CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, May, Establishment of a new lightning location system in Croatia

Similar documents
Flash Density Maps of Serbia for

Lightning current field measurement on a transmission line, comparison with electromagnetic transient calculations

University of Zagreb Faculty of Electrical Engineering and Computing

Lightning Overvoltage Performance of 110 kv Air-Insulated Substation

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Development Progress of Dual-band Lightning Locating System

A Real Time Lightning Locating Approcah for the Transmission System in Geographic Information System

Lightning and Power Systems. Application of Lightning Locating System for Improvement of Medium Voltage Power Systems Planning and Operation

PROTECTION RELAY FOR SHAFT CURRENT AND VOLTAGE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

MULTI-STATION SHORT BASELINE LIGHTNING MONITORING SYSTEM

PERFORMANCE CHARACTERISTICS OF THREE DISTINCT LIGHTNING DETECTION NETWORKS COVERING BELGIUM

PROFEO : PROGRAMME FRANCILIEN D ETUDES DES ORAGES. P. Blanchet, P. Lalande, P. Laroche Onera Châtillon France

IMPROVEMENTS OF THE FACILITIES FOR LIGHTNING RESEARCH AT MORRO DO CACHIMBO STATION

Observing Lightning Around the Globe from the Surface

Review of CIGRE Report Cloud-to-Ground Lightning Parameters Derived from Lightning Location Systems The Effects of System Performance

Sferic signals for lightning sourced electromagnetic surveys

Ariadna Instruments. Power cable identifier & LV live network phase and feeder identifier

MULTIPLE-INPUT MULTIPLE-OUTPUT (MIMO) The key to successful deployment in a dynamically varying non-line-of-sight environment

Evaluation for the performance of the Guangdong- Hongkong-Macau Lightning Location System

EUCLID NETWORK PERFORMANCE AND DATA ANALYSIS

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Paper presented at the Int. Lightning Detection Conference, Tucson, Nov. 1996

Protection criteria for arrival time difference receivers operating in the meteorological aids service in the frequency band 9-11.

2000 Mathematics Subject Classification: 68Uxx/Subject Classification for Computer Science. 281, 242.2

ELECTRIC FIELD WAVEFORMS OF UPWARD LIGHTNING FORMING HOT SPOT IN WINTER IN JAPAN

723 Specialized 80 to 500 MHz Radio Direction Finding System For Airport Interference Detection

The Problem of Interference

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

FREQUENCY DECLARATION FOR THE ARGOS-4 SYSTEM. NOAA-WP-40 presents a summary of frequency declarations for the Argos-4 system.

PD Solutions. On-Line PD Measurement Devices

Lightning Warning System Carlos A. Morales 1, João R. Neves 1, Evandro M. Anselmo 1, Marcio A. Mathias 2, Cesar S. Rabak 3 and Keyla Sampaio Camara 4

The line-lightning performance and mitigation studies of shielded steelstructure

GROUNDING OF CONTROL CABLE SHIELDS: DO WE HAVE A SOLUTION?

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Wavelet Analysis for Negative Return Stroke and Narrow Bipolar Pulses

ABSTRACTS of SESSION 6

The Lightning Event. White Paper

In order to minimise distribution (11 and 22 kv) feeder breaker

Matching and Locating of Cloud to Ground Lightning Discharges

Study on monitoring technology of aircraft engine based on vibration and oil

Lightning scatter: a faint and rare mode of propagation

ANSE VISUAL, developed within the

Electromagnetic Shielding Analysis of Buildings Under Power Lines Hit by Lightning

Performance Evaluation for a Lightning Location System Based on Observations of Artificially Triggered Lightning and Natural Lightning Flashes

2 INTRODUCTION TO GNSS REFLECTOMERY

Modeling insulation in high-voltage substations

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

Session 2002 CIGRÉ. Evaluation of Lightning Location Data Employing Measurements of Direct Strikes to a Radio Tower

