How does electrical equipment rate? By Bill Mairs Technical Manager NHP Electrical Engineering Products Pty Ltd

Similar documents
TECHNICAL NEWS CABLE CONSIDERATIONS [ISSUE 46] DECEMBER 05 FEATURES:

DC Traction and bar contactors

7P Series - Surge Protection Device (SPD) Features 7P P P

Harmonic Filtering. Compact, fast response harmonic mitigation solution. POWER QUALITY. NHP Electrical Engineering Products Pty Ltd

Low voltage products in high altitudes

Choosing the right Pico Technology active differential probe

Power Quality Solutions

Technical News. Part 2: Harmonics. The link between harmonics and power factor. Industrial Electrical and Automation Products, Systems and Solutions

Active: Active probes achieve low input capacitance and high sensitivity by buffering and amplifying the signal close to the point of measurement.

Australian/New Zealand Standard

EE 1402 HIGH VOLTAGE ENGINEERING

VI 3 - i TABLE OF CONTENTS

A Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables

Capacitor Switching Contactors

Prepared by Mick Maytum

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition

TEST REPORT IEC Low-voltage switchgear and controlgear - Part 2: Circuit-breakers

Insulation Co-ordination For HVDC Station

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

3 - Protection components Circuit-breakers

HIGH VOLTAGE Insulation Coordination

COURSE PLANNER. Subject: TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS ( ) B.E. Fourth Year (8 th Sem) Branch Electrical Engineering

NT & NQ CLASS II TRANSFORMERS FOR SIGNALLING SYSTEMS. A Balfour Beatty and Alstom Company

ELECTRICAL EQUIPMENT. Inspection. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

LC1D12BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

LC1D32BD TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 24 V DC coil

Power Quality and Reliablity Centre

page 2 of 86 Report reference No:

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

technical information

Technical features table for miniature circuit-breakers SH 200 Series

NIRAPOD 1. High performance circuit breaker mcb and combined mcb with remote controls. LV Distribution Products 2-63A

Appendix B to Working on Exposed Energized Parts

DESIGN STANDARD NO. DS 21

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

CB Testing Laboratory...:EZÚ Address...:Pod Lisem Praha71-Trója Testing location/ procedure...: CBTL RMT SMT WMT TMP IEC60947_2C

H A 6 6 CHANNEL STEREO HEADPHONE AMPLIFIER INSTALLATION AND OPERATION MANUAL

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY

Solid State Relay, 1-phase

Underground System Design TADP 547

INTERPLANT STANDARD - STEEL INDUSTRY

Transformers connected via a cable Overvoltage protection

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

Univerter-MV. Medium Voltage Variable Speed Drive

, Power Industries and Communications Industry Training Board

DEVELOPING TESTING PROCEDURES FOR HIGH VOLTAGE INNOVATION TECHNOLOGIES

Modeling insulation in high-voltage substations

Residual Current-operated Circuit Breakers (RCCBs) F 360 and F 370 Range

Electrical Measurement Safety. Sponsored By:

Electrical Protection System Design and Operation

Low voltage switchgear

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

AS/NZS :2013 (IEC , , MOD)

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering

VBS TBS KTS BSS LFS UFS

7. INSPECTION AND TEST PROCEDURES

Progetto in Inchiesta Pubblica

Grounding System Theory and Practice

Energy Division. Bowthorpe LV/MV Surge Arresters

FUNCTIONS OF CIRCUIT BREAKERS

Gas-Insulated Medium-Voltage Switchgear siemens.com/8dab12

VACUUM INTERRUPTER APPLICATION NOTES Filename: VIAN X-Rays and Vacuum Interrupters Revision: 0 PAGE 1

INTERNATIONAL STANDARD

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

T e c h n i c a l C a t a l o g u e MCCB. Moulded Case Circuit Breaker

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

# - - Internal * On Line Examination

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

isw switches Control Local control IEC/EN , isw switch with indicator light. IEC/EN , isw switch without indicator light.

