SPECIFICATION FOR OVERCURRENT RELAYS

Similar documents
High precision measurement system for current and voltage IHC-A/B-RM01/03

RS Pro ENGLISH. Datasheet

RS Pro ENGLISH. Datasheet

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Overcurrent Protection / 7SJ45

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

CP-T range Product group picture

Jewell DPM EINE BEST IN CLASS

NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

SWT 3000 Teleprotection technical data siemens.com

CP-T range Benefits and advantages

RE17LLBM asymmetrical flashing relay s V AC - solid state output

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

2620 Modular Measurement and Control System

Instantaneous Overcurrent Relay

CP-E range Benefits and advantages

RE17RMMW time delay relay 10 functions - 1 s..100 h V AC/DC - 1 OC

Utility Communications Teleprotection Equipment TPT-200

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Primary switch mode power supplies Product group picture

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

satech SynchroStar GPS 200 Series

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H018F1 variable speed drive ATV kW hp V - 1ph


REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

ASHIDA Numerical 3OC + 1EF Protection Relay

Type CP-S, CP-C & CP-A Switch mode

Harmonic restraint earth fault or single-phase overcurrent protection

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Side view View from below Rear view

RE17RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

AMIK 200 / 201 Technical Data Sheet

Time over/underfrequency relay with protection assemblies

Solid-state Timer H3DS

SPECIFICATION. Online UPS 3000VA

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

IRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Stabilized Differential Relay SPAD 346. Product Guide

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

27/04/2015

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

RE22R2MMU Multifunction Timer Relay - 24VDC/ V AC - 2 C/O

PD30CNB25xxPS. Photoelectrics, Background suppression reflective - PointSpot. Main features. Main functions. Description

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

EMC Seminar Series All about EMC Testing and Measurement Seminar 1

1 INTRODUCTION ORDER CODE / INFORMATION

Harmonic Current emission EN :2014 Class A Pass. Voltage Fluctuation and Flicker EN :2013 Clause 5 Pass

Three-phase monitoring relays

Test Specification for Type Approval

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

Discontinuous Disturbance (Click) EN :2006+A1:2009+A2:2011 Clause N/A** Radiated Emission, 30MHz to 1000MHz

Digital Multifunction Instrument - Rish Master 3440

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

PART NUMBERING SYSTEM

CLP0205 Open Frame Power Supply Vac input; 5Vdc output; 200W Output Power; 0.25A stdby

PowerPact H-, J-, and L-Frame Circuit Breakers General Information. Vibration. Electromagnetic disturbances. Tropicalization

Transformer differential protection

ZBRRA Programmable receiver - 2 relays V AC/ DC - 2 pusbuttons - 6 LEDs

This annex is valid from: to Replaces annex dated: Locations where activities are performed under accreditation

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

EMC Test Report. Report Number: M030826

Guidance and Declaration - Electromagnetic Compatibility (EMC) for the Delfi PTS ii Portable Tourniquet System

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

EN :2007+A1:2011 Electromagnetic compatibility Emission standard for residential, commercial and light-industrial environments

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

A Comparison Between MIL-STD and Commercial EMC Requirements Part 2. By Vincent W. Greb President, EMC Integrity, Inc.

24 V DC, 12 W output 12 V DC, 12 W output 24 V DC, 36 W output

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5.

Time relay RXKA 1. (xx jpg) RXKA 1

Data Sheet. RISH Master Record %THD

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

DRTS-6. DRTS-6 has been designed to test: DRTS-6. Advanced Protection Relay Test Set and Measurement System

TEST REPORT... 1 CONTENT...

