLE OF CONTENTS

Stray Voltage and Swimming Pools

An Effective Cable Sizing Procedure Model for Industries and Commerial Buildings

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

CONTINUING EDUC ATION

ECE 528 Understanding Power Quality

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Instruction Manual for Digital Grounding Resistance Meter

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Factors Affecting the Sheath Losses in Single-Core Underground Power Cables with Two-Points Bonding Method

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

INTEGRATED METHOD IN ELECTROMAGNETIC INTERFERENCE STUDIES

CROSS-CONNECT CABINET

Earthing of Low Voltage Electrical Systems: Personnel Protection Equipment Protection

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

7P Series - Surge Protection Device (SPD) Features 7P P P

Generation of Sub-nanosecond Pulses

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

Collection of standards in electronic format (PDF) 1. Copyright

CP Cu1. Advanced Test Equipment Rentals ATEC (2832) Multi-purpose coupling unit for CPC 100. Measurement System for

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

LIGHTNING EARTHING SYSTEM : A PRACTICAL GUIDE

Single Line Diagram of Substations

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Appendix B to Working on Exposed Energized Parts

Single Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):

SCIENCE & TECHNOLOGY

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Fig.1. Railway signal system

Guidelines for the design, installation, testing and maintenance of main earthing systems in substations

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Increasing the Cost-Effectiveness of AC Interference Mitigation Designs with Integrated Electromagnetic Field Modeling

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

Compact Model of a Combined Overhead-Cable Line for Ground Fault Application Transfer Analysis

Reference Number PDS 04 (RIC Standard: EP SP)

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Fatima Michael college of Engineering and Technology

WinIGS. Windows Based Integrated Grounding System Design Program. Training Guide. Last Revision: June 2017

Computer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation

Assessment of Step and Touch Voltages for Different Multilayer Soil Models of Complex Grounding Grid

6. Internal lightning protection

Analysis of the Electromagnetic Interferences between Overhead Power Lines and Buried Pipelines

Lightning performance of a HV/MV substation

Smart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation


Unit 2. Single Line Diagram of Substations

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

Examples of Design for Cathodic Protection Systems

Investigation on the Performance of Different Lightning Protection System Designs

Distance Protection of Cross-Bonded Transmission Cable-Systems

Basic Principles and Operation of Transformer

Transcription:

Earth Mat Design for a 66kv Substation Abija Baby 1, Jeswin James 2, Sharanya Vinod 3, Vyshnavy Sobhan 4, Asst.Pro. Thomas George 5, Dept. of EEE, Mar Baselios Institute of Technology and Science, Nellimatom, Kerala, India 5 UG Student, Dept. of EEE, Mar Baselios Institute of Technology and Science, Nellimatom, Kerala, India 1234 ABSTRACT: This paper presents the design of Earthing system for 66 KV substation and calculation of its parameters. Successful operation of entire power system depends to a considerable extent on efficient and satisfactory performance of substations. Hence substations in general can be considered as heart of overall power system. In any substation, a well-designed grounding plays an important role. Since absence of safe and effective grounding system can result in mal-operation or non-operation of control and protective devices, grounding system design deserves considerable attention for all the substations. Grounding system has to be safe as it is directly concerned with safety of persons working within the substation. Main purpose of this work is designing safe and cost effective grounding systems for 66KV substations. Initially significance of Earthing is explained & methodology for design of substation grounding system is discussed for 66KV substation. This paper mentions the calculation of the desired parameters for 66 kv substation. KEYWORDS: Earthing, Earth electrodes, Ground grid, 66 KV substations, Power systems, Safety, Touch and Step voltages I. INTRODUCTION Earth behaves as an Electrical conductor but its characteristics is that its conductivity is variable and unpredictable. The resistance of an earth connection varies with earth s composition, chemical contents, moisture, temperature, season of the year, depth and diameter of rod and other reasons[1]. The resistance offered to AC and DC also differs considerably. Earthing practices adopted at Generating Stations, Substations, Distribution structures and lines are of great importance. It is however observed that this item is most often neglected. Substation earthing system is essential not only to provide the protection of people working in the vicinity of earthed facilities and equipment s against danger of electric shock but to maintain proper function of electrical system. The object of earthing system is to provide a surface under and around a station, which shall be at a uniform potential (nearly zero or absolute earth potential). This Earth surface should be as nearly as possible to the system. This is in order to ensure that, all parts of apparatus other than live parts and attending personnel shall be at earth potential at all times. Due to this there exists no potential difference, which could cause shock or injury to a person, when short circuit or any other type of abnormalities takes place. This paper is concerned with earthing practices and design for outdoor AC substation of 66KV for power frequency in the range of 50 Hz. II. ADVANTAGES OF EARTHING Reduced operation & Maintenance cost Reduction in magnitude of transient over voltages. Improve lightning protection. Simplification of ground fault location. Improved system and equipment fault protection. Improved service reliability Greater safety for personnel & equipment Prompt and consistent operation of protective devices during earth fault. Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1649

