SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

Similar documents
KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

TABLE OF CONTENTS. 1.0 Scope. 2.0 References. 3.0 Definitions. 4.0 Submission and Design Requirements. 5.0 Materials 5.1 General 5.

Standard Specifications

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

SECTION G ESTIMATE OF QUANTITIES

A. Extent of structural precast concrete work is shown on drawings and in schedules.

SECTION CONCRETE REINFORCEMENT FOR STEAM UTILITY DISTRIBUTION

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION MANHOLES

SECTION PRECAST CONCRETE STRUCTURES

B422 - PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS - OPSS 422

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18

SECTION MANHOLES

SECTION TRACER WIRE FOR NONMETALLIC PIPE

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17

EXCAVATION AND BACKFILL

4.1. Foremen 4.2. Concrete plant manager 4.3. Concrete plant operator 4.4. Personnel performing saw cutting and joint sealing

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

ALUMINUM PIPE GUIDERAIL 01/01/

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST

STEEL PIPE GUIDERAIL 01/01/

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SECTION STRUCTURAL STEEL. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

D. Thermally Sprayed Metallic Coating (Flame Spray): STD SPEC

IGGA Guide Specification: Dowel Bar Retrofit (DBR) Introduction

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

SECTION TRAFFIC SIGNAGE

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

UNDERGROUND UTILITY TRENCHES AND VAULTS Page 1 of 6 ADDENDUM #1

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846

SECTION METAL FABRICATIONS

SECTION SAND CUSHION TERRAZZO FLOORING

Section 914. JOINT AND WATERPROOFING MATERIALS

SECTION BULLET- RESISTANT DOORS

SECTION SITE FURNISHINGS FOR CFCRT. 1. American Society for Testing and Materials (ASTM).

580 - NOISE BARRIERS OPSS 580 INDEX

1.1 RELATED DOCUMENTS

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

For crossing under a railroad, contact the specific railroad company's engineering department.

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

Item 550 Chain Link Fence

Special Provision No. 904S14 October OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows:

Special Provision No. 999F29 March 2018 REQUIREMENTS FOR INSTALLATION OF METALLIC DOWELS INTO CONCRETE

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work

A. Suggested Tool List

SECTION 1085 PRECAST REINFORCED CONCRETE BOX CULVERT

SECTION DEWATERING TANKAGE PART 1 - GENERAL 1.1 RELATED DOCUMENTS

2016 Specification Treads, Base, Stringers and other Amenities Wausau Tile Precast Epoxy Terrazzo

METAL FABRICATION SECTION 8: METAL FABRICATION SCOPE MATERIAL.

MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX

A. Dewatering observation wells are part of dewatering allowance.

A. Deviation from this standard must be approved by the Project Architect.

PART MATERIALS. Section Fencing Materials. Description

shawprecastsolutions.com BEBO Arch Systems PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions.

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

STANDARD BID ITEM NUMBERS

SECTION DEWATERING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

Special Provision No. 999S29 May 2010

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

SURFACE FINISH. A galvanized finish is MnDOT s standard on new traffic control signal poles, mast arms, transformer bases, and luminaire extensions.

2. All work and materials shall be in full accordance with Local and State ordinance and with any prevailing rules and regulations.

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

BPDL Architectural precast concrete specifications USA TESTING AND INSPECTION A. Testing by Independent Agency : Materials and workmanship furn

SECTION ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

SECTION CHAIN LINK FENCING

24" B B Joint X501 Joint See MARKINGS Note PCB-RXX-350-TL3 " X501 Y301 (Typ.) " A PLAN (reinforced casting option shown) A " dia. Hinge Bar (Typ.) NOT

STRUCTURES FOR SANITARY AND STORM SEWERS

SECTION SIGNAGE

SECTION PUBLIC UTILITY MANHOLES AND STRUCTURES. 2. Modular precast concrete pump wetwell. 5. Manhole bedding and cover materials.

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS

Construction Specification for Watermain and Water Service Tracer Wire

The School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS

2' x 3' Polymer Pull Box Cover 4'-0" 7'-0" 24" x 76" Access Opening 3'-6"

Customer Requirements Commercial Secondary Service

BEDSPREADS BEDSPREADS

Manholes Table of Contents

SECTION SHEET METAL FLASHING AND TRIM

No No No

B. Shop Drawings: Include elevations, door edge details, frame profiles, metal thicknesses, preparations for hardware, and other details.

