Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later

Similar documents
Maryland Building Officials Association Typical Deck Details

Page 1 of 70

City of Virginia Beach, Virginia Typical Deck Details

Typical Deck Details

Typical Deck Details Based on the City of Nixa Residential Deck Ordinance

Pulaski County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code

Typical Deck Details

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

Typical Deck Details

Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder. Installation Instructions Revised 9/2/2016

Deck Design Guide. One and Two Family Residential Dwellings

PRESCRIPTIVE RESIDENTIAL DECK CONSTRUCTION GUIDE. Based on the 2015 International Residential Code

Residential Decks. Typical Deck Details DECKING REQUIREMENTS

24" max from each end of the ledger. See detail 6A & 6B, typ. both ends IRC R Ledger R507.2

Prescriptive Residential Wood Deck Construction Guide Based on the 2006 International Residential Code

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems Overview Revised 9/2/2016

Sections & Details VOCABULARY

DECKS. Stairway illumination Positive attachment of ledger Lateral load connection required board (R507.2) required (R ) (R311.7.

SDWH TIMBER-HEX Screw

COMPACT DECK. Compact Deck SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

FASTENERS BUILDING DEPARTMENT

APPLICATION FOR A BUILDING PERMIT

APA Performance Rated Rim Boards

Deck Evaluation Checklist

ONE AND TWO FAMILY DWELLINGS Uncovered Decks July, 2007

THE ENGINEERED WOOD ASSOCIATION

3.1 General Provisions

FREDERICK COUNTY USBC/IRC 2015

TRELLIS. Trellis SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

Fastener Schedule. a, b, c. FASTENER Roof 3-8d (2 1 / ) / ) 3-10d. 3-10d ( ) 3-16d box nails. (3 1 2 toe nails on one side

Ohlson Project Property Owner: Kathy Ohlson Property Address: Deer Lake Rd. Derwood MD 20855

TYPICAL PATIO COVERS. OWNER: ADDRESS: PHONE:

Load Tables, Technical Data and Installation Instructions

Featuring TJ Rim Board and TimberStrand LSL

CSS Central Mount System

Sections & Details. WOOD SILL and FLOOR CONSTRUCTION NOTES

REVISION CHANGES: REV. NO. REV. DATE

STORAGE SHED. Storage Shed SOUTHERN FOREST PRODUCTS ASSOCIATION SOUTHEASTERN LUMBER MANUFACTURERS ASSOCIATION

10x12 FOUNDATION GUIDE 10x12 TRICO AND FLORA SHEDS

installation Guide What you don t Safety I-Joist Storage and Handling United states Installation Instructions for Residential Floor Systems

Sturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models

Step 2 - Measure and install joist hangers every 16". See Figure "B" above. Fill every hole in each

How to Build Good Decks..

TRUS JOIST RIM BOARD. Featuring TJ Rim Board and TimberStrand LSL. Multiple thicknesses, grades, and products to cover all your rim board needs

Boardwalk Construction Guidelines

BUILDING & SAFETY DIVISION 110 E. LA HABRA BLVD. LA HABRA, CA Rev. 06/17

Call (770) STEP 6: Caulk bolt hole within the bracket for protection from the elements.

When is a Building Permit Required? Deck Details: What Must be Submitted with a Building Permit Application?

ICC-ES Evaluation Report

SECTION ROUGH CARPENTRY

2x6. 2x8. 2x10. Size. 2-2x10 8'-5" w/ 2 NJ 7'-3" w/ 2 NJ

17.0 Printable Pages: Documents, Forms, And Current Drawings


Introducing AJSTM INSTALLATION GUIDE USA. 8 th Edition USA

ROOF-CEILING CONSTRUCTION

VERSA-LAM BCI INSTALLATION GUIDE LIMIT STATES DESIGN CANADA

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Deck Designer Specification Kit For AZEK. All rights reserved copyright 2015 AZEK Building Products

A. Rough carpentry includes but is not limited to the following:

Deck Designer Specification Kit For AZEK. All rights reserved copyright 2015 AZEK Building Products

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

INDEX PAGE RELEASE SECTION NUMBER DATE

TREX POST MOUNT DECKING AND CONCRETE

TOLL FREE:(888) FAX:(941) ASSEMBLY of ProTEC CONCRETE STRUCTURAL INSULATED PANEL

PRE-ENGINEERED HORSE STALL SYSTEMS 4884 HSD STANDARD SLIDING DOOR. & Assembly. Installation Instructions

Use the Design Properties (100% Load Duration) Table from Page 3 for questions 1-7

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Lateral Tension System

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

8x8 Shed Plans and Building Guide

APPENDIX FENCE GENERAL NOTES

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

PAINT & MISC. Notes. Table of Contents. Front Handrail Posts Front Handrails Closet Shelving Exterior Deck...