III. IMPORTANCE The earthing system in a plant / facility is very important for a few reasons, all of which are related to either the protection of people and equipment and/or the optimal operation of the electrical system. These include: Equipotential bonding of conductive objects to the earthing system prevent the presence of dangerous voltages between objects (and earth). The earthing system provides a low resistance return path for earth faults within the plant, which protects both personnel and equipment. The earthing system provides a low resistance path for voltage transients such as lightning surges and over voltages. Equipotential bonding helps prevent electrostatic build up and discharge, which can cause sparks with enough energy to ignite flammable atmospheres. The earthing system provides a reference potential for electronic circuits and helps reduce electrical noise for electronic, instrumentation and communication systems. IV. EARTHING DESIGN FOR 66KV SUBSTATION 1. EARTHING Earthing means an electrical connection to the general mass of earth to provide safe passage to fault current to enable to operate protective devices and provide safety to personnel and Equipment s. [2] 2. TYPES OF EARTHING EQUIPMENT EARTHING It comprises earthing of all metal work of electrical equipment other than parts which are normally live or current carrying. This is done to ensure effective operation of the protective gear in the event of leakage through such metal work, the potential of which with respect to neighbouring objects may attain a value which would cause danger to life or risk of fire. SYSTEM EARTHING Earthing done to limit the potential of live conductors with respect to earth to values which the insulation of the system is designed to withstand and this to ensure the security of the system. 3. EARTH ELECTRODE A Galvanized Iron (GI) pipe in intimate contact with and providing an electrical connection to earth. 4. EARTHING GRID A system of a number of interconnected, horizontal bare conductors buried in the earth, providing a common ground for electrical devices and metallic structures, usually in one specific location. 5. TOUCH VOLTAGE (E TOUCH) The potential difference between a ground metallic structure and a point on the earth s surface separated by a distance equal to the normal maximum horizontal reach of a person, approximately one meter. 6. STEP VOLTAGE (E STEP) The potential difference between two points on the earth's surface separated by distance of one pace that will be assumed to be one meter in the direction of maximum potential gradient. 7. MESH VOLTAGE (E MESH) The maximum touch voltage to be found within a mesh of an earthing grid. 8.EARTHING LEAD It is the conductor by which the final connection to the earth is made. Its size should be of sufficient cross sectional area so that it will not fuse under worst fault condition. Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1650

