IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4

Similar documents
ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester

Analysis of Major Changes to Arrester Standards IEC STEVE BREWER

Effective February 2017 Supersedes January 2012 (CP1122)

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters

AMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS

UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report

INTERNATIONAL STANDARD

Transformers connected via a cable Overvoltage protection

Eaton s Cooper Power Series DEADFRONT ARRESTERS

CLU Arrester. Certified Test Report. IEEE Standard C

INTERNATIONAL STANDARD

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

Low voltage products in high altitudes

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

EE 1402 HIGH VOLTAGE ENGINEERING

Electric Stresses on Surge Arrester Insulation under Standard and

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

Selection of MO surge arresters Overvoltage protection

شركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.

VariSTAR Type AZL heavy-duty distribution-class MOV arrester

Tab 8 Surge Arresters

NXCT 345 kv Test Performance Record For LAPEM

COOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

Test Specification for Type Approval

Prepared by Mick Maytum

7P Series - Surge Protection Device (SPD) Features 7P P P

Surge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester

35 kv Class M.O.V.E. DirectConnect elbow arrester

Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

I P I OUT R L. Applications. Standards. N 52.D ; Page 1/8

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary circuit and the secondary circuit.

TECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

REPORT OF PERFORMANCE TIC

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

I Pr I P I OUT R L. Applications. Standards

TECHNICAL SPECIFICATION

Center for Quality Engineering. Test Report No.: B0JA0002

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Unipolar voltage - Current output 4-20 ma Ref: DVL 50-UI, DVL 150-UI, DVL 250-UI, DVL 500-UI, DVL 750-UI, DVL 1000-UI, DVL 1500-UI

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

LIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED

V P N. Voltage transducer DVM 4200 = 4200 V

V P N. Voltage transducer DVM 2000-B = 2000 V

SOLARLOK PV BAR Junction Box

Insulation Co-ordination For HVDC Station

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

TT 0710/03. TYPE TEST OF 3 Phase Solid Earthing Bonding Link Box, Type: LB.W.3SA.3.1

Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Energy Division. Bowthorpe LV/MV Surge Arresters

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

OIML R 75-2 RECOMMENDATION. Edition 2002 (E) ORGANISATION INTERNATIONALE INTERNATIONAL ORGANIZATION

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Our experience. Our products

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Metallized Polypropylene Film Capacitor AC Filtering Radial Type

VI 3 - i TABLE OF CONTENTS

Ordering Information. PCB Relay G6RL. Model Number Legend: Low-profile power relay with maximum switching of 10 A

V P N. Voltage transducer DVL 1000 = 1000 V

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

KP 376 KP/MMKP 376. AC and pulse metallized polypropylene film capacitors. Fig.1 Simplified outlines.

I P. /dt. di p V S+ Applications. Standards. 1) IEC ed1.0: 2007; IEC : ed1.0: 2012

High voltage engineering

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

CVVOZE Power Laboratories (CVVOZEPowerLab)

POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and secondary circuit.

Comparison of CAN/CSA C88.1, IEEE C /01 & IEC 60137

Metallized Polypropylene Film Capacitor AC Filtering Radial Type

Modeling insulation in high-voltage substations

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Shunt Reactor Switching

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

= 1000 V. Voltage transducer DVC 1000-P V P N

WDBR Series (RoHS compliant)

Precision Thin Film Chip Resistor Array

For the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv

LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Current Transducer CTSR 1-P = 1A

Low profile safety relay with forcibly guided double contacts FEATURES. Relay height, 14.5mm. 4a2b

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

BCcomponents DATA SHEET. MBA 0204; MBB 0207; MBE 0414 Professional leaded resistors. Product specification File under BCcomponents, BC08.

page 2 of 86 Report reference No:

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Ref: HLSR 10-SM, HLSR 16-SM, HLSR 20-SM, HLSR 32-SM, HLSR 40-SM, HLSR 50-SM

INTERNATIONAL STANDARD

TRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Transcription:

IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M. G. Comber Manager, Engineering Date: 4/11/2007 Separate reports provide details of each test, according to the following table: Report No. Description Clause Issue date EU1517-H-01.1 Insulation Withstand Test on Arrester Housing 8.2.6, 8.2.7, 4/11/2007 8.2.8 EU1517-H-02.1 Residual Voltage 8.3.1, 8.3.2, 4/11/2007 8.3.3 EU1517-H-03.1 Long Duration Current Withstand 8.4 4/11/2007 EU1517-H-04.1 Accelerated Aging Procedure 8.5.2 4/11/2007 EU1517-H-05.1 Heat Dissipation Behavior of Test Section 8.5.3 4/11/2007 EU1517-H-06.1 Switching Surge Operating Duty 8.5.4 4/11/2007 EU1517-H-07.1 Short Circuit 8.7/Annex N 4/11/2007 EU1517-H-08.1 Internal Partial Discharge 8.8 4/11/2007 EU1517-H-09.1 Bending Moment 8.9 4/11/2007 EU1517-H-10.1 Seal Leak Rate 8.11 4/11/2007 EU1517-H-11.1 RIV 8.12 4/11/2007 EU1517-H-12.1 Power Frequency Voltage Versus Time Annex D 4/11/2007 EU1517-H-13.1 Artificial Pollution Annex F 4/11/2007

