Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network

Similar documents
A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Power Quality improvement of a three phase four wire system using UPQC

Improvement of Power Quality Using a Hybrid Interline UPQC

A Power Control Scheme for UPQC for Power Quality Improvement

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

A Novel Approach to Simultaneous Voltage Sag/Swell and Load Reactive Power Compensations Using UPQC

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Mitigation of Voltage Sag/Swell Using UPQC

Control of Shunt Active Power Filter for Improvement of Power Quality

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Performance of DVR under various Fault conditions in Electrical Distribution System

Harmonic Analysis in Non-linear Load by using Hybrid UPQC

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

2020 P a g e. Figure.2: Line diagram of series active power filter.

Power Quality Improvement using Shunt Passive Filter

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Comparative Analysis of Grid Power Quality using DVR, DSTATcom, Open UPQC and SVC Light In Grid Wind Energy System

Control Strategy for a cross phase connected and a conventional UPQC

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

Simulation Study of PWM Techniques for Voltage Source Converters

Application of Fuzzy Logic Controller in Shunt Active Power Filter

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Performance of DVR & Distribution STATCOM in Power Systems

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

A Modified Control Method For A Dual Unified Power Quality Conditioner

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Power Quality Improvement in Fourteen Bus System using UPQC

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Power Quality Improvement using Active shunt Power filter using PI Controller

Power Quality Improvement using Hysteresis Voltage Control of DVR

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Power Quality Improvement By Using DSTATCOM Controller

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Harmonics Reduction using 4-Leg Shunt Active Power Filters

UPQC for Improvement Power Quality.

UPQC (Unified Power Quality Conditioner)

Power Quality enhancement of a distribution line with DSTATCOM

Power Control Scheme of D-Statcom

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

ISSN Vol.03,Issue.11, December-2015, Pages:

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

PSPWM Control Strategy and SRF Method of Cascaded H-Bridge MLI based DSTATCOM for Enhancement of Power Quality

Downloaded from

SIMULATION OF D-STATCOM IN POWER SYSTEM

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Application of Distribution Static Synchronous Compensator in Electrical Distribution System

ANALYSIS OF UNIFIED POWER QUALITY CONDITIONER DURING VOLTAGE SAG AND SWELL CONDITIONS

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

ISSN Vol.07,Issue.21, December-2015, Pages:

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

International Journal of Research (IJR) e-issn: , p- ISSN: X Volume 2, Issue 09, September 2015

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Modeling and Simulation of SRF and P-Q based Control DSTATCOM

Review on Shunt Active Power Filter for Three Phase Four Wire System

ISSN Vol.04,Issue.08, July-2016, Pages:

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

ISSN: [Yadav* et al., 6(5): May, 2017] Impact Factor: 4.116

Mitigation of Power system Disturbance by Using MC-UPQC with PI, ANN & FUZZY Controller Technique

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Mitigation of Voltage Sag, Swell and Load Hamonics by the Combined Opertation of Series APF and Solar System

DESIGN A D STATCOM FOR VOLTAGE HARMONIC SUPPRESSION IN DISTRIBUTION SYSTEM

Transcription:

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 01, 2014 ISSN (online): 2321-0613 Analysis & Function of Unified Power Quality Conditioner for Power Quality Improvement of Distributed Network Kushang Parmar 1 Jaydeep Sarvaiya 2 1 M. E. [Electrical] Student 2 Assistant Professor 1, 2 Department of Electrical Engineering 1,2 Shantilal Shah Engineering College, Bhavnagar, Gujarat, India Abstract--- In this paper a technical review of the integration of a Unified Power Quality Conditioner (UPQC) in a distributed generation network is presented.. The increasing use of the Nonlinear devices, such as power electronics converters, inject harmonic currents in the AC system and increase overall reactive power demanded by the equivalent load. Also, the number of sensitive loads that require ideal sinusoidal supply voltages for their proper operation has increased. This paper deals with the shunt APF, series APF and the unified power quality conditioner (UPQC) which aims at the integration of series and shunt active filters. The main purpose of a UPQC is to compensate for voltage flicker/imbalance, reactive power, negative sequence current and harmonics. In other words, the UPQC has the capability of improving power quality at the point of installation on power distribution systems or industrial power systems. & reduce the THD of voltage & current level. Keywords: Active power filter (APF), harmonic compensation, power quality, reactive power compensation, unified power quality conditioner (UPQC), voltage sag and swell compensation. I. INTRODUCTION This paper represent about that It has been always a challenge to maintain the quality of electric power within the acceptable limits. Poor power quality may result into increased power losses, abnormal and undesirable behavior of equipment s, interference with nearby communication lines, and so forth. The widespread use of power electronic based systems has further put the burden on power system by generating harmonics in voltages and currents along with increased reactive current. So by reduce the voltage sag, voltage swell, and harmonic distortion by these custom power devices. The term active power filter (APF) is a widely used terminology in the area of electric power quality improvement.so by reduces the power quality problem like a voltage sag voltage swell, harmonic distortion by these custom power devices. Custom power devices like SOLID STATE TRANSFER SWITCH, D STATCOM, DYNAMIC VOLTAGE RESTORER, UNIFIED POWER QUALITY CONDITIONER devices. II. SUPERIORITY OF UPQC OVER OTHER DEVICES Each of Custom Power devices has its own benefits and limitations. The UPQC is expected to be one of the most powerful solutions to large capacity loads sensitive to supply voltage and load current disturbances imbalance. The most effective type of these devices is considered to be the Unified Power Quality Conditioner (UPQC). There are numerous reasons why the UPQC is preferred over the others. UPQC is much flexible than any single inverter based device. It can simultaneously correct for the unbalance and distortion in the source voltage and load current whereas all other devices either correct current or voltage distortion. Therefore the purpose of two devices is served by UPQC only. III. UNIFIED POWER QUALITY CONDITIONER (UPQC) The best protection for sensitive loads from sources with inadequate quality, is shunt-series connection i.e. unified power quality conditioner (UPQC).Recent research efforts have been made towards utilizing unified power quality conditioner (UPQC) to solve almost all power quality problems for example voltage sag, voltage swell, voltage outage and over correction of power factor and unacceptable levels of harmonics in the current and voltage The basic configuration of UPQC is shown in fig1.the main purpose of a UPQC is to compensate for supply voltage flicker/imbalance, reactive power, negative-sequence current, and harmonics.in other words, the UPQC has the capability of improving power quality at the point of installation on power distribution systems or industrial power systems. The UPQC, therefore, is expected as one of the most powerful solutions to large capacity sensitive loads to voltage flicker imbalance. Unified Power Quality Conditioner (UPQC) for non-linear and a voltage sensitive load has following facilities: It eliminates the harmonics in the supply current, thus improves utility current quality for nonlinear loads. UPQC provides the VAR requirement of the load, so that the supply voltage and current are always in phase, therefore, no additional power factor correction equipment is necessary. UPQC maintains load end voltage at the rated value even in the presence of supply voltage sag. The voltage injected by UPQC to maintain the load end voltage at the desired value is taken from the same dc link, thus no additional dc link voltage support is required for the series compensator. The UPQC consists of two three phase inverters connected in cascade in such a manner that Inverter I is connected in series with the supply voltage through a transformer inverter II is connected in parallel with the load. The main purpose of the shunt compensator is to compensate for the reactive power demanded by the load, to eliminate the harmonics and to regulate the common dc link voltage. The series compensator is operated in PWM voltage controlled mode. It injects voltage in quadrature advance to the supply voltage (current) such that the load end voltage always maintained at the desired value. The two inverters operate in a coordinated manner. All rights reserved by www.ijsrd.com 717