9. EARTHING GRID An earthing grid is formed by means of bare GI rod of appropriate size buried at a depth of about 600 mm below the ground level and connected to earth electrodes. The connection between electrodes and the grid shall be means of two separate and distinct connections made with 75 mm x 8 mm GI flat. Fig.1:Earth mat The connection between the GI flat and the GI rod shall be made by welding, while that between the earth electrode and the GI flats through GI links by bolted joints. The earth electrodes shall be provided at the outer periphery of the grid. As far as possible the earthing grid conductors shall not pass through the foundation block of the equipment. All crossings between longitudinal conductors and transverse conductors shall be joined by welding. The longitudinal and transverse conductors of the earthing grid shall be suitably spaced so as to keep the step and touch voltage within the acceptable limit. However the overall length of the earthing grid conductors shall not be less than the calculated length. The size of the earthing grid conductor shall be decided based on the incoming system voltage and fault level. The fault level considered shall take into account the anticipated increase in fault current during the life span of the station. 10. EARTH MAT DESIGN Earthing System in a Sub Station comprises of Earth Mat or Grid, Earth Electrode, Earthing Conductor and Earth Connectors. Primary requirement of Earthing is to have a low earth resistance. Substation involves many Earthlings through individual Electrodes, which will have fairly high resistance. But if these individual electrodes are inter linked inside the soil, it increases the area in contact with soil and creates number of parallel paths[3]. Hence the value of the earth resistance in the inter linked state which is called combined earth value which will be much lower than the individual value. The inter link is made through flat or rod conductor which is called as Earth Mat or Grid. It keeps the surface of substation equipment as nearly as absolute earth potential as possible. To achieve the primary requirement of Earthing system, the Earth Mat should be design properly by considering the safe limit of Step Potential, Touch Potential and Transfer Potential. 11. THE FACTORS WHICH INFLUENCE THE EARTH MAT DESIGN ARE: Magnitude of Fault Current, Duration of Fault, Soil Resistivity, Resistivity of Surface Material, Shock Duration Material of Earth Mat, Conductor Earthing Mat Geometry. 12. THE DESIGN PARAMETERS ARE: Size of Earth Grid Conductor, Safe Step and Touch Potential, Mesh Potential (Emesh), Grid configuration for Safe Operation, Number of Electrodes required 13. DESIGN PROCEDURE The Investigation of soil characteristics has to be done along with the determination of maximum ground current. After that preliminary designing of grounding system need to done. After that calculation are made possible including Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1651

calculation of resistance of grounding system, calculation of maximum grid potential rise, calculation of step voltages at periphery, calculation of internal step and touch voltages. After the investigation of transferred potential and special danger points are made correction of preliminary design can be made if any necessary. Construction of earthing system. Field measurement of resistance of earthing system. Review and modification of earthing system, if necessary. IV. MATHEMATICAL CALCULATION 1. Prerequisites The following information is required / desirable before starting the calculation: A layout of the site. Maximum earth fault current into the earthing grid. Maximum fault clearing time. Ambient (or soil) temperature at the site. Soil resistivity measurements at the site (for touch and step only). Resistivity of any surface layers intended to be laid (for touch and step only). 2. Step and touch voltage criteria The tolerable step voltage criteria is Estep= [1000+(6 Cs ρs)]*(0.116/ ts) The tolerable touch voltage criteria is Etouch= [1000+(1.5 Cs ρs)]*(0.116/ ts) Where, Estep = the step voltage in V Etouch = the touch voltage in V Cs = 1for no protective layer Ρs = the resistivity of the surface material in Ω m Ts = the duration of shock current in seconds The earth grid conductor size formula I=A ((TCAP 104)/(tc αr ρr)) *ln(k0+tm/k0+ta) Where, I = rms value in ka A = conductor sectional size in mm² Tm = maximum allowable temperature in C Ta = ambient temperature for material constants in C α = thermal coefficient of resistivity at 0 C Fig.2: schematic diagram of earth mat Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1652

αᵣ = thermal coefficient of resistivity at reference temperature Tr ρᵣ = the resistivity of the ground conductor at reference temperature Tr in ua/cm3 K = 1/α or 1/α - Tr tc = time of current flow in sec TCAP = thermal capacity factor 3.Evaluation of ground resistance A good grounding system provides a low resistance to remote earth in order to minimize the GPR. For most transmission and other large substations, the ground resistance is usually about 1 Ω or less. In smaller distribution substations, the usually acceptable range is from 1 Ω to 5 Ω, depending on the local conditions.[3] For calculation of grounding resistance, the following formula is used Rg= ρ[1/lt+1/ 20A(1+(1/1+h 20A)] Where ρ = soil resistivity Ωm Lt = total length of grid conductor m A = total area enclosed by earth grid m2 h = depth of earth grid conductor m For calculation of grid current, IG= (CP Df Sf I) For calculation of grid potential rise GPR=(IG Rg) 4. Actual Step Potential & Touch Potential Calculations Mesh voltage : Em =[ρ Km Ki Kim/LL+LB+LA+(1.15 LE)] Step voltage : Es =[ρ Km Ki Kis/LL+LB+LA+(1.15 LE)] Where ρ = soil resistivity, ohms-m Em = mesh voltage at the center of corner mesh in V Es = step voltage between point in V Km = spacing factor for mesh voltage Kis = spacing factor of step voltage Kim = correct factor for grid geometry LL= Length of grid conductor along length of switch yard LB= Length of grid conductor along breadth of switch yard LA= Length of riser and auxiliary mat in switch yard LE= Length of earth electrodes in switch yard LT= Total length of earth conductor in switch yard LT=(LL+LB+LA+LE) Grid resistance = 0.24Ω Ground potential rise = 3570V V. RESULT Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1653

