EPR Safety Mat Modelling & Field Testing Summary Report

Similar documents
HV Substation Earthing Design for Mines

EMC Philosophy applied to Design the Grounding Systems for Gas Insulation Switchgear (GIS) Indoor Substation

Field Instruction. Induced voltages can occur in overhead lines, underground cables, or in switchyards.

Earthing of Electrical Devices and Safety

ABSTRACT 1 INTRODUCTION

PRACTICAL PROBLEMS WITH SUBSTATION EARTHING

MODERN COMPUTATIONAL METHODS FOR THE DESIGN AND ANALYSIS OF POWER SYSTEM GROUNDING

Operating Instructions. Earthing System Test Equipment. Off-Frequency Low Current Injector LCI2000C. Tuned Voltmeter TVM1100

Fall-Of-Potential Calculations Using MALZ

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

AC Voltage- Pipeline Safety and Corrosion MEA 2015

Industrial and Commercial Power Systems Topic 7 EARTHING

Grounding for Power Quality

Investigation of Earth Potential Rise on a typical single phase HV network

CP CU1. Coupling unit for line and ground testing

Evaluating Step and Touch Potential Risks on Earthing Systems of High Voltage Cable Systems TP, THINUS DU PLESSIS ESKOM SOUTH AFRICA HJ, HARTMUT JAGAU

LET-60-VPC USERS MANUAL. REFERENCE: AIBVMV02 Edition: 01/07/96 Version: 2 LET-60-VPC TOUCH & STEP VOLTAGE AND EARTH MEASUREMENT UNIT.

Investigation on the Performance of Different Lightning Protection System Designs

HIGH VOLTAGE Insulation Coordination

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

6B.6 Substation Grounding

ECE 528 Understanding Power Quality

A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid

ACCURATE SIMULATION OF AC INTERFERENCE CAUSED BY ELECTRICAL POWER LINES: A PARAMETRIC ANALYSIS

Grounding Strategies for Solar PV Panels

SAFETY ISSUES RELATED TO THE CONNECTION OF MV AND HV GROUNDING

RAPTOR Step and Touch Function

Webinar: An Effective Arc Flash Safety Program

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

ABSTRACTS of SESSION 6

Appendix B to Working on Exposed Energized Parts

EDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS

Standardized Measurements for Elevated NEV and Energized Object Concerns Doug Dorr, Charles Perry, Mark McGranaghan Arindam Maitra, Wes Sunderman

Smart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation

DESIGN STANDARD DS 23

Evaluation of Soil Resistivity Characteristics forsubstation Grounding: a Case Study of a University Campus in South-West Zone, Nigeria

A Practical Method to Test the Safety of HV/MV Substation Grounding System

Importance of Grounding in Power System. Presented by Mr. H Jayakumar Ex- Joint Director CPRI

DIGITAL RESISTANCE METER

What Are We Protecting? Over-Voltage Protection for CP Systems. Personnel (primary) Equipment (secondary)

High Voltage Pylon earth Measurements. Tycom (Pty) Ltd Frank Barnes Comtest (Pty) Ltd Presented by Gavin van Rooy

EVALUATION OF THE EARTH RESISTANCE VALUE FOR ESE LIGHTNING ARRESTOR TECHNIQUE FOR THE SOLAR PLANTS IN INDIA

kv AC substation

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

Immunity Testing for the CE Mark

ANALOG RESISTANCE METER USER S MANUAL

The Lightning Event. White Paper

ANALOG RESISTANCE METER

Earth Mat Design for a 66kv Substation

Energy Division. Bowthorpe LV/MV Surge Arresters

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

Safety earthing. Sector Energy PTI NC. Copyright Siemens AG All rights reserved. Theodor Connor

Earthing Guidance Notes

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Power System Neutral/Ground Voltages Causes, Safety Concerns and Mitigation

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Modeling insulation in high-voltage substations

1. The topographic map below shows a depression contour line on Earth's surface.

Stray Voltage and Swimming Pools

The Confusion Surrounding Stray Voltage

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Guidelines for the design, installation, testing and maintenance of main earthing systems in substations

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

DCVG Coating Survey Data Sheet

Analysis of lightning performance of 132KV transmission line by application of surge arresters

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

CP Cu1. Advanced Test Equipment Rentals ATEC (2832) Multi-purpose coupling unit for CPC 100. Measurement System for

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT


Utility System Lightning Protection

High Voltage Pylon Earth Measurements

GROUND TESTERS For all of your Ground Testing needs...