EMC standards. Presented by: Karim Loukil & Kaïs Siala

PART NUMBERING SYSTEM

RE11RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

Transcription:

SPECIFICATION FOR OVERCURRENT RELAYS 1/9

1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous answer to the requirements hereafter; this file should be provided in paper form (2 copies) and in electronic form One relay to be classified, for testing purposes, including a complete set of documentation These documents and relay should be sent to Synergrid (att. Secretary of the TCE), Rodestraat 125, 1630 Linkebeek. After receipt of all documents and relay, Synergrid will send a quotation to the manufacturer for the requested analysis and classification. The analysis will start only after the order has been received from the manufacturer. 2/9

2. Identification Form Overcurrent Protection Manufacturer : Type : Version: Date start approval Type of approval : New relay New version of approved relay New version of existing file Approved : YES / NO Date of approval : 3. Additional Information Overcurrent Protection Comments : 3/9

4. Technical Characteristics Main characteristics Type Function Requirements Remarks OK? Interface Rating analog input 1 and 5 A available (not necessarily in the same version) number At least 4 (3 phase currents + zero sequence) Tripping contacts 2 (at least 1 user defined) Signalling contacts 2 + watchdog Signalling contacts User defined contacts Signalable informations Programmable + watchdog Indicator lights or panel display Trip functions, started functions, service Possibility of local reset Leds indication memorized Input contacts 2 (user defined) Input contact voltage Same as supply voltage Supply Power supply At least, possibility to feed with DC supply MM-Interface Autosurpervision Consumption 35W Software compatibility At least windows XP, and more recent windows versions User software standardised (common for one family of relays) Use language At least English Use compatibility With all previous versions of the relay Frequent settings numerical input (no potentiometers or DIPswitches) Sealing of the settings At software level (password) Watchdog supply, memories, processor, software General Stability of working Normal operation of the relay while in 4/9

communication Local display Presence of a local display required Visualization of primary currents required Local port Presence of a local port for communication with relay (USB, Ethernet or local conversion mean provided with relay by manufacturer : USB or Ethernet) Date and time setting Possibility to program date and time precision Possibility to set : year, month, day, hour, minutes, seconds Event registers Available informations Trip + start of the functions Fault currents (primary values) Numbers of records 20 FIFO buffer overwrite principle Time stamp Each event must have an absolute time stamp (precision : ms) Disturbance recorder Number of records 3 Memory principle FIFO buffer overwrite principle start Possibility to start on pick-up Length of records 2 s user defined prefault User defined (at least 500 ms) Sampling frequency 400 Hz Available information Analog channels : currents (phase + ground) Digital channels : all starts of prot functions + trip File format COMTRADE 5/9

Technical characteristics Type Function Requirements Remarks OK? Electric strength 50Hz-1minute 2kV Surge-1,2/50µs, 0.5J 5kV Mechanical endurance Working 10000 workings of trip contact Insert/Remove 200 times Limits of quantities and influencing factors Vibrations Class 1 according to CEI 255-21-1 Ambient air temperature -5 C to 55 C Storage temperature -20 C to 55 C Power supply 80% to 115% U auxiliary Relative humidity According to CEI 68-2-30 Currents inputs Permissible continuous current 2*IN Thermal overload 100*IN RMS during 1s Dynamic overload 250*IN peak during ½ period consumption < 3 VA for I<IN Tripping contacts Voltage 230V AC/DC Permissible continuous current 5A AC/DC Permissible current during short 15A 0.2sec AC/DC time Making capacity 10A AC/DC Breaking capacity (in DC with L/R<40ms) 0.2A at 110V DC 0.5A at 48V DC Signaling contacts Voltage 230V AC/DC Permissible continuous current 1A AC/DC Permissible current during short 10A 0.2sec AC/DC time Making capacity 1A AC/DC Breaking capacity (in DC with L/R<40ms) 0.2A at 110V DC 0.5A at 48V DC 6/9