Voltage-Source Converter based Custom power devices are increasingly being used in custom power applications for improving the power quality (PQ) of power distribution systems. Devices such as distribution static compensator (DSTATCOM) and dynamic voltage restorer (DVR) are extensively being used in power quality improvement. A DSTATCOM can compensate for distortion and unbalance in a load such that a balanced sinusoidal current flows through the feeder. It can also regulate the voltage of a distribution bus. A DVR can compensate for voltage sag/swell and distortion in the supply side voltage such that the voltage across a sensitive/critical load terminal is perfectly regulated. A unified power-quality conditioner (UPQC) can perform the functions of both DSTATCOM and DVR. The UPQC consists of two voltage-source converters (VSCs) that are connected to a common dc bus. One of the VSCs is connected in series with a distribution feeder, while the other one is connected in shunt with the same feeder. The dc links of both VSCs are supplied through a common dc capacitor. Fig. 1: Configuration of UPQC. The Unified Power Quality Conditioner is a custom power device that is employed in the distribution system to mitigate the disturbances that affect the performance of sensitive and/or critical load. It is a type of hybrid APF and is the only versatile device which can mitigate several power quality problems related with voltage and current simultaneously therefore is multi functioning devices that compensate various voltage disturbances of the power supply, to correct voltage fluctuations and to prevent harmonic load current from entering the power system. Fig1 shows the system configuration of a single-phase UPQC. Unified Power Quality Conditioner (UPQC) consists of two IGBT based Voltage source converters (VSC), one shunt and one series cascaded by a common DC bus. The shunt converter is connected in parallel to the load. It provides VAR support to the load and supply harmonic currents. The series converter connected in series to the load provides voltage compensation. Thus UPQC improves the power quality by preventing load current harmonics and by correcting the input power factor. IV. BASIC CONFIGURATION OF UPQC The main components of a UPQC are series and shunt power converters, DC capacitors, low-pass and high-pass passive filters, and series and shunt transformers: Series converter It is a voltage-source converter connected in series with the AC line and acts as a voltage source to mitigate voltage distortions. It is used to eliminate supply voltage flickers or imbalance from the load terminal voltage and forces the shunt branch to absorb current harmonics generated by the nonlinear load. Control of the series converter output voltage is usually performed using sinusoidal pulse-width modulation (SPWM). The gate pulses required for converter are generated by the comparison of a fundamental voltage reference signal with a high-frequency triangular waveform. Shunt converter It is a voltage-source converter connected in shunt with the same AC line and acts as a current source to cancel current distortions, compensate reactive current of the load, and improve the power factor. It also performs the DC-link voltage regulation, resulting in a significant reduction of the DC capacitor rating. The output current of the shunt converter is adjusted using a dynamic hysteresis band by controlling the status of semiconductor switches so that output current follows the reference signal and remains in a predetermined hysteresis band. Midpoint-to-ground DC capacitor bank It is divided into two groups, which are connected in series. The neutrals of the secondary transformers are directly connected to the DC link midpoint. As the connection of both three-phase transformers is Y/Yo, the zero-sequence voltage appears in the primary winding of the series-connected transformer in order to compensate for the zero-sequence voltage of the supply system. No zero-sequence current flows in the primary side of both transformers. It ensures the system current to be balanced even when the voltage disturbance occurs. Low-pass filter It is used to attenuate high frequency components at the output of the series converter that are generated by high-frequency switching. High-pass filter It is installed at the output of shunt converter to absorb current switching ripples. Series and Shunt transformers These are implemented to inject the compensation voltages and currents, and for the purpose of electrical isolation of UPQC converters. The UPQC is capable of steady-state and dynamic series and/or shunt active and reactive power compensations at fundamental and harmonic frequencies. However, the UPQC is only concerned about the quality of the load voltage and the line current at the point of its installation, and it does not improve the power quality of the entire system. Fig. 2: Equivalent circuit for UPQC In this circuit, VS represent the voltage at power supply All rights reserved by www.ijsrd.com 718