EU1517-H-01.1 IEC Type Test Report Report No. EU1517-H-01.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Insulation Withstand Test on Arrester Housing This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M. G. Comber Manager, Engineering Date: 4/11/2007 1

EU1517-H-01.1 IEC TYPE TEST REPORT Insulation Withstand Test on Arrester Housing TESTS PERFORMED: Insulation withstand tests were made on one arrester unit with internal components removed. Tests were conducted according to the procedures of Clauses 8.2.6, 8.2.7 and 8.2.8 of IEC 60099-4, which stipulate that the external insulation withstand of the arrester housing shall conform to the following: Lightning impulse withstand voltage in dry conditions shall not be less than the lightning impulse protective level of the arrester unit multiplied by 1.3. Switching impulse withstand voltage in wet conditions shall not be less than the switching impulse protective level of the arrester unit multiplied by 1.25. Power frequency withstand voltage (peak value) in wet conditions shall not be less than the switching impulse protective level of the arrester unit multiplied by 1.06 for a duration of 1 min. RESULTS: The H4 series of arresters use four different housing lengths, all of the same individual weathershed geometry. The insulation withstand tests were performed on a sample constructed with the longest housing. The highest U r used in this housing is 144 kv, for which the lightning impulse protective level is 365 kv at 20kA and the maximum switching impulse protective level is 291 kv at 2kA. Lightning impulse The lightning impulse test was performed under dry conditions by applying 15 positive and 15 negative full-wave lightning-impulse voltages to the test sample. The impulse voltages had a virtual front time of 1.2 µs (±30%) and a virtual time to half value of 50 µs (±20%). The test sample withstood all impulses without disruptive discharge. The withstand voltages obtained were corrected to standard atmospheric conditions in accordance with IEC 60060-1. The required minimum lightning impulse withstand voltage is 1.3 times the maximum lightning impulse protective level, or 1.3 x 365 = 475 kv. Switching impulse The switching impulse test was performed under wet conditions by applying 15 positive and 15 negative full-wave switching-impulse voltages to the test sample. The precipitation conditions and resistivity of the water were in accordance with the requirements of IEC 60060-1. The impulse voltages had a time to crest value of 250 µs (±20%) and a time to half value of 2500 µs (±60%). The test sample withstood all impulses without disruptive discharge. The withstand voltages obtained were corrected to standard atmospheric conditions in accordance with IEC 60060-1. The required minimum switching impulse withstand voltage is 1.25 times the maximum switching impulse protective level, or 1.25 x 291 = 364 kv. 2

EU1517-H-01.1 Power frequency The power frequency test was performed under wet conditions by applying a 60 Hz voltage for a duration of 1 min. The precipitation conditions and resistivity of the water were in accordance with the requirements of IEC 60060-1. The test sample withstood the applied voltage without disruptive discharge. The required minimum power frequency withstand voltage is 1.06 times the maximum switching impulse protective level, or 1.06 x 291 = 309 kvpeak. Tests were successfully performed at levels higher that exceeded the minimum levels indicated above. Results are summarized in Table 1. Withstand test Lightning impulse, pos Lightning impulse, neg Switching impulse, pos Switching impulse, neg Table 1. Measured and corrected withstand values Uncorrected withstand voltage kv pk Atmospheric conditions Correction factors Corrected Ambient Air Absolute Air Humidity withstand temperature pressure humidity density o C KPa gm -3 k 1 k 2 kv peak 490 28.2 98.3 18.06.959 1.070 477 491 28.2 98.3 18.06.959 1.070 478 419 25.3 98.5 Wet test -- 1.000 419 420 22.9 98.5 Wet test -- 1.000 420 60 Hz 410 21.4 98.2 Wet test -- 1.000 410 3

EU1517-H-02.1 IEC Type Test Report Report No. EU1517-H-02.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Residual Voltage This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M. G. Comber Manager, Engineering Date: 4/11/2007 1

