Howard Smart Transformer Specification Guide

Similar documents
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

7. INSPECTION AND TEST PROCEDURES

Distribution Transformers

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL

Distribution/Substation Transformer

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

SECTION TRANSFORMERS

Substation transformers

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

The Variable Threshold Neutral Isolator (VTNI)

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

Reactor and inductor are names used interchangeably for this circuit device.

CITY OF TACOMA Transmission & Distribution

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

35 kv Class M.O.V.E. DirectConnect elbow arrester

SINGLE-PHASE VSV SWITCH

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

The Isolator/Surge Protector (ISP)

Power Processor - Series 700F 10KVA to 150KVA

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

HPS Universal BUCK-BOOST TRANSFORMERS

INTERNATIONAL STANDARD

Intelligent Distribution Transformer. Fine tune your distribution system to its most efficient operation for any given time of the day or year

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Warehouse Stock Transformers

Section 2 Outdoor Voltage Transformers

Improve asset protection and utilization

SECTION DISTRIBUTION SWITCHBOARDS

The Isolator/Surge Protector (ISP)

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

INTELLIMETER REGISTER

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

SINGLE-PHASE VSV SWITCH

SECTION 16322B SUBSTATION TRANSFORMERS DRY-TYPE

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

Functional specification for 3-in-1 pad-mounted multi-phase 32-step voltage regulator with communication-ready controls

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

SECTION DISTRIBUTION SWITCHBOARDS

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

Review 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel.

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Figure 1. Two- and Three-phase MagneX Interrupter.

Two- and three-phase MagneX interrupter

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

CONTINUING EDUC ATION

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

MILITARY SPECIFICATION TRANSFORMERS, POWER, STEP-DOWN, SINGLE-PHASE, 60-HERTZ, 1-KILOVOLTAMPERE APPROXIMATE MINIMUM RATING, DRY TYPE, NAVAL SHIPBOARD

UNIFIED FACILITIES GUIDE SPECIFICATIONS

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

TOSHIBA International Corp

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

Component Requirement Specification for SGI 500XT Isolation Transformer

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

USER S MANUAL EMPOWER POWER METER TRINITY. Empower Operational Manual

Basic Principles and Operation of Transformer

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

TIGHTENING TORQUE ON WOODEN CORE CLAMP (Nm) (STEEL FASTENER) 1 M M M M M

Electrical Wiring: Commercial, Seventh Canadian Edition

Grounding and Utility Enclosure

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION PANELBOARDS

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

Steps for Selecting the Proper Transformer

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

2.5. Contents Description Motor Drive Isolation Transformers... Mini Power Centers... Totally Enclosed Non-Ventilated Transformers

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

REP Design LLC. 193 Winding Ridge Rd, Southington, CT INSTALLATION INSTRUCTIONS:

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

Advanced, accurate and intelligent monitoring for your transformer

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

DOCUMENT TR2028/R3- PICO BASE STATION WITH GPS SYNC

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE

SECTION COMMON WORK RESULTS FOR HVAC

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

Transcription:

Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as applicable to the latest revision of the following IEEE standards: C57.12.00, C57.12.20, C57.12.28, C57.12.70, C57.12.80 and C57.12.90. Size and Ratings The transformer shall have a kva rating of one of the following sizes: 15, 25, 37.5, 50, 75, 100, 167, 250, 333 and 500kVA based on not exceeding a 65 C average winding temperature rise. Transformers shall have two primary bushings with ratings per Table I. Coil Bonding and Terminating Coils shall be tightly bonded utilizing double adhesive insulation paper or tape and heat cured for bonding. Hardened aluminum tabs shall be welded to soft aluminum secondary leads to assure a durable connection at the bushings. Tabs shall have embossed markings. Any alternate shall have prior approval of the Avista Utilities Engineering Department. Clamping and Bracing Transformer coils shall be clamped, and leads supported in such a manner as to be capable of withstanding, without injury, the mechanical and thermal stresses of short circuits defined in ANSI C57.12.00 and C57.12.90. Parallel Connection Operation Transformer to be used in 120/208 banks shall have windings factory connected in parallel across X1 and X2. The X3 bushing will float and the X3 CT will be out of the circuit. At the time of order a -P will be added to the stock number. The - P designation is intended to assist for tracking by manufacturer. Because 120/208 connected units are physically identical to 120/240 units, they will not have a different stock number for Avista inventory. Parallel Connected Identification Units shipped from the factory shall be identified by covering the X3 bushing with electrical tape. Secondary Arresters Shall include double pole secondary arrester, Cooper ASZ175B2 or equivalent. The arrester shall be installed on the tank and connected to secondary bushings. If the transformer has the windings connected in parallel, both arrester poles shall be connected across the coils.

