PAPILLON 250 ARTICULATED ARM OPENERS 24V DC GEAR MOTOR USER MANUAL

Similar documents
Istructions. Central control board for electromechanical gearmotors HERCULES 24V

G703. Installation instructions. residential gate opener for sliding gates. remote control openers security at your fingertips

Radio Control Installation and Operating Instructions System 4

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Z07- SWING GATE HOME AUTOMATION. zero Z07 - SWING GATE MOTOR SUPPLY V HOME AUTOMATION IT EN FR Z07.REV USER MANUAL AND CONFIGURATION PG1

eguard EG2233, EG3333, EG3355, EG3388 & EG8406: Installation and Set-up Procedures Tx 2200 and Rx 4200 Boards

Wing Gate Instructions. Applicable Models: FB1000 / FB3000 FB1200 / FB3200 Version: 1.0 Date: Jun. 2016

PRO Professional Radio Control Series Applications

This document is the property of Teleco Automation Srl who reserves all reproduction and copying rights

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

impact VC-500LR Monolight INSTRUCTIONS

BFS / BFSM SERIES Installation & Maintenance Manual

RF Remote Control Unit SEAV

AMERITRON RCS-12 AUTOMATIC ANTENNA SWITCH

Multi Drop Bus 5-Tube Coin Changer. Series. Service Manual B D A C E SAT

GLR43308 and GLR2708. Setup and programming instructions. for the 8 channel Gigalink receiver. Programming Videos

Operating Instructions

DUCATI Control box. DUCATI Kontrol large DUCATI Kontrol small 10. PREDISPOSITIONS

USERS GUIDE EAGLE SMR MOTION SENSOR

Wireless Receiver E28Q Mounting and Operating Instructions (Original operating instructions)

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

COD GB / 1.0 RBAND/UMS - RBAND/CSM

IRIS \ IRIS-I QUICK SET-UP GUIDE STEP 1 INSTALL

Motor 1- GENERAL DESCRIPTION

IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

PROFLY / PROBLADE Professional Radio Control PRO-BLADE8

SHEREX FASTENING SOLUTIONS PNEUMATIC SPIN-SPIN INLINE STYLE RIVET NUT INSTALLATION TOOL SSG-902 MANUAL

K580M GUIDA ALL INSTALLAZIONE INSTALLATION GUIDE INSTALLATIONSANLEITUNG NOTICE D INSTALLATION GUÍA PARA LA INSTALACIÓN

CS-200. PORTABLE TRAFFIC LIGHT CONTROLLER (Software 1.05) OPERATION AND SERVICE MANUAL

120x165mm. 85x165mm TEMPLATE. ELECTRONIC DEADBOLT model no.: & & Toll-free Number:

Modular Radio Telemetry System

Modular Radio Telemetry System

LIGHT- INDUSTRIAL SLIDING GATE OPERATORS

CAME QP- V4.4 SPECIFICATION STANDARDS CABLE PLAN CABLE TYPES Z SERIES AUDIOCODE CONTROL SET FOR DOUBLE LEAF GATES

Robus 600/1000. Programmable functions using the Oview programmer. STF ROBUS Rev00 Firmware: RF02

Top spin Nr /

SL300 Snow Depth Sensor USL300 SNOW DEPTH SENSOR. Revision User Manual

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

English RACON SERIES II RADIO CONTROL SERVICE MANUAL

MEDIUM FLAT PANEL DISPLAY TILT MOUNT MSP-MT (MTR-V)

DJA3000. Cellular Communication Jammer. Installation and Operations Manual. Series DJA3000. Description: Cellular Communication Jammer

12 24 VAC/VDC ±10% (inhibited when voltage is applied) min. pulse width duration = 50 ms. Normal mode or Background Analysis mode

LBI-4938C. Mobile Communications MASTR II POWER AMPLIFIER MODELS 4EF4A1,2,3. Printed in U.S.A. Maintenance Manual

Cat. No. H8861 Model: RCL-S-STAT

User Manual. ProRF Encoder Transmitter & Receiver

SHEREX FASTENING SOLUTIONS PNEUMATIC SPIN-SPIN RIGHT ANGLE INLINE STYLE RIVET NUT INSTALLATION TOOL SSG-913 MANUAL

SABRETrap Control. Description

CAMTO. Arc detecting relay. system. January Revised August D D1200

Technical Description. DCF77 Receiver-Module 4460

f i r e - p a r t s. c o m

Tube Facing Tool.

