Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids

Similar documents
AORC Technical meeting 2014

Using Fault Current Limiting mode of a Hybrid DC Breaker

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults

Transient system behaviour under DC fault conditions in meshed HVDC system

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation

Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich

DC Line Protection for Multi-terminal (MT)- HVDC Systems

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Impact of VSC Converter Topology on Fault Characteristics in HVDC Transmission Systems

DC VACUUM CIRCUIT BREAKER

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Review of HVDC Circuit Breakers Topologies.

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

DC current interruption tests with HV mechanical DC circuit breaker

Protection Strategy for Multi-terminal DC Networks with Fault Current Blocking Capability of Converters

Fixed Series Compensation

Challenges in Fault Detection and Discrimination in Multi-terminal HVDC Grids and Potential Solutions M. H. Naushath, A.D.

Past CIGRE and Emerging IEEE Guide Documents on FCLs

A Review on HVDC Circuit Breakers

Fault Current Characterisation in VSC-based HVDC Systems

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

(2015) 8 (3) ISSN

In power system, transients have bad impact on its

Compact Systems for HVDC Applications Dr. Denis Imamovic

U I. HVDC Control. LCC Reactive power characteristics

Fault Current Control Methods for Multi-Terminal DC Systems based on Fault Blocking Converters

Facilitating Bulk Wind Power Integration Using LCC HVDC

Control and protection strategy for MMC MTDC system under converter-side AC fault during converter blocking failure

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

The Thyristor based Hybrid Multiterminal HVDC System

Grounded HVDC Grid Line Fault Protection Using Rate of Change of Voltage and Hybrid DC Breakers. Jeremy Sneath. The University of Manitoba

The University of Nottingham

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

A Fast Local Bus Current-Based Primary Relaying Algorithm for HVDC Grids

Trans Bay Cable A Breakthrough of VSC Multilevel Converters in HVDC Transmission

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Efficient Modeling of Hybrid MMCs for HVDC Systems

LCL VSC Converter for High-Power Applications

Surge Arrester based Load Commutation Switch for Hybrid HVDC breaker and MV DC breaker

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Effects and Mitigation of Post-Fault Commutation Failures in Line-Commutated HVDC Transmission System

Impact of SFCL on the Four Types of HVDC Circuit Breakers by Simulation

ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

DC Transmission Grid with Low Speed Protection using Mechanical DC Circuit Breakers

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

Overview of Actuation Thrust

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Assessment of Saturable Reactor Replacement Options

IMPORTANCE OF VSC IN HVDC

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

Copyright 2008 IEEE.

Distributed Current Sensing Technology for protection and Fault Location Applications in HVDC networks

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

MMC based D-STATCOM for Different Loading Conditions

Protect and survive. Fault protection analysis in low-voltage DC microgrids with photovoltaic generators

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator

VSC Transmission. Presentation Overview. CIGRE B4 HVDC and Power Electronics HVDC Colloquium, Oslo, April LCC HVDC Transmission

Topology Assessment for 3+3 Terminal Offshore DC Grid considering DC fault management

ABB Power Systems AB Sweden

Modeling and Analysis of Superconducting Fault Current Limiters Applied in VSC-HVDC Systems

Robustness Evaluation of Fast Breaker Failure Backup Protection in Bipolar HVDC Grids

POWER QUALITY ENHANCEMENT BY DC LINK SUPPLIED INDUSTRIAL SYSTEM

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Operating DC Circuit Breakers with MMC

Unit Auxiliary Transformer (UAT) Relay Loadability Report

Overview of Actuation Thrust

THE modular multilevel converter (MMC), first presented

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

POWER UPGRADATION AND POSSIBILITY OF SMALL POWER TAPPING FROM COMPOSITE AC- DC TRANSMISSION SYSTEM

DC side faults in high voltage direct current (HVDC)

I -limiter The world s fastest switching device

D6.2 Develop system level model for mechanical DCCB

ESB National Grid Transmission Planning Criteria

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

EH2741 Communication and Control in Electric Power Systems Lecture 2

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs

CONTENTS. 1. Introduction Generating Stations 9 40

EMERGING distributed generation technologies make it

FPGA-based Implementation of Modular Multilevel Converter Model for Real-time Simulation of Electromagnetic Transients

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

IEEE 2011 Electrical Power and Energy Conference

AC and DC fault ride through hybrid MMC integrating wind power

AEIJST - July Vol 3 - Issue 7 ISSN A Review of Modular Multilevel Converter based STATCOM Topology

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

Efficient Modeling of Modular Multilevel Converters for Fast Simulation of Large-Scale MMC-HVDC Embedded Power Systems

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

Power Transmission of AC-DC Supply in a Single Composite Conductor

This is the published version of a paper presented at EPE 14-ECCE Europe. Citation for the original published paper:

Fault Current Limiter Selection Considerations for Utility Engineers

ABSTRACT I. INTRODUCTION

Transcription:

Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids J. SUN, Y. SONG, M. SAEEDIFARD, and A. P. MELIOPOULOS Georgia Institute of Technology Email: jingfan@gatech.edu SUMMARY The hybrid solid-state DC circuit breakers (DC CBs) have become one of the most promising technologies to address the protection challenges within multi-terminal DC (MTDC) grids. Those breakers are designed in such a way that a large number of identical modules are connected in series to enable extinguishing the fault current with the arresters embedded in them. Conventionally, these modules are commanded to trip simultaneously, creating significant overvoltage and overcurrent stresses for the rest of the system. To attenuate these adverse impacts, in this paper, a sequential tripping method is proposed to improve the performance of hybrid DC CBs through commanding the main breakers to trip in a sequential manner. It has been verified that by the proposed method, fault clearance is expedited while the maximum overcurrent is reduced. To address the unbalanced energy absorptions among the different modules of the CB, a modified sequential tripping scheme is also proposed. By rescheduling the sequential tripping sequence, this method enables an equal redistribution of energy, which greatly reduces the risk of thermal overloading. Both of the proposed methods are evaluated and tested under a practical six-terminal DC grid in the PSCAD/EMTDC software environment. The performance and effectiveness of the proposed methods are confirmed by simulation results. KEYWORDS Multi-terminal DC (MTDC) grids, Hybrid DC circuit breaker, Sequential tripping, DC-side faults Page 1

1. INTRODUCTION High voltage DC (HVDC) transmission is a mature technology with many installations around the world [1][2]. Over the past few years, significant breakthroughs in Voltage-Sourced Converters (VSCs) along with their attractive features have made the HVDC technology even more promising in providing enhanced reliability and functionality and reducing cost and power losses. Concomitantly, significant changes in generation, transmission, and loads such as integration and tapping renewable energy generation in remote areas, the need for relocation or bypassing older conventional and/or nuclear power plants, increasing transmission capacity, urbanization and the need to feed the large cities have emerged [1]. These new trends have called for Multi-Terminal DC (MTDC) systems, which when embed within the AC grid, can enhance stability, reliability, and efficiency of the power grid [2]. Amid the optimism surrounding the benefits of MTDC grids, their protection against DC-side faults remains one of their major technical challenges. Proper protection of the MTDC grids necessitates the DC circuit breakers (DC CBs) to selectively and quickly isolate any faulty line/cable without interrupting the entire system. Among the proposed DC CBs, the hybrid solid-state one is the most promising option as its breaking time is in the order of a few milliseconds while its conduction losses during normal operation are low [3][4]. Figure 1: The hybrid DC circuit breaker. Consisting of three paths, i.e., the nominal current path (NCP), the current commutation path (CCP), and the energy absorption path (EAP), a hybrid DC CB, as shown in Fig. 1, is designed to clear a fault through commutating the fault current from the NCP to the CCP and EAP. During normal condition, the current flows through the ultra-fast disconnector (UFD) and the load commutation switch (LCS) in the NCP. Subsequent to a fault, the fault current is routed to the CCP, which is comprised of a number of identical modules with parallel connected main breakers and arresters. Once the current on the NCP reaches zero, the UFD opens immediately to prevent the LCS from exposure to high voltage. Conventionally, the opening of UFD is followed by simultaneous tripping of all series-connected modules on the CCP and the EAP [3]-[6]. This tripping method results in a high counter voltage applied by the arresters, which is used to distinguish the fault current. However, this counter voltage introduces high voltage stress across the UFD, which takes 2-3 ms to establish sufficient voltage withstanding capability [3]. This delay ultimately limits the speed of the DC CB. To address this issue, in this paper, a sequential tripping strategy is proposed to speed up the CB operation. The proposed strategy enables step-by-step tripping of the breaker modules even before the UFD is fully opened. Based on the proposed approach, the fault is interrupted in an earlier stage by applying the counter voltage of arrester banks in each module in a progressive manner. This Page 2

