Planning Guidelines. Lightcloud. Best Practices for Installing Lightcloud

Similar documents
FR FAQS CONTENTS

CAM ALL WEATHER TRANSMITTER AND RECEIVER SYSTEM

Wireless Ceiling Mount Sensor

Taxonomies, Classifications, and Categories Residential dimmers, motion sensors, controls, & photo cells Wireless occupancy/vacancy sensor

Parking Lot Application

Radio Powr SavrTM Wireless Occupancy / Vacancy Ceiling Sensor

Huawei Indoor WLAN Deployment Guide

Experiencing trouble with your zboost setup? Installation Tips. Please note the following important factors in determining zboost performance:

ATEK Access Technologies. TankScan System. Instruction Guide.

CONTENTS. La Crosse Technology, Ltd. Page 1

LRF20CR2BPWH Ceiling MNT Wireless Occ Sensor

GENERAL INFORMATION BATTERIES: WHAT DO I NEED TO KNOW ABOUT BATTERIES?

XD-V Digital Wireless Systems

At the completion of this guide you should be comfortable with the following:

Wireless Ceiling Motion Sensor for Occupancy / Vacancy Detection with integrated diagnostic tools INSTALLATION GUIDE

Wilson. iden 800 MHz. Adjustable Gain In-Building Wireless Smart Technology Signal Booster. Appearance of device and accessories may vary.

Occupancy Sensors for High-Bay Applications

GR FAQS. La Crosse Technology, Ltd. Page 1

CONTENTS. Note: If using Alkaline Rechargeable battery place solar panel under light source for 6 hours with rechargeable battery in place to charge.

Radio Powr SavrT Occupancy / Vacancy Sensor

name (h) phone (m) phone time zone door style* *required finish* *required designer

ēko Pro Series System

10/17/2011. I have an Air-Card. I have Satellite Internet. Why would I use Wi-Fi? Just for

Lumewave and LumInsight IoT. Gateway and Base Station Installation Guide

Battery-Free Wireless Pushbutton Useful Tips for Reliable Range Planning

ROAM XL. Commercial Remote Control. ROAM XL Commercial Remote Control Owner s Manual and Programming Instructions

Chapter 23. Garage Construction

v3 360 Passive Infrared Line Voltage Occupancy Sensor

Wireless Ceiling Mount Sensor for Occupancy / Vacancy Detection INSTALLATION GUIDE

Mach Wall Installation Instructions

IMPORTANT SAFEGUARDS READ AND FOLLOW ALL SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE

Wireless sensor system

Guide. Installation. Wilson Electronics, Inc. Direct Connection High Power iden Amplifi er 800 MHz Band. Contents:

GreenParking. Design guide. GreenParking

University of Central Florida Main Campus. Electric. Service and Meter Installations Requirements. Issued January 26 th, 2017.

MC CHANGER CABINET INSTALLATION INSTRUCTIONS

GE Lighting. control. Aware Occupancy and Photo Sensors

Guidance Notes for Wireless Alarm System Installations


Installation and Setup of Crestron RF Products. Best Practices Crestron Electronics, Inc.

TABLE OF CONTENTS BATTERIES. S84107 FAQS... 1 Batteries... 1 Weather Station Factory Restart... 2 Battery Change Power requirements...

CONTENTS. Batteries. Half of all warranty issues can be resolved with fresh batteries of the appropriate voltage. La Crosse Technology, Ltd.

Wireless Facility Peer Engineering Review

Instruction Manual. Quick Setup

POWERRISE PLATINUM TECHNOLOGY REMOTE CONTROL GUIDE

Cisco Aironet 5-GHz MIMO 6-dBi Patch Antenna (AIR-ANT5160NP-R)

Smart Task Motion Activated Task Light Installation Manual

Ambient Weather WS-0270 Wireless Indoor / Outdoor Thermometer with Indoor Humidity User Manual

Cisco Aironet 2.4-GHz/5-GHz MIMO 4-Element Patch Antenna (AIR-ANT2566P4W-R)

Colubris Networks. Antenna Guide

SolidRF SOHO Tri-Band Cell Phone Signal Booster for GSM, GPRS, CDMA 3G and Verizon 4G LTE. 700 MHz(Band 13) / 850 MHz / 1900 MHz ONLY

DESCRIPTION & OPERATION: PIR OCCUPANCY SENSOR MSWSFSP221B-D FEATURES:

FM Transmission Systems Course

LESSON 1: UNDERSTANDING CONSTRUCTION DRAWINGS

Helloway TM. PTE-L70 In-Building Signal Booster. User Manual 1 / 6

Installation Manual. Ultra RF Analogue Transmitter QC0168. Manual Ref: QC0168. Version: March

Cabinet Planning Guide

Yagi and Omni Antennas Installation Manual

RoamAbout Outdoor Antenna Site Preparation Guide


Limelight by Lutron Wireless Lighting Control System

Quality Control Checklist - Design Drawings

Wireless Occupancy Sensor User Guide

OCCUPANCY SENSOR REMOTE USER GUIDE

TS-WS-07 Wireless Indoor/Outdoor 8-Channel Thermo-Hygrometer with Jumbo Display User Manual

Frequently Asked Questions

EmagiKit. Privacy Pod Plus. Quiet. Easy. Affordable. INSTRUCTIONS ASSEMBLY

VideoComm Technologies. Wireless Video Solutions

Operating Instructions

CX-100. Installation Instructions. PIR Occupancy Sensor SPECIFICATIONS

Appearance of device and accessories may vary.

SureCall TM CM800 65dB


Common Safety Concerns

Cisco Aironet 5-dBi Diversity Omnidirectional Antenna (AIR-ANT2452V-R)

HIGH/LOW/OFF PIR OUTDOOR PHOTO/MOTION SENSOR IN IP66 ENCLOSURE FOR FLEXIBLE MOUNTING

86N80.10 Economy Dovetail Jig

Guide. Installation. Wilson Electronics, Inc. In-Building Wireless Amplifi er. Contents:

TRAINING BULLETIN. EFFECTIVE DATE: 05/06 DOC NO: TB198 CROSS REF: Communications Checklists

Radio Window Sensor and Temperature Sensor Programming in HomeWorks QS

Wireless Networks. Lecture 7: WLAN Design Models & Frames Types. Prof. Huda N.N. 1

This Antenna Basics reference guide includes basic information about antenna types, how antennas work, gain, and some installation examples.

Vive Integral Fixture Controls

GSM Repeater Systems & Accessories

POWERRISE PLATINUM TECHNOLOGY REMOTE CONTROL GUIDE

Pre-Installation Guide

Occupancy/Vacancy Sensor Design and Application Guide

Installation Manual Multi Input Temperature Logger QC0163. Manual Ref: QC0163. Version: FEB17 1.0

Ham Radio Safety In & Out Of The Shack

Chapter 14. Signage Guidelines 14.2 GENERAL DESIGN OBJECTIVES 14.1 INTRODUCTION AND PURPOSE 14.3 GENERAL SIGN DESIGN GUIDELINES

W7070A2000 ZAPP WIRELESS RECEIVER

The Basics of Signal Attenuation

APPENDIX H PRICE WORKSHEETS, REVISED 12/26/15 1. BATTERIES, MODULAR FLOODED LEAD-ACID 2. BATTERIES, MODULAR VALVE REGULATED LEAD ACID

Mx-RPW Room Control Module (Built-In Occupancy Sensor)

King Cloud III. Warning. Obstruction Detection. Instructions for Reclining Sofas

Dialight Daylight Harvesting Sensor User Guide

HeLAN Motor Control Board

1. Name the horizontal member that rests on the foundation wall to support other wood members.

WS-7136U Wireless 433 MHz Temperature Station. Instruction Manual

Find the optimum placement to receive the best reception.

Transcription:

Best Practices for Installing Lightcloud Planning Guidelines Lightcloud Network Wireless Networking Considerations Wireless Mesh Network Placement of Devices Powering Devices Placing the Gateway Installation Checklists Installing Lightcloud Sensors Lightcloud Planning Guidelines Best Practices for Installing Lightcloud 1

Getting Started Setting up a Lightcloud system is simple. Following these guidelines will make setup even easier. Proper placement and planning is the most important part of a successful Lightcloud installation. Please read this entire guide prior to installation. Table of Contents Lightcloud Network Wireless Network Considerations Wireless Mesh Network Range through Building Materials Obstruction Examples Layout & Alignment 3 4 5 Placement of Devices Outdoor Space & Corners Multiple Buildings 8 Powering Devices Placing the Gateway Installation Checklists Installing Lightcloud Sensors Coverage Proximity 11 12 13 14