EU1515-H-02.1 IEC TYPE TEST REPORT Residual Voltage TESTS PERFORMED: Residual voltage measurements were made on three single resistor elements. Tests were conducted in accordance with clauses 8.3.1, 8.3.2 and 8.3.3 of IEC 60099-4, to determine steep current impulse residual voltages at 20 ka, lightning impulse residual voltages at 10 ka, 20 ka and 40 ka, and switching impulse residual voltages at 0.5 ka and 2 ka. Oscillograms of current and voltage were obtained for each test. For each test sample, all measured voltages have been rationalized to the lightning impulse residual voltage of that sample at nominal discharge current (20 ka 8/20), and the results have been displayed in graphical form. RESULTS: Tables 1, 2 and 3 show the residual voltages measured on test samples 1, 2 and 3, respectively. For each test sample, the measured residual voltages have been expressed in per unit of the lightning impulse residual voltage at nominal discharge current (20 ka, 8/20). Table 1. Measurements made on test sample 1 Test Wave Current magnitude Waveshape Residual Voltage Oscillogram ka _s kv p.u. number Steep current 20 1/2 12.03 1.104 28 10 10.07 0.924 4 Lightning 20 8/20 10.90 1.000 7 impulse 40 12.13 1.113 10 Switching 0.5 8.13 0.746 16 38/84 impulse 2 8.69 0.797 22 Table 2. Measurements made on test sample 2 Current Test wave magnitude Waveshape Residual Voltage Oscillogram ka _s kv p.u. number Steep current 20 1/2 11.99 1.104 29 10 10.04 0.925 5 Lightning 20 8/20 10.86 1.000 8 impulse 40 12.07 1.111 11 Switching 0.5 8.07 0.743 17 38/84 impulse 2 8.64 0.796 23 2

EU1515-H-02.1 Table 3. Measurements made on test sample 3 Current Test wave magnitude Waveshape Residual Voltage Oscillogram ka _s kv p.u. number Steep current 20 1/2 11.99 1.103 30 10 10.04 0.924 6 Lightning 20 8/20 10.87 1.000 9 impulse 40 12.07 1.111 12 Switching 0.5 8.09 0.744 18 38/84 impulse 2 8.65 0.796 24 The results are shown graphically in the following chart. 1.2 Residual voltage - p.u. 1.1 1 0.9 0.8 Switching impulse Steep front Lightning impulse 0.7 0 10 20 30 40 Current - ka Annex The values shown in this chart are all normalized to the lightning impulse residual voltage at nominal discharge current (20 ka). These values (Per-unit U res-chart ) are used to calculate the residual voltage characteristics (U res-arrester ) of assembled H4 series 3

EU1515-H-02.1 arresters. For the cases of switching impulse and lightning impulse residual voltages, the arrester residual voltages are calculated as follows: U res-arrester = Per-unit U res-chart x U res-nom where Ures-nom is the published maximum lightning impulse residual voltage of the arrester, as verified by routine test at time of arrester manufacture. For the case of steep current impulse residual voltage, the arrester residual voltage is calculated as follows: U res-arrester = Per-unit U res-chart x U res-nom + L h I n / T f where L is the inductivity per unit length (= 1 µh/m) h is the length of the arrester (excluding the resistors since resistor inductance is already included in the test measurements) I n is the nominal discharge current (= 20 ka) T f is the front time of the steep current impulse (= 1µs) 4

EU1515-H-02.1 Oscillograms 5

EU1517-H-02.1 Oscillogram 4 Sample 1 6

EU1515-H-02.1 Oscillogram 5 Sample 2 7

EU1515-H-02.1 Oscillogroam 6 Sample 3 8

EU1515-H-02.1 Oscillogram 7 Sample 1 9

EU1515-H-02.1 Oscillogram 8 Sample 2 10

EU1515-H-02.1 Oscillogram 9 Sample 3 11

EU1515-H-02.1 Oscillogram 10 Sample 1 12

EU1515-H-02.1 Oscillogram 11 Sample 2 13

EU1515-H-02.1 Oscillogram 12 Sample 3 14

EU1515-H-02.1 Oscillogram 16 Sample 1 15

EU1515-H-02.1 Oscillogram 17 Sample 2 16

EU1515-H-02.1 Oscillogram 18 Sample 3 17

EU1515-H-02.1 Oscillogram 22 Sample 1 18

EU1515-H-02.1 Oscillogram 23 Sample 2 19

EU1515-H-02.1 Oscillogram 24 Sample 3 20

EU1515-H-02.1 Oscillogram 28 Sample 1 21

EU1515-H-02.1 Oscillogram 29 Sample 2 22

EU1515-H-02.1 Oscillogram 30 Sample 3 23

EU1517-H-03.1 IEC Type Test Report Report No. EU1517-H-03.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Long Duration Current Impulse Withstand Tests This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007-1 -