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201

TeSys circuit-breakers Thermal-magnetic motor circuit-breakers types GV2, GV3 and GV7

Protection of Electrical Networks. Christophe Prévé

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil

Earthing of Electrical Devices and Safety

Components for Marine applications

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Reference Number PDS 04 (RIC Standard: EP SP)

Selection of MO surge arresters Overvoltage protection

G. KOEPPL Koeppl Power Experts Switzerland

(With the possibility of a tripping coil for remote control) (Generally optional with an electronic tripping device)

DCM w Power Amplifier

SECURITY SCREENS FABRICATION REFERENCE

HARMONICS CAUSES AND EFFECTS

UNDERSTANDING POWER QUALITY

Transcription:

100 percent Australian Owned TECHNICAL NEWS Issue 28 April 1999 Please circulate to Quarterly Technical Newsletter of Australia s leading supplier of low-voltage motor control and switchgear. How does electrical equipment rate? By Bill Mairs Technical Manager NHP Electrical Engineering Products Pty Ltd IN THIS ISSUE How does electrical equipment rate Conventional enclosed thermal current Voltage ratings Rated impulse withstand voltage What needs to happen Reader response 1 2 3 4 5 6 Electrical equipment is defined by a bewildering array of ratings. Few people fully understand these ratings as some of even the fundamental ratings have a history of international manipulation and compromise. This has resulted in obscure meanings that can leave the newcomer totally confused. While the international playing field might be more level with Australia basically adopting IEC standards the placement of the goal posts is by no means fixed. The manufacturers and users of electrical equipment often find themselves aiming for different ends of the field. The early Australian standards had a strong British influence and were full of practical approaches. In those days for instance the small wiring cables only had one current rating. Technical correctness had been put aside for the sake of simple understanding. This paper looks at a few of the ratings with some explanation of how we got where we are today. Device rating needs to be understood to make correct selections. Ratings based on current Current influences the temperature rise, electromagnetic forces and the contact life of a device. There is a range of ratings based on current for normal and abnormal operating conditions. Conventional free air thermal current (I th ) This is most fundamental of all the ratings as the $/amp is usually the first comparison made when selecting between products from different suppliers. Given its basic importance it is easy to see that if the Ith is increased so the price equation improves. It is not surprising therefore that when IEC principles were adopted, equipment

2(Continued from Page 1 Circuit breaker enclosure ratings increased. It would seem that the pressure groups at the time ensured that the test methods maximized the results that could be obtained in the standard tests. To achieve this the standard test conductors were made large and thus provided heat sinking of the device under test. The temperature restrictions were also increased to allow hotter running. The problem was compounded when the Australian Wiring Rules included tables for busbar ratings which implied busbar temperature rises of 70 o C were acceptable. This is in stark contrast to the temperature rise of test conductors. These are proportioned to give a temperature rise of about 20 o C in the test configuration. Conventional enclosed thermal current (I the ) This is the value of current the device can carry when mounted in a defined enclosure. While most electrical switchgear is intended to be enclosed, I the is not normally quoted. The variations caused to the actual temperature rise by the enclosure design and the heating caused by other equipment means that in most situations I the will also vary. Manufacturers can provide some guide to a suitable derating of enclosed equipment but the designer of the assembly must take responsibility for the final outcome. Test current 2000 amps 3 100 x 5 Cu bars for test. In free air AS3000 lists 2 63 x 6.3 as suitable. Rated operational current (I e ) The operational current relates to the devices switching ability at its operational voltage. It is often less than the thermal current rating. Rated service short-circuit breaking capacity (I cs ) and Rated ultimate short-circuit breaking capacity (I cu ) Before the adoption of IEC standards there were separate 2m Typical test arrangement for enclosed current rating. Test busbars are of large cross section. performance standards for Moulded Case Circuit Breakers (MCCB) and Air Circuit Breakers (ACB). The term Air Circuit Breaker referred to the fact that the breaking process was in air as against the old oil immersed style. A more accurate distinction between the two would have been metal clad as compared to moulded case. While in principle the two Circuit breakers can be selected on the basis of Icu. Actual fault currents are normally less than the circuit prospective.