Tolerable touch potential = 717V Attainable touch voltage = 670.70V Tolerable step voltage = 2379V Attainable step voltage = 5698V VI. CONCLUSION This paper has a focus on designing of a 66 kv AC substation earthing system. The results for earthing system are obtained by computational method. For earthing conductor and vertical earth electrode, mild steel are used. The step by step approach for designing a substation earthing system is presented. The various kinds of conductor sizes for earth equipment are mentioned in this paper. Construction of earthing grid is expressed in here. The step and touch voltages are calculated.substation grounding is a crucial part of substation design. The design has to be both safe and reliable. There are many steps to design a safe and effective grid. This project provides equations that are involved with a grid design. Finally an equation is provided using real world data. This example was designed to meet the design criteria for a safe ground grid. REFERENCES [1] N.M. Tabatabaei, S.R. Mortezaeei; Design of Grounding System in Substation by ETAP Intelligent Softwereǁ,IJTPE Journal, March 2010, Page(s):45-49 [2] Chae-Kyun Jung; Jong-kee choi; Ji-won Kang, A study on effect of grounding system on transient voltage in 154kV Substationǁ, IEEE Conference Publications, 2009, Page(s): 1-6 [3] "IEEE guide for safety in AC Substation Grounding, IEEE 80-2000,pp.1-192. [4] IEEE std 81-1983," IEEE guide for Measuring earth Resistivity, Ground impedance, and earth surface potentials for a ground system" [5] IEEE 142,"IEEE recommended practice for grounding industrial and commercial power systems" [6] "Indian standard specifications, IS 3043 Earthing, pp.1-50. [7] Dwarka Prasad, H.C.Sharma," Significance of Step and Touch Voltage "International Journal of Soft Computing and Engineering (IJSCE) Volume-1, Issue-5, November 2011,pp.193-197. [8] Ashwani Kumar, Member, IEEE, and Hans R. Seedhar, Senior Member, IEEE, " Grounding System for High Resistivity Limited Area Substations in Hilly Region of Himachal Pradesh 16th National Power Systems Conference, Dec.2010, pp.516-522. [9] Dr. Attia A. El-fergany, Senior Member (IACSIT), Member (IEEE),"Design & Optimize substation grounding Grid based on IEEE Std.80-2000 Using GUI & MATLAB Codes,IJEST Vol. 3.2011, pp.6063-6039. [10] R. J. Heppe, Computation of potential at surface above an energized grid or other electrode, allowing for nonuniform current distribution,ǁ IEEE Trans. on PAS, vol. 98, no. 6, pp. 1978 1989, Nov. Dec. 1979. [11] Marlar Thein oo, Ei Ei Cho,Design of earthing system for new substation project, Myanmar. pp.430-434. [12] IEEE, IEEE Recommended Practice for Determining the Electric Power Station Ground Potential Rise and Induced Voltage From a Power Fault, IEEE Std 367-1996, 1996, pp. 1-125 [13] Rao Sunil S., Switchgear Protection and Power Systems. 12th edition, Khanna Publishers, New Delhi, 2007 [14] Mc Donald John D., Electrical Power Substation Engineering, CRC Press, 2006. [15] Puttarach A., Chakpitak N., Kasirawat T. and Pongsriwat C. 2007, Ground layer depth and the effect of GPR, IEEE PES Conference and Exposition, Johannesburg, South Africa, pp. 1 5. Copyright to IJAREEIE DOI:10.15662/IJAREEIE.2018.0704014 1654