Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Similar documents
NJWA - Harmonics and Drives Proper System Design

Understanding Input Harmonics and Techniques to Mitigate Them

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Effective Harmonic Mitigation with Active Filters

Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions

Open-Delta Systems Affect Variable Frequency Drives

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

7/15/2002 PP.AFD.08 1 of 28

Harmonics White Paper

Simulation of H bridge Inverter used for Induction Melting Furnace

Harmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

22.0 Harmonics in Industrial Power Systems

Drives 101 Lesson 5. Power Input Terminology for a VFD

Harmonic Distortion Evaluations

PQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement

Power quality improvement of self- excited induction generator using Multipulse AC-DC converters - A comparison

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Harmonic Distortion and Variable Frequency Drives

Harmonics and Their Impact on Power Quality. Wayne Walcott Application Engineering Manager June, 2017

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Three-Phase Multi-Pulse Converter with Phase-Shifting Transformer

Peteris Spels, ABB Inc., WMEA, November 18, 2011 HARMONICS. ABB Group December 14, 2011 Slide 1

IMPACT OF VARIABLE FREQUENCY DRIVES ON ELECTRICAL SYSTEM

Alternators Reactance for Nonlinear Loads

Introduction to Rectifiers and their Performance Parameters

Harmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

An Active Interphase Transformer for 12-Pulse Rectifier System to Get the Performance Like 24- Pulse Rectifier System

Application Note. Applicable Product: AC Drives

Technical Paper. Harmonic Distortion in Data Centers

VFDs and Harmonics in HVAC Applications

Comparison of Concepts for Improving the Line Power Quality of Electrostatic Precipitator Systems

Low Pass Harmonic Filters

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

ZENER ELECTRIC PTY LTD

International Journal of Research Available at

Harmonic Mitigation Harmonic Data Comparisons

16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, VARIATION OF HARMONICS AND RIPPLE WITH PULSE NUMBER Pulse Number

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

Harmonic Filtering in Variable Speed Drives

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

The increase in the application

Analysis of Harmonic Distortion in Non-linear Loads

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Mitigation in Variable Frequency Drives: 6-Pulse Drive with MTE Matrix AP Harmonic Filter vs. 18-Pulse Drive

APPLICATION GUIDE. Harmonics in HVAC applications

How adjustable speed drives affect power distribution

Harmonic Mitigation in AC DC Converters for Induction Motor Drives by Vector Controlled

CHAPTER 1 INTRODUCTION

New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications

ABB DRIVES Technical guide No. 6 Guide to harmonics with AC drives

ISSN: [Neha* et al., 6(5): May, 2017] Impact Factor: 4.116

Closed Loop Control of Multipulse Rectifier Using Novel Modulation Techniques

International Journal of Advance Engineering and Research Development. 18 Pulse Uncontrolled Rectifier

Harmonic control devices. ECE 528 Understanding Power Quality

ABB n.v. Power Quality Products, October 2014

Part Five. High-Power ac Drives

Reliable power onboard and offshore

ISSN Vol.03,Issue.07, August-2015, Pages:

Economical Solutions to Meet Harmonic Distortion Limits[4]

VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY

THE rapid development of power electronics in recent

Harmonic Distortion Effects and Mitigation in Distribution Systems

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

Power Quality Improvement in Induction Motor Drive using 24-Pulse AC-DC Converter Employing Pulse Multiplication Technique

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Thyristorised Automatic Power Factor

Electromagnetic Harmonic Filters Technical Guide

Shunt Active Power Filter for Compensation of System Harmonics

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Harmonic Mitigating Transformer - Technical Guide

Tuningintobetter power quality

Harmonic Design Considerations for Wind Farms

Harmonics Reduction using 4-Leg Shunt Active Power Filters

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation

NPTEL

MIRUS International Inc.

Handling System Harmonic Propagation in a Diesel-Electric Ship with an Active Filter

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System

RECENTLY, the harmonics current in a power grid can

Harmonic Filters and Reactors

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

New power tools provide quality and efficiency By

Frequently Asked Questions (FAQs) MV1000 Drive

Product Application Note

CHAPTER - 3 CONVENTIONAL SOURCE INVERTER FED INDUCTION MOTOR DRIVE. output voltage could be fixed or variable at a fixed or variable frequency.

p. 1 p. 6 p. 22 p. 46 p. 58

Matrix Drives Boost Power Quality and Energy Savings

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS

CONCLUSIONS AND SUGGESTIONS FOR FUTURE WORK

Harmonic control devices

LINEATOR. Advanced Universal Harmonic Filter

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

Transcription:

White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 1/6

Input current INTRODUCTION Adjustable speed AC drives are mainly made up of two power sections, i.e., a rectifier section and an inverter section. The AC source voltage is converted into a DC voltage by the rectifier circuit, and then the DC voltage is converted again into a PWM controlled variable voltage AC output by the inverter circuit. The six-diode bridge rectifier is most widely used as an AC-to-DC converter. This diode rectifier has a nonlinear (i.e. non-sinusoidal) load characteristic causing harmonic currents flow into the power source and results in line voltage distortion. Excessive harmonics in a power source raise many practical problems such as; - The rms current increase and input power factor reduction - Overheating of grid-connected motors, cables, transformers, and other distribution equipment - Resonating and harmonic heating of the power factor correction capacitors - Nuisance tripping of the thermal circuit breakers - Malfunction of PLCs, computers, and other harmonics sensitive equipment. The Yaskawa E7,F7,G7, and P7-series drives above 30HP have a built-in DC link choke as a standard easily mitigating input current harmonics. In case of six-diode bridge rectifier, the input current Total Harmonic Distortion (THD) is approximately 40% at a full load condition. The harmonic currents can be further reduced to about 30% with the addition of input AC reactors in combination with a DC link choke. For further harmonics reduction, multipulse rectifier topologies are good practical solutions, which reduce input current harmonics to levels below 10%. This paper introduces general features and advantages of Yaskawa s multi-pulse solutions that include 12-pulse and rectifier topologies. 6-PULSE RECTIFIER The 6-pulse rectifier circuit is adopted in most AC drives because of its simple and low cost structure. However, at full load conditions, the input current THD can exceed 100% with no harmonic filter with the 5 th, 7 th and 11 th harmonics being the dominant harmonic components. Figure 1 shows a six-diode bridge (six-pulse) rectifier with a DC link reactor (DCL) and the input current waveform. Yaskawa drives above 30HP have a built-in DC link choke as a standard, and input current THD is approximately 40% at full load conditions. If additional input AC reactors are combined with the DC link choke, the harmonic currents can be further reduced to about 25%. Practically, there are limitations in reducing the THD below 30 % due to increasing AC reactor size and line voltage drop. DCL DC bus 3-phase input Figure 1. A 6-pulse rectifier power circuit and an input current waveform time Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 2/6

Input current 12-PULSE RECTIFIER SOLUTION The Yaskawa drives above 30HP have a built-in DC link choke and a 12-pulse rectifier as standard. The Yaskawa 12-pulse rectifier solution consists of two 6-pulse diode bridges combined with a multi-phase transformer. The output of two diode bridge rectifiers can be connected in parallel through a DC link choke as shown in figure 2 or separately connected to two isolated drives. The multi-phase transformer can be an autotransformer or an isolated transformer with 30 displacement to provide two three-phase voltage sources that cancel the 5 th and 7 th harmonics. Figure 2 shows a 12-pulse rectifier with a delta-delta-wye isolation transformer and the resulting input current waveform where 11 th and 13 th harmonics are the dominant harmonic components. The input current THD of about 10% can be achieved. However, the values can vary depending on the source voltage distortion and imbalance. Two 30 displaced three-phase voltage sources can be achieved by several different approaches that include ; - a phase-shifting isolation transformer such as a delta-delta-wye or a Zig-Zag transformer - a phase-shifting autotransformer - a combination of a half-power transformer and a series reactor directly fed from power source (hybrid 12-pulse). Each approach has different features and performances. For example, the autotransformer method is a good solution to feed two separately isolated drives. The isolated transformer has the best performance, but is relatively bulky and expensive. Yaskawa provides the best solution which takes into consideration many aspects that include ; customer s power system environment, input harmonics requirements, EMI noise, and cost, etc. DCL DC bus 3-phase input Delta-Delta-Wye Transformer or hybrid 12-pulse time Figure 2. A 12-pulse rectifier power circuit and an input current waveform 18-PULSE RECTIFIER SOLUTION The rectifier topology consists of a multi-phase transformer and three 6-pulse diode bridges, the output of which are connected in parallel through a DC link choke as shown in figure 3 or separately connected to three isolated drives. In the theoretical system, the three phase-shifted voltage sources connected to the three 6-diode bridges will cancel the 5 th, 7 th,11 th,and 13 th harmonics and the remaining dominant harmonic components are the 17 th and 19 th. The multi-phase transformer can be an autotransformer or a phase-shifting isolation transformer with 20 displacement used to provide three three-phase voltage sources that cancel the 5 th Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 3/6