Electric Staple/Nail Gun

Model: 5001 INSTALLATION AND OPERATING INSTRUCTIONS

SERVICE MANUAL PARTS LIST MODEL: NH40

Keyed latch. Cover. Service Outlet 115VAC, 15A. Plastic base. Unpack. Operator. the Operator

1410T/LCD-A INSTALLATION AND OPERATING INSTRUCTIONS

ELECTRONIC PANEL MC15

CA80 Series Vari-Angle IR Illuminator

User Manual. Specifications...3. Control and Operation Microphone...8. Installation...9. Installation of Main Unit...9


RADIOBAND V3 Programming & Installation Manual

MTY (81)

Remote Control Extender AUDIO / VIDEO DEVICES EXTENDING SYSTEM

Earth Fault Indicator EFI-BLZ-50 User Manual

SMART TOILET CONTROL

Transmitter System USER S MANUAL. Light Series

Operating instructions Contrast sensor O5K / / 2016

INMOTION Controls Series INSTALLATION & OPERATION MANUAL. INMOTION Series - INMOTION INMOTION-260. Page: 1/15

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

MODEL 1703E THE CHAMBERLAIN ARM TM INSTALLATION INSTRUCTIONS To be used in conjunction with the Lift-Master Garage Door Operator Owner's Manual

Model:CB-MRC. Instruction Manual of Mini Recessed Motorized Screen

AD-8100 & AD-8200 Servo Amplifiers

Senior Swing. Caution

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology

RF NiceRF Wireless Technology Co., Ltd. Rev

INSTALLATION INSTRUCTIONS. Large Flat Panel Wall Mount Model: PRO-2000 Series

Wireless Occupancy Sensor User Guide

Installation and Operating Instructions. Power IT Power Factor Controller RVC

K125M GUIDA ALL INSTALLAZIONE INSTALLATION GUIDE INSTALLATIONSANLEITUNG NOTICE D INSTALLATION GUÍA PARA LA INSTALACIÓN

Astra-R Kit Wireless Alarm System Operation Manual

1000 SERIES INSTALLATION SUPPLEMENT Rev. 7/1/10

INSTALLATION GUIDE. Galaxy II

200, 201 Series Radio Telemetry Transmitters

Pow-R-Feed Systems Service Manual

QL55 Series Luminescence Sensor


USERS GUIDE MATRIX2 DIGITAL INDUCTIVE LOOP SENSORS

1000 SERIES INSTALLATION SUPPLEMENT Rev

Wireless Vehicle Sensor Installation Manual

OPERATION MANUAL. Linear Valve Actuator. Electrical Valve Actuator. September, nd

Alpha 3000 I n d u s t r i a l R a d i o R e m o t e C o n t r o l S y s t e m Operation & Parts Manual

Model: Smart Stat III INSTALLATION AND OPERATION INSTRUCTIONS

SA-505 Supervised Wireless Multi-Layer Repeater Installation Manual 1. General Description

TABLE OF CONTENTS DRAWINGS

Model: 5301P INSTALLATION AND OPERATION INSTRUCTIONS

CM48 Series Vari-Angle IR Illuminator

Before fitting door, check opening size and squareness of timber frame. The door is made smaller to give correct clearance within the frame.