VSR VL ISh is the series-apf for voltage compensation, represents the load voltage and is the shunt-apf for current and VSR compensation. Due to the voltage Distortion, the system may contain negative phase sequence and harmonic components.in general, the source voltage in Figure 2 can be expressed as: Vs + Vsr = VL To obtain a balance sinusoidal load voltage with fixed amplitude V, the output voltages of the series-apf should be given by; Vsr = (V V1p) sin(ωt+θ1p) VLn(t)- (t) where, V1P: positive sequence voltage amplitude fundamental frequency θ1p: initial phase of voltage for positive sequence V1n: negative sequence component The shunt apf acts as a controlled current source and its output component should included harmonic,reactive negative sequences components in order to compensate these quantities in the load current,when the output current of shunt apf Ish is kept to be equal to the component of the load as given in the following equation. il = I1p cos(ωt+θ1p)sinφ1p + ILn+ φ1p =φ1p - θ1p where, φ1p: initial phase of current for positive sequence As seen from the above equations that the harmonic, reactive and negative sequence current is not flowing into the power source. Therefore, the terminal source current is harmonic-free sinusoid and has the same phase angle as the phase voltage at the load terminal V. FUNCTIONS OF UPQC Reactive Power Compensation Voltage Regulation Compensation for voltage sag and swell Unbalance Compensation for current and voltage (for 3-phase systems Neutral Current Compensation (for 3-phase 4-wire systems). VI. CONTROL STRATEGY OF UPQC The control strategies are proposed here to generate reference signals for both shunt and series APFs of UPQC. An approach based on two closed loop PI controllers for shunt APF utilization and other strategy UTT is exploited to get reference voltage signals for the series APF. Fig.4 shows the reference voltage generation for series and shunt. Fig. 3: Control strategy for Series Active Power Filter A. Reference voltage signal generation for series APF: The extraction of three-phase voltage reference signal for series APF is based on Unit Vector Template Generation, and this is achieved with the help of PLL. These Unit Vector Templates are multiplied with the desirable peak amplitude (Vm) of load voltage to obtained reference load voltages denoted by va*, vb* and vc*. Va*=Vm*ua Vb*=Vm *ub Vc*=Vm *uc B. Reference current signal generation for shunt APF The control strategy for shunt APF is based on the utilization of closed loop PI controllers. These PI controllers are used to get the amplitude of the in-phase components of reference supply currents (Im), The PI controller is realized on the sensed and reference values of DC bus voltage of back-back VSI capacitor of UPQC. To regulate the voltage at PCC the three-phase reference supply currents have component and this component of reference supply currents in-phase with the voltage at PCC. It is very essential to feed active power to the load and the losses of UPQC. The second component is in quadrature component which is quadrature with the voltage at PCC. From above mentioned constrained, the algorithm for control of the shunt APF of UPQC is made flexible to achieve good voltage regulation. The multiplication of amplitude of the in-phase components of reference supply currents (Im) with in-phase unit current vectors(ua, ub and uc) results in the in-phase components (ia*, ib* and ic*) of three-phase reference supply currents. (ia*, ib* and ic*). C. Pulse generation for shunt and series APFs For the generation of gating pulses of MOSFET.s of shunt APF, a carrier-less hysteresis current controller is employed over the reference and sensed supply currents similarly for generation of gating pulses of MOSFET.s All rights reserved by www.ijsrd.com 719

of series APF again a carrier-less hysteresis voltage controller is employed over the reference and sensed voltages at PCC. In this control scheme, the fast changing APF current/voltages is replaced by the current and voltage control is applied over the fundamental components, which reduces the computational delay and the number of required sensors. Inductive Reactive Power=400 VAR Voltage Vrms=11kV, 5 Motor load Frequency 50 Hz 6 Transformer1 Y/Δ/Δ 13/115/115kV 7 Transformer2 Δ/Y 115/11kV Table 1: Technical Parameters for field oriented control induction motor load for Test The proposed model of a three-phase four-wire UPQC and the proposed control scheme are developed in the MATLAB/SIMULINK environment first the reference voltages and the reference currents are generated and then the reference voltages are compared with the actual load voltages and the reference currents are compared with the actual source currents and then the error signals are given to the hysteresis controllers for generating the switching signals for the switches of series active power filter and the shunt active power filter. And the generated pulses are then given to the series and shunt APF.s and accordingly the switches are turned on and off to compensate for the voltage and current harmonics. Fig. 4: Control strategy for Shunt Active Power Filter VII. ADVANTAGE & DISADVANTAGE To eliminate the offset, should be adjusted and reach a constant value when error becomes zero. The integral mode will change the bias value until the error becomes zero eliminate offset. The action is not immediate until the integral becomes significant. Also, the integral mode tends the system to be more oscillatory, even unstable. Advantages are Fast action, eliminate the offset. Disadvantage are Oscillatory or unstable with integral control, one more parameter to tune. VIII. RESULT AND DISCUSSION Technical Parameters for field oriented control induction motor load for Test S. No. System Quantities Standards 1 Source 3-phase, 13kV, 50Hz 2 Inverter parameters 3 PI controller IGBT based, 3-arm, 6-Pulse Carrier Frequency=1080 Hz, Sample Time=5 μs KP=0.5, Ki=1000 for series control Kp=0.5, Ki=1000 for shunt control, Sample time=50 μs 4 RL load Active power = 1kW, Fig. 5: Matlab Simulink Model Of Upqc Using Foc Induction Motor Drive IX. RESULTS WHEN FIELD ORIENTED CONTROL INDUCTION MOTOR DRIVE IS USED AS LOAD An ideal three-phase sinusoidal supply voltage is applied to the non-linear load (Field oriented control Induction motor drive) injecting current and voltage harmonics into the system. Figure 6(a) shows load current in three-phase before compensation Figure 6(b) shows THD level for uncompensated load current. Figure 7(a) shows the load current for compensated system Figure 7(b) shows THD level for compensated load current. Figure 8(a) shows load All rights reserved by www.ijsrd.com 720

