Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Similar documents
Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Application of Fuzzy Logic Controller in Shunt Active Power Filter

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

Mitigation of Current Harmonics with Combined p-q and Id-IqControl Strategies for Fuzzy Controller Based 3Phase 4Wire Shunt Active Filter

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

2020 P a g e. Figure.2: Line diagram of series active power filter.

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Improving Passive Filter Compensation Performance With Active Techniques

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

ISSN Vol.04,Issue.16, October-2016, Pages:

A Reduction of harmonics at the Interface of Distribution and Transmission Systems by using Current Source active Power Filter

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

A New Control Method for Series Active Filter in Distribution System using Unit Vector Control

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Improvement of Power Quality Using a Hybrid Interline UPQC

Simulation of D-STATCOM for Power Quality Improvement With Fuzzy Based Phase Locked Loop Control Strategy

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Enhancement of Power Quality Using Advanced Series Active Power Filters

RECENTLY, the harmonics current in a power grid can

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Power Quality improvement of a three phase four wire system using UPQC

Efficient Hybrid Shunt Active Power Filter for Improvement of Power Factor and Harmonic Suppression using MATLAB

Improvement of Power Quality by using Active Filter based on Vectorial Power Theory Control Strategy on the MATLAB-Simulink Platform

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement using Shunt Passive Filter

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Review on Shunt Active Power Filter for Three Phase Four Wire System

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Harmonics Reduction using 4-Leg Shunt Active Power Filters

29 Level H- Bridge VSC for HVDC Application

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

MMC based D-STATCOM for Different Loading Conditions

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

American International Journal of Research in Science, Technology, Engineering & Mathematics

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Reactive Power Compensation of LC Coupling Hybrid Active Power Filters by DC Link Voltage Controls

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER OF UPQC

Design and Simulation of Passive Filter

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Levels of Inverter by Using Solar Array Generation System

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

ISSN Vol.03,Issue.07, August-2015, Pages:

P.CHAITHANYAKUMAR, T.VARAPRASAD/

Design and Development of MPPT for Wind Electrical Power System under Variable Speed Generation Using Fuzzy Logic

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

Power Quality Improvement using Active shunt Power filter using PI Controller

Harmonic Analysis and Its Mitigation Using Different Passive Filters

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

Voltage Balancing Control of Improved ZVS FBTL Converter for WECS

Literature Review for Shunt Active Power Filters

Study of Power Factor Correction in Single Phase AC-DC Converter

Fuzzy Logic Control of APF for Harmonic Voltage Suppression in Distribution System

A Novel Cascaded Multilevel Inverter Using A Single DC Source

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

ISSN Vol.04,Issue.08, July-2016, Pages:

Hybrid Power Quality Compensator for Traction Power System with Photovoltaic Array

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

A Three Phase Seven Level Inverter for Grid Connected Photovoltaic System by Employing PID Controller

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Power Quality Improvement in Fourteen Bus System using UPQC

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Implementation of Cascade Multilevel Inverter in Distribution Systems as Power Line Conditioner

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

ISSN Vol.03,Issue.42 November-2014, Pages:

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Transcription:

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current B. Pedaiah 1, B. Parameshwar Reddy 2 M.Tech Student, Dept of EE E, St. Mark College, Affiliated to JNTUA, AP, India 1 Assistant Professor, Dept of EE E, St. Mark College, Affiliated to JNTUA, AP, India 2 ABSTRACT: Many consumer appliances demand quality power continuously for their operation. The performance of the end user equipment is heavily dependent on the quality of power supplied to it. But the quality of power delivered to the end user is affected by various external and internal factors. They are like voltage and frequency variations, faults, outages etc., These power quality problems reduce the life time and efficiency of the equipment. Thus, to enhance the performance of the consumer equipment and also the overall performance of the system these problems should be mitigated. The main affect caused by these problems is the presence of harmonics. This leads to the overheating of the equipment, insulation failure and over speeding of induction motors etc. The solution to overcome these problems is to filter out these harmonics. For this purpose there are many filters topologies present in the literature. In this project a hybrid power conditioner is composed of a neutral-line current attenuator and a hybrid power filter. The hybrid power filter, configured by a three-phase power converter and a three-phase tuned power filter, is utilized to filter the nonzerosequence harmonic currents in the three-phase four-wire distribution power system. This project presents the control strategy to control the filter in such a way that the harmonics are reduced. The proposed control strategy is simulated in MATLAB SIMULINK and the results are presented. KEYWORDS: Dynamic-Implications of Technology, Technology Social Factors, Privacy. I. INTRODUCTION Three-Phase four-wire distribution power systems been widely applied in office buildings and manufacturing- office buildings to supply single-phase or three-phase loads. The third harmonic is very serious in single-phase nonlinear loads. The third-order harmonic current of each phase is synchronous and regarded as the zero-sequence current. Therefore, the zero-sequence currents of each phase are summed up and flow into the neutral line of three-phase fourwire distribution power systems. Furthermore, single-phase loads may result in serious load unbalance, and the unbalanced load current also flows into the neutral line of the three-phase four-wire distribution power systems. In many applications, the neutral-line current will exceed the phase currents. Excessive neutral-line current may cause accidents due to overload of the neutral line. Moreover, it will lead to fluctuation in ground voltage of the load, which may influence the operation of precision equipment. Hence, the major problems of three-phase four-wire distribution power systems are harmonic currents and neutral-line current. The zig-zag transformer, connected to the load in parallel, has been employed to attenuate the neutral-line current. However, the attenuation of neutral-line current is dependent on the ratio between the impedance of the utility system and the zig-zag transformer. Furthermore, the zigzag transformer also has a low impedance path for zero-sequence voltage of the unbalanced utility, which will further cause a significant neutral line current. A single-phase power converter can be combined with the zig-zag transformer to advance the performance of the neutral-line current suppression. The single-phase power converter is inserted at the neutral line between the load and the utility, thus causing fluctuation in the ground voltage of the load. A neutral-current suppression scheme, configured by a Δ-Y transformer Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18219

and a single-phase power converter connected in series, is connected to the load in parallel to suppress the neutral- line current. The neutral line of the load is directly connected to that of the utility, and the fluctuation in ground voltage of the load can thus be avoided. A series of active power filters connected to the neutral line between the utility and the load can suppress the neutral-line current, thus eliminating the need of the transformer for a zero current path. However, there is fluctuation in ground voltage of the load because the neutral lines of the load and utility are separated. Conventionally, passive power filters have been employed to solve the problems of harmonic currents and neutral-line current in three-phase four-wire distribution power systems. Although passive power filters have the advantage of low hardware cost, their performance is often significantly affected by the system impedance. Furthermore, salient problems, including large volume, parallel resonance, and series resonance may further offset the benefits of this method. With advances in power semiconductor technology, power-electronic- based active power equipment is gradually replacing or sharing the role of passive power equipment. Active power filters have been proposed for suppressing the harmonic currents in single-phase and three-phase three-wire distribution power systems. The three-phase four-wire active power filter can further suppress the neutralline current in three-phase four-wire distribution power systems. Although active power filters can solve the majority of problems of three-phase four-wire distribution power systems, the capacity of the power converter must be larger than the product of the utility voltage and the current including the fundamental reactive current and the harmonic current of the load. Therefore, the capacity and manufacturing cost of this type of power converter is very high, thus limiting wide application of active power filters. Moreover, the switching power loss of the power converter due to high voltage and high current switching is significant. Hybrid power conditioners have been developed to solve the problems of passive and active power conditioners. A hybrid power filter consists of a passive power filter and a power converter. In operation, the passive power filter can reduce the capacity of the power converter while the power converter is employed to improve the filter characteristics of the passive power filter. Hybrid power filters can be divided into series-linked type and shunt type. In hybrid power filters of the series-linked type, the power converter is conne ted between the utility and the load through a linked transformer, and the passive power filter is parallel to the load. The voltage drop on the power converter is low in order to reduce the dc bus voltage. However, the current of the power converter, including the fundamental current of the load and the fundamental reactive current of the passive power filter, is still large. In hybrid power filters of the shunt type, the power converter is connected to the passive power filter in series and then connected to the load in parallel. The major part of the utility voltage will drop on the passive power filter. In this way, the dc bus voltage and voltage rating of the power converter can be significantly reduced. However, the current of the power converter, including the harmonic currents of the load and the fundamental reactive current of the passive power filter, is not diminished. Although the shunt-type hybrid power filter can be applied to improve problems of the neutral-line current in three-phase four-line distribution power systems, it cannot attenuate the fundamental component of neutral-line current caused by the unbalanced load. In addition, the current of the power converter is not diminished yet. A new hybrid power conditioner for solving the problems of harmonic currents and neutral-line current in three-phase fourwire distribution power systems is proposed in this paper. This hybrid power conditioner is configured by a neutral-line current attenuator and a hybrid power filter. The hybrid power filter, configured by a three-phase power converter and a three phase tuned power filter, is utilized to filter the nonzerosequence harmonic currents in the three-phase four-wire distribution power system. The neutral-line current suppressor is connected between the power capacitors of the three-phase tuned power filter and the neutral line to attenuate the neutral-line current in the three-phase four-wire distribution power system. The proposed hybrid power conditioner can effectively reduce the power rating of passive and active elements. A hardware prototype is developed to verify the performance of the proposed hybrid power conditioner. Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18220