EU1517-H-03.1 IEC TYPE TEST REPORT Long Duration Current Impulse Withstand Tests TESTS PERFORMED: Long duration current impulse withstand tests were performed on three test samples, each consisting of two resistors in series, with sample U r of approximately 12 kv. The resistors were selected to represent the lowest acceptable reference voltage level. The tests were conducted in accordance with Clause 8.4.2 of IEC 60099-4. Prior to the administering of line discharges, measurements were made of the residual voltage and reference voltage on each test sample. The transmission line parameters conformed to the requirements for Line Discharge Class 4 in Table 5 of IEC 60099-4. Table 1 below lists the measured residual voltage and reference voltage for each sample, and lists the corresponding transmission line parameters used for the test. Table 1. Parameters for Line Discharge Tests Parameter Sample 1 Sample 2 Sample 3 Initial Residual Voltage (kv) @ 20 ka, 8/20 Reference Current (ma) I ref Reference Voltage (kv c ) V ref COV ( kv rms) U c Rating (kv rms) U r Arrester Classification (ka) Line Discharge Class Virtual Duration of Peak (µs, 90-90%) - min Surge Impedance (Ω) Z g - max (0.8 U r ) Charging Voltage (kv) U L min (2.6 U r ) 29.33 17 17.59 9.70 12.12 20 4 2800 9.70 31.51 29.28 17 17.55 9.68 12.10 20 4 2800 9.68 31.46 29.21 17 17.56 9.69 12.11 20 4 2800 9.69 31.49 Each sample was subjected to 18 line discharges, administered in six groups of three discharges. Within each group of three discharges, the time interval between discharges was 50 to 60 seconds. The samples were allowed to cool to ambient temperature between groups of discharges. - 2 -

EU1517-H-03.1 RESULTS: A short circuit test was performed on the generator to confirm that generator impedance and duration of the current discharge met the requirements listed in Table 1. The oscillogram of Figure 1 shows Z g = 8,960 V / 936.89 A = 9.564 Ω Virtual Duration of Peak = 2885 µs Table 2 lists the current and voltage magnitudes and discharge energy measured on each of the 18 discharges on each of the three test samples. Figures 2, 3 and 4 show oscillograms of the first and eighteenth discharges for each of the three samples, respectively. Ambient air temperature at the time of the test was 22 C. - 3 -

EU1517-H-03.1 Figure 1. Oscillogram of discharge current for generator short circuit set up test Impulse I (A) Table 2. Line Discharge Test Measurements Sample 1 Sample 2 Sample 3 V E V I V I (A) E (kj) (kv) (kj) (kv) (A) (kv) E (kj) 1 972 22.63 65.4 976 22.59 65.2 974 22.57 65.3 2 943 22.90 64.0 941 22.90 64.0 941 22.86 64.0 3 914 23.23 63.0 916 23.11 63.0 916 23.11 63.0 4 966 22.63 64.9 968 22.63 65.0 972 22.57 65.0 5 939 22.94 63.8 941 22.90 63.8 945 22.84 63.9 6 912 23.13 62.7 916 23.13 62.9 918 23.09 63.0 7 962 22.67 64.7 960 22.65 64.8 968 22.65 65.0 8 933 22.92 63.6 937 22.90 63.7 939 22.90 63.9 9 910 23.19 62.6 912 23.13 62.8 916 23.15 62.9 10 957 22.65 64.6 960 22.67 64.6 966 22.59 64.6 11 926 22.98 63.3 935 22.92 63.6 937 22.90 63.5 12 906 23.21 62.4 908 23.13 62.5 906 23.13 62.5 13 956 22.71 64.7 964 22.65 64.7 966 22.67 64.9 14 928 22.98 63.4 939 22.96 63.6 937 22.94 63.7 15 912 23.13 62.6 912 23.21 62.7 912 23.13 62.6 16 1022 23.19 70.7 978 22.63 65.9 982 22.65 66.0 17 949 22.98 64.9 949 22.94 64.8 953 22.96 64.8 18 926 23.21 63.9 926 23.19 63.8 926 23.19 63.8-4 -

EU1517-H-03.1 Sample 1, Discharge 3 Sample 1, Discharge 18 Figure 2. Oscillograms of line discharges for sample 1-5 -

EU1517-H-03.1 Sample 2, Discharge 3 Sample 2, Discharge 18 Figure 3. Oscillograms of line discharges for sample 2-6 -

EU1517-H-03.1 Sample 3, Discharge 3 Sample 3, Discharge 18 Figure 4. Oscillograms of line discharges for sample 3-7 -

EU1517-H-03.1 Subsequent to the completion of the transmission line discharges, the residual voltage at nominal discharge current was re-measured and compared to the initial values for each test sample. Results are summarized in Table 3. The maximum change of residual voltage of the three samples is less than the permissible change of 5 % defined by IEC 60099-4. Table 3. Initial and final residual voltage measurements. Sample Residual voltage (kv) Before After Change 1 29.33 29.31-0.1 % 2 29.28 29.26-0.1 % 3 29.21 29.14-0.2 % Disassembly of the test samples at the end of the electrical tests revealed no evidence of physical damage. - 8 -