earlier interruption of fault reduces the maximum fault current as well as fault clearance time. To address the unbalanced energy absorptions among different CB modules, a modified sequential tripping scheme is also proposed. By rescheduling the sequential tripping sequence, this method enables an equal redistribution of energy, which greatly reduces the risk of thermal overloading. Performance and effectiveness of the proposed sequential switching strategies are evaluated through time-domain simulation of a practical six-terminal MTDC system in the PSCAD/EMTDC software environment. 2. ANALYSIS OF SEQUENTIAL TRIPPING SCHEME The sequential tripping scheme is developed to speed up the fault clearance of the DC CB by reducing the voltage stress applied to the UFD during its opening process. The switches of the main breaker are switched off sequentially so that the opening of the breaker is divided into N stages. When the switch at n $% stage (n {1,2,, N}) is tripped, the voltage across it quickly increases. This increased voltage is clamped by the corresponding module arrester, of which the rated voltage is a fraction of the rated voltage of the EAP. This allows the voltage across the hybrid CB to increase incrementally. The voltage withstand requirement of the UFD can be reduced in this way. Meanwhile, instead of waiting for complete opening of the UFD, main breaker modules are tripped earlier. Consequently, the fault clearance time can be reduced and, subsequently, the overvoltage and the overcurrent stresses on the system are relieved as well. Figure 2: Comparison between simultaneous and sequential tripping for a four-stage DC CB during a fault occurring at t = 1 s: (a) current flowing through the CB, (b) voltage across the CB, and (c) energy absorbed by the arresters (all four arresters using simultaneous tripping have identical energy curves, only one of them is shown). The current flowing through and voltage across a DC CB tested with both simultaneous and a four-stage sequential tripping schemes are shown in Fig. 2. With the sequential tripping implemented, the breaker modules are switched starting from t = 1.0018 s, 1.6 ms earlier than the simultaneous case. Furthermore, the maximum current is 1.7 ka less and the fault is cleared 0.9 ms faster. The energy absorbed by the arresters is depicted in Fig. 2(c). In the simultaneous tripping case, the energy is distributed evenly while in the sequential case, the earlier tripped arrester tends to dissipate more energy. To prevent any of the arresters from thermal overloading, a modified sequential tripping strategy is proposed. Assuming the clamped voltage of an arrester inside module i is v 567,8 and the corresponding current is i 567,8, the energy absorption of the arrester i can be expressed by Page 3

$ < W 567,8 = : v 567,8 i 567,8 dt $ =, where W 567,8 is the absorbed energy, t > and t? are the starting and ending time instants of insertion of arrester in module i, respectively. As observed from Figs. 2(a) and (b), during the period when the four modules are tripped sequentially ( t = 1.0018 s to t = 1.0035 s ), the current does not substantially change. As a result, the energy absorbed by each of the four arresters is largely proportional to the duration in which each of them is inserted into the circuit. To equally distribute the energy among the sequentially tripped arresters, the insertion duration should be kept equal as well. Table 1: Demonstration of modified sequential tripping. Normal Sequential Tripping Modified Sequential Tripping Modules 1 2 3 4 1 2 3 4 t > ~ (t? t > ) 2 (t? t > ) 2 ~t? t? ~ (t G t? ) 2 è (t G t? ) 2 ~t G t G ~ (t H t G ) 2 (t H t G ) 2 ~t H t H ~ (t I t H ) 2 (t I t H ) 2 ~t I To achieve the aforementioned distribution, the sequential tripping sequence is modified as shown in Table 1. t > to t H represent the time instances when the arresters 1 to 4 are tripped with the normal sequential tripping, as annotated in Fig. 2(b). t I is the instant when all four arresters are completely inserted. The periods t > to t I are evenly divided into 10 subintervals. The circle indicates the insertion of corresponding arrester during the specific subinterval indicated on the left most column. In normal sequential tripping method, arrester 1 is inserted in all ten subintervals while arrester 4 is just inserted in two subintervals. The modified strategy provided on the right-hand side keeps the number of circles in each row. Meanwhile, the tripping sequence is redistributed in such a way that every arrester is inserted for the same duration of time (the summation of each column is same) before t I, from when all four arresters are inserted at the same time. The modified sequential tripping method protects the arresters from thermal overloading. 3. TEST MTDC SYSTEM One of the Grid Modernization Laboratory Consortium (GMLC) projects led by Pacific Northwest National Laboratory (PNNL) and Oak Ridge National Laboratory (ORNL) has developed a continental-level 14-terminal meshed MTDC system [7][8] connecting the two major power system interconnections in North America, i.e., Western and Eastern Interconnections. With a maximum transfer capacity of 14.4 GW between the Eastern and the Western Interconnections, this system relieves congestion, mitigates loop flows in AC networks, and brings significant economic benefits [7]. Page 4

(a) (b) Figure 3: The test six-terminal DC system: (a) overview of the six-terminal system with real locations on the US map, and (b) circuit diagram of the six-terminal system [7][8]. Fig. 3 shows the layout of the six-terminal test system adopted in this paper, which is the first step of the implementation of the 14-terminal grid. The test system, which represents a ±320 kv sixterminal HVDC grid, is comprised of six VSC stations connecting the Eastern and the Western Interconnections. The length of the transmission lines are obtained from the measurements between real locations. DC CBs are located at both ends of each HVDC link. The detailed configuration of Line23 is depicted in Fig. 3(b) while other lines use simplified representation. The VSC stations, which are based on the well-known Modular Multilevel Converters (MMCs), are modelled using the Page 5