SV613 USB Interface Wireless Module SV613

PART #MSP-DCCPPWS Plasma Wall Swing-Out (PWS) Wall Mount

Transcription:

PAPILLON 0 ARTICULATED ARM OPENERS V DC GEAR MOTOR USER MANUAL

INDEX. WARNINGS. MOTOR INSTALLATION. DIMENSION CHART. MPONENTS OF INSTALLATION. INSTALLATION OF ARTICULATED ARM OPENER. EMERGEY RELEASE. POWER SUPPLY NNECTIONS. WIRING NNECTION. MASTER MOTOR IS INSTALLED AT LEFT SIDE.. STANDARD INSTALLATION.. ADVAED INSTALLATION (MOTOR WITH LIMIT SWITCH). MASTER MOTOR IS INSTALLED AT RIGHT SIDE.. STANDARD INSTALLATION.. ADVAED INSTALLATION (MOTOR WITH LIMIT SWITCH). TRANSMITTER MEMORIZING AND ERASING PROCESS. SYSTEM LEARNING PROCESS. GET MOTOR RUNNING. RESTORE DEFAULT SETTING. LED INDICATION.9 GATEMOVING LOGIC.0 CHECKING THE GATE MOVEMENT. MEANING OF LED DISPLAY. ADVAED FUTION PARAMETER SETTING. HOW TO CHANGE. ADVAED FUTION PARAMETER. PHOTOCELL INSTALLATION. PHOTOCELL WORKING LOGIC ADJUSTMENT. GREEN BOX INSTALLATION (OPTIONAL). TROUBLE SHOOTING. TECHNICAL FEATURES. DIMENSION. TECHNICAL FEATURE. MAINTENAE 9 9 9 9 0 0. WARNINGS WARNING : This user manual is only for qualified technicians who is specialized in installations and automations. () All installations, electrical connections, adjustments and testing must be performed only after reading and understanding of all instructions carefully. () Before carrying out any installation or maintenance operation, disconnect the electrical power supply by turning off the magneto thermic switch connected upstream and apply the hazard area notice required by applicable regulations. () Make sure the existing structure is up to standard in terms of strength and stability. () When necessary, connect the motorized gate to reliable earth system during electricity connection phase. () Installation requires qualified personnel with mechanical and electrical skills. () Keep the automatic controls (remote, push bottom, key selectors etc) being placed properly and away from children. () For replace or repair of the motorized system, only original parts must be applied. Any damage caused by inadequate parts and methods will not be claimed to motor manufacturer. () Never operate the drive if you have any suspect with what it might be faulty or damage to the system. (9) The motors are exclusively designed for the gate opening and closing application, any other usage is deemed in appropriate. The manufacture should not be liable for any damage resultingfrom the improper use. Improper usage should void all warranty, and the user accepts sole responsibility for any risks thereby may accrue. (0) The system may only be operated in proper working order. Always follow the standard procedures by following the instructions in this installation and operating manual. () Only command the remote when you have a full view of the gate. Please keep this installation manual for future reference.

. MOTOR INSTALLATION x. mm x0. mm TX x0. mm RX x0. mm x. mm x. mm Optional Optional. V DC blinker with integrated antenna. Push Button. Photocells. V DC articulated arm opener. PR Transmitter. DIMENSION CHART Plea n the chart for proper installation. If necessary, please adjust the gate structure to the best operation. Before starting the installation, please make sure that the gate moves freely and that : ) Hinges are properly positioned and greased. ) No any obstacle in the moving area. ) No frictions between two gate leafs or and on the ground while moving. ) Installation reference: to open the gate with 90 degree, please refer the data table below: A: Distance between the gate hinge and the wall bracket. B: Distance between the gate hinge and side face of the motor. C: Distance between the gate hinge and the fixing point of the arm. B C B A C 0 00 0 00 0 00 0 00 0 00 0 / unit: mm 0 0 / / / / A To open 90 degree.