EU1517-H-04.1 IEC Type Test Report Report No. EU1517-H-04.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Accelerated Aging Procedure This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-04.1 IEC TYPE TEST REPORT Accelerated Aging Procedure TESTS PERFORMED: Accelerated aging tests were performed on two resistor elements. The tests were conducted in accordance with Clause 8.5.2 of IEC 60099-4. The test samples were placed in an air oven and energized at a voltage equal to the corrected maximum continuous operating voltage, U ct, for 1000 hours. The temperature of the samples was maintained at 115 C ± 2 C for the duration of the test. Power dissipation was measured on each sample throughout the 1000 h test period. Clause 8.5.2 of IEC 60099-4 defines three power dissipation values: P 1ct, measured 1 h to 2 h after the initial voltage application P 2ct, measured after 1000 h P 3ct, the minimum value attained during the 1000 h test period. If P 2ct is equal to or less than 1.1 times P 3ct, then the switching surge operating duty test of Clause 8.5.5 of IEC 6099-4 is to be performed on new resistors. Furthermore, if P 2ct is equal to or less than P 1ct, then the rated voltage and continuous operating voltage used for the operating duty test are not subject to any modification. RESULTS: Figure 1 graphically displays the measurements made during the 1000 h test period. Table 1 summarizes the values of P 1ct, P 2ct and P 3ct for each sample. The requirements that P 2ct is equal to or less than 1.1 times P 3ct, and P 2ct is equal to or less than P 1ct are met for both samples. Consequently, no modification needs to be made to the rated voltage and continuous operating voltage in the operating duty test, and the operating duty test can be performed on new resistors. Table 1. Power dissipation values Power dissipation at 2 h Power dissipation at 1000 h Minimum power dissipation Sample Number P 1ct (W) P 2ct (W) P 3ct (W) 1 5.20 2.82 2.82 2 5.97 2.91 2.91-2 -

EU1517-H-04.1 7.0 120 6.0 Temperature 100 Power Dissipation - W Voltage - kvrms 5.0 4.0 3.0 Sample 2 Voltage 80 60 40 Temperature - C Sample 1 2.0 20 1.0 0 200 400 600 800 1000 Time - h 0 Figure 1. Power dissipation, voltage and temperature measurements during 1000 h test period - 3 -

EU1517-H-05.1 IEC Type Test Report Report No. EU1517-H-05.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Heat Dissipation Behaviour of Test Section This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-05.1 IEC TYPE TEST REPORT Heat Dissipation Behaviour of Test Section TESTS PERFORMED: Tests were performed as described in Clause 8.5.3 and Annex B of IEC 60099-4, to compare the cooling characteristics of the test section used for type tests with those of a full-size arrester unit. For this purpose, a specially modified arrester unit with U r = 144 kv unit and a test section with U r = 10.6 kv were prepared. The 144 kv rated unit, which represents the highest individual unit rated voltage and the most resistors per unit length of all units used in the arrester design, was equipped with a thermocouple located between one-third and one-half of the unit length from the top of the resistor stack. The test section was comprised of two resistor elements assembled into a short section of porcelain housing, insulated on top and bottom ends to control the rate of cooling to meet the requirements that the test section cools at a rate not greater than that of the assembled unit. A thermocouple was located at the mid-height of the two-resistor stack Both assembled unit and test section were heated electrically with a power frequency overvoltage to raise the average temperature of the resistors to 120 o C in the same amount of time. The voltage was removed and the samples allowed to cool naturally. Temperature measurements were made throughout the cooling period. RESULTS: The resistors in both the assembled unit and the test section were heated by applying a voltage sufficiently above U r to raise the resistor temperature to 120 o C in approximately 4 min. Figure 1 graphically displays the cooling of both samples over a period of approximately 3 hours. With both samples starting from the same initial temperature of 120 o C, the temperature of the resistors in the test section remain at or above the temperature of the resistors in the fully assembled unit throughout the cooling period. This demonstrates the validity of the test section for use in type tests involving thermal recovery. - 2 -

EU1517-H-05.1 140 120 100 Arrester unit cooling curve Test section cooling curve Temperature - C 80 60 40 20 0 0 20 40 60 80 100 120 140 160 180 200 Time - min Figure 1. Cooling curves of fully assembled unit and test section - 3 -