General Smart Transformer Requirements Shall be equipped with a computer circuit board in a weather tight enclosure mounted to the exterior of the transformer. Shall monitor the operation of the transformer and report data to Avista DMS system via cellular radio. Sensing Capabilities Senses the temperature of the transformer using thermocouples Measures both low voltage half-winding temperatures via thermocouples embedded in the coils Measures top-oil temperature via a thermocouple mounted inside the transformer at the top level of the oil Measures ambient temperature outside the transformer via a thermocouple mounted on the circuit board s enclosure Calculates the coil hot-spot temperature using a mathematical model based on the above temperature readings Measures the temperature inside the electronics enclosure Measures both secondary RMS voltages Measures both secondary RMS currents Measures secondary watts, volt-amps, and power factor Measures cumulative kwatt-hours Analysis Capabilities Estimates the remaining insulation life of the transformer Uses ANSI equation for insulation aging, based on hot-spot temperature of coil over time Keeps up with percent of insulation life used Reporting Capabilities The following values can be reported on demand or automatically on a customerselected interval. Temperature of both low voltage half-windings Temperature of top-oil Temperature of ambient outside of the transformer Temperature inside the circuit board enclosure Calculated current hot-spot temperature of the coil Peak hot-spot coil temperature recorded Minimum hot-spot coil temperature recorded Percent insulation life used Secondary RMS voltages Secondary RMS currents Secondary watts, volt-amps, and power factor Cumulative kwatt-hours Power fail indication if transformer loses power Current date and time

Serial number of transformer Catalog number of transformer Primary voltage rating of transformer Power rating of transformer in KVA Structure number (customer entered) Location of transformer (GPS coordinates) Firmware version of Smart Transformer circuit board Controllable/Configurable Settings Reset peak and minimum temperature readings Enable or disable periodic reporting of data Change the time interval for periodic data reporting Set insulation life consumption value Set custom coefficients for the ANSI insulation aging formula Set normal expected insulation life value Communications retry time interval Communications retry attempt count Hardware/Firmware Features Low power circuit board that draws its power from the transformer secondary Front-end surge suppression to protect the circuit board Long-life, industrial-grade circuit components Long-life super capacitors are used instead of batteries to keep the circuit board powered for over a minute in the event of a power failure. This provides sufficient time to send a power fail notification message to the customer s SCADA system, indicating the location of the power fails. Cellular radio board with embedded or external antenna to communicate with customer s cellular network and SCADA system Industry-standard DNP3 protocol is used for communications Non-metallic, weather-tight enclosure mounted to the exterior of the transformer tank encloses the circuit boards Thermocouple wires and power / voltage sense wires routed from the interior of the transformer through a sealed feed-through or connector on the transformer tank wall to the circuit board enclosure Radio Board Configuration Radio Board shall be preconfigured to operate on the Avista Smart Grid wireless mesh system using the provided network configuration information. This includes, but is not limited to, a static IP address, subnet mask, default gateway, service set identifier (SSID) and DNP3 port of 20500. This information shall be cross-reference to the transformer stencil number. All information shall be provided to Avista in electronic form. OTA Firmware Update Capabilities