Lightcloud Network Two Independent, Wireless Networks Wireless Mesh 3G Cellular Phone PRIVATE 3G VPN Gateway Cell Tower Lightcloud Servers Internet Computer Note: All Lightcloud Devices extend the Lightcloud network s range except for Daylight which does not repeat a mesh network signal. Lightcloud operates on two different networks: 3G Cellular and a wireless mesh. The 3G Cellular network connects the Lightcloud system via the Gateway to RAB allowing remote management of the system including lighting controls from your phone. If the Gateway doesn t have a 3G signal, there s no way to set up the Lightcloud system or control it remotely. Lightcloud Devices communicate with each other using a wireless mesh network. For any Device to join the network, the Device has to be within range of another Device on the network. This has a great advantage over traditional WiFi networks. With traditional WiFi, each Device must be within range of the router. With a mesh network, each Device extends the range of the network by repeating the signal from other Devices. Advantages to using a mesh network for lighting controls Scalability - Lightcloud Devices don t need to be within direct range of the Gateway. All Lightcloud Devices except for Daylight extend the range of the network. This allows for a much larger network using only one Gateway. Reliability - Mesh networks are self-healing, meaning that if a Device goes offline, traffic is routed around it to other Devices in the network, without interruption of service. When an offline Device comes back online, it rejoins the network seamlessly. As is the case with setting up any new wireless network, it pays to think ahead and consider a few key factors to make sure your Lightcloud network functions optimally. Planning Guidelines Best Practices for Installing Lightcloud 3

Wireless Network Considerations Things to Avoid Wireless signals are greatly affected by building materials and wireless interference. For a Lightcloud system to function properly, Devices need to be placed in unenclosed areas, preferably without significant interference from things like cordless phones, microwaves, WiFi routers, or large motors such as those found in elevator rooms. Avoid Enclosures Do not place the Gateway or other Lightcloud Devices inside metal enclosures inside panels. Metal enclosures will greatly reduce wireless transmission. Avoid Interference When possible, avoid placing Lightcloud Devices near common sources of wireless interference, such as microwave ovens, cordless phones, WiFi routers, or large motors such as those found in elevator machine rooms. Avoid Obstructions All wireless networking works by sending messages through the electromagnetic field the same as light, but not visible. Just as with visible light, it can be bent, reflected or outright stopped. If you can see a straight or reflected line from one Device to another, the signal should be strong. Dense materials such as concrete may obstruct wireless signals and require routing around. Avoid Moisture Water (in the form of humidity and occupancy by people will absorb RF signals, reducing effective range. Very humid environments or areas that will be populated by large numbers of people will require reduced distance between Lightcloud Devices. Planning Guidelines Best Practices for Installing Lightcloud 4

Wireless Mesh Network Range Through Building Materials The range and reliability of the Lightcloud wireless mesh network is greatly impacted by building materials and environmental factors. For the purposes of maintaining a high quality, reliable installation, the maximum indoor wireless range of a Lightcloud Device is 100 feet. Note: Devices with a clear line-of-sight to each other (no obstructions whatsoever) can exceed this limit but other factors such as interference can still limit that distance. Effective range is reduced by transmitting through building materials. Wireless Range in Feet Material 0ft 10ft 20ft 30ft 40ft 50ft 60ft 70ft 80ft 90ft 100ft Glass 0.25 (-3ft) Glass 0.5 (-5ft) Lumber 3 (-10ft) Brick 3.5 (-15ft) Masonry Block 8 (-20ft) Brick 7 (-30ft) Concrete 4 (-40ft) Brick 10.5 (-45ft) Masonry Block 16 (-45ft) Coated/Insulated Glass (-55ft) Concrete 8 (-80ft) Reinforced Concrete 3.5 (-85ft) Masonry Block 24 (-90ft) Concrete 12 (-95ft) = Signal Range = Signal Loss Coated/Insulated Glass with Thin Metal Layer (-100ft) Calculating the effective range of communication between two Devices Subtract the building material s loss amount from the chart above from 100. If there are multiple materials between Devices, add them up. The result is the maximum suggested distance between those Devices. If this distance is below 10, it may be necessary to route around that obstruction with other Devices (see page 6). Planning Guidelines Best Practices for Installing Lightcloud 5