INSTALLATION OF LSA ON A 400 KV DOUBLE-CIRCUIT LINE IN RUSSIA

ELECTROMAGNETIC FIELD APPLICATION TO UNDERGROUND POWER CABLE DETECTION

Investigation on the Performance of Different Lightning Protection System Designs

Some studies of solar flare effects on the propagation of sferics and a transmitted signal

Analysis of Electromagnetic Transients in Secondary Circuits due to Disconnector Switching in 400 kv Air-Insulated Substation

LOCATION ACCURACY EVALUTION OF THE AUSTRIAN LIGHTNING LOCATION SYSTEMS ALDIS

Understanding Design, Installation, and Testing Methods That Promote Substation IED Resiliency for High-Altitude Electromagnetic Pulse Events

NETWORK INNOVATION COMPETITION ANGLE-DC PROJECT HOLISTIC CIRCUIT CONDITION MONITORING SYSTEM REPORT

GPS and GSM Based Transmission Line Monitoring System with Fault Detection Introduction:

Lightning observations from space: Time and space characteristics of optical events. Ullrich Finke, FH Hannover 5 th December, 2007

Data Analysis for Lightning Electromagnetics

Abstract. 1 Introduction

Earthing of Electrical Devices and Safety

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

Electric Power Systems Research

t =1 Transmitter #2 Figure 1-1 One Way Ranging Schematic

CONTENTS. 1. Introduction Generating Stations 9 40

Summary of Research Activities on Microwave Discharge Phenomena involving Chalmers (Sweden), Institute of Applied Physics (Russia) and CNES (France)

ELEC Transmission i and

IEEE Transactions on Power Delivery. 15(2) P.467-P

Modeling of overhead transmission lines with line surge arresters for lightning overvoltages. Poland

Photonic Power. Application Overview

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Recommendation ITU-R F (05/2011)

Fault Location Using Sparse Wide Area Measurements

The Influence of Atmospheric Overvoltages on High-Voltage SF 6. Substations

HF-Radar Network Near-Real Time Ocean Surface Current Mapping

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

Time-Frequency Analysis of Narrow Bipolar Pulses observed in Sri Lanka

Lightning Interferometer via VHF Emission (LIVE)

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Partial Discharge Measurement and Monitoring on High Voltage XLPE Cables

Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies

Diagnostic testing of cast resin transformers

Transmission of Electrical Energy

Cable Protection against Earth Potential Rise due to Lightning on a Nearby Tall Object

Questions on Electromagnetism

Hybrid system using both USBL and LBL for shallow waters

The Role of the Grounding System in Electronics Lightning Protection

An Introduction to Remote Sensing & GIS. Introduction

Investigation of skin effect on coaxial cables

Light measures current

720 VHF/UHF 80 to 500 MHz Maritime and Coastal Surveillance

Information on the Evaluation of VHF and UHF Terrestrial Cross-Border Frequency Coordination Requests

Radio Direction Finding System, a new perspective for global crust diagnosis

T Mani Bhowmik Dated:

Hazard of Induced Overvoltage to Power Distribution Lines Jiang Jun, Zhao Rui, Chen Jingyang, Tian Hua, Han Lin

ATP SIMULATION OF FARADAY CAGE FOR THE ANALYSIS OF LIGHTNING SURGES

Technical Requirements for Fixed Radio Systems Operating in the Bands GHz and GHz

Safety Code 6 (SC6) Measurement Procedures (Uncontrolled Environment)

Transcription:

CIGRE C4 Colloquium on Lightning and Power System, Kuala Lumpur, 16 19 May, 2010 Establishment of a new lightning location system in Croatia I. UGLEŠIĆ V. MILARDIĆ B. FRANC B. FILIPOVIĆ-GRČIĆ Faculty of Electrical Engineering and Computing, University of Zagreb Croatia J. HORVAT Končar Power Plant and Electric Traction Engineering Inc. Croatia SUMMARY At the end of 2008, a new lightning location system (LLS) was established as part of LINET lightning detection network, which was developed in Germany and nowadays counts over 100 sensors installed across Europe. Four sensors were installed in different parts of Croatia. Together with sensors in neighbour countries, a sensor baseline of 250 km has been achieved covering Croatian territory. First data analysis show satisfactory detection efficiency (DE) and location accuracy (LA) with a statistical error less than 300 m. However, conducted analyses showed that network performance improvement is possible by installing two additional sensors. Software for real time lightning tracking with alarm function, analysis of lightning history, statistical calculations, correlation with power lines and creation of lightning density maps is being developed. Additional functionalities are in plan by connecting lightning data with SCADA, which enables a complete time and space correlation between lightning strikes and faults on transmission lines. Application of this software could provide as an effective decision making tool in control, maintenance and development of power systems. Paper shows examples of software application in power systems. Lightning data analysis for a period of one year are conducted in order to achieve a more comprehensive statistics. Analysis will show: number and ratio of lightning detected in Croatia distributed by type and polarity in different time periods; lightning current amplitude distribution; mean and average values of current amplitude and locating error. KEYWORDS Lightning location system, LINET, GIS, spatial correlation, SCADA, relay protection, lightning data analysis bojan.franc@fer.hr

1. INTRODUCTION Tracking and surveillance of atmospheric discharges in real time and space can be an effective mean and great help in power system control. Lightning locating systems (LLS) are constantly developed and used in countries around the world for more than twenty years. 2. LIGHTNING LOCATING SYSTEM LINET European lightning locating system LINET was developed in Germany, where 30 sensors are installed around the country. Additional 65 sensors are installed across different European countries. The established sensor network covers the most of European territory (Figure 1). In the year 2006 the LINET lightning locating system started to operate [1]. LINET uses very low and low frequency (VLF/LF) band and registers the true waveform B(t) of the magnetic flux upon an atmospheric discharge. Main features of LINET system are: a) Ability to detect and locate the total atmospheric discharge with same locating error for inter-cloud (IC) and cloud-ground (CG) discharges; b) Great accuracy in location of both IC and CG discharges of low current amplitude; c) New 3D technique for a reliable discrimination of IC and CG discharges; d) Altitude reports for IC discharges; e) Locating accuracy up to 100 m. Figure 1 Location of LINET sensors in Europe [6] 1

2.1. LIGHTNING DETECION PRINCIPLES The LINET sensors measure the density of magnetic flux directly into the dependence of time. This feature is useful for the treatment of small signals. Magnetic flux component of detected signals are measured using orthogonal loop (antenna) in real time. Amplified value is induced current, not voltage, and as a result, the time dependence of the magnetic induction in the range 0.1 to 130 nt is obtained [2]. The system LINET uses TOA (Time Of Arrival) method for determining the location of lightning impact assisted with method for determining the direction (DF, eng. Direction Finding). Primarily TOA method is used for determining the location, where minimum four detection sensors are required. By combining TOA and DF methods the discharge can be detected by two or three sensors, but in this case, the location determine error is increased [1]. In LINET system important components are optimized to determinate all lightning discharge, including those whose amplitude is less than 5 ka, where sensors should not be too far away [3]. LINET uses the same VLF/LF method for detection of CG and IC lightning discharges [4]. Special consideration should be taken into account to distinct these two types of lightning. For this reason, a new three-dimensional (3D) geometric algorithm for VLF / LF networks was developed [5]. The procedure relies on the well-known fact that CG strikes broadcast VLF / LF discharge dominant in ionized channel near the ground level, while IC discharge occur in the ionized channel between clouds, high above the ground. The corresponding differences in time spreading of electromagnetic waves (Figure 2) caused by high and low centers of stationary discharge were used to locate the discharge position. This method is satisfactory, as long as the distance between the lightning stroke and the nearest sensor does not exceed 100 km (corresponding to distance between sensors of 200 km), or differences in results of this method become too small to be noticeable. All the signals are processed regardless of their waveform; this is possible because the IC- CG resolution is carried out using specially developed 3D algorithms in the central processing unit, not with measurement of waveform in sensors. This 3D technology is very reliable, especially if it is possible that the minimum distance between the sensors does not exceed 200 to 250 km. Figure 2 The principle of detection of IC discharge - IC and CG signals from the same 2D location come from the time difference dt = TP-TH (P = VLF emission center, S = sensor location; H = height of emission source) [1] Particular efforts were made to achieve high location accuracy in monitored area. Today, it is achieved that the mean location accuracy is approximately 100 m. 2