EU1517-H-06.1 IEC Type Test Report Report No. EU1517-H-06.1 H4 Series Porcelain-housed Arrester 10,000 A Line Discharge Class 4 Switching Surge Operating Duty Test This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-06.1 IEC TYPE TEST REPORT Switching Surge Operating Duty Test TESTS PERFORMED: Switching surge operating duty tests were performed on three prorated test sections prepared based on the results of the tests to verify heat dissipation behaviour of test sample. Each section consisted of two resistors in series and had U r of approximately 12kV. The resistors were selected to represent the lowest acceptable reference voltage level. The tests were conducted in accordance with Clause 8.5.5 of IEC 60099-4. Prior to the conditioning portion of the test, measurements were made of the lightning impulse residual voltage of each section, and also of reference voltage of each section. Additional measurements were made of power dissipation at U c, and an adjusted value U c was determined such that the power dissipation of each sample represented the maximum power dissipation of resistors that could be used in arrester assembly. The adjusted value Uc was used in the thermal recovery portion of the test. The conditioning portion of the test consisted of two parts. In the first part, a series of twenty 8/20 lightning current impulses were applied to each section, with peak value of the impulses being equal to the nominal discharge current. The series of impulses was divided into four groups of five, with the interval between impulses within each group being between 50 and 60 seconds and the interval between groups being between 25 and 30 minutes. Test sections were energized at 60 Hz voltage of 1.2 U c during the application of the impulses within each group. The impulses were timed to occur 60 before the crest of the 60 Hz voltage with the same polarity of the impulse. In the second part, a series of two 100kA 4/10 impulses were applied to each section, with the section allowed to cool to ambient temperature between impulses. Following the conditioning portion of the test, each section was placed in an oven and heated overnight to 60 ± 3 C. After removal from the oven, each section was subjected to two long duration current impulses, with time between impulses being between 50 and 60 seconds. The parameters of the transmission line used to generate these impulses conformed to the requirements for Line Discharge Class 4 in Table 5 of Clause 8.4.2 of IEC 60099-4. Within 100 milliseconds of the second long duration current impulse, rated voltage (U r ) was applied to each section for 10 seconds, immediately followed by the adjusted U c for 30 minutes, during which period the power dissipation was monitored to verify thermal stability. At the end of the above test sequence, each section was allowed to cool to ambient temperature, at which point the lightning impulse residual voltage at nominal discharge current was re-measured. Table 1 lists the initial measurements of residual voltage and reference voltage for each section, and lists the corresponding transmission line parameters used for the test. - 2 -

EU1517-H-06.1 Table 1. Initial Measurements and Parameters for Line Discharge Tests Parameter Sample 1 Sample 2 Sample 3 Initial Residual Voltage (kv) @ 20 ka, 8/20 Reference Current (ma) I ref Reference Voltage (kv c ) V ref COV ( kv rms) U c Adjusted COV 9kVrms) Uc Rating (kv rms) U r Arrester Classification (ka) Line Discharge Class Virtual Duration of Peak (µs, 90-90%) - min Surge Impedance (Ω) Z g - max (0.8 U r ) Charging Voltage (kv) U L min (2.6 U r ) 29.11 17 17.55 9.68 10.38 12.10 20 4 2800 9.68 31.46 29.01 17 17.54 9.67 10.59 12.09 20 4 2800 9.67 31.43 29.00 17 17.52 9.66 10.39 12.08 20 4 2800 9.66 31.41 RESULTS: Figures 1, 2 and 3 show recordings made during application of the 5 th and 20 th lightning impulse conditioning discharges on each section. Figures 4, 5 and 6 show recordings made during application of the 1 st and 2 nd high current conditioning impulse on each section. A short circuit test was performed on the generator to confirm that generator impedance and duration of the current discharge met the requirements listed in Table 1. The oscillogram of Figure 7 shows Z g = 8,960 V / 936.89 A = 9.564 Ω Virtual Duration of Peak = 2885 µs Table 2 lists the current and voltage magnitudes and discharge energy measured on each of the two line discharges for each of the three test samples. Impulse I (A) Table 2. Line Discharge Test Measurements Section 1 Section 2 Section 3 V V V E (kj) I (A) E (kj) I (A) (kv) (kv) (kv) E (kj) 1 955 22.83 65.3 956 22.82 65.0 955 22.71 64.8 2 924 23.08 63.7 924 23.11 65.6 921 23.10 63.6-3 -

EU1517-H-06.1 Section 1: 5 th conditioning impulse Section 1: 20 th conditioning impulse Figure 1. Oscillograms of 20kA 8/20 conditioning impulses for section 1-4 -

EU1517-H-06.1 Section 2: 5 th conditioning impulse Section 2: 20 th conditioning impulse Figure 2. Oscillograms of 20kA 8/20 conditioning impulses for section 2-5 -

EU1517-H-06.1 Section 3: 5 th conditioning impulse Section 3: 20 th conditioning impulse Figure 3. Oscillograms of 20kA 8/20 conditioning impulses for section 3-6 -