Fig.1. Configuration of the conventional shunt-type hybrid power filter. Fig.2. Configuration of the advanced hybrid power filter. II. THREE-PHASE FOUR-WIRE HYBRID POWER FILTER Fig. 1 shows the configuration of a conventional shunt-type hybrid power filter applied to the three-phase four-wire distribution power system. In the conventional shunt-type hybrid power filter, the power converter is connected to the passive power filter in series and then connected to the load in parallel. The power converter can be configured by a four-arm bridge structure or a three-arm bridge structure with a split-capacitor arm. The passive power filter is configured by three-phase tuned power filters with an inductor and a capacitor connected in series in each phase, and their tuned frequency is the dominant harmonic frequency of the load. The tuned frequency of the tuned power filters is designed at the third harmonic requency in the application of three-phase four-wire distribution power systems. As seen in Fig.1, the major part of the utility voltage will drop on the passive power filter. In this way, the dc bus voltage and voltage rating of the power converter can be significantly reduced. However, the current of the power converter, including the harmonic currents of the load and the fundamental reactive current of the passive power filter, is not diminished. An advanced hybrid power filter, shown in Fig. 2, is proposed to further reduce the power rating of the power converter. As seen in Fig. 2, the power converter is connected to the inductors of the three-phase tuned Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18221

power filter in parallel. Since the power converter is parallel to the inductors of the tuned power filters, the major fundamental reactive current of the three-phase tuned power filter and the dominant harmonic current of the load will flow through the inductors of the three-phase tuned power filter by proper control of the power converter, thus decreasing the current flowing through the power converter. Fig.3. System configuration of the proposed hybrid power conditioner. The major role of the conventional shunt-type hybrid power filter applied to the three-phase four-wire distribution power system is to filter harmonic currents of the load. If the three phase loads are unbalanced, the neutral-line current of the load contains a fundamental component. The conventional shunt type hybrid power filter cannot respond to this fundamental component of the neutral-line current. Therefore, it cannot effectively suppress the neutral-line current under the unbalanced load. III. SYSTEM CONFIGURATION OF THE NEW HYBRID POWER CONDITIONER Fig3 shows the system configuration of the proposed hybrid power conditioner. In comparison with the conventional hybrid power filter, a neutral-line current attenuator is integrated into the hybrid power filter in the proposed hybrid power conditioner. The integrated neutral-line current attenuator can advance the filter performance of the hybrid power filter under the unbalanced load. Hence, the proposed hybrid power conditioner can simultaneously and effectively solve the problems of harmonic currents and neutral-line current in three-phase four-wire distribution power systems. To further reduce the power rating of the power converter, the advanced hybrid power filter is used with the three-phase power converter connected to the inductors of the three-phase tuned power filter in parallel. By incorporating the neutral- line current attenuator, the hybrid power filter is utilized to suppress only the nonzerosequence harmonic currents in three-phase fourwire distribution power systems. Hence, the three-phase power converter is configured by a three-arm bridge structure and the tuned frequency of three-phase tuned power filter is set at the fifth harmonic frequency. With an increase in tuned frequency of the tuned power filters, the inductance of inductors can be reduced. ( IV. CONTROL PRINCIPLE Current-mode control is adopted to control the three-phase power converter of the hybrid power filter. The output currents of the three-phase power converter are controlled to be harmonics, and the second term is for regulating the dc bus voltage of three-phase power converter. Since the three-phase power converter is parallel to the inductors of the Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18222