Output data is discharge time, location, current amplitude (including sign), the division between IC and CG discharge, discharge height for IC and 2D locating error. LINET is capable of detecting multiple-stroke flashes where every stroke is represented by individual set of data. A LINET sensor consist of two passive parts: the GPS antenna and the antenna for measuring magnetic flux (two orthogonal cooper rings); and one active unit the sensor PC. Such sensor design enables the sensor to be very cost effective with a straightforward installation (Figure 3). Figure 3 LINET sensor antennas (orthogonal rings) and GPS antenna In Croatia five sensors are installed at: Dubrovnik, Split, Zadar, Rijeka and Zagreb. 3. SOFTWARE AND ANALYSES For efficient usage of data acquired by lightning locating system, adequate basic and advanced software is required. Basic software implies visualization and archiving of gathered data. With development of advanced software support, custom data analyses are available, like correlation with relay system protection and generation of lightning density maps. Software being developed is based on 3-tier architecture (Figure 4): a) Server-tier (database, mapping server); b) Web-tier (web server); c) Client-tier (thin clients web browsers). 3

Figure 4 LLS software support 3-tier architecture [8] 3.1. STORAGE OF LIGHTNING DATA Data gathered by LINET sensors is transmitted in raw form over Internet lines to Nowcast (LINET) center where it is analysed, bind and transformed into a format ready to be transmitted to clients. Data flow is shown on Figure 5. Figure 5 LINET data flow [7] Lightning data taken from LINET sensor network is archived into a local database. Clients can access data at any time and conduct queries and analyses. Lightning data since 18 th of January 2009 are available: a) Date and time (UTC, 100 ns resolution); b) GPS location Latitude and Longitude (WGS84); c) Stroke current amplitude (0.1 ka resolution); d) Lightning discharge type (IC, CG); e) Altitude for IC discharges; f) 2D location error (meter). 4

Table 1 Lightning data: GPS DATE and TIME TYPE ALTITUDE CURRENT ERROR 15.8932 45.7170 29.4.2009 18:57:05.5952183 CG - -15 ka 42 m 15.8920 45.7036 29.4.2009 19:07:32.7712689 CG - -5.2 ka 57 m 15.8508 45.7407 29.4.2009 18:50:47.1437623 CG - 72.2 ka 54 m 15.8502 45.7388 29.4.2009 19:00:03.8719696 CG - 8.1 ka 67 m 15.8914 45.7283 29.4.2009 19:00:03.9402258 CG - -2.9 ka 81 m 15.8214 45.7566 29.4.2009 18:50:47.1127271 IC 3600 (m) -5.5 ka 58 m 15.8963 45.7263 29.4.2009 19:09:53.8456357 IC 4800 (m) 7.4 ka 63 m 15.8647 45.7595 29.4.2009 19:07:01.6730042 IC 4100 (m) 4.7 ka 60 m 15.8117 45.7558 29.4.2009 18:49:09.4577769 IC 5900 (m) -10.7 ka 89 m Figure 6 shows number of lightnings detected in Croatia and the average locating (statistical) error, distributed by month. Territory of Croatia with a 3 km buffer (100 348 km 2 ) is taken while performing spatial analyses. Table 2 No. of lightning strokes in Croatia in 1 year period CG+ CG- IC+ IC- 230 000 592 741 158 205 150 568 160.000 No. of lightning strokes and average locating error for Croatia 400 CG+ CG- 140.000 IC+ CG+ error IC- CG- error 350 IC+ error IC- error 120.000 300 100.000 250 No. of lightnings 80.000 60.000 200 150 Locating error (meter) 40.000 100 20.000 50 0 0 Month Figure 6 Number of lightning and average locating error in Croatia 5