Wireless Mesh Network Obstruction Examples Brick Wall Concrete Wall with Glass Window Brick and Concrete Walls Less than 85ft Less than 57ft Introduce additional Devices Two Devices are separated by a 3.5 -thick brick wall: 100-15 = 85. Don t place these Devices farther than 85 apart. Two Devices are separated by a 4 -thick concrete wall and glass window: 100ft - 40ft - 3ft = 57ft. Don t place these Devices farther than 57ft apart. Two Devices are separated by two 7 brick walls and a 4 -thick concrete wall: 100-30 - 30-40 = 0. You will need to introduce additional Devices to route around or through these obstructions. Connect Devices Separated by an Obstruction When two Devices are separated by an obstruction like brick or concrete, add a Controller in Repeater mode near one side of the obstruction. Controllers in Repeater mode extend the mesh network without controlling a load. Controller Mode: Repeater Controller 50ft 7 Brick Wall 50ft Controller Mode: Control Loss of Range: 30ft Mode: Control Planning Guidelines Best Practices for Installing Lightcloud 6

Wireless Mesh Network Layout & Alignment Avoid long lines or chains When possible, avoid installing Lightcloud Devices in a long line or chain, as this can make the network more fragile. 100ft 100ft If a Device goes down, Devices at the end lose connectivity! No Connection Maximum range exceeded Tight-linked chains If it is unavoidable to create a chain of Devices, try to place them closer together so that if one Device can t communicate, the surrounding Devices will still be able to reach each other. 50ft 50ft If a Device goes down, Devices at the end won t lose connectivity! Create a mesh pattern Ideally, Devices should be able to mesh together with other Devices in order to create redundancy. 100ft 100ft! If a Device goes down, the other Devices aren t affected Optimal Controller Alignment For most applications, Controller alignment isn t a concern, however when pushing Controller separation to its limits or going through lots of building materials, aligning Controllers can increase connection strength. IDEAL Planning Guidelines Best Practices for Installing Lightcloud 7

Placement of Devices Outdoor Space Outdoor Devices with no interference or obstructions have a maximum range of 1000ft and suggested mounting height of greater than 10ft. Raising Controllers above obstructions such as trees improves netowrk reliability and prevents signal loss. Keep in mind, some obstructions are temporary such as cars and people these obstructions could cause intermittent connection loss. Place Controller too low! No connection Obstructions Place Controllers above obstructions > 10ft installation height < 1000ft Finalize pole installation before leaving site Lift may be needed Planning Guidelines Best Practices for Installing Lightcloud 8

Placement of Devices Outdoor Space & Corners Connecting Lightcloud inside a building to an adjacent outdoor space Place a Controller on the exterior of the building within range of the interior and exterior mesh network. Multiple Controllers on the exterior of the building will improve mesh network reliability.! No connection Range exceeded > 100ft Interior of building to outdoor space Signal needs to travel through exterior wall, then all the way to the pole. > 100ft Exterior of building to outdoor space Optional Controller on roof if there are obstructions between building and poles Controller. Devices around corners If you need to direct a wireless mesh signal around the corner of a building, you can install two Controllers in a 90 fashion from each other as pictured. TOP VIEW SIDE VIEW Planning Guidelines Best Practices for Installing Lightcloud 9

Placement of Devices Multiple Buildings It is highly recommended that one Gateway is used for each building. Lightcloud mesh networks can be extended into multiple buildings using a single Gateway, but it is not a recommended practice as it increases the chances of the building without a Gateway disconnecting from the mesh network. IDEAL Gateway #1 Gateway #2 Controller configuration to connect two buildings If a single Gateway must be used for two buildings, place a Controller outside each building at both bases and roofs. The two buildings must be in range of each other.! No connection Range exceeded Connection Clear line of sight < 1000ft Controllers are inside buildings 1. Place a Controller on top of each building. 2. Place an additional Controller outside each building but near an indoor Controller using the Controller configuration below. This creates two line-of-sight pathways between the buildings, increasing reliability. Planning Guidelines Best Practices for Installing Lightcloud 10

Powering Devices Lightcloud Devices require a constant hot feed Avoid putting Gateways, Controllers, Sensors and other AC-powered Devices downstream of any electrical component that interrupts power, for example, a photocell, occupancy sensor, or another switching Device. Note: Daylight does not require a hot feed. POWER LOAD When power for sensor is set to OFF Controller is disconnected from network POWER OFF LOAD When power switch is set to OFF Controller is disconnected from network POWER OFF LOAD When power switch is set to OFF, Controller won t control load LOAD LOAD All Devices are receiving a constant hot feed BREAKER BOX OR CONSTANT POWER SOURCE Planning Guidelines Best Practices for Installing Lightcloud 11