Chapter 33: Lofts (Or Second Floors)

Beam & Header Technical Guide. LP SolidStart LVL. 2900F b -2.0E. U.S. Technical Guide U.S. TECHNICAL GUIDE

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233

Deck Designer Specification Kit For AZEK. All rights reserved copyright 2015 AZEK Building Products

Installation Guide. 203 Chesterra Drive, Dahlonega, GA Toll-Free ~ Fax ~

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year.

Deck Designer Specification Kit For AZEK. All rights reserved copyright 2015 AZEK Building Products

Installation of Balustrade Systems

Trusted ICC ES PASLODE, Evaluation. report, or as to any. ICC-ES Evaluation

Best Barns USA Assembly Book

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

INSTALLATION SHOP DRAWINGS FOR MINNEAPOLIS, MN

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Build Like a Pro: Building a Deck

Deck Designer Specification Kit For. TimberTech. All rights reserved copyright 2015 AZEK Building Products

Best Barns USA Assembly Book

10x10 Shed Plans and Building Guide

COMPACT DECK. Compact Deck Project Plan #850 Sheet 1 of Riverside Dr., Suite 212 Metairie, LA SouthernPine.com SouthernPineDecks.

Best Barns USA Assembly Book

Best Barns USA Assembly Book

Transcription:

Lateral Support Decks over 24 above grade require lateral support* *Exceptions to be discussed later

Decking Types of Decking: -2x4s & 2x6s -five quarter span rated decking boards -Wood plastic composite -Plastic decking requires professional testing organization testing to support 40LL psf & installed per MFR Decking: 45 or 90 To Joists?

Deck Example Summary Deck size: 20-0 x 16-0 Joists: Southern Pine 2x10 @ 16 o.c. w/ 2 overhangs Beam: Southern Pine (2) 2x10 w/ 1-0 overhangs Footings: 19 diameter & 8 thick Posts: 6x6 @ 6-0 apart Decking: 2x6 @ 45 Attached to house 4-0 above grade

Typical Framing Plan Can use this or make your own

16-0 2-0 14-0 Sample Framing Plan 1-0 6-0 6-0 6-0 1-0 20-0

Sample Checklist 14 0 2 0 1 0 3 6 19 8 16 0 20 0

Construction The Rest of Appendix B

Section 1: General requirements Lumber Wood-Plastic Components Fasteners Hardware Electrical Requirements Loading Safety Glazing NEC 210.52(E)(3)

Lumber Douglas fir/larch Hemlock/fir Spruce/pine/fir (SPF) Southern pine, Must be grade #2 or better Appendix C Adds: Ponderosa Pine Red Pine Redwood Must be pressure treated & ground contact when needed

Hardware & Fasteners Nails must be threaded: Spiral-Grooved or Ring-Shanked Lag-Screws Carriage-Bolt w/ washer @ bolt head (substitute for through-bolts) Fasteners & hardware must be same material, galvanized steel or stainless steel

Section 2: Footings, & Post Connections Concrete Footings Attachments Connections Concrete min. 3,000 pounds per in 2 (compressive strength)

Footings, & Post Connections Post Attachment Figure 1, plus expansion anchors Figure 1 1 min. base plate* unless ground contact lumber used Expansion Anchors are permitted *MFRs may require min. edge distance

Footings Post over middle 1/3 of footing Footings min 48 below grade or frost line whichever is greater Not on unprepared fill material, organic soil, alluvial soil, or mud Bearing capacity of the soil at least 2,000 PSF 4 4 4 Example: 12 footing 12/3 = 4 size of middle 1/3 of footing Place anywhere in this circle

Free-Standing Deck Footings Footings prohibited over utility lines or service pipes

Section 3:Post-Beam-Connection Beam Splices Require Min. 6 x6 Posts

Post-Beam-Connection Toe nailing prohibited Post caps per MFR specs Recommended to field-treat cut ends of posts with wood preservative

Section 4: Beams Multiple 2x members for a beam, see Figure 4. Pressure preservative treated glulam beams require design and plan submission with permit application.

Section 5: Joists Full Height 2x blocking/bridging for 2 x10 or deeper joists 8 feet apart. Blocking above beam, can reduce up to 60% of height for drainage. Attach blocking/bridging with (3)10d toe nails at each end.