After one year of gathering data, an error map has been formed showing the statistical error of lightning data. With 5 sensors inside Croatia and additinal 20 sensors in neighbour countries, average locating error across Croatia varies from 50 to 150 m (Figure 7). Figure 7 LLS Average locating error map (0.05 grid) Lightning amplitude distribution graph (Figure 8) shows a good detection of strokes including small amplitude lightning. 60.000 Lightning by amplitude distribution 50.000 CG+ IC+ CG- IC- 40.000 No. of lightnings 30.000 20.000 10.000 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Amplidute (ka) Figure 8 Amplitude distribution of lightning in Croatia in 1 year period 6

3.2. LIGHTNING DATA VISUALIZATION An effective lightning locating system should cover a wider geographic area, like the south-east of Europe where Croatia is located. Lightning visualization (Figure 9 and Figure 10) enables immediate sensing of lightning storm encounter, which helps in power system management assuring the time needed for implementing appropriate security measures. Storm evolvement and CG IC ratio for the monitored storm is depicted in Figure 11. Figure 9 Lightning activity over Croatia on 1st of May 2009 (green CG, red IC) Figure 10 Monitoring of lightning storm over Croatia on 1st of May 2009 (green CG, red IC) 7

Lightnings over Croatia by type 1.000 900 800 700 CG IC No. of strokes 600 500 400 300 200 100 0 12 13 14 15 16 17 18 19 20 Hour Figure 11 Lightnings over Croatia on 1st of May 2009 by type 3.3. SPATIAL CORRELATION WITH GIS DATA GIS (Geographic Information System) data of transmission lines and substations are linked with LLS data, i.e. precise location and time of atmospheric discharge. GIS is a software decision making tool for gathering, storage, querying, analysing and viewing of spatial data. Using GIS software it is easier to locate faults on transmission lines caused by lightning strikes, so service teams can be rapidly and precisely deployed. Figure 12 and Figure 13 show an example of lightning detection inside a 500 m radius buffer of a doublecircuit 220 kv line during a storm in Croatia. Figure 12 Lightning activity during a storm, inside a transmission line buffer area Figure 13 Lightning strokes correlated with a 500 m buffer of a powerline 8

3.4. CREATION OF ISOKERAUNIC AND DENSITY MAPS Isokeraunic maps display number of lightning days per year for a specified territory. Lightning data has been used to create a isokeraunic map of Croatia. Results have been compared with existing isokeraunic map (Figure 14) [9] showing good overlap. Figure 14 LLS created isokeraunic map compared to previously created party map An important function of lightning locating system is generation of lightning density maps (Figure 15), especially around transmission lines and substations. This data is a great decision making help to engineers while choosing adequate protection (e.g. surge arresters) and finding the optimal location for protection installation. For better understanding of density maps displayed in this paper, an explanation will be given. As lightning data obtained from LINET records each stroke as an individual set of data, and stroke multiplicity is a well known fact [10] (especially for negative CG flashes), density maps will display noticeable higher values. Additionally, time period of one year may be too short to represent a detailed distribution. Figure 15 Density map for Croatia (1 year period, 1km grid, individual strokes) 9

