Bauart gepruft Sicherheit egelma ge od o s be wac g www. tuv.com ID 2000000000 500W Single Output Power Supply
SPECIFICATION MODEL OUTPUT INPUT PROTECTION ENVIRONMENT SAFETY & OTHERS NOTE RSP-500-5 DC VOLTAGE RATED CURRENT CURRENT RANGE RATED POWER 5V 240A 0 ~ 240A 200W 2V 25A 0 ~ 25A 500W 5V 00A 0 ~ 00A 500W 24V 63A 0 ~ 63A 52W 27V 56A 0 ~ 56A 52W 48V 32A 0 ~ 32A 536W RIPPLE & NOISE (max.) Note.2 50mVp-p 50mVp-p 50mVp-p 50mVp-p 50mVp-p 200mVp-p VOLTAGE ADJ. RANGE 4.5 ~ 5.5V 0 ~ 3.5V 3.5 ~ 6.5V 20 ~ 26.4V 24 ~ 30V 43 ~ 56V VOLTAGE TOLERANCE Note.3 ±2.0% ±.0% ±.0% ±.0% ±.0% ±.0% LINE REGULATION ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% LOAD REGULATION ±2.0% ±0.5% ±0.5% ±0.5% ±0.5% ±0.5% SETUP, RISE TIME 500ms, 00ms at full load HOLD UP TIME (Typ.) 0ms at full load 4ms at full load 6ms at full load VOLTAGE RANGE 90 ~ 264VAC 27 ~ 370VDC FREQUENCY RANGE 47 ~ 63Hz POWER FACTOR (Typ.) 0.95/230VAC 0.98/5VAC at full load EFFICIENCY (Typ.) 80% 87% 87% 90% 90% 9% AC CURRENT (Typ.) 7A/5VAC 8A/230VAC INRUSH CURRENT (Typ.) 30A/5VAC 60A/230VAC LEAKAGE CURRENT <2.0mA / 240VAC 05 ~35% rated output power OVERLOAD Note.5 Protection type : Constant current limiting unit will shut down o/p voltage after 5sec. Re-power on to recover OVER VOLTAGE ALARM SIGNAL OUTPUT WORKING TEMP. WORKING HUMIDITY STORAGE TEMP., HUMIDITY TEMP. COEFFICIENT VIBRATION SAFETY STANDARDS WITHSTAND VOLTAGE ISOLATION RESISTANCE 5.75 ~ 6.75V 3.8 ~ 6.8V 7 ~ 20.5V 27.6 ~ 32.4V 3 ~ 36.5V 57.6 ~ 67.2V Protection type : Shut down o/p voltage, re-power on to recover Compensate voltage drop on the load wiring up to 0.3V. Please refer to the Function Manual. Power OK signal. Please see the Function Manual. -20 ~ +70 (Refer to "Derating Curve") RSP-500-2 RSP-500-5 RSP-500-24 RSP-500-27 RSP-500-48 OVER TEMPERATURE Shut down o/p voltage, recovers automatically after temperature goes down OUTPUT VOLTAGE PROGRAMMABLE(PV) Adjustment of output voltage is allowable to 70 ~ 00% of nominal output voltage. Please refer to the Function Manual. CURRENT SHARING Up to 6000W or (3+) units. Please refer to the Function Manual. FUNCTION