. MPONENTS OF INSTALLATION 0 9 9 0 Straight arm Curved arm Ushaped fixing plate Mechanical stopper Frontend fixing bracket Screw Nut Ø0 Screw Gasket Screw Spring washer Nut Ø Cable gland pce pce pce pcs pce pcs pcs pcs pcs pcs pcs pcs pce. INSTALLATION OF ARTICULATED ARM OPENER. Refer to the Dimension Chart to choose the correct dimensions of the motors and position to be installed.. Check if the mounting surface of the brackets to be installed is smooth, vertical and rigid.. Arrange the cables for power supply cable of the motors.. Motor installation and setting for mechanical stopper in opened and closed position. ) Remove the upper cover and mechanical stoppers on the bottom of motor. ) Place the gate in the full closed position and fix the Ushaped fixing plate on the wall.

) Install the motor on the Ushaped fixing plate with corresponding screws and nuts. ) After positioning the front of curved arm on the bottom of motor, release the motor and position the minor arm on the end of curved arm and mounting bracket with corresponding screws and nuts. 0 9 ) Closed position adjustment :. After the full closed position decided, fix the corresponding mechanical stopper at the position.. After the full closed position decided, make the pointer on limit switch aligned with the pointer on the curved arm. (Red points shown on the figure below indicate the pointers) Mechanical Stopper ) Opened position adjustment :. Adjust the gate to full opened position and after the position decided, fixed with corresponding mechanical stopper.. Adjust the gate to full opened position and after the position decided, make the pointer on the electromechanical limit switch aligned with the pointer on the curved arm. (Red points shown on the figure below indicate the pointers) Limit switch. EMERGEY RELEASE ) Insert the release key to the release slot ) Turn the release key anticlockwise ) Pull out the release bar ) Turn the release key clockwise to fix the release bar, the release bar has to be in pulled out position when turning the release key clockwise

. POWER SUPPLY NNECTIONS Please kindly notice that the operation of power connection should be carried out by a qualified electrician with following steps: ). Make sure the gearmotor is not connected to the power supply before the installation is done. ). Make sure all the wires are firmly connected. ). Supply the gearmotor with the power.. WIRING NNECTION Figure () Flashing Latch Light Photocells connection is Dual / Single Open Only detailed on page Gate (FJ) Device Green Box PhVcc Ph GND PhVcc Ph GND SKey DKey LED LED 0 GND Lmt Lmt GND Lmt Lmt GND S S 9 V M M M M Lat Lat Lit Lit LED Antenna 0 9 Blue LED RF Learning LED Push button or Key selector LED Photocell LED Photocell RFLEARN RFLEARN UP SET SET LED Display DOWN Transformer

T DB SW UP SW SET SW Transformer DOWN SW F RFLEARN Q PC90PCB 0A K K K K J R0 R0 R0 J MOV T R0 R0 R0 R0 R R0 R R RF ANT GND DB LED J SW LED LED J J UP Lit Lit J Remark: Limit, Limit (Open limit) Limit, Limit (Close limit) Lat M M Lat M 9 0 M V S S GND Lmt Lmt GND Lmt Lmt GND 9 0 SW J SET DKey SKey GND Ph PhVcc GND Ph PhVcc SW DOWN SW F RFLEARN Limit Q M Limit GND M GND K Limit Limit M Limit Switch Motor Power Figure () K K K RF PC90PCB 0A M Limit Switch Motor Power.. ADVAED INSTALLATION (MOTOR WITH LIMIT SWITCH) J ANT GND LED J Lat M M Lat M M LED LED J J Lit Lit 9 0 V S S GND Lmt Lmt GND Lmt Lmt GND J 9 0 DKey SKey GND Ph PhVcc GND Ph PhVcc M M M M M Motor Power Figure () M Motor Power Physical stopper mounted under motor unit (optional) Driveway gate stopper (optional).. STANDARD INSTALLATION. MASTER MOTOR IS INSTALLED AT LEFT SIDE