For each transmission line high-resolution density map (Figure 16) can be made and the most exposed sections can be located. With analyse of lightning currents and polarities, optimal protection can be chosen. Lightning density maps can be used for determination of optimal routes for building new transmission lines, avoiding exposed areas, thus minimising the risks of failure. Lightning density is calculated by formula (1): 2 [ strokes / km year] n N g = / (1) A t n no. of strokes; A area (km 2 ); t time period (years) Figure 16 Density map (1 year period, 1km grid, individual strokes) 3.5. CORRELATION WITH SCADA Lightning locating system can be linked to SCADA, correlating in real-time events registered in the power system (faults, automatic reclosures, etc.) with lightning data. If correlated with GIS data of transmission lines and substations, very accurate time and space correlations are possible. Correlations can be displayed on map in near real-time. Figure 17 shows a simplified correlation schema. Figure 17 Correlation schema LLS - GIS SCADA 10

A short example of correlation is given to demonstrate the time-space correlation of LLS, GIS and SCADA. Lightning data has been correlated with SCADA events and proximate (500 m error) GIS data of a double-circuit 220 kv line connecting hydropower plant (HPP) and a substation. HPP registered failures on both circuits at 16:27 local time (more precise time information is not available). LLS registered 3 strikes (2 of them are multiple) as candidates causing the failures (Table 3). For more precise discrimination, GPS synchronization of SCADA is needed. Table 3 Lightning candidates causing failures on the double-curcuit 220 kv line GPS location Date and time Amplitude Location error 16.7177 43.6103 4.5.2009 16:26:12.8821294-25 (ka) 40 m 16.6969 43.6126 4.5.2009 16:26:12.9216174-14.7 (ka) 40 m 16.7242 43.6112 4.5.2009 16:26:56.8094749-38.9 (ka) 60 m 16.7205 43.6099 4.5.2009 16:26:56.8322992-25.5 (ka) 40 m 16.7203 43.6102 4.5.2009 16:26:57.1222884-9.8 (ka) 60 m 4. CONCLUSION Lightning locating systems continuously improve and evolve, and nowadays are a powerful tool in planning, protection and management of power systems. LLS are also used in other technological systems and networks, e.g. telecommunication, transmitter and repeater stations, oil and gas pipelines, insurance companies, military, meteorology, air travel, fire department, etc. This paper demonstrates a lightning locating system applied in power systems. First lightning data has been archived and analysed. Archived data shows good detection efficiency and locating accuracy. Lightning data has been correlated with GIS data of transmission lines and events in power system gathered from SCADA. Analyses demonstrated positive impacts of LLS in management of power system. Correlated data can improve response time for repairs and minimize faults caused by lightning strikes. BIBLIOGRAPHY [1] Betz H. D., Schmidt K., Laroche P., Blanchet P., Oettinger W. P., Defer E., Dziewit Z., Konarski J.: LINET An international lightning detection network in Europe, 2007. [2] Betz H. D., Kulzer R., Gerl A., Eisert B., Oettinger W.P., Jakubassa D.,: On the Correlation between VLF-Atmospherics and Meteorological data, ICLP Firence, 1996. [3] Betz H. D., Schmidt K.,Fuchs B., Oettinger W.P., Hoeller H.: Cloud Lightning: Detection and Utilization for Total Lightning Measured in the VLF/LF Regime, Journal of Lightning Research, August 2007. [4] Betz H. D., Oettinger W.P., Schmidt P., Wirz M.: Modern Lightning Detection and Implementation of a New Network in Germany, Europe, European Geosciences Union 2005, Geophysical Research Abstracts, Vol. 7, 00685,2005. [5] Betz H. D., Schmidt K., Laroche P., Blanchet P., Oettinger W.P., Defer E.: LINET A new lightning detection network in Europe, 13th International Conference on Atmospheric Electricity, August 13-18, 2007., Beijing, China. [6] https://www.nowcast.de/en/produkte-und-vorteile/linet-data.html, 2 nd of March 2010 [7] https://www.nowcast.de/en/produkte-und-vorteile.html, 2 nd of March 2010 [8] http://sandbox.mapguide.com/index.php/main_page, 2 nd of March 2010 [9] Uglešić I., Milardić V.: Elected Topics of High Voltage Engineering, Croatia, 2007 [10] Hileman A. R.: Insulation Coordination for Power Systems, USA, 1999 11