Upgrading Your Electrical Distribution System To Resistance Grounding

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Tab 8 Surge Arresters

EDS EARTHING DESIGN CRITERIA, DATA AND CALCULATIONS

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Contact Voltage Detection

A New Technology. for Measuring Overhead Line and Cable Impedance Values and the Ground Impedance of Large Substations. Feature

Keywords: Absolute potential, grounding system software, ETAP , Ground potential rise (GPR), Step and Touch Potentials

THE EFFECTS OF INCREASED FAULT CURRENT ON THE EXISTING SUBSTATION GROUNDING SYSTEM a Case Study

Coaxial Cable Protection

AC INTERFERENCE OF TRANSMISSION LINES ON RAILWAYS: INFLUENCE OF TRACK-CONNECTED EQUIPMENT I. ABSTRACT

Earthing for EMC in Installations

LONGITUDINAL INDUCTION VOLTAGE MEASUREMENT ON COMMUNICATION CABLES RUNNING PARALLEL TO OVERHEAD LINES

EPR Fundamentals of Calculation of Earth Potential Rise in the Underground Power Distribution Cable Network by Ashok K.

Engineering Technical Report 129. ROEP Risk Assessment For Third Parties Using Equipment Connected To BT Lines. Draft for Approval

Slide 1. New Delhi India Oct CIGRE AORC Meeting New Delhi October 2017

Harmonic filter design for electrified railways

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

EDS FAULT LEVELS

Lightning Protection of Distribution Substations by Using Metal Oxide Gapless Surge Arresters Connected in Parallel

Licensed Electricians Practical Assessment (LEP)

APPLICATION OF THE ELECTROMAGNETIC FIELD METHOD TO STUDY A COMMUNICATION SATELLITE SITE DAMAGED BY LIGHTNING

SCIENCE & TECHNOLOGY

Options to Improve the MEN System into the 21 st Century

Transcription:

EPR Safety Mat Modelling & Field Testing Summary Report 15 April 2014 1. Purpose This document present a summary of the calculations and field testing used to prove the efficacy of the new EPR Safety Mat product, namely to provide potential equalisation and redistribution of the surface voltage profile to help mitigate EPR-related hazards such as step and touch voltage. The calculation-based verification of the EPR safety mat uses CDEGS modelling of a typical installation scenario. The field-based verification was obtained from actual current injection testing carried out in early April 2014 on a mine site, involving an 11 kv power distribution system. 2. Background Electrical discharge events present a significant hazard to equipment and assets via earth potential rise and can cause injury or death to animals and humans. Particularly hazardous electrical discharge events include lightning strikes and electric power system faults. The EPR Safety Mat provides a simple means for mitigating these hazards via its unique threelayer design. The central, electrically-conductive layer rapidly equalises the electrical potential across the mat whilst the upper layer insulates the asset from the electrically-conductive layer. The lower layer is made of a special, electrically-conductive layer that protects the central layer and provides electrical continuity to that layer. Key practical features of the EPR safety mat have also been considered. All of the layers are sufficiently flexible to enable the mat to rolled and unrolled as required in temporary and semipermanent applications. Furthermore, mats can be joined to make larger mats as required.

