SECTION PRECAST CONCRETE SECTIONAL MANHOLES

Similar documents
SECTION MANHOLES

SECTION 39 - MANHOLES TABLE OF CONTENTS

Standard Specifications

SECTION PUBLIC UTILITY MANHOLES AND STRUCTURES. 2. Modular precast concrete pump wetwell. 5. Manhole bedding and cover materials.

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

SECTION MANHOLES

STRUCTURES FOR SANITARY AND STORM SEWERS

SECTION PRECAST CONCRETE STRUCTURES

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17

SPECIFICATIONS FOR THE MANUFACTURE AND DESIGN OF PRECAST THREE SIDED ARCH STRUCTURES, WINGWALLS AND HEADWALLS

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18

A. Extent of structural precast concrete work is shown on drawings and in schedules.

REQUEST FOR BIDS WELL #4 ABANDONMENT

4.1. Foremen 4.2. Concrete plant manager 4.3. Concrete plant operator 4.4. Personnel performing saw cutting and joint sealing

KANSAS DEPARTMENT OF TRANSPORTATION SPECIAL PROVISION TO THE STANDARD SPECIFICATIONS, 1990 EDITION

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

D. Thermally Sprayed Metallic Coating (Flame Spray): STD SPEC

PART MATERIALS. Section Fencing Materials. Description

Section 914. JOINT AND WATERPROOFING MATERIALS

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

AMENDMENTS Manual of STANDARD SPECIFICATIONS. Adopted by Standard Specifications Committee. Amendment. No. 6. Published by

Section COUPLINGS AND COUPLING ADAPTERS. This Section covers couplings and coupling adapters for ductile iron and steel pipe.

SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS

Manholes Table of Contents

UNDERGROUND UTILITY TRENCHES AND VAULTS Page 1 of 6 ADDENDUM #1

B. Installation Instructions. Provide installation instructions, including any special equipment, to address the following.

CONCRETE MANHOLES.

2016 Specification Treads, Base, Stringers and other Amenities Wausau Tile Precast Epoxy Terrazzo

1. INTRODUCTION 2. REFERENCE SPECIFICATIONS. Page -1- Bonding and Grouting

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

SECTION METAL FABRICATIONS

SECTION PRECAST CULVERT STEAM TUNNEL

IGGA Guide Specification: Dowel Bar Retrofit (DBR) Introduction

Proposal PROJECT MANUAL P R O P E R T Y M A N A G E M E N T F A L L O N C O U N T Y. Baker, MT P.O. Box 846

NITTERHOUSE CONCRETE PRODUCTS, INC Molly Pitcher Highway South Chambersburg, PA

SECTION SHEET METAL FLASHING AND TRIM

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

STANDARD SPECIFICATIONS SECTION PRECAST CONCRETE 1.2 REQUIREMENTS FOR MANUFACTURERS AND SUPPLIERS BEFORE DELIVERY

Pipe Product Catalog Table of Contents

SECTION TRACER WIRE FOR NONMETALLIC PIPE

5/16" Flange nut. Bolt Keeper Plate (8" Sq. SYS.) (3) 1/2" x 3" Hex head connector zinc plated bolt w/ washers and nut. Anchor 3" sq. 7 Ga.

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN

INSTALLATION GUIDE PermaTrak. Patented Product: U.S. Patent #5,906,084 #8,302,362 #8,522,505 #8,839,588 #9,096,975

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION COUNTERTOPS ecox PART 1 GENERAL

SECTION PRECAST HOLLOW CORE PLANKS

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

Pioneers in Gate Design

11-1/4 OD at Transition Point. Microcosmic. 4th and Brannan Street Platform Station Project. Elevation. Moto Ohtake 2014

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

Edgerail Aluminum Bridge Railing System Specification & Installation Instructions

SECTION 1085 PRECAST REINFORCED CONCRETE BOX CULVERT

Design and Construction of Highway Pavement Joint Systems

GENERAL ISOMETRIC LAYOUT

MEDIUM DUTY CAST IRON SLIDE GATES SERIES 20-10C

BPDL Architectural precast concrete specifications USA TESTING AND INSPECTION A. Testing by Independent Agency : Materials and workmanship furn

CS3 represents manufacturers of products for use in the municipal waterworks industry.