Placing the Gateway Signal & Power For the Gateway to connect to both the 3G and mesh network, the Gateway must be placed in an area with reliable cellular service and within range of at least one but preferably several Lightcloud Devices. If you ve identified multiple locations inside the building with a reliable cellular signal, pick a location near the center of the Lightcloud installation. The Gateway should be at the edge of a building, or closer to a window if possible. 1. Use Your Cellphone Start by using your cellphone. If your cellphone doesn t have service, then the Gateway most likely won t either. Look for a location in your installation that is both as central to the other Devices as possible, and has good cellular reception. Cellular reception is more vital than being in a central location. You can always add additional Lightcloud Devices to improve the mesh network, but you can t improve the cellular reception. 3G 3:14 PM 3G 2. Test the Gateway Signal Once you ve chosen a few possible locations for your Gateway, make sure you test the cellular reception on the Gateway itself. The cellphone is a good starting point for gauging reception, but every Device has a slightly different antenna and may be on a different network. The Gateway has a cellular indicator light that will show signal strength once powered. It may be necessary to wait several minutes to receive an accurate measurement. To test the cellular signal strength on the Gateway, there are two options: charge the battery or wire a temporary plug. POWER SIGNAL STRENGTH SYSTEM STATUS 2a. Charge the Battery 2b. Wire a Temporary Plug Connect the Gateway to line voltage and let it charge the included battery backup for half an hour. Disconnect the Gateway from the line voltage, and carry the Gateway to the potential installation location. If the signal light is green, you re ready to install the Gateway. The Gateway can be temporarily wired to a cord and plug. Plug the Gateway into an outlet near the potential installation location and test for signal strength. If you see a green light, you re ready to install the Gateway. 3. Permanent Power to the Gateway The Gateway is designed for a permanent, mains-powered installation. Once you ve found a location with a strong cellular signal, hard-wire the Gateway to a constant power source. Planning Guidelines Best Practices for Installing Lightcloud 12

Installation Checklist Gateway Gateway has cellular reception Gateway is located centrally to other Lightcloud Devices Gateway is installed to permanent, constant power Gateway is free from locations with heavy interference Gateway is in an unobstructed location Installation Checklist Other Devices Touch Sensor Controller Dimmer Daylight Device is within range of one or more Lightcloud Device Device is wired to permanent, constant power (except for Daylight) Device is free from locations with heavy interference Device is in an unobstructed location Planning Guidelines Best Practices for Installing Lightcloud 13

Installing Lightcloud Sensors Coverage Sensor coverage is determined by mounting height and the distance between sensors. Motion cannot be detected through windows. Standard Mounting Height (8 to 12 feet) Coverage radius 15 feet at 9 foot mounting height High Bay (25 to 45 feet) Coverage radius 20 feet at 30 foot mounting height 9 SIDE VIEW 15 7.5 0 7.5 15 30 SIDE VIEW 20 14 0 14 20 15 20 7.5 14 0 30 TOP VIEW 0 40 TOP VIEW 7.5 14 15 20 Adding Multiple Sensors For rooms requiring more coverage than offered by a single Ceiling Sensor, position multiple sensors with overlapping coverage. < 30 ft Standard Mount < 40 ft High Bay > 30 ft Standard Mount > 40 ft High Bay Planning Guidelines Best Practices for Installing Lightcloud 14

Installing Lightcloud Sensors Proximity Proximity to Doors When Installing a Sensor in a single room with a door or window, be mindful of the coverage radius to make sure that movement is only detected inside the room and not outside the door. < 15 ft Standard Mount < 20 ft High Bay < 15 ft Standard Mount < 20 ft High Bay Proximity to HVAC Do not place Sensors within 6 feet of HVAC vents as this may interfere with occupancy/vacancy detection. < 6 ft > 6 ft HVAC HVAC Planning Guidelines Best Practices for Installing Lightcloud 15

Ready to Install? lightcloud.com 1 (844) LIGHTCLOUD 2018 RAB Lighting, Inc. RAB is continually improving our products. Specifications may change without notice. The designs of RAB fixtures are protected under U.S. and international intellectual property laws.