3. Verification of the EPR Safety Mat A. Modelling Outcomes TECHNICAL PAPER The CDEGS software package was used to model an extremely severe EPR scenario, viz. a 100 ka cloud-to-ground lightning flash at a distance of 50 metres. Calculations were performed for a soil resistivity of 250 m 1 at four unique sinsusoidal frequencies (50, 500, 5000 and 50,000 Hz). The soil EPR in the surrounding area was modelled for two scenarios, i.e., with and without the EPR safety mat. In each case, the expected step and touch voltage was computed. Figure A1 of Annex A shows an EPR contour plot for each scenario. It can be seen that the EPR safety mat attains, across its physical extent, a mean voltage representative of the soil potential its location. Figures A2 and A3 of Annex A show the step and touch voltage expected in the case of a person standing on the ground versus on the safety mat, respectively. A sharp contract (improvement) is seen in these two figures. An assessment of frequency dependence of the results was carried out in order to allow for the fact that a lightning discharge (in contrast to power system faults) is a high-frequency transient. It was found that the phenomenon being investigated (EPR effects and consequences) is relatively insensitive to the frequency of the current injected into the ground. B. Field Testing Outcomes Field testing of the EPR Safety Mat involved the use of current injection techniques, namely the well-known fall-of-potential (FOP) methodology, as described in ENA EG1, IEEE Std. 80, IEEE Std. 81 and other standards around the world. The method is shown in Figure B1 of Annex B. In other words, earth potential rise was created by injecting a known, constant current into the circuit comprising a real earthing system (e.g., a substation earth grid) and a temporary set of current injection electrodes. The testing was carried out with a calibrated Mitton LCI 2000 current injection test set. This professional-grade instrument is used for testing all types of earthing systems. It is capable of injecting a constant current of up to 10 A into the earthing system. The test frequency is 58 Hz in order to avoid interference from power frequencies. The injector was used with special tuned voltmeters (TVM) which are designed to pick up only the 58 Hz frequency injected. All EPR and step and touch voltage measurements were made with two calibrated TVM1000P-GPS meters. Step and touch voltage measurements with the TVM s were made with flat aluminium plates to simulate the electrical contact of a human foot with the ground. One large plate (approx. 400 cm 2 ) was used for touch voltage measurements to simulate the contact of two feet in parallel. Two smaller plates (each approx. 200 cm 2 ) were used for step voltages. 1 This resistivity value is known to be in the worst case range from the viewpoint of personnel safety.

The overall test procedure comprised measurements of step and touch voltage at specified locations without the EPR Safety Mat, followed by the same measurements in the same locations with the mat installed. Figures B2 to B5 in Annex B show some typical scenarios that were assessed. The locations chosen for testing the EPR Safety Mat were those ones found to have very high touch voltages (and hence most likely to be non-compliant). Whilst the testing involved a HV power system, the efficacy of the EPR Safety Mat for mitigating the effects of lightning will be essentially identical. Lightning injects a fault current into the soil in much the same way, even though the magnitude is often larger. Table 1 shows the results of the testing with and without the EPR Safety Mat installed. A significant reduction in step and touch voltages can be seen across the board. Note that the upper insulating layer of the mat provides an additional benefit in limiting the body current in the case of elevated touch voltages. This aspect is not taken into account in the raw values shown in Table 1. Table 1: Results obtained for step and touch voltage with and without the EPR Safety Mat for locations where high EPR was found. The values tabulated apply to a fault current of 10 ka. Some touch voltage values are presented for two configurations, namely with and without an electrical bond between the mat and the touchable item. These are shown in blue and black respectively. Without Mat With Mat LOCATION Touch Voltage (V) Step Voltage (V) Touch Voltage (V) Step Voltage (V) 11 kv / 415 V transformer bay gate 93,000 22.7 40,000; 773 2.7 11 kv switchroom handrail front 329.3 87.3 5.0 1.0 11 kv / 415 V transformer yard fence corner 287.7 256.0 114.3 0.3 Crib room outdoor wash basin 730.0 4.7 286.7; 8.3 1.0

4. Conclusions The modelling and field testing carried out clearly demonstrates the efficacy of the EPR safety mat in redistributing the surface voltage profile to help mitigate EPR-related hazards. The CDEGS modelling demonstrated that a significant reduction in step and touch voltage is achieved when the EPR safety mat is used in situations where living beings and assets are at risk. The function of the EPR safety mat was verified via a full-scale current injection test in the field in situations where hazardous voltages were detected. A significant reduction in step and touch voltages was seen across the board. Whilst the EPR Safety Mat can be used without an electrical bond to the touchable item (since it redistributes the surface voltage profile), enhanced performance and voltage reduction is achieved when an electrical bond is used.