AUXILIARY POWER 2V@0.A(Only for Remote ON-OFF control) REMOTE ON-OFF CONTROL Please see the Function Manual. EMC (Note 4) REMOTE SENSE EMC EMISSION EMC IMMUNITY 20 ~ 90% RH non-condensing -40 ~ +85, 0 ~ 95% RH ± 0.05%/ (0 ~ 50 ) 0 ~ 500Hz, 2G 0min./cycle, 60min. each along X, Y, Z axes UL60950-, TUV EN60950- approved I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC I/P-O/P, I/P-FG, O/P-FG:00M Ohms / 500VDC / 25 / 70% RH Parameter Standard Conducted Radiated Harmonic Current Voltage Flicker EN55024, EN6204-3, EN6000-6-2 Parameter ESD Radiated EFT / Burst Surge Conducted Magnetic Field Voltage Dips and Interruptions EN55022 (CISPR22) / EN550 (CISPR) Class A EN55022 (CISPR22) / EN550 (CISPR) Class A EN6000-3-2 ----- EN6000-3-3 ----- Standard EN6000-4-2 EN6000-4-3 EN6000-4-4 EN6000-4-5 EN6000-4-6 EN6000-4-8 EN6000-4- Test Level / Note Test Level / Note Level 3, 8KV air ; Level 2, 4KV contact Level 3 Level 3 Level 4, 2KV/Line-Line 4KV/Line-Earth Level 3 Level 4 >95% dip 0.5 periods, 30% dip 25 periods, >95% interruptions 250 periods MTBF 265.3K hrs min. Telcordia SR-332 (Bellcore) ; 90.3K hrs min. MIL-HDBK-27F (25 )7F (25 ) DIMENSION 278*27*83.5mm (L*W*H) PACKING 3.0Kg; 4pcs/3Kg/.9CUFT
Block Diagram PFC fosc : 70KHz PWM fosc : 00KHz I/P EMI FILTER ACTIVE INRUSH CURRENT LIMITING RECTIFIERS & PFC PFC CONTROL POWER SWITCHING O.L.P. RECTIFIERS & FILTER O.V.P. +S -S O.T.P. PWM CONTROL DETECTION CIRCUIT POK AUX POWER LOAD SHARING FAN REMOTE CONTROL RECTIFIERS & FILTER RC LS AUX POWER (2V/0.A) Static Characteristics INPUT MODEL 5V 2V 5V 00 90 80 00~264VAC 90VAC 200W 240A 960W 92A 500W 25A 200W 00A 500W 00A 200W 80A LOAD (%) 70 60 50 MODEL INPUT 00~264VAC 24V 52W 63A 27V 52W 56A 48V 536W 32A 90 00 20 40 50 60 80 200 220 240 264 INPUT VOLTAGE (V) 60Hz 90VAC 209.6W 50.4A 209.6W 44.8A 228.8W 25.6A Derating Curve Efficiency vs Load (48V Model) 92 LOAD (%) 00 80 60 50 40 20 +2V,+5V +5V Others EFFICIENCY (%) 90 88 86 84 82 80 78 76-20 0 0 20 30 40 45 50 60 70 AMBIENT TEMPERATURE ( ) (HORIZONTAL) 0% 20% 30% 40% 50% 60% 70% 80% 90% 00% LOAD The curve above is measured at 230VAC.