voltage in three-phase before compensation Figure 8(b) shows THD level for uncompensated load voltage. Figure 9(a) shows the load voltage for compensated system Figure 9(b) shows THD level for compensated load voltage. The Total Harmonic Distortion (THD) for load current which was 6.35% in Figure 6(b) before compensation and effectively reduces to 3.59 % in Fig.7(b) after compensation using PI controller. Shunt inverter is able to reduce the harmonics entering into the system. The Total Harmonic Distortion (THD) for load voltage which was 29.30% in Fig.8(b) before compensation and effectively reduces to 29.19 % in Fig.9(b) after compensation using PI controller. The voltage compensation is small because system consists of transformers which are already doing compensation for voltage. Fig. 7(b): Total harmonic distortion with UPQC for current Fig. 8(a): Voltage waveform without UPQC Fig. 6:(a): Current waveform without UPQC Fig. 8(b) Total harmonic distortion without UPQC for voltage Fig. 9(a): Voltage waveform with UPQC Fig. 6(b): Total harmonic distortion without UPQC for current Fig. 7(a): Current waveform with UPQC Fig. 9(b): Total harmonic distortion with UPQC for voltage X. CONCLUSION The MATLAB/SIMULINK were used to carry out extensive simulation studies on unified power quality conditioner and for the controlling purpose the proportional integral controller is used and adjustable speed drive is used as a load. Therefore, UPQC is considered to be an efficient solution. Unified power quality conditioner is capable of reducing the level of THD in the case of networks which are connected to the harmonics generating load (like ASD). All rights reserved by www.ijsrd.com 721

REFERENCES [1] C. Sankaran, Power Quality, CRC Press LLC, 2002. [2] Alexander Kusko and Marc T.Thompson, Power Quality in Electrical Systems, McGraw-Hill, 2007. [3] Roger C. Dugan, Mark F. McGranaghan, Surya Santoso and H.Wayne Beaty, Electrical Power Systems Quality, The McGraw-Hill, Second Edition, 2004. [4] K. R. Padiyar, Facts Controllers in Power Transmission and Distribution, New Age International Publishers, 2007. [5] Power Quality Compensation Using Universal Power Quality Conditioning System generic loads, IEEE Trans. Power Delivery, vol. 8, no. 2, pp. 697-703, Apr. 1993 [6] Combined Operation of Unified Power-Quality Conditioner With Distributed Generation [7] B. Han, Senior Member, IEEE, B. Bae, H. Kim, and S. Baek IEEE TRANSACTIONS ON POWER DELIVERY VOL. 21, NO. 1, JANUARY 2006 [8] Role of Custom Power Devices (CPDs) in Power Distribution &Transmissions ISSN: 2321 1806 Oriental International Journal of Innovative Engineering Research (OIJIER) Volume 1 No 1, April 2013 [9] Enhancing Electric Power Quality Using UPQC: A Comprehensive Overview Vinod Khadkikar, IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 27, NO. 5, MAY 2012 [10] The Unified Power Quality Conditioner: The Integration of Series- and Shunt-Active FiltersHideaki Fujita, Member, IEEE, and Hirofumi Akagi, Fellow, IEEE IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 2, MARCH 1998 [11] Integration of UPQC for Power Quality Improvement in Distributed Generation NetworkShafiuzzaman K Khadem, Student Member, IEEE, Malabika Basu, Member, IEEE and Michael [12] F Conlon, Member, IEEE 2011-12-05 [13] Modeling analysis and solution of PowerMahesh Singh SSCET BHILAI INDIA Vaibhav Tiwari CSIT BHILAI INDIA [14] Interline Unified Power Quality Conditioner.Amit Kumar Jindal, Student Member, IEEE, Arindam Ghosh, Fellow, IEEE, and Avinash Joshi IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 [15] Different Modeling Aspects and Energy Systems of Unified Power Quality Conditioner (UPQC): An Overview Payal Deshpande INTERNATIONAL JOURNAL of RENEWABLE ENERGY RESEARCH et al., Vol.3, No.2, 2013 [16] Kushang M Parmar, PG-student of SSGEC Bhavnagar. I am pursuing my Master s degree in Power Systems(Electrical Engg.). All rights reserved by www.ijsrd.com 722