3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FX (816) 765-8955 ID23 CURTIN TYPE STTIC FIRE DMPERS 3 OUR UL555 RTED FOR USE IN STTIC SYSTEMS pplication Ruskin Model ID23 3 hour UL classified static (fans off) curtain style fire damper for use in VC systems that shut down during a fire event. Fire dampers used for the protection of openings in walls, partitions, or masonry floors with fire resistance ratings of 3 hours or more and shall have a 3 hour fire protection rating. The ID23 can be installed vertically in walls or horizontally in masonry floors and is rated for airflow in either direction. STNDRD CONSTRUCTION FRME ND LDES MTERIL Galvanized steel (in gauges required by UL listing R-5531). CLOSURE springs (horizontal mount only) 301 stainless steel constant force type. FUSILE LINK 165 F (74 C) is standard. 212 F (100 C) optional. damper sizes See pages 2-5 for minimum and maximum UL sizes. See page 6-9 for construction details on multiple section assemblies. OPTIONS FM pprovals as Specification Tested Product SP200 Switch Package to allow remote indication of damper blade position PFM ngles factory supplied two-side installation. Other angles of various sizes and gauges for two-side installation Factory s of various lengths and gauges to insure field compliance with UL installation requirements MCP Control panels for monitoring purpose ccess Door factory mounted access door in common sleeve. Models ID23 series meet the requirements for fire dampers established by: National Fire Protection ssociation NFP Stand ards 80, 90, 92, 92, and 101 ICC International uilding Codes CSFM California State Fire Marshal ID23 #3225-0245:0004 New York City ME 450-06-M UL CLSSIFIED UL555 Listing R5531 SEE COMPLETE MRKING ON PRODUCT FM pprovals Specification Tested Product (Option) Notes: 1. Dimensions shown in parentheses ( ) indicate millimeters. 2. Single section dampers ordered with either 12" (305), 14" (356) or 16 (406) long sleeve; the ID230, 430 and 630 models may be substituted. Spec ID23-114/New LL STTED SPECIFICTIONS RE SUJECT TO CNGE WITOUT NOTICE OR OLIGTION. Ruskin 2014
DMPER STYLES ND SIZES Style Frame and blades in air stream optional 75-85% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 6"h (152 x 152) Vertical Installation 36"w x 36"h (914 x 914) orizontal Installation 30"w x 45 1 /2"h (762 x 1156) Multiple Section ssembly Vertical Installation 90"w x 72"h (2286 x 1829) orizontal Installation 90"w x 9h (2286 x 2311) 4 1 /2" (114) 6" (152) Min. Style w/o Style w/ Style lades out of air stream optional 80-90% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 4"h (152 x 102) Vertical Installation 36"w x 32"h (914 x 813) orizontal Installation 30"w x 40"h (762 x 1016) Multiple Section ssembly Vertical Installation 90"w x 68"h (2286 x 1727) orizontal Installation 90"w x 8h (2286 x 2057) 4 1 /2" (114) 3/4" (19) = Duct Width = Duct eight = Overall Damper eight Style w/o Style w/ C Style lades out of air stream Fully welded sleeve required 80-90% free area Vertical Installation 4"w x 4"h (102 x 102) orizontal Installation 6"w x 4"h (152 x 102) Vertical Installation 36"w x 32"h (914 x 813) orizontal Installation 30"w x 40"h (762 x 1016) Multiple Section ssembly Vertical Installation 90"w x 68"h (2286 x 1727) orizontal Installation 90"w x 8h (2286 x 2057) 10" (254) Min. 2 1 /2" (64) 5" (127) Min. 10" (254) Min. = Duct Width = Duct eight = Overall Damper eight C Style w/
DMPER STYLES ND SIZES C and WC Style Square or Rectangle Transition Frame and blades out of air stream required 95-100% free area C Style sealed assembly WC Style fully welded Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssembly Vertical Installation 88"w x 67"h (2235 x 1702) orizontal Installation 88"w x 8h (2235 x 2057) + 2" C Style w/ 1 1 /2" (38) = Duct Width = Duct eight = Overall Damper eight + 2" 1. Style C duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WC duct connection extends beyond the sleeve. WC Style w/ CR and WR Style Round Transition Frame and blades out of air stream required 95-100% free area CR Style sealed assembly WR Style fully welded Vertical or orizontal Installation 4" diameter (102) Vertical or orizontal Installation 3 diameter (787) orizontal Installation 28" diameter (711) Multiple Section ssembly Vertical Installation 67" diameter (1702) orizontal Installation 8 diameter (2057) CR Style 1 1 /2" (38) D = = Overall Damper eight 1. Style CR duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WC duct connection extends beyond the sleeve. 3. Transition collars to be sealed (y Others). WR Style