CITY OF PITTSBURG ENGINEERING DEPARTMENT CONTRACT NO A WATER TREATEMENT PLANT CAPITAL IMPROVEMENTS PHASE 1A ADDENDUM #1 FENCE AND DITCH AUGUST

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

A. Deviation from this standard must be approved by the Project Architect.

This addendum forms a part of the Contract Documents dated: August 10, 2012.

MATERIAL COMBINATION NUMBER 2: Corrosive environment requiring harder, wear-resistant seating faces and resistance to dezincification.

To: New York State Department of Transportation ENGINEERING INSTRUCTION. Approved:

3400 Tectura Designs Precast Concrete

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL

RAIL PANEL AT TRANSITION SECTION PLAN - POST DETAIL PLAN - TUBE SPLICE. Colorado Department of Transportation. Staff Bridge Branch

SECTION SITE FURNISHINGS FOR CFCRT. 1. American Society for Testing and Materials (ASTM).

DISTRIBUTION VAULT 8' x 14' x 9'-4" DEEP TRAFFIC FLAT WALL WITH 5' x 8' OPENING

Large Scale CalArc Pavers for Sand-Set Pedestrian Use Installations

.1 Materials and installation for steel piping, valves and fittings for hydronic systems in building services piping..2 Related Sections.

Jointed Precast Concrete Pavement

Appendix C Construction Details

A. Compatibility: Products shall be suitable for piping service fluids, materials, working pressures, and temperatures.

SECTION THERAPEUTIC POOL ACCESSORIES

SECTION BASIC MATERIALS AND METHODS

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

Anti-Trust Statement

CVO/169897A OCTOBER 29, GROUT

RELINER INSIDE DROP SYSTEM SPECIFICATIONS

SECTION SHEET METAL FLASHING AND TRIM

Segmental ring types provided by F P McCann: Segments in stock are front bolted. Back bolted segments are available to order: Cross joint Corbel Ring

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

WAL-MART SUPERCENTER # ; Milwaukie, OR: SPECIFICATIONS. Revisions to Specification Fence

"A" "A" SECTION "A-A" X-SECTION VERTICAL CURB (TYPE B) Village STREET & PAVEMENT STR-05. Engineering Department

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

ALUMINUM PIPE GUIDERAIL 01/01/

SECTION G ESTIMATE OF QUANTITIES

SECTION ARCHITECTURAL PRECAST CONCRETE PART 1 - GENERAL

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

PERFORM WITH PRECISION WELDED DOWEL ASSEMBLY LOAD TRANSFER PRODUCTS CONCRETE CONSTRUCTION SOLUTIONS BROCHURE

SECTION TRAFFIC SIGNAGE

SECTION MANUFACTURED CASEWORK

14 March 2016 City Hall Station Renovations Bid Documents 15 th Street Station Phase Station Improvements SECTION PRECAST CONCRETE

Product Guide Specification

Transcription:

SECTION 02545 PRECAST CONCRETE SECTIONAL MANHOLES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Precast reinforced concrete cylindrical sectional manholes, complete with openings, inserts, hardware, covers and frames. 2. Precast reinforced concrete manholes with precast bases, barrels, risers, cones, and flat tops. 3. For Cast-In-Place Concrete Specification, see Section 03310. B. Related Sections: 1. Section 02302: Earthwork for Pipelines 2. Section 03310: Reinforcing Steel, Cast-In-Place Concrete and Concrete Finish 1.02 REFERENCES A. American Society for Testing and Materials (ASTM), Standard Specifications: 1. A36 Structural Steel 2. A48 Gray Iron Castings 3. C150 Portland cement 4. C478 Precast Reinforced Concrete Manhole Sections B. American Association of State Highway and Transportation Officials (AASHTO), Standard Specifications for Highway Bridges. C. Federal Specification: SS-S-210: Sealing Compound, Preformed Plastic, for Expansion Joints and Pipe Joints. 1.03 SUBMITTALS A. Submit the following to the Engineer for review. B. Product Data: 1. Descriptive details of the manufacturer s proposed standard products, including: a. Precast manhole sections. b. Precast roof slab or cone section. c. Precast base slab. d. Minimum concrete 28-day compressive strength. e. Cement certification. f. Manhole cover and frame. 2. Shop drawings, including: a. Design criteria. b. Reinforcing steel location and concrete cover. c. Layout of all inserts, attachments and openings. d. Location and type of joints. 02545-1