Edgerail Aluminum Bridge Railing System Specification & Installation Instructions

How to Estimate the Cost of a. Precast Concrete Parking Structure

SECTION PRECAST CULVERT STEAM TUNNEL

STATE OF OHIO DEPARTMENT OF TRANSPORTATION SUPPLEMENT 1073 PRECAST CONCRETE CERTIFICATION PROGRAM JULY 20, 2018

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS

Work Type Definition and Submittal Requirements Work Type: Subsurface Utility Engineering (SUE)

Large Scale CalArc Pavers for Sand-Set Pedestrian Use Installations

14 March 2016 City Hall Station Renovations Bid Documents 15 th Street Station Phase Station Improvements SECTION PRECAST CONCRETE

SUBSTATION SECURITY WALL INSTALLATION MANUAL

1.1 SUMMARY. A. This Section includes the following: 1. Loose steel lintels. 2. Shelf angles. 3. Metal floor plate. 4. Pipe bollards.

Testing. Material testing will be according to applicable AASHTO, ASTM or Department methods as specified.

Precast Concrete. Installation Guide V GR-WI-599. Page 1

Section 808. FENCING

Transcription:

SECTION 58 PRECAST CONCRETE BOX CULVERT 58.1 DESCRIPTION A. General This work consists of furnishing and installing Pre-cast Concrete Box Culverts. B. Related Work Section 51 Section 52 Section 53 Section 54 Section 108 Section 200 Section 202 Structure Excavation for Box Culvert Box, Pipe, and Plate Culvert Undercutting Drainage Fabric Protection for Reinforced Concrete Box Culvert Pipe Culverts Concrete Curing Materials Controlled Low strength Material Engineering Fabric 58.2 MATERIALS Pre-cast Concrete Box Culvert materials design and fabrication shall conform to the requirements of AASHTO M 259 or M 273, except as modified on the plans and by this Specification. Configurations in variance with those provided by AASHTO will be accepted provided the AASHTO materials, design and fabrication specification requirements and requirements of this Specification are complied with. A. End Section (inlet or outlet) materials, design and fabrication shall conform to the requirements of AASHTO Standard Specifications for Highway Bridges and Materials Specifications. B. Drainage Fabric shall conform to the requirements of Section 202. C. Polyethylene Sheeting shall conform to the requirements of Section 108. D. Steel wire bar supports, in contact with the casting forms, shall be stainless steel, hot dipped galvanized or plastic tipped extending at least one-half (1/2) inch from the form surface. 58.3 CONSTRUCTION REQUIREMENTS A. Design Page 1 of 5

1. Pre-cast Box Culverts shall be designed to satisfy load conditions shown on the plans. The design shall conform to the AASHTO design requirements for the depth of fill, including surfacing, etc., as well as live load or loading indicated on the plans. The specified live load shall apply to all barrel sections. 2. Prior to fabrication of box culvert sections, the Contractor shall furnish, for Engineering Division review, shop drawings and a checked design. The drawings shall be complete and comprehensive and show all reinforcing steel, its placement, configuration, and total quantities for the complete structure. A checked design for barrel sections will not be required to be submitted if the proposed fabrication dimensions and reinforcement conform to AASHTO M 259 or M 273. A checked design for end sections will be required. B. Fabrication 1. The minimum length of pre-cast sections shall be four (4) feet. 2. Joint ties as detailed on the plans shall be provided on all sections. 3. Steel wire bar supports shall be used to maintain proper reinforcement location and concrete cover. Cutting of reinforcement and bending to the form surface, for support, will not be permitted. 4. Welding of reinforcing steel will not be permitted. C. Installation 1. Foundation preparation shall be in accordance with Sections 51, 52, and 54. 2. The foundation shall be shaped to provide the template section and uniform density, satisfactory to the Engineer. 3. The floor joint between adjacent sections shall be sealed with pre-formed mastic. A strip of drainage fabric shall be placed along the wall and sides to provide a minimum of two and one-half (2 1/2) feet of fabric centered on the joint. Where required, transverse joints in the fabric shall be accomplished by overlapping the fabric at least two (2) feet. Polyethylene sheeting shall be placed between the fabric and the pre-cast box culvert. Sufficient adhesive will be permitted along the edge of the fabric and polyethylene sheeting to hold it in place during backfilling. Lift holes shall be covered or plugged. 4. Each section shall be tied to adjacent sections with joint ties as detailed on the plans. Page 2 of 5