DMPER STYLES ND SIZES CO and WO Style Oval Transition Frame and blades out of air stream required 95-100% free area CO Style sealed assembly WO Style fully welded Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssembly Vertical Installation 88 w x 67 h (2235 x 1702) orizontal Installation 88"w x 8h (2235 x 2057) = Duct Width = Duct eight = Overall Damper eight 1. Style CO duct connection extends 1 1 /2" (38) beyond the sleeve. 2. Style WO duct connection extends beyond the sleeve. 3. Transition collars to be sealed (y Others). + 2" + 2" CO Style WO Style 1 1 /2" (38) 1 1 /2" (38) LR Style Round Transition Round enclosure - frame and blades out of air stream optional non-sealed assembly 95-100% free area Vertical or orizontal Installation 4" diameter (102) Vertical Installation 3 diameter (787) orizontal Installation 28" diameter (711) Multiple Section ssemblies Not available in style LR. See Style CR for larger assemblies D = = Overall Damper eight LR Style Without 1. Style LR without sleeves the duct connection extends beyond the damper. 2. Style LR with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). 12"(305) Min. 12" (305) Min. LR Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves 1 1 /2" (38)
DMPER STYLES ND SIZES LO Style Oval Transition Frame and blades out of air stream optional non-sealed assembly 95-100% free area Vertical or orizontal Installation 4"w x 4"h (102 x 102) Vertical Installation 34"w x 3h (864 x 787) orizontal Installation 28"w x 39"h (711 x 991) Multiple Section ssemblies Not available in Style LO. See Style CO for larger assemblies + 2" = Duct Width = Duct eight = Overall Damper eight LO Style Without 1. Style LO without sleeves the duct connection extends beyond the damper. 2. Style LO with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). + 2" 12" (305) Min. 12" (305) Min. LO Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves 1 1 /2" (38) R Style Round Transition Round enclosure. lades partially in the air stream optional non-sealed assembly 85-95% free area Vertical or orizontal Installation 4" diameter (102) Vertical Installation 34" diameter (864) orizontal Installation 28" diameter (711) Multiple Section ssemblies Not available in Style R. See Style CR for larger assemblies R Style D = = Overall Damper eight 12" (305) Min. 1. Style R without sleeves the duct connection extends beyond the damper. 2. Style R with sleeves the duct connection extends 1 1 /2" (38) beyond the sleeve. 3. Transitions and collars to be sealed in the field (y Others). 12" (305) Min. 1 1 /2" (38) R Style w/ vailable with 12" (305), 14" (356) or 16" (406) long sleeves
SSEMLY ND DIMENSIONL INFORMTION Dampers normally fabricated approximately 1 /4" (6) less than given duct dimensions. (width) and (height) dimensions shown describe maximum UL Classified sizes. Multiple section damper assemblies ordered without sleeves are shipped in individual sections, for field assembly. Multiple section dampers ordered with factory furnished sleeves are normally shipped in complete assemblies, ID23 STYLE DMPERS vertical installation 'X' LDE STCK DIMENSION '' Damper eight 14" (102) thru 12" (305) 11/2" (39) 13" (331) thru 16" (407) 17" (432) thru 23" (585) 24" (610) thru 29" (737) 3" (77) 36" Max (914) 72" Max (1829) 30" (762) thru 33" (839) 3 1 /2" (89) 34" (864) thru 38" (966) 4" (102) 37" (940) thru 46" (1168) 47" (1194) thru 58" (1473) 59" (1499) thru 66" (1676) 3" (77) 3 1 /2" (89) 36" Max (914) 67" (1702) thru 72" (1829) 4" (102) 90" Max (2286) 'X' ORIZONTL installation 'X' LDE STCK DIMENSION '' Damper eight 16" (152) thru 12" (305) 1 1 /2" (39) 13" (331) thru 18" (457) 45 1 /2" Max. (1156) 30" Max (762) 19" (483) thru 23" (585) 24" (610) thru 29" (737) 30" (762) thru 33" (839) 34" (864) thru 38" (966) 39" (991) thru 44" (1118) 3" (77) 3 1 /2" (89) 4" (102) 4 1 /2" (115) 45" (1143) 5" (127) Two section high 9 Max (2311) 90" Max (2286) 'X' LDE STCK DIMENSION '' Damper eight 46" (1168) 47" (1194) thru 58" (1473) 59" (1499) thru 66" (1676) 67" (1702) thru 80" (2032) 8 (2057) thru 88" (2235) 5" (127) 6" (153) 7" (178) 8" (203) 9" (228) 89" (2261) thru 9 (2311) 9 1 /2" (241) 'X' dimension is the total for two sections high