1.04 QUALITY ASSURANCE A. Provide products of a manufacturer who has been regularly engaged in the design and manufacture of the product for the last five years. B. Demonstrate to the satisfaction of the Engineer that the quality is equal to the product made by those manufacturers specifically named herein, if an alternate product manufacturer is proposed. 1.05 DELIVERY, STORAGE AND HANDLING A. General: Provide storage and handling of all materials so that upon delivery, they are undeteriorated and ready for use. PART 2 - PRODUCTS 2.01 DESIGN CRITERIA A. General: ASTM C478, and also: 1. Roof slab live load: AASHTO Loading Class HS 20-44. 2. Backfill material: Suitable native or import backfill. 2.02 PRECAST SECTIONS A. General: 1. Manhole cone section: Concentric taper. 2. Cement: ASTM C150, Type V, low alkali. 3. Roof slab opening: Size to support the manhole cover frame. 4. Lifting eyes: Provide for each section. B. Manufacturer: Teichert Precast, Sacramento, CA; Cook Concrete Products; or equal. C. If manhole invert elevation is 5 feet or greater below grade, use concentric taper top cone section per Drawings. D. If manhole invert elevation is less than 5 feet below grade, do not provide a cone section, but install a flat top reinforced concrete slab per Drawings. 2.03 SEALANT GASKETS A. Type: Preformed, continuous rope form plastic material, protected by removable two-piece wrapper. B. Sealing Compound: Reinforced hydrocarbon resins blended with plasticizing compounds and reinforced with inert mineral filler. No solvents, irritating fumes or obnoxious odors. C. Adhesive and Cohesive Strength: Not dependent on oxidizing, evaporating, or chemical action. D. Conform to Federal Specification SS-S-210. 02545-2

E. Provide: RAM-NEK as manufactured by K. T. Snyder Company, Inc., Houston, TX; QUIKSEAL as supplied by Associated Concrete Products, Santa Ana, CA; Kent Seal; or equal. 2.04-A CAST- IRON FRAMES AND COVERS (IN ROADWAY) A. Material: Cast iron; ASTM A48, Class 30B. B. Marking: In raised letters on manhole cover as shown on the Standard Drawings. C. Coating: Bituminous paint, black. D. Size: 24-inch-diameter cover. E. Pick Hole: Closed. F. If specified on Drawings, provide a sealed (water tight) frame and cover. Connection shall be a bolt down cover into frame. Use four 3/8-inch diameter stainless steel bolts, coarse thread, flush with top seal with 1/8-inch thick, ½- inch-wide continuous circular neoprene gasket. Provide continuous ¼-inch diameter neoprene O ring between frame and cover. G. Manufacturer: South Bay Foundry, Hayward, CA; D & L Supply; Alhambra Foundry Company Ltd., Alhambra, CA; or equal. 2.04-B COMPOSITE FRAMES AND COVERS (OUT OF ROADWAY) A. Marking: In raised letters on manhole cover as shown on the Standard Drawings. B. Coating: Black C. Size: 24-inch-diameter cover. D. Pick Hole: Closed. E. If specified on Drawings, provide a sealed (water tight) frame and cover. Connection shall be a bolt down cover into frame. Use four 3/8-inch diameter stainless steel bolts, coarse thread, flush with top seal with 1/8-inch thick, ½- inch-wide continuous circular neoprene gasket. Provide continuous ¼-inch diameter neoprene O ring between frame and cover. F. Manufacturer: GMI Composites Inc. 24 2600 Series Titus Lock Frame & Cover 2.05 LADDER RUNGS (NOT USED) 2.06 ACCESSORIES A. Flexible Manhole Connectors: ASTM C923 and manufactured by Kor-N-Seal, A-Lok or equal. 02545-3