Input current THD (%) Input current, 7 th,11 th,and 13 th harmonics. In many cases, a phase-shifting autotransformer is a practical approach when considering the size and cost. If additional input AC reactors are combined with the rectifier, the input current THD is about 5%; however, this can vary based on voltage source distortion and imbalance. This 18- pulse rectifier solution complies with IEEE-519-1992 standard at the equipment level. Phase-shifting transformer DCL DC bus 3-phase input autotransformer or isolation transformer time Figure 3. A rectifier power circuit and an input current waveform MULTI-PULSE RECTIFIER PERFORMANCE Figure 4 shows the effect of increasing the AC input % impedance on the input current harmonics. The 6-pulse rectifier cannot reduce the input current THD below 25 % even with an input AC reactor with 10% impedance. However, the 12-pulse and rectifiers can achieve an input current THD of less than 10% with the addition of an input AC reactor of 1-2% impedance. 60 6-pulse 50 40 30 12-pulse auto 20 10 0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 10.0 AC input impedance (%) Note : Values may vary depending on the power system environment. Figure 4. Input current THD according to the rectifier types, input AC reactor size, and a 3% DC link choke. Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 4/6

Voltage THD (%) Current THD (%) Figure 5 shows the input current THD of three different rectifier topologies according to the short circuit current ratio of the power distribution system at the PCC [1] assuming all nonlinear loads. IEEE 519-1992 distortion limits are a guideline for the total current THD at the PCC. Thus, linear (i.e., sinusoidal) loads in the distribution system will reduce the THD value at the PCC. Figure 6 shows the input voltage distortion created by the harmonic currents that flow into power source. As can be seen from Figures 4-6, the 12-pulse and rectifier solution provides good harmonic reduction. Especially figures 5-6 show that the rectifier complies with IEEE 519-1992 distortion limits in most cases if the voltage distortion and imbalance are negligible. 50 45 40 35 30 25 20 15 10 5 6-pulse 12-pulse IEEE-519 limits 0 20 40 60 80 100 120 140 160 180 200 Short circuit current ratio (Isc/IL) Figure 5. Input current THD according to the rectifier types, the short circuit current ratio, and a 3% DC link choke. 12.0 10.0 6-pulse 12-pulse 8.0 6.0 IEEE-519 limits 4.0 2.0 0.0 20 40 60 80 100 120 140 160 180 200 Short circuit current ratio (Isc/IL) Note: Values in figures 6-7 may varies in figures 6-7 may vary depending on the power system environment. Figure 6. Input voltage THD according to rectifier type, the short circuit current ratio, and a 3% DC link choke. Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 5/6

SUMMARY Yaskawa provides multi-pulse input current harmonics mitigation solutions. The 6-pulse diode rectifier on Yaskawa drives above 30 HP have low input current harmonics of about 40% due to a built-in DC link choke. The combination of the built-in 12-pulse rectifier and a DC link choke circuit from 30 HP above also help to easily implement the12-pulse rectifier solution. Both 12-pulse and solutions can effectively reduce the input current THD to less than 10% when combined with an additional input AC reactor. The rectifier has a input current THD of about 5% and it provides a solution that complies with IEEE 519-1992 standard at the equipment level if input voltage imbalance is negligible. Table 1. Multi-pulse Rectifier Comparison Rectifier type Input current THD *1 Remarks 6-pulse with no DC link choke 6-pulse with *2 DC link choke 12-pulse *2 (package) (package) 110 % High input rms current and large harmonic components. 40 % Simple and low cost but large 5 th,7 th, and11 th harmonic components. 10% Relatively low harmonics. 11 th and13 th harmonic components are dominant. 5% Very low harmonics. Compliance with IEEE 519-1992 standard. *1 Values may vary depending on the power system environment. *2 The 6-pulse and 12-pulse rectifier with built-in DC link choke are standard on Yaskawa drives 30HP and above. REFERENCE 1. IEEE519 working group web site : Go to http://grouper.ieee.org/groups/519/ 2. IEEE-Std 519-1992, IEEE Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems, IEEE Inc., New York, NY, April 1993. 3. Yaskawa Electric America, Power line harmonics and installation considerations for AC and DC drives, Go to https://www.yaskawa.com/links?type=documents&docnum=an.afd.04&name= Doc#: WP.AFD.02 Copyright Yaskawa Electric America, Inc. 2018 www.yaskawa.com December 1, 2005 6/6