EU1517-H-06.1 Section 1: 1 st conditioning impulse Section 1: 2 nd conditioning impulse Figure 4. Oscillograms of 100kA conditioning impulses for section 1-7 -

EU1517-H-06.1 Section 2: 1 st conditioning impulse Section 2: 2 nd conditioning impulse Figure 5. Oscillograms of 100kA conditioning impulses for section 2-8 -

EU1517-H-06.1 Section 3: 1 st conditioning impulse Section 3: 2 nd conditioning impulse Figure 6. Oscillograms of 100kA conditioning impulses for section 3-9 -

EU1517-H-06.1 Figure 7. Oscillogram of discharge current for generator short circuit set up test Figures 8, 9 and 10 show oscillograms of the second line discharge and the 10 s application of U r on each section. Ambient air temperature at the time of the test was 22 C. Table 3 lists measurements made during this period. Time (s) Table 3. Measurements made during 10 s application of U r. Section 1 Section 2 Section 3 Voltage Current Time Voltage Current Time Voltage (kvc) (mac) (s) (kvc) (mac) (s) (kvc) Current (mac) 0.08 17.31 116 0.07 16.82 110 0.09 17.21 100 1 17.31 114 1 17.21 110 1 17.18 96 2 17.28 110 2 17.26 108 2 17.20 97 4 17.28 108 4 17.24 102 4 17.18 94 6 17.29 108 6 17.26 104 6 17.19 92 8 17.31 110 8 17.26 102 8 17.19 93 10.2 17.29 105 10.2 17.25 100 10.2 17.17 89-10 -

EU1517-H-06.1 Figure 8. Oscillogram of second line discharge for section 1 Figure 9. Oscillogram of second line discharge for section 2-11 -

EU1517-H-06.1 Figure 10. Oscillogram of second line discharge for section 3 Figures 11, 12 and 13 show oscillograms of voltage and current at the beginning and end of the 30 min application of U c on each section. Table 4 lists measurements of power dissipation made during this period. Table 4. Measurements of power dissipation made during 30 min at U c Time (min) Power Dissipation (W) Section 1 Section 2 Section 3 0 47.6 41.5 41.3 0.5 37.1 38.0 35.3 1 35.7 34.4 33.5 2 33.9 32.6 31.3 5 29.5 29.9 27.2 10 26.8 27.2 24.6 20 25.0 25.0 22.3 30 23.2 24.1 20.1-12 -

EU1517-H-06.1 Figure 11. Oscillograms of voltage and current at the beginning and end of the 30 min application of U c for section 1-13 -

EU1517-H-06.1 Figure 12. Oscillograms of voltage and current at the beginning and end of the 30 min application of U c for section 2-14 -

EU1517-H-06.1 Figure 13. Oscillograms of voltage and current at the beginning and end of the 30 min application of U c for section 3-15 -

EU1517-H-06.1 Subsequent to the completion of the thermal recovery, and after the sections had cooled to ambient temperature, the residual voltage at nominal discharge current was re-measured and compared to the initial values for each test sample. Results are summarized in Table 5. The maximum change of residual voltage of the three samples is less than the permissible change of 5 % defined by IEC 60099-4. Table 5. Initial and final residual voltage measurements. Section Residual voltage (kv) Initial Final Change 1 29.11 29.32 + 0.7% 2 29.01 29.22 + 0.7% 3 29.00 29.25 + 0.9% Disassembly of the test samples at the end of the electrical tests revealed no evidence of physical damage. - 16 -

EU1517-H-07.1 IEC Type Test Report Report No. EU1517-H-07.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Short Circuit This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007-1 -

EU1516-H-07.1 IEC TYPE TEST REPORT Short Circuit TESTS PERFORMED: High current short circuit tests were performed at the CESI high power laboratory in Milan, Italy according to the procedures described in Clause 8.7 of IEC 60099-4. The H4 series of arresters has a rated short circuit capability of 63000 A symmetrical. Verification of capability requires three high current tests, performed with rated short circuit current (63000 A) and two reduced short circuit currents (25000 A and 12000 A). For these tests, fully assembled test units were prepared, each containing as many resistor elements as possible within the available stacking length. The internal elements of each test unit were shorted by a fuse wire running along the outside of the stack of elements. The units tested represented the longest unit used in the H4 series of arresters. RESULTS: Complete results of the testing are contained in a CESI test report that is available on request. Results are summarized in the following extracts from the CESI report. The test samples had an overall unit length of 1308 mm. Figure 1 shows the general arrangement of the test set up. Figure 2 shows one of the units in the test chamber. All three samples successfully withstood their respective short circuit current tests with no fracturing of the porcelain housing (in the case of the 12000 A and 63000 A tests, a small amount of breakage of weathersheds occurred, but the porcelain pieces did not fall outside the enclosure). Actual prospective rms values of test currents were 12600 A, 25500 A and 67000 A. For the rated current test, the peak of the first half cycle of test current was 169000 A, meeting the requirement that this be at least 2.5 times the rms value of the rated short circuit current. Data sheets for the tests are shown in Figures 3 5, and associated oscillograms are shown in Figures 6-9. - 2 -