UP SW SET SW DOWN SW F RFLEARN Q PC90PCB 0A K K K K J R0 R0 R0 R0 R0 R0 R0 R R0 R R RF J MOV T J Remark: Limit, Limit (Close limit) Limit, Limit (Open limit) ANT DB GND LED J LED LED SW UP J J SW Lit Lit Lat M M Lat M 9 0 M V S S GND Lmt Lmt GND Lmt Lmt GND 9 0 J SET DKey SKey GND Ph PhVcc GND Ph PhVcc SW DOWN SW F RFLEARN Q M M Limit Limit GND GND Limit Switch Motor Power Limit K Limit M Figure () PC90PCB 0A M Limit Switch Motor Power K K K.. ADVAED INSTALLATION (MOTOR WITH LIMIT SWITCH) RF Antenna J ANT GND LED J M M Lat M 9 0 M LED LED J J Lat V S M Lit S GND Lmt Lmt GND Lmt Lmt GND J 9 0 DKey SKey GND Ph PhVcc GND Ph PhVcc M M Lit M M Motor Power M Motor Power Figure () Physical stopper mounted under motor unit (optional) Driveway gate stopper (optional).. STANDARD INSTALLATION. MASTER MOTOR IS INSTALLED AT RIGHT SIDE

. TRANSMITTER MEMORIZING AND ERASING PROCESS (A) Transmitter Memorizing: Press and hold the RFLEARN button on the PCB for second and then the blue LED indicator on the RF board will be ON. Press A button for dualgate installation ; press B button for singlegate installation on the transmitter within seconds. The transmitter learning is completed when the blue indicator is OFF. (B) Transmitter Memory Erasing: Press and hold the RFLEARN button on the PCB for 0 seconds until blue LED off. (C) One radio receiver can be memorized with 00pcs of transmitters.. SYSTEM LEARNING PROCESS Step: Connect the master motor wires to M terminals and the slave motor wires to M terminals correctly. If only one gate is installed, the motor wires have to be connected to M terminals. Step: Set the function F for dual gate learning; or set the function F for single gate learning. Step: To start dual gate system learning. To start dual gate system learning. Press and hold the SETDOWN button on the PCB for seconds. The LED display will show LEA and DG. Press the button (A) on the transmitter within 0 seconds to activate the system learning automatically. LED display will show ARN, do not interrupt this procedure by pressing the transmitter or stop the gate. In system learning mode, the gates will proceed with the following procedures figure (). LED display will show RUN once system learning completed. To start single gate system learning. LED Press and hold the SETDOWN button on the PCB for seconds. The LED display will show LEA and SG. Press LED the button (B) on the transmitter within 0 seconds to activate the system learning automatically. LED LED display will show ARN, do not interrupt this procedure by pressing the transmitter or stop the gate. In system learning mode, the gates will proceed with the following procedures figure (). LED display will show RUN once system learning completed. SET DOWN Press Sec ON OFF

SYSTEM LEARNING IN PROCESS A. Dual Gate: Slave Gate Close Slave Gate Close Master Gate Close Master Gate Close Master Gate Open Slave Gate Open B. Single Gate : Master Gate Close Master Gate Open Master Gate Close Notes: (A) System learning fails and needs to be learned again when an unpredictable interruption occurs. (B) Once the system learning is completed, there is no need to proceed with the learning process again when there isa power failure. (C) The slave gate opens seconds after the master gate opens and the master gate closes seconds after the slave gate closes. (D) While using limit switch mode, please make sure the motor hit limit switch when it s in deceleration speed.. DUAL/SINGLE GATE OPERATION Press the button A on the transmitter for dualgate operation. A B Press the button B on the transmitter for singlegate operation in either singlegate or dualgate installation.. RESTORE DEFAULT SETTING Press and hold UPSETDOWN button on the PCB for seconds. The system will restore to the default setting without any system learning memory.