high-fidelity MMC model developed by ORNL [7][8]. Detailed parameters of the MMC and sixterminal DC system are provided in Table 2. Table 2: System parameters. AC line-to-line rms voltage 333kV Number of submodules in each arm 400 MMC arm resistance 0.1 Ω MMC arm inductance 65 mh MMC submodule capacitor 15 mf Arrester voltage rating 140 kv Current limiting reactor 50 mh 4. CASE STUDY The proposed sequential tripping methods are implemented in the test MTDC system using the PSCAD/EMTDC software. A pole-to-pole fault is initiated at t = 1 s on Line34, 100 km from MMC3. The simulation results of this case are already provided in Fig. 2. To reveal more details of the sequential tripping scheme, the method is commanded to start from different time instances and the results are compared with the normal/simultaneous tripping method. Figure 4: Comparison between the simultaneous and sequential tripping methods initiated at different time instances: (a) current flowing through the CB, and (b) voltage across the CB. As shown in Fig. 4, one of the sequential tripping tests is triggered 0.5 ms earlier than the other one. This results in 0.5 ka less maximum overcurrent and 0.5 ms faster fault clearance time. However, it should be noted that this improvement is not unlimited. The sequential tripping cannot be initiated until adequate voltage withstanding capability across the UFD has been established to withstand the counter voltage inserted by the first arrester. Page 6

Figure 5: Evaluation of energy absorption using the modified sequential tripping method: (a) comparison between normal and modified sequential tripping, and (b) comparison between simultaneous and modified sequential tripping. Using the strategy described in Table 1, the breaker switching logic is upgraded to the modified sequential tripping method. The performance is tested under the same fault scenario and the distributions of arrester energy absorption are presented in Fig. 5. At the beginning of sequential tripping, only module 1 is tripped. Therefore, the red and black curves are closely matched prior to t = 1.0023 s. Later on, the modified method tends to balance the energy absorption among different modules through distributing the clamping tasks among all arresters. Fig. 5(a) confirms that the modified method can satisfactorily achieve this goal. The modified sequential tripping is further compared with the simultaneous tripping as shown in Fig. 5(b). The final energy absorbed by the sequential case is 10% less than the simultaneous case. This verifies the superiority of the sequential tripping methods. 5. CONCLUSION In this paper, a sequential tripping method is proposed to improve the performance of hybrid DC CBs through commanding the main breaker modules to trip in a sequential manner. It has been verified that by the proposed method, fault clearance is expedited while the maximum overcurrent is reduced. To address the unbalanced energy absorptions among different CB modules, a modified sequential tripping scheme is also proposed. By rescheduling the sequential tripping sequence, this method enables an equal redistribution of energy, which greatly reduces the risk of thermal overloading. Performance and effectiveness of both of the proposed methods are evaluated and tested under a practical six-terminal DC grid in the PSCAD/EMTDC software environment. Page 7

BIBLIOGRAPHY [1] Working Group B4-52, HVDC Grid Feasibility Study, CIGRE Technical Brochure 533, Apr. 2013. [2] N. Chaudhuri, B. Chaudhuri, R. Majumder, and A. Yazdani, Multi- terminal Direct-Current Grids: Modeling, Analysis, and Control. John Wiley & Sons, 2014. [3] J. Häfner and B. Jacobson, Proactive Hybrid HVDC Breakers: A key innovation for reliable HVDC grids, in CIGRE Bologna Symp., Bologna, Italy, 2011, pp. 1-8. [4] M. K. Bucher and C. M. Franck, Fault Current Interruption in Multiterminal HVDC Networks, in IEEE Transactions on Power Delivery, vol. 31, no. 1, pp. 87-95, Feb. 2016. [5] M. Callavik, A. Blomberg, J. Ha fner, and B. Jacobson, The hybrid HVDC breaker: An innovation breakthrough enabling reliable HVDC grids, ABB Grid Syst.ems, Technical Paper Nov. 2012. [6] J. Sneath and A. D. Rajapakse, Fault Detection and Interruption in an Earthed HVDC Grid Using ROCOV and Hybrid DC Breakers, in IEEE Transactions on Power Delivery, vol. 31, no. 3, pp. 973-981, June 2016. [7] Y.V. Makarov, M.A. Elizondo, J.G. O'Brien, Q. Huang, H. Kirkham, Z. Huang, M. Chinthavali, D. Suman, N. Mohan, W. Hess and D. Duebner, Models and methods for assessing the value of HVDC and MVDC technologies in modern power grids, No. PNNL-26640. Pacific Northwest National Lab.(PNNL), Richland, WA (United States), 2017. [8] S. Debnath and J. Sun, Fidelity Requirements with Fast Transients from VSC-HVdc, in IECON 2018-44th Annual Conference of the IEEE Industrial Electronics Society, Washington, D.C., Oct. 2018. Page 8