5. Backfilling shall conform to the requirements of Section 54. Hand compaction methods or use of flowable fill may be required for satisfactory compaction under and adjacent to corners with a radius and between culverts on multiple installations. D, Precast Concrete Box Culvert Tests: 1. General: A visual inspection and/or a television inspection test shall be performed as specified herein for all precast concrete box culvert(s) (box culvert(s)) as a condition of acceptance by the City. The Engineer shall determine whether a visual test or television test or both tests will be required. All tests shall be performed after backfill is complete but prior to any surface restoration. 2. Pre-Cleaning: Prior to testing newly installed precast concrete box culverts the Contractor shall remove all accumulated construction debris, rock, gravel, sand, silt, and other foreign matter from the precast concrete box culvert. The Contractor shall be responsible for all work necessary to make the precast concrete box culvert acceptable for usage including removal of all mud, silt, rocks, or blockages that make said box culverts unacceptable for final acceptance and usage. Also included is all cleanup work required prior to final acceptance. The City will not be responsible for cleaning box culverts prior to the visual inspection and televising the box culvert. In the event that the box culvert is not acceptable for visual inspection or televising, due to the Contractor s operations, the Contractor will be notified. It will be the Contractor s responsibility to arrange to clean the box culvert and make it acceptable for the visual inspection or television work. If not cleaned in a timely manner, the City may cause to take any actions necessary and charge the Contractor one and a half (1½) times the cost incurred. 3. Tests: All newly installed box culverts shall pass a visual inspection by the Engineer and/or a television inspection by the City Utility Maintenance Division. The visual and/or television inspection shall consist of viewing the inside of all box culverts installed to determine proper alignment, grade, joining, etc. The Contractor shall correct, at his own expense, any defects discovered from the visual and/or televising inspection. A visual and/or television inspection shall be completed unless specified otherwise in the Detailed Specifications or on the Drawings. Waiving the visual and/or television inspections shall only be done in writing by the Engineer and will only be considered if requested by the design engineer. The expense of the initial visual and/or television inspection and one additional reinspection will be borne entirely by the City. If defective workmanship of material or construction is noted, the Contractor at no expense to the City, shall Page 3 of 5

correct the deficiency. The City will perform additional visual and/or television inspections to review if the repairs were made properly and in accordance with the specifications. The expense of any additional visual and/or television inspections beyond the initial inspection and one additional reinspection will be borne entirely by the Contractor. The Contractor shall be responsible for all related costs, including concrete or asphalt resurfacing if the street has been surfaced. The Contractor shall be required to repair all deficiencies. The City may cause to take any actions necessary for any items not completed or repaired in a timely manner and may charge the contractor one and a half (1½) times the costs incurred. It is the Contractors responsibilities to notify both the Engineer/City Inspector and Utility Maintenance that the box culvert is ready for inspection. From the time initial notification that the box culvert is ready to be inspected the Contractor shall allow the City at least four (4) weeks to perform the visual and/or television inspections. Any surfacing started prior to visual and/or televising the box culvert and said box culvert being accepted is at the Contractors own risk. 58.4 METHOD OF MEASUREMENT A. Furnishing Pre-cast Box Culvert Furnishing pre-cast box culverts will be measured by the linear foot of box culvert furnished and accepted, excluding end sections. The footage shall be obtained by multiplying the nominal length of the sections by the number of sections furnished and accepted and rounding to the nearest whole foot. B. Installing Pre-cast Box Culvert Installing pre-cast box culvert will be measured by the linear foot. The footage shall be obtained by multiplying the nominal length of sections by the number installed. C. Furnishing Pre-cast Box Culvert End Sections Furnishing pre-cast box culvert end sections will be measured per each of end sections furnished and accepted. D. Installing Pre-cast Box Culvert End Sections Installing pre-cast box culvert end sections will be measured per each of end sections installed and accepted. 58.5 BASIS OF PAYMENT A. Furnishing Pre-cast Box Culvert Page 4 of 5

Furnish pre-cast box culvert will be paid for at the contract unit price per linear foot to the nearest whole foot of pre-cast box culvert furnished and accepted. Payment for this item will be full compensation for furnishing the box culvert, joint seal mastic, drainage fabric, polyethylene sheeting, and joint ties. B. Installing Pre-cast Box Culvert Installing pre-cast box culvert will be paid for at the contract price per linear foot to the nearest whole foot of pre-cast box culvert installed and accepted. Payment for this item will be full compensation for pre-cast box culvert installation and will include compensation for foundation preparation, backfilling, testing, and all other work incidental to the installation. C. Furnishing Pre-cast Box Culvert End Sections Furnishing pre-cast box culvert end sections will be paid for at the contract unit price for each end section accepted. D. Installing Pre-cast Box Culvert End Sections Installing pre-cast box culvert end sections will be paid for at the contract unit price for each end section accepted. END OF SECTION Page 5 of 5