Annex A: Modelling Results Scalar Potentials/Scalar Potentials [ID:SafetyMat_none @ f=50.0000 Hz ] 7.5 SPOT LEVELS x 1.E+3 Maximum Value : 90.403 Minimum Value : 70.633 90.40 2.5-2.5-7.5-7.5-2.5 2.5 7.5 88.43 86.45 84.47 82.50 80.52 78.54 76.56 74.59 72.61 Potential Profile Magnitude (Volts) (a) Scalar Potentials/Scalar Potentials [ID:SafetyMat @ f=50.0000 Hz ] 7.5 SPOT LEVELS x 1.E+3 Maximum Value : 90.149 Minimum Value : 70.713 90.15 2.5-2.5-7.5-7.5-2.5 2.5 7.5 88.21 86.26 84.32 82.37 80.43 78.49 76.54 74.60 72.66 Potential Profile Magnitude (Volts) (b) Figure A1: Plot of the EPR contours due to 100 ka cloud-to-ground lightning flash. (a) Without the EPR safety mat. (b) With the EPR safety mat.

4.5 3.0 Scalar Potentials/Step Voltages (Gradient) [ID:SafetyMat_none_S&T @ f=50.0000 Hz ] LEGEND Maximum Value : 1753.094 Minimum Value : 1448.906 1753.09 1722.68 1.5 0.0-1.5-3.0-1.5 0.0 1.5 3.0 1692.26 1661.84 1631.42 1601.00 1570.58 1540.16 1509.74 1479.32 Gradient Step Voltage Magn. (V/M) (a) 4.5 3.0 Scalar Potentials/Touch Voltages/Worst Spherical [ID:SafetyMat_none_S&T @ f=50.0000 Hz ] SPOT LEVELS x 1.E+6 Maximum Value : 4 Minimum Value : 11.646 1.5 0.0-1.5-3.0-1.5 0.0 1.5 3.0 Touch Voltage Magn. (Volts) [Wors] (b) Figure A2: Contour plot for the (a) step and (b) touch voltage resulting from the 100 ka cloud-toground lightning flash for a scenario in which a person is standing on the ground (no safety mat).

4.5 3.0 Scalar Potentials/Step Voltages (Gradient) [ID:SafetyMat_S&T @ f=50.0000 Hz ] LEGEND Maximum Value : 1701.188 Minimum Value : 12.344 1701.19 1532.30 1.5 0.0-1.5-3.0-1.5 0.0 1.5 3.0 1363.42 1194.53 1025.65 856.77 687.88 519.00 350.11 181.23 Gradient Step Voltage Magn. (V/M) (a) 4.5 3.0 Scalar Potentials/Touch Voltages/Worst Spherical [ID:SafetyMat_S&T @ f=50.0000 Hz ] LEGEND Maximum Value : 566.789 Minimum Value : 0.785 566.79 510.19 1.5 0.0-1.5-3.0-1.5 0.0 1.5 3.0 453.59 396.99 340.39 283.79 227.19 170.59 113.99 57.39 Touch Voltage Magn. (Volts) [Wors] (b) Figure A3: Contour plot for the (a) step and (b) touch voltage resulting from the 100 ka cloud-toground lightning flash for a scenario in which a person is standing on the mat.

Annex B: Field Testing Results Figure B1: Typical FOP test layout (from ENA EG1). Figure B2: Touch voltage measurement at a switchroom handrail.

Figure B3: Step and touch voltage measurement near an 11 kv substation fence.

Figure B4: Step and touch voltage measurement at an outdoor wash basin where a transfer voltage hazard was detected.

Figure B5: Step and touch voltage measurement near an 11 kv / 415 V transformer bay.=