UP SW SET. LED INDICATION SW DOWN Blue LED on receiver board: Blinks three times when remote learning is completed. LED External device : If the switch of the key selector, or the push button is activated, LED will be on. LED Photocells : LED will be on when the first pair of the photocells are activated. LED Photocells : LED will be on when the second pair of the photocells are activated. SW F RFLEARN PC90PCB 0A Q K K K RF K ANT LED J Lit Lit Lat Lat M M M M LED LED GND J J 9 0 V S S GND Lmt Lmt GND Lmt Lmt GND 9 0 Antenna J J DKey SKey GND Ph PhVcc GND Ph PhVcc.9 GATEMOVING LOGIC (A) In gateopening phase: The gates stop if the transmitter/push button/key selector is activated, and close when the transmitter/push button/key selector is reactivated. (B) In gateclosing phase: The gates stop if the transmitter/push button/key selector is activated, and open when the transmitter/push button/key selector is reactivated. (C) In gateopening or gateclosing phase: For safety purpose, the gates stop if encountering obstacles..0 CHECKING THE GATE MOVEMENT ). Release the gearmotor with the release key and move the gate to the middle so that it is free to move in both opening and closing directions; then lock the gearmotor. ). Perform the gate opening and closing several times and make sure the gates reaches the limit switch at least ~ centimeters before the mechanical stop.. MEANING OF LED DISPLAY LED Display Programmable Functions LED Display Programmable Functions [LEA] means motor into the The memory of the system is all system learning mode, do not deleted/cleaned by press and hold the interrupt during this procedure. UP SET DOWN button together for s [DG] means motor completed and the panel will be back to default settings. the learning procedure for dual gate installation. [SG] means motor completed The motor is operating to open direction. the learning procedure for single gate installation. The motor is stopped. The motor is operating to close direction. 9

. ADVAED FUTION PARAMETER SETTING. HOW TO CHANGE For exmple: How to set the function F0 ; the steps are following: Step Operations LED Display after the Step () Press the SET button for seconds then releases it, and the system enters the first option. The LED will display F (*) as the. right handside picture. (*) If you would like to enter F function or others as the first option, please press the UP button to adjust F~F until you get F. () After completing the operation (), then press the SET button again, you will enter the second option as the right handside picture. And you will see the third number for the second option. () Continually press the Down button until you search the function 0 (**) of F as the right handside picture. F0 is set completely. (**) If you would like to set one of functions 0 ~ as the second. option, please press the UP or Down button to adjust it. () If you would continue setting up the next functions, please press SET to return the first option, like F or F or F or F. For example, after complete F0 setting. You would continue setting F, please press SET to return the formal option. The LED display shows the first two numbers as as the first option as the right handside picture, F. And then follow the operation (*) and () ~ () until you get F as the right handside picture. F is set completely. After setting all functions you need, then wait for 0seconds, the LED. will display RUN. And you can use transmitter to operate the gate. 0

. ADVAED FUTION PARAMETER LED Display F F F Definition Motor Type Dual or Single Gate Over Current Setting F Over Current Setting F Operation Speed Parameter Table Description F Motor only F Motor with Limit Switch F Motor with Hall sensor F Dual Gate F Single Gate F A. The factory setting is "F", F A. F setting is for F Motor only and F Motor with F A F A. The factory setting is "F".. The factory setting is "F". Limit Switch Note(F Setting is for F Motor with Hall sensor): Only in F Hall sensor mode, the PCB will record all the current value while learning mode. Please set F function after learning mode. The LED display 0 to indicate all of the recorded values will increase ampere as the over current value. In other words, the LED shows 0 to indicate all the recorded values will increase ampere as the over current value. The value can be adjusted by pressing button UP and DOWN. The maximum value is 0(.0A) and the minimum value is 0(0.A). F 00% Full speed F 0% Full speed F Function ON F Function OFF F 0% Full speed. The factory setting is "F". F Deceleration function F Deceleration Speed F 0% Full speed F Open/Close delay of dual F sec gate operation adjustment F sec F sec F sec F sec F sec F sec F 9 sec F9 0 sec F0 Function OFF F sec the end position or stopped manually. If the transmitter, F 0 sec push button, or the key selector is activated before the F 0 sec F 0 sec F 0 sec F 0 sec F 0 sec F 00 sec F9 Mode F9 Mode F9 Mode F9 Mode FA0 Function OFF FA Function ON F F9 FA AutoClose adjustment Photocell function mode Pedestrian Mode function. The factory setting is "F".. The factory setting is "F".. The factory setting is "F".. Autoclose mode activates when the gates move to autoclose counting, the gate will close immediately.. The factory setting is "F".. The factory setting is "F9".. When funciton on and push B key in the transmitter, one gate will open partically.. The factory setting is "FA". FB PreFlashing function FB0 Function OFF FB Function ON. When function ON, the light will flash before the gate operate seconds. If set OFF, the flash light will operate with motor in the same time.. The factory setting is "FB0".