three-phase tuned power filter and its output currents are controlled. The major fundamental reactive currents of the tuned power filters and the dominant harmonic currents of the load will flow through the inductors of the tuned power filters. Therefore, the currents flowing through the three-phase power converter can be effectively decreased. The single-phase power converter of the neutral-line current attenuator is controlled by the general pulse width modulation(pwm). V. CONTROL BLOCK DIAGRAM Fig. 4 shows the simulation diagram the hybrid power conditioner under the unbalanced three phase load. The three-phase power converter adopts the current-mode control. The current references should be calculated first. The current references should be equal, and they contain a fundamental signal and a harmonic signal. The detected three-phase utility currents are sent to the band stop filters to extract their harmonic components. The outputs of the band stop filters are sent to the amplifier with gain, and the harmonic signals of the current references are then obtained. The detected dc bus voltage of the three-phase power converter is compared with the setting voltage, and the compared result is sent to a proportional-integral (PI) controller. The output of the PI controller is. Both the outputs of the PI controller and the detected three-phase utility voltages are sent to the multipliers so that the fundamental signals of the current references are obtained. The current references are obtained by summing up the harmonic signals and the fundamental signals. VI. SIMULATION RESULTS Fig 5. Simulation results of the hybrid power conditioner under the balanced three-phase load: (a) phase a utility current, (b) phase c utility current, (c) phase b utility current, and (d) neutral line current of the utility. Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18223

Fig 6. Simulation results of the three-phase four-wire hybrid power conditioner under the transient of applying the netral-line current attenuator: (a) phase a utility voltage, (b) phase a utility current, (c) phase a load current, and (d) neutral line current of the utility. Fig 7. Simulation results of the hybrid power conditioner under the transient of increasing load: (a) phase a utility voltage, (b) phase a utility current, (c) phase a load current, and (d) neutral line current of the utility. Fig 8. THD- hybrid power conditioner by pi controller under the transient of increasing load. Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18224

Extension Results In the Extension Total harmonic Distortions are reduced as shown in fig12 Fig 9. Simulation results of the hybrid power conditioner ny Fuzzy logic controller under the transient of increasing load: (a) phase a utility voltage, (b) phase a utility current, (c) phase a load current, and (d) neutral line current of the utility. Fig 10.THD- hybrid power conditioner by fuzzy logic controller under the transient of increasing load VII. CONCLUSION Three-phase four-wire distribution power systems have been widely applied to low-voltage applications; however, they encounter serious problems of harmonic current pollution and large neutral-line current. In this paper, a new hybrid power conditioner, composed of a hybrid power filter and a neutral- line current attenuator, is proposed. In the proposed hybrid power conditioner, the power capacity of power converters in the hybrid power filter and neutral-line current attenuator can be effectively reduced, thus increasing its use in high-power applications and enhancing the operation efficiency. A prototype is developed and tested. Experimental results verify that the proposed hybrid power conditioner can suppress the harmonic currents and attenuate the neutral-line current effectively whether the loads are balanced or not. Hence, the proposed hybrid power conditioner is an effective solution to the problems of harmonic currents and neutral-line current in three-phase four-wire distribution power systems. Besides, the output current of the three-phase power converter is much smaller than the conventional hybrid power filter, and the power rating of the zigzag transformer is smaller than the rating of the conventional neutral-line current attenuator. Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18225

REFERENCES [1] B. Singh, P. Jayaprakash, T. R. Somayajulu, and D. P.Kothari, Reducedrating VSC with a zig-zag transformer for current compensationin a three-phase four-wire distribution system, IEEE Trans. PowerDel., vol. 24, no. 1, pp. 249 259, Jan. 2009. [2] R. M. Ciric, L. F. Ochoa, A. Padilla-Feltrin, and H. Nouri, Fault analysisin four-wire distribution networks, Proc. Inst. Elect. Eng., Gen.,Transm. Distrib., vol. 152, no. 6, pp. 977 982, 2005. [3] J. C. Meza and A. H. Samra, Zero-sequence harmonics current minimizationusing zero-blocking reactor and zig-zag transformer, in Proc.IEEE DRPT, 2008, pp. 1758 1764. [4] H. L. Jou, J. C.Wu,K.D.Wu,W. J. Chiang, andy. H. Chen, Analysisof zig-zag transformer applying in the three-phase four-wire distributionpower system, IEEE Trans. Power Del., vol. 20, no. 2, pt. 1, pp.1168 1178, Apr. 2005. [5] S. Choi and M. Jang, Analysis and control of a single-phase-inverterzigzag-transformer hybrid neutral-current suppressor in three-phasefourwire systems, IEEE Trans. Ind. Electron., vol. 54, no. 4, pp.2201 2208, Aug. 2007 Copyright to IJIRSET DOI:10.15680/IJIRSET.2017.0609087 18226