3 400. 200. 0. -200. Transient voltage recorded during short circuit testing of a miniature circuit breaker. Actual peak is off scale. styles of circuit breaker were much the same the ACB was considered more robust and had the ability to withstand short duration fault currents with the contacts remaining closed. This ability allows time grading with down stream circuit breakers. The ACB was also expected to withstand an extra operation at maximum fault levels. The ACB was generally applied at the main switchboard and MCCBs used for lower rated distribution circuits. As product ranges developed MCCBs increased in current rating and some ACBs used an increasing number of mouldings. These trends and the similar purpose of the two styles of circuit breakers resulted in a single standard being produced. The greatest difficulty in combining the two was the difference in the number of close open operations required at the rated short circuit level. For the MCCB, to increase the number of operations would have meant the short circuit rating would need to be reduced. For the ACB, to reduce the number would remove one of the main differences between the two styles of breaker. This issue was resolved by introducing the concept of Ultimate (I cu ) and Service (I cs ) short circuit ratings. The Ultimate rating requiring an open / close open test sequence while the Service rating an open / close open / close open sequence. Unfortunately this has resulted in confusion ever since. There is no guide given in the standard as to how to apply the two ratings. Based on the history of the ratings there is no reason why MCCBs should not be chosen on the basis of the Ultimate rating. There are very few MCCB problems that have resulted from the MCCB being selected on the basis of the Ultimate rating instead of the Service rating. Voltage ratings The voltage ratings are critical to the performance of electrical switchgear. While the IEC standards show a consistent treatment of the voltage ratings, modifications introduced by Australia have distorted the concepts to some degree. Rated operational voltage (U e ) This is the voltage at which the operational tests are performed. Several ratings may be applied for use at different supply voltages. This rating is fairly straight forward. Rated insulation voltage (U i ) This rating is equal to or greater than Ue and relates to the voltage at which the dielectric and creepage distances are referred. Testing for this rating includes allowances for overvoltages. As the standards specify a particular test voltage as covering a range of Ui ratings it is normal to specify Ui as the highest value in the range. It should never be assumed that a device can be operated at Ui as it may be incapable of breaking any current at that voltage. Rated impulse withstand voltage (U imp ) Relates to the peak value of

4 voltage that the equipment can withstand without flashover or damage. The occurrence of transient overvoltages in electrical systems is a normal event. They are caused by switching transients and induced effects from lightning strikes. The voltage withstand of the equipment needs to be high enough to prevent flashover. If flashover does occur this can often provide the means for a continuing arc to be established, resulting in severe damage. The IEC approach is to establish a coordinated insulation system. The transients need to be limited to a level below the impulse withstand levels of the associated equipment. The magnitude of possible transients is considered greatest at the service entrance level and decreases at the distribution circuit and equipment levels. Surge arresters are normally required for transient control. In Australia the use of surge arresters has not been common and there has been substantial resistance to adopting the IEC principles. The Wiring Rules and the Australian versions of the switchboard standards have always specified quite large creepage and clearance distances. Based on experience the values specified have been sufficient to allow quite high transients to pass without flashovers. The basic switchgear standard AS3947 accepts the principles IEC preferred values of rated impulse withstand voltage when protected by surge-arresters. Overvoltage category I II III IV Specially Load Distribution Origin of protected (appliance circuit installation level equipment) level (service level entrance) level 1.5kV 2.5KV 4kV 6kV Minimum clearance required for inhomogeneous field conditions for above impulse levels. 0.5mm 1.5mm 3mm 5.5mm Impulse level as modified by AS4349 for the live conductors in Australian switchboards. 10kV 10kV 10kV Minimum clearance required by AS3439 12mm 12mm 12mm Australian requirements for switchboard surge ratings in not matched in Australian switchgear standards. Surge diverters are being used to protect equipment of insulation coordination and does not set specific requirements for Australia. On the other hand, AS3439, the switchboard standard, has been modified away from IEC requirements to require high withstand levels. The impulse level has been specified as 10kV and this effectively results in requiring the same creepage and clearance distances that have been used for many years. This difference makes flashover of busbars unlikely but failure of the equipment possible. This can be seen with sensitive electronic equipment as damage by electrical transients is common. The damage has reached a point were the domestic consumer is well aware of the problem and many surge arresters are being purchased to prevent loss of expensive equipment or data. In industrial applications failures are occurring with flashover of equipment inside switchboards. At this level