LED Display Definition FC Photocell function FD Photocell function FE Buzzer function FF Latch release function Function Table FC0 Function OFF FC Function ON FD0 Function OFF FD Function ON FE0 Function OFF FE Function ON FF0 Function OFF FF Function ON Description. The factory setting is "FC0".. The factory setting is "FD0".. The factory setting is "FE".. If the function on, the gate will move forword a little before the gate operate for releasing the latch.. The factory setting is "FF". FG FH FI FJ Open/Stop/Close/Stop FG A Key function key FG B Key FG C Key FG D Key FH0 Function OFF FH A Key FH B Key FH C Key FH D Key FI0 No key to control. The key is to turn on or off the AutoClose function. FI A Key. The factory setting is "FI". FI B Key.When the flasher and buzzer is running, the auto closed FI C Key FI D Key Dual/single gate on Skey FJ0 Dual gate terminal FJ single gate Pedestrian Mode function key AutoClose function Key. The factory setting is "FG".. The factory setting is "FH". button has no function till flasher and buzzer finish running.. Function activated when Skey teminal is connected

. PHOTOCELL INSTALLATION The safety photocells are security devices for control automatic gates. Consist of one transmitter and one receiver based in waterproof covers; it is triggered while breaking the path of the beams. SPECIFICATION: Figure () Detection Method Through Beam Sensing Range M Input Voltage AC/DC ~V Response Time 00MS Emitting Element IR LED Operation Indicator Red LED(RX): ON(When Beam is Broken), Green(TX):ON Dimensions 9**mm Output Method Relay Output Current Consumption Max TX: MA/Rx: MA (When beam aligned properly); TX: MA/ Rx: 0MA (When beam is broken) IP Water Proof INSTALLATION: Wire Connection of Photocells TX: Connect terminals and on the transmitter with the terminals GND and PhVcc on the PC90 PCB. RX: Connect terminals, and on the receiver with the terminals GND, PhVcc, and Ph/Ph on the PC90 PCB. And use an extra wire to connect terminals and on the receiver as a bridge. Figure () Lens Beam Alignmnet Indicator Power Led Indicator RX Terminal Block Power Terminal Block TX

TX RX RX TX DKey SKey GND Ph PhVcc GND Ph PhVcc 9 0 M M Figure ()

. PHOTOCELL WORKING LOGIC ADJUSTMENT The actions of the photocells safety edge loop detector when they detecting obstacles.. F9 Position of Gate When safety devices are activated Safety Device : Safety Device : PhotocellOPEN PhotocellCLOSE FULLY CLOSED Open not allowed FULLY OPENED Reload automatic closing time Type of Safety Device STOP DURING MOVING Open not allowed Reload automatic closing time CLOSING Open OPENING Close. F9 Position of Gate When safety devices are activated Safety Device : Safety Device : Safety Edge PhotocellCLOSE Open not allowed Type of Safety Device FULLY CLOSED FULLY OPENED Reload automatic closing time STOP DURING MOVING Locks Reload automatic closing time CLOSING Reverse to open for seconds Open OPENING Reverse to clsoe for seconds. F9 Position of Gate When safety devices are activated Type of Safety Device FULLY CLOSED Safety Device : Safety Device : Opening Device PhotocellCLOSE Open FULLY OPENED Reload automatic closing time STOP DURING MOVING Open Reload automatic closing time CLOSING Open Open OPENING. F9 Position of Gate Type of Safety Device FULLY CLOSED When safety devices are activated Safety Device : Safety Device : PhotocellOPEN/CLOSE PhotocellCLOSE Open not allowed FULLY OPENED STOP DURING MOVING Close not allowed, Open for seconds when auto closing is ON Locks Close not allowed CLOSING Stop Open OPENING Stop