The radio board shall support Over-the-Air (OTA) firmware updates through Tropos Control or OpenWay Control. Mesh Network Capabilities Smart transformers shall have the ability to actively participate in the mesh network, supporting mesh links to downstream Itron and/or Tropos routers. Terminals High and low voltage terminals shall accommodate conductor sizes specified in ANSI C57.12.20. Two external tank ground terminals shall be provided and shall accommodate conductor sizes up to #2 stranded copper or aluminum. One tank ground shall be under H2 low on the tank. The second tank ground shall be three to four inches below the X2 terminal. The primary terminals shall accommodate the use of a box end ratchet wrench (Fargo) for tightening the connector nut. Neutral Ground Strap A low voltage neutral ground shall be provided from X2 to the tank wall for all units with 120/240 volt secondaries. Arrester Mounting Provisions The top arrester mounting nut shall be located a nominal distance of 5" down from the top of the tank. The spacing to the bottom arrester mounting nut shall be 2.5" center to center after beading to accommodate a standard 10.5" arrester mounting bracket Auxiliary Devices Transformers shall not have secondary breakers, overload lights or internal fuses. Transformers shall have lightning arrester mounting bosses provided for each primary bushing. Mounting bosses shall be 1/2 x 13 thread size, spaced vertically 2.5" on center with a 5/8" depth. Mounting Cleats For transformers 100kVA and larger, two mounting cleats shall be provided on the bottom of the tank. These shall be located 45O relative to the X2 bushing. The cleats shall be drilled with a 9/16" bolt to accommodate half inch mounting hardware. Hanger Brackets Hanger brackets shall be provided on transformers up through 100kVA. No brackets are required for 167kVA and larger. Pressure Relief Valve Each unit shall be equipped with an automatic pressure relief valve (PRV) having a minimum flow rate of 35 SCFM at 15 PSIG. The valve shall be located above the oil level.

Paint Finish The transformer shall have a gray (ANSI-70) corrosion resistant finish that will endure the following paint tests: Salt Spray, Adhesion, Humidity, Impact, Oil Resistance, Weathering and Abrasion, all as prescribed in the IEEE C57.12.31. Nameplate The transformer nameplate shall be so labeled to indicate that at the time of manufacture the transformer liquid contained less than one part per million PCB s. Labeling Shall include the following labels as shown on Page 1 of this specification as follows: Two sequential Stencil Numbers. 8 x 2-1/2 nominal dimensions, black on silver 3M engineering reflective background. One shall be on the side of the unit and the second shall be on the bottom. Non-PCB per Avista Specification 6620.220 Two kva rating per Avista specification 6411.500. One shall be on the side of the unit and the second shall be on the bottom. Secondary Voltage (if coils are connected in parallel for 120/208 operations for example) per Avista Specification 6411.500 Smart Transformer Identification Decal, 2.5 high x 6 wide with ¼ high black letters on silver reflective background. Shall read: All 120/240 and 120/208 connected units shall have an additional label located under the X2 bushing. The label shall read Smart transformer board is powered from X1 and X2. When paralleling secondaries for 120/208 operation, always use X1 and X2 bushing, float the X3 bushing for parallel operation and leave the X3 CT out of the circuit Losses and Tests Core and coil losses shall be in accordance with Avista Utilities current statement of Cost of Losses. Each transformer shall be tested for actual no load and load losses, percent impedance, and exciting current (100% voltage). The purchaser shall reconcile the certified test results with the quoted values using the formula: (Average total cost of actual losses - quoted total cost of losses) X (number of transformers) X 1.15 (Administrative Overheads) = penalty cost. (Average per IEEE C57.12.00.9.3). Insulating oil test for PCB s shall be per ASTM D4059. Shipping and Identification Transformers shall be shipped on a pallet. Units shall be appropriately protected during shipment to ensure they are delivered clean and free of surface contamination.