SSEMLY ND DIMENSIONL INFORMTION and C style dampers vertical installation '' Damper eight 36" Max (914) 33" (76) thru 12" (305) 1 3 /4" (44) 13" (331) thru 22" (559) 23" (585) thru 32" (813) 33" (839) thru 46" (1168) 47" (1194) thru 68" (1727) 32" Max (813) 68" Max (1727) 'X' dim. + '' dim. = '' dim. 90" Max (2286) 'X' ORIZONTL installation '' Damper eight 33" (76) thru 12" (305) 13" (331) thru 22" (559) 23" (585) thru 32" (838) 33" (839) thru 40" (1016) 1 3 /4" (44) 4 3 /4" (121) 40" Max (1016) 30" Max (762) 'X' dim. + '' dim. = '' dim. two section high '' Damper eight 4 (1041) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. 8 Max (2057) 90" Max (2286)
SSEMLY ND DIMENSIONL INFORMTION C, WC, CO, WO and LO style dampers vertical installation '' Damper eight + + 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 32" (838) thru 45" (1143) 4 3 /4" (121) 3 Max (787) 67" Max (1702) 46" (1168) thru 67" (1702) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. LO Style is limited to single section only. 34" Max (864) Typical Style C and WC 88" Max (2235) + 3 Max (787) 34" Max (864) Typical Style CO, WO and LO Construction '' Damper eight 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 32" (838) thru 39" (991) 5 3 /4" (146) 'X' dim. + '' dim. = '' dim. two section high '' Damper eight 40" (1016) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. ORIZONTL installation 28" Max (711) + 36" Max (965) 39" Max (991) 8 Max (2057) + Typical Style CO and WO Construction 3 Max (787) 88" Max (2235) + Typical Style CO, WO and LO Construction
SSEMLY ND DIMENSIONL INFORMTION CR, WR and LR style dampers vertical installation '' dimension 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. LR Style is limited to single section only. TWO section high '' dimension 332" (838) thru 45" (1143) 46" (1168) thru 67" (1702) 4 3 /4" (121) 'X' dim. + '' dim. = '' dim. Dia. 34" Max (864) Dia. 67" Max (1702) ORIZONTL installation '' dimension 33" (76) thru 1 (279) 12" (305) thru 2 (533) 22" (559) thru 3 (787) 4 3 /4" (121) 32" (838) thru 39" (991) 5 3 /4" (146) 'X' dim. + '' dim. = '' dim. two section high '' dimension 40" (1016) thru 45" (1143) 5 1 /2" (140) 46" (1168) thru 64" (1626) 7 1 /2" (191) 65" (1651) thru 8 (2057) 9 1 /2" (241) 'X' dim. + '' dim. = '' dim. Dia. 8 Max. (2057) Dia. 28" Max. (711)
SSEMLY ND DIMENSIONL INFORMTION R style dampers vertical OR ORIZONTL installation Dia. 28" Max. (711) 34" Max (864) Vertical orizontal suggested specification Furnish and install at locations shown on plans, static fire dampers tested, constructed and labeled in accordance with the last edition of UL standard 555. Dampers shall have a fire of 3 hours and shall meet the requirements of the latest edition of NFP90. Curtain type fire dampers suitable for vertical wall or partitions; and horizontal (masonry floor/ceiling) with a fire resistance rating of 3 hours and greater. Fire Dampers shall be produced in an ISO 9001 certified factory. Damper frame and blades shall be galvanized steel in gauges required by UL listing R-5531 installed in a factory mounted sleeve and shipped loose mounting angles. Damper blades shall be steel interlock to provide fire shield in gauges required by UL listing R-5531. Closure springs on horizontal mounted dampers shall be of 301 stainless steel and shall be constant force type. Each fire damper shall have a 3 hour fire protection rating and shall be supplied with a 165 F (74 C) or 212 F (100 C) fusible link. Damper shall be installed in static (fan off) systems only. Submittal information shall include the fire protection rating and manufacturer s UL installation instruction. Optional FM pprovals Specification Each fire damper shall be listed in Factory Mutual (FM) pprovals Specification Tested Product and labeled accordingly. Static fire dampers shall be Ruskin model ID23. (Consult www.ruskin.com for electronic version of this Quick spec as well as for complete 3- part CSI MasterFormat Specifications). 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FX (816) 765-8955 www.ruskin.com Printed on recycled paper using vegetable based inks