5 Flashover of test station terminals caused by a voltage transient. Test duration 0.2 seconds 50kA prospective current. (Continued from Page 4 however there seems to be a lower understanding of the problem than at the domestic level. There is of course a major difference in the consequences of the flashover. An electronic device that has been killed by a transient still looks the same but a fault in a switchboard usually results in extensive arcing damage even though the causes may have been identical. What needs to happen The thermal performance of equipment requires a balance between the device, the enclosure and the connecting conductors. The 1991 edition of the Wiring Rules was in conflict with the switchgear standards in regard to busbar selection but a better approach has been published in AS4388-1996. This standard details a method for switchboard temperature rise assessment and includes more realistic temperatures for the operation of busbars. Unfortunately, the busbar sizes are metric while imperial bar sizes are still common in Australia. This standard needs to be revised to include the imperial sizes. The confusion between ultimate and service short circuit ratings needs to be clarified by perhaps a statement in the Wiring Rules. For normal distribution circuits the prospective short circuit level of the circuit needs only to be matched by the ultimate rating. While those experienced in the electrical industry have a fair understanding of the problems of temperature rise the causes and remedies of electric flashover are very poorly understood. The destruction caused by the arc often hides the evidence but breakdown does occur even with quite large clearances as there is often no surge arrester in the system. As a flashover often involves substantial financial loss, litigation is often threatened but seldom undertaken because the issue quickly becomes quite technical. The presence and cause of a destructive transient is also very difficult to prove after the event. To overcome the situation Australian Standards need to remove the fuzzy approach to insulation coordination and accept that surge arresters should be required.

6 If you would like previous copies of Technical News, please complete the following form and fax to NHP on (03) 9429 1075 marked to the attention of the Marketing Services Department. Name:...Title:... Company:... Address:... Telephone: ( )...Fax: ( )... Catalogue CPB Other titles currently available. Please tick those you would like to receive. The quality Switchboard (Switchgear and protection devices for switchboards) RCDs are saving lives (Earth leakage protection; RCDs) Terminations, good or bad? (Terminals) Power Factor, what is it? (Power Factor Correction) Talk about torque (Motors and torque) What's the difference about safety (Safety devices and their application) Pollution of the airwaves (Unwanted signals and their effects on motor protection devices) Some don't like it hot (Temperature rise in electrical switchgear) The thinking contactor (The development of the contactor) Electrical surges can be expensive (Electrical surges) Application guide to lamp selection (Industrial pushbutton controls) Start in the correct gear (Application of different motor starters) Taking the 'hiss' out of DC switching (DC switching principles) Electrical life of contactors (How and why contactors are tested) Don't forget the motor protection (Motor protection devices and application) Utilisation categories (Electrical life of switches) IP ratings what do they mean? (IP Ratings, use and meaning) Set the protection (MCCB breakers and application) NHP Electrical Engineering Products Pty Ltd A.C.N. 004 304 812 www.nhp.com.au MELBOURNE 43-67 River Street, Richmond, Vic. 3121 Phone: (03) 9429 2999 Fax (03) 9429 1075 SYDNEY 30-34 Day Street North, Silverwater, N.S.W. 2128 Phone: (02) 9748 3444 Fax: (02) 9648 4353 BRISBANE 25 Turbo Drive, Coorparoo, Qld. 4151 Phone: (07) 3891 6008 Fax: (07) 3891 6139 ADELAIDE 50 Croydon Road, Keswick, S.A. 5035 Phone: (08) 8297 9055 Fax: (08) 8371 0962 PERTH 38 Belmont Ave., Rivervale, W.A. 6103 Phone: (08) 9277 1777 Fax: (08) 9277 1700 NEWCASTLE 575 Maitland Road, Mayfield West, N.S.W. 2304 Phone: (02) 4960 2220 Fax: (02) 4960 2203 TOWNSVILLE 62 Leyland Street, Garbutt, Qld. 4814 Phone: (07) 4779 0700 Fax: (07) 4775 1457 ROCKHAMPTON 208 Denison Street, Rockhampton, Qld. 4700 Phone: (07) 4927 2277 Fax: (07) 4922 2947 TOOWOOMBA Cnr Carroll St., & Struan Crt., Toowoomba, Qld. 4350 Phone: (07) 4634 4799 Fax: (07) 4633 1796 CAIRNS 14/128 Lyons Street, Bungalow, Qld. 4870 Phone: (07) 4035 6888 Fax: (07) 4035 6999 DARWIN 3 Steele Street, Winnellie, N.T. 0820 Phone: (08) 8947 2666 Fax: (08) 8947 2049 Agents: HOBART 199 Harrington Street, Hobart, Tas. 7000 Phone: (03) 6234 9299 Fax: (03) 6231 1693 LAUNCESTON 59 Garfield Street, Launceston, Tas. 7250 Phone: (03) 6344 8811 Fax: (03) 6344 4069 BURNIE 6 Wellington Street, Burnie, Tas. 7320 Phone: (03) 6432 2588 Fax: (03) 6432 2580 Version 1 Editorial content: - Please address all enquiries to 'The Editor - 'NHP Technical News' PO Box 199, Richmond Victoria 3121. TNL 28-4/99-14M