. GREEN BOX INSTALLATION (OPTIONAL) Green Box is for purpose when gate opener is in standby mode to allow it enter the power saving mode. Green Box OFF ON Cable AC out AC in Installation manner: AC IN: connect the electricity AC OUT: connect the power of gate opener, and connect the transformer V CABLE: connect pins white socket of control board Please make sure the switch of Green Box is off before proceeding the system learning and installation of device. Wait for the system learning and installation of device to be completed, power on the Green Box Gate opener will enter power saving mode without receiving any instruction in min, and red LED light on Green Box will be activated. Gate opener start the operation, red LED light and power saving mode will turn off. CAUTION: In case of loop or installation of photocell which need power consumption anytime, please do not install Green Box.

. TROUBLE SHOOTING Overheated Backup Batteries The gate doesn t move when pressing the button of the transmitter Check the wiring connection of the batteries.. Check if LED or is OFF.. Check if the voltage of the batteries is upon V.. Make sure all the wiring connections are firmly connected to the terminals on the PCB.. Make sure the fuse is workable. The gate only moves a little distance when pressing the button of the transmitter. The transmitting distance is too short Make sure the wiring connection of the hall sensor is firm. The gear motors run very slowly The Flashing light does not work The leaves shall be closed instead of opening The leaves suddenly stop during moving The leaves does not move or only move toward one direction The master gate closes to the end first and the slave gate stops, the flashing light blinks fast for five seconds. The gear motors does not run and the relay is noisy when operating the gate opening and closing Make sure the connecting terminals of the Antenna is firm. Check the dip switch setting of the speed adjustment. Check if the wiring connection of the flashing light is correct. Change the polarity connection of the positive () with the negative () of the gear motors.. Check if the RESET socket is activated.. Make sure the wiring connection of the gear motors is firm.. Make sure the hall sensor wiring connection is firm.. The GND terminal of the photocells on the PCB must be shortcircuited if no photocells installed.. Make sure the fuse is workable.. Check if the RESET socket is activated.. Make sure the wiring connection of the gear motors is firm.. Make sure the hall sensor wiring connection is firm.. The GND terminal of the photocells on the PCB must be shortcircuited if no photocells installed. Cut off the AC input power and the output of the batteries. Release the master gate and slave gate manually, then open the master to the end and close the slave gate to the end by hand, then power the whole unit by connecting the AC and battery terminals. Check if the fuse is burned.. TECHNICAL FEATURES.mm. DIMENSION 0mm 90mm

. TECHNICAL FEATURE: Model Motor Gear type Nominal thrust Maximum Gate Weight Maximum Gate Length Operating Temperature Dimension Weight PAPILLON 0 Vdc motor Electromechanical worm gear 00N 0 kg per leaf. meters per leaf 0oC~0oC x x mm kg Model Main power supply Backup battery Receiver board Installation Operating Temperature Dimension CB9 0Vac/0Vac, 0Hz/0Hz pcs of batteries for emergency operation,.a each.9mhz; 00 transmitters memory Built in PCBA 0oC~0oC mm x 9mm x 0mm. MAINTENAE Conduct the following operations at least every months. If in high intensity of use, shorten the period in between. Disconnect the power supply: () Clean and lubricate the screws, the pins, and the hinge with grease. () Check the fastening points are properly tightened. () Make the wire connection are in good condition. Connect the power supply: () Check the power adjustments. () Check the function of the manual release. () Check the function of photocells or other safety devise. 000D