Rim Joists Continuous rim joist per Figures 5 and 7 unless blocking or bridging each joist at the beam where overhang begins. Figure 5 Attached To House Attach rim joist to end of each joist with (3)10d nails or (3)#10 by 3 inch wood screws. Figure 7 Free-Standing

Section 6: Joist-To-Beam Connection

Section 7: Joist Hangers 1. Joist hanger depth, at least 60% of joist depth. 2. MFR width of joist hanger must match number of plies. 3. Do not bend hanger flanges to fit field conditions. Hanger Min. 60% of Joist depth

Joist Hangers Flange bent for angle of deck 3 ply beam,2 ply hanger Angles cannot be used instead of hangers Wrong hanger type

Section 8: Ledger Attachments Follow Section 8 & 9 for ledger board attachment to existing houses. Ledger board depth joist depth & min. 2x8. Existing band board on house must be able to support deck. If not, free standing deck or engineered design. Top of ledger board & top of deck joists must flush. Metal plate connected wood floor trusses used in house, see section 6 of Appendix C.

Figure 11 Note the Continuous flashing with drip edge.

Figure 12

Figure 13

Flashing Continuous flashing with drip edge per Figure 11. Remove exterior finish, before installing ledger board.

Flashing Flashing must be a corrosion resistant metal such as: galvanized steel coated with zinc copper (attached using copper nails only) stainless steel UV resistant plastic per MFR recommendations Do not use aluminum in direct contact with lumber treated with preservatives that contain copper, I.e. ACQ, copper azole, or ACZA. Galvanized steel Stainless steel Copper

Section 9: Ledger-Board Fasteners 6 Lead anchors are prohibited Prohibited Attachments

Through-Bolts 1/2 diameter with washers at bolt head & nut. Bolts should be tightened 6 to 12 months after construction due to drying and wood shrinkage. With ½ stacked washers

Expansion Anchors Bolt or threaded rod of expansion anchors 1/2 inch, which in some cases may result in needing a 5/8 inch diameter anchor. Expansion anchors installed in accordance with manufacturer s instructions & have washers.

Adhesive Anchors Approved adhesive anchors with 1/2 inch diameter threaded rod. Anchor examples: Epcon Acrylic 7 by ITW Ramset/Red Head, & HY 20 by Hilti. Adhesive anchors also permitted with concrete or solid masonry installations. Adhesive anchors installed in accordance with manufacturer s instructions & have washers. Adhesive cartridges should remain on the jobsite for inspector verification.

Lag Screws Lag screws must be equipped with washers.

Section 11: Lateral Support Decks over 24 inches above grade must resist lateral loads. Individual diagonal braces may be omitted if less than 2' of vertical clearance.

Diagonal Bracing Diagonal bracing both parallel & perpendicular to beam at each post. When parallel to beam, bolt bracing to post & beam. When perpendicular to beam, bolt bracing to post & a joist or blocking between joists.

Lateral Support Exception 1 Bracing is not required perpendicular to the house for a deck that is attached to the house with both a ledger board under sections 8 and 9 and the connection specified in either Figure 19 or 20. Section 8: Ledger Attachments (includes flashing) Section 9: Ledger-Board Fasteners And either: Figure 19: Tension-Tie Connection, W/ Ledger Board Or: Figure 20: Hold-Down Tension Device, W/ Ledger Board

Lateral Support Exception 2 Free standing deck attached to the house per Figure 21, bracing parallel to the house may be omitted at the beam adjacent to the house.

Lateral Support Exception 3 All bracing may be omitted for a deck which is attached to the house in accordance with sections 8 and 9 or Figure 21 and which has all of its decking installed at a 45 degree angle to the deck joists. Either: Section 8: Ledger Attachments Section 9: Ledger-Board Fasteners with 45 Degree Angle Decking Or Figure 21: Attachment of Free- Standing Deck To House with 45 Degree Angle Decking

Tension Tie Requirements Not for free-standing decks Minimum capacity of each tension tie, 750 pounds. Tension ties not G 185 zinc coated require MFR recommended barrier membrane between tie & treated joist Approved tension ties include: LTS19 TZ from USP DTT1Z from Simpson Strong Tie

Tension Tie Requirements ½ lag screw Installed min. of 3 into sill plate or top plate For concrete walls, adhesive or expansion anchors & a 1/2 inch threaded rod, with a withdrawal capacity of at least 750 pounds per MFR specs may be used.