Function Manual. Remote Sense The Remote Sense compensates voltage drop on the load wiring up to 0.3V CN PIN7 -S PIN8 +S LOAD Sense lines should be twisted in pairs to minimize noise pick-up. 2. Output Voltage Programming (or, PV / remote voltage programming / remote adjust / margin programming / dynamic voltage trim) In addition to the adjustment via the built-in potentiometer, the output voltage can be trimmed to 70~00%(Typ.) of the nominal voltage by applying EXTERNAL RESISTANCE CN PIN7 -S PIN8 +S Connect an external resistor between TRIM(pin4) & -S(pin3 or pin4 or pin5) on CN or CN2, and +S &, -S & also need to be connected. Vout 00% 90% 80% 70% 0Ω 470Ω.8KΩ OPEN Fig. 2.2 External Resistance (Typical) R
3.Remote ON-OFF Remote ON-OFF is activated by the configuration with respect to CN,CN2 and CN3 as shown in the following diagram. CN2 PIN RCG PIN2 RC2 PIN5 RC PIN4 AUXG CN3 PIN6 AUX Example 3.2(A): Using external voltage source AUX 2V typ. 2.2KΩ 50Ω RC RC2 RCG 620Ω 5V SW AUXG Example 3.2(B): Using internal 2V auxiliary output 2V typ. 2.2KΩ 50Ω AUX RC RC2 RCG SW AUXG Example 3.2(C): Using internal 2V auxiliary output 2V typ. 2.2KΩ 50Ω AUX RC RC2 SW RCG AUXG Connection Method SW Logic Fig. 3.2(A) Fig. 3.2(B) Fig. 3.2(C) Output on SW Open SW Open SW Close Output off SW Close SW Close SW Open
4.Alarm Signal Output Alarm signal is sent out through " POK" & " POK GND" and pins on CN3. Please acknowledge an external voltage source is required for this function. CN3 PIN P OK GND PIN2 P OK Function POK Description The signal is "Low" when the power supply is above 65% of the rated output voltage, or say, Power OK The signal turns to be "High" when the power supply is under 65% of the rated output voltage, or say, Power Fail Table 4. Explanation of alarm Output of alarm(p OK) Low (0.5V max at 0mA) High or open (External applied voltage 0mA max.) POK 0.uF 00KΩ R V P OK GND External voltage and R (The max. Sink is 0mA and 50V) Fig. 4. Internal circuit of P OK (Open collector method)
5.Current Sharing with Remote Sense RSP-500 has the built-in active current sharing function and can be connected in parallel, up to 4 units, to provide higher output power as exhibited below : The power supplies should be paralleled using short and large diameter wiring and then connected to the load. Difference of output voltages among parallel units should be less than 0.2V. The total output current must not exceed the value determined by the following equation: Maximum output current at parallel operation=(rated current per unit) (Number of unit) 0.9 No.(Master) AC/L AC/N When remote sensing is used in parallel operation, the sensing wire must be connected only to the master unit Sense lines should be twisted in pairs to minimize noise pick-up. No.2(Slave) AC/L AC/N No.3(Slave) +S -S Load AC/L AC/N No.4(Slave) AC/L AC/N +S,-S and CS are connected mutually in paralle.
Mechanical Specification Case No.943A Unit:mm 240.2 6 max. 83.5 38. 22.7 38 8-M4 L=5(Both Sides) 6 278 240.2 OUTPUT Air flow direction 27 4-M4 L=5 7.5 93 I/P 0 CN CN2 CN3 8642 642 2 864 3 3 7 7 5 5 5 3 LED SVR 2 3 4 3 Mounting Instruction Hole No. Recommended Screw Size MAX. Penetration Depth L Recommended mounting torque M4 5mm 7~0Kgf-cm Mounting Surface Chassis of RSP-500 Control Pin No. Assignment (CN,CN2) : HRS DF-8DP-2DS or equivalent 8 2 7 Mating Housing Terminal HRS DF-8DS or equivalent HRS DF-**SC or equivalent Mounting Screw L CN and CN2 are connected internally. Pin No. 2 3,5,7 4 6 8 Function RCG RC2 -S TRIM LS(Current Share) +S Description Remote ON-OFF Ground Remote ON-OFF Negative sensing for remote sense Connection for output voltage programming Current Share Postive sensing for remote sense
Control Pin No. Assignment (CN3) : HRS DF-6DP-2DS or equivalent 6 2 Mating Housing HRS DF-6DS or equivalent 5 Terminal HRS DF-**SC or equivalent Pin No. 2 3 4 5 6 Function P OK GND POK RCG AUXG RC AUX Description Power OK Ground Power OK Signal Remote ON-OFF Ground Auxiliary Ground Remote ON-OFF Auxiliary Output AC Input Terminal Pin No. Assignment Pin No. 2 3 Assignment FG Diagram Mx a imum mounting torque AC/N 8Kgf-cm AC/L Installation Manual Please refer to : http://www.meanwell.com/webnet/search/installationsearch.html