B. Epoxy bonding agent for manhole grade ring and frame: Sikadur 32, Hi-Mod; Master Builders Concresive 1090; or equal. 2.07 WATERSTOP A. Rubber water seal shall be Adeka Ultraseal; Fernco Manhole Waterstop; or equal. 2.08 SOURCE QUALITY CONTROL A. Precast Sections: 1. Verify concrete compressive strength test results are satisfactory for the sections supplied. 2. State the curing method. Identify the start and end dates for the sections supplied. B. Frames and Covers: 1. Verify cast test bar tensile strengths are satisfactory. PART 3 - EXECUTION 3.01 INSTALLATION A. Compact subgrade to 93% relative density for 6-inch minimum depth. B. Provide a 6-inch gravel layer using 3/4-inch crushed rock under the base slab and compact to 93% relative density prior to placement. C. For poured in place base and precast manhole sections, set precast manhole sections in a concrete base joint groove, formed in the cast-in-place concrete base slab. D. Apply primer to joint surfaces in accordance with manufacturer's instructions. Make all joints watertight with sealant gaskets. E. Backfill around the manhole with Suitable Native or Import Backfill material. Compact the backfill material to 93% of relative density from the pipe bedding and base slab up to final finish grade or subgrade in paved areas or roadways, over an area defined as being within a distance of 2 feet from the exterior walls of the manhole. For open areas, compact to 90% of relative density. Backfill will be compacted by mechanical compactor and not a sheep s foot wheel roller. F. Accurately locate and place the manhole frames to within 1/8-inch vertical elevation in paved or roadway areas. In unpaved areas, manhole frames shall be 12- to 15-inches above existing grade unless otherwise specified on the Drawings. Coordinate the activities of all trades so that this tolerance is achieved. G. In paved areas, a concrete collar shall be used to secure frame per the Drawings. In unpaved areas, bond the cast iron frame to grade rings, cone section or flat top slab using epoxy adhesive. 02545-4

H. Install the manhole cover in the frame. Machine the cover if necessary to obtain a solid fit, without rattling under load. I. In unpaved areas, install a warning pole centered within 3 feet of manhole center as shown on the Drawings. J. Fill all precast base lifting lugs with non-shrink grout. 3.02 FIELD QUALITY CONTROL A. Verify all precast sections are continuously sealed with gaskets. B. Verify all manhole covers fit quietly in the frames. 3.03 TEST FOR MANHOLES A. Vacuum Testing: Perform vacuum testing of manholes in accordance with the following: 1. Sewer manholes shall be vacuum tested in accordance with ASTM C1244 after installation, but prior to backfilling. Contractor will also vacuum test manhole after backfilling. 2. All testing equipment and labor shall be provided by the Contractor. 3. All pipes entering the manhole shall be plugged, taking care to securely brace the plugs from being drawn into the manhole. 4. The test head shall be placed at the inside of the top of the cone section and the seal inflated in accordance with the manufacturer s recommendation. 5. A vacuum of 10 inches of mercury (approximately 5 psi) shall be drawn and the vacuum pump shut off. With the valves closed, the time shall be measured for the vacuum to drop to nine inches. The manhole shall pass if the time is greater than 60 seconds for 48-inch diameter manhole, 75 seconds for 60-inch, and 90 seconds for 72-inch. 6. If the manhole fails the initial test, necessary repairs shall be made with a non-shrink grout while the vacuum is still being drawn. Retesting and/or replacement shall proceed until satisfactory test is obtained. No grout shall be placed in the horizontal joints before testing. END OF SECTION 02545-5