EMC requirements Standard Concerned Requirements Remarks OK? IEC 60255-25 emission this test applies to the auxiliary power supply inputs only Conducted emission limits 0,15 MHz - 0,5 MHz : 79 db (µv) Quasi peak, 66 db (µv) Average 0,5 MHz - 30 MHz : 73 db (µv) Quasi peak, 60 db (µv) Average Radiated emission limits 30 MHz - 230 MHz : 40 db (µv/m) quasi peak, measured at 10 m distance 230 MHz -1000 MHz : 47 db (µv/m) quasi peak, measured at 10 m distance IEC 60255-22-2 Electrostatic discharge tests IEC 60255-22-3 Radiated electromagnetic field disturbance test IEC 60255-22-4 electrical fast transient/burst immunity test IEC 60255-22-5 Surge immunity test Enclosure port Class 3 of severity test : 6 kv for contact discharge to conductive surfaces 8 kv air discharge at insulating surfaces Enclosure port Antenna facing the front and the rear of the relay 80 1000 MHz 1400 2700 MHz 80 % AM (1 khz) Communication Ports AC, DC low voltage Input and Output power ports Auxiliary power supply inputs Functional earth port Communication Ports 10 V/m r.m.s. within the swept frequency range 80 MHz to 1000 MHz and 1400 to 2700 MHz Test severity level: Class A 2 kv ± 10% / repetition rate 5 khz 4 kv ± 10% /repetition rate 5 khz 4 kv ± 10% / repetition rate 5 khz 4 kv ± 10% / repetition rate 5 khz Test severity level: Class A Line to earth:2 kv ± 10% AC, DC low voltage Input and Output power ports, auxiliary power supply ports Line to earth:4 kv ± 10% ; Line to line: 2 kv ± 10% 7/9

IEC 60255-22-6 conducted disturbances induced by radio frequency fields IEC 60255-22-7 Power frequency immunity test IEC 61000-4-8 Power frequency magnetic field IEC 60255-22-1 1 MHz oscillatory waves IEC60255-11 DC voltage interruption Communication Ports AC, DC low voltage Input and Output power ports, auxiliary power supply ports DC status input port Enclosure port Auxiliary power supply ports AC, DC low voltage Input and Output power ports Communication Ports Auxiliary power supply ports 10 V R.M.S. 10 V R.M.S. 10 V R.M.S. 10 V R.M.S. Test level class A Differential Mode (DM) tests 150 V r.m.s. Common mode (CM) tests 300 V r.m.s 30 A/m continuous 300 A/m for 1 to 3 s CM: 2,5 kv ± 10% / DM 1 kv ± 10% / Oscillation frequency 1 MHz CM: 2,5 kv ± 10% / DM 1 kv ± 10% / Oscillation frequency 1 MHz CM: 1 kv ± 10% / DM 0 kv / Oscillation frequency 1 MHz 100% reduction 5,10,20,50,100,200 ms interruption time Protection functions Type Function Requirements Remarks OK? Currents General Possibility to disable each function I> At least DT characteristics Settable time delay : 0 to 60 s (maximal step 0.1 s) Settable threshold : 0.3 to 2.5 IN I>> At least DT characteristics Settable time delay : 0 to 2 s (maximal step 0.1 s) Settable threshold : 1 to 30 IN I0> At least DT characteristics Possibility to use dedicated input for CT torus Settable time delay : 0 to 2 s (maximal step 0.1 s) 8/9

Settable threshold : 0,05 to 5 I0N Signal filtration harmonics < 10 % threshold for H N 20 % H 1 Influence of ripple control signal < 10 % threshold Used frequencies : 175, 180, 216, 273, 283, 317, 1350 Hz Accuracy current 0.05 A sec Time 30 ms Instantaneous trip time 50 ms Drop-off value 10 % of threshold Marking Marking Remarks OK? Marking in English Constructor name or fabrication brand (front panel) Designation of type (front panel) and serial number Software version (digital relays) (or available via display) Nominal values of supply voltages Rated values CE marking Indication of the execution of the factory acceptance tests (stamp of conformity tests) Documents User manual with connection plans Report of dielectric tests and EMC tests Description of factory acceptance tests Remarks OK? 9/9