EU1516-H-07.1 Figure 1. Test circuit arrangement - 3 -

EU1516-H-07.1 Figure 2. Test sample mounted in test chamber - 4 -

EU1517-H-07.1 Figure 3. Data sheet for 12000 A test - 5 -

EU1516-H-07.1 Figure 4. Data sheet for 25000 A test - 6 -

EU1516-H-07.1 Figure 5. Data sheet for 63000 A test - 7 -

EU1517-H-07.1 Figure 6. Oscillograms for 12000A test Figure 7. Oscillograms for 25000A test - 8 -

EU1516-H-07.1 Figure 8. Oscillograms for 63000A test - 9 -

EU1517-H-08.1 IEC Type Test Report Report No. EU1517-H-08.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Internal Partial Discharge This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-08.1 IEC TYPE TEST REPORT Internal Partial Discharge Clause 8.8 of IEC 60099-4 requires that the longest electrical unit of the arrester design be subject ed to an internal part ial discharge ty pe test. Under the prescribed test ing procedure, the part ial discharge level at 1.05 times the cont inuous op erating volt age of the unit shall not exceed 10 pc. Clause 9.1 c) of this same st andard requires that all manufactured unit s be subject ed to an internal part ial discharge test that is identical to that of Clause 8.8, and that the part ial discharge level of all unit s produced shall not exceed 10 pc. Rout ine test reports are provided on request verifying that this requirement has been met. By performing the rout ine test ing of unit s according to Clause 9.1 c), the ty pe test requirements of Clause 8.8 are automat ically met. - 2 -

EU1517-H-09.1 IEC Type Test Report Report No. EU1517-H-09.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Bending Moment This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-09.1 IEC TYPE TEST REPORT Bending Moment TESTS PERFORMED: Bending moment tests were performed as described in Clause 8.9 of IEC 60099-4 on fully assembled arrester units. Test units were securely mounted to the horizontal base of the test equipment and lateral (horizontal) loading was applied at a rate necessary to reach the bending moment corresponding to the maximum permissible dynamic service load (MPDSL) in approximately 90 s. The load was then maintained at not less than this level for at least 60 s. After release of load, the test sample was inspected to verify that no mechanical damage had occurred, and then the test sample was subjected to standard seal leak and partial discharge tests to verify that no damage to the sealing mechanism or to the internal structure had occurred. RESULTS: According to the requirements of IEC 60099-4, if the arrester design consists of multiple units or where the arrester has different specified bending moments at each end, it is necessary to verify the integrity of each different design bending moments. The H4 series of arresters uses one, two, three, four or five units depending on voltage rating and overall creepage distance requirements. The design uses one general porcelain housing type (all housings have the same diameter and weathershed profile, differing only in height), and two different end fitting designs. The arrester unit combinations that give rise to the highest bending moments for each end fitting type are schematically illustrated in Figure 1. The MPDSL assigned to H4 arresters is that load that results in a bending moment of 8000 Nm at the base of the arrester. Table 1 indicates the worst case combinations i.e. those that give rise to the highest moments at each end fitting location when MPDSL is applied to the top of the arrester. The maximum bending moment at locations of end fitting type F1 is 17000 Nm, while the maximum bending load at locations of end fitting type F2 is 5983 Nm. To verify the design capability, two bending moment tests were performed on two 1308- mm units, one equipped with end fittings of type F1 and the other equipped with end fittings of type F2. The first (F1) unit was loaded at the top end to subject the bottom end to a minimum bending moment of 17000 Nm for 60 s, while the second (F2) unit was loaded at the top end to subject the bottom end to a minimum bending moment of of 5983 Nm for 60 s. Loading curves for these two tests are shown in Figures 2 and 3. These indicate that the loads were actually maintained at higher levels and for longer time than required. The gradual reduction of load during the hold period resulted from slow loss of pressure in the hydraulic system, and does not reflect any change in the mechanical property of the tested unit. - 2 -

EU1517-H-09.1 Subsequent to the loading tests, the test units were examined and found to have suffered no visual mechanical damage. The units were then returned to the factory for seal leak rate check and partial discharge tests. Seal leak rate was found to be less than 1x10-7 Pa.m 3 s -1, and partial discharge at 1.05 U c was found to be less than 10pC, both levels being below the limits allowed by IEC 60099-4. Unit L M F2 0 5.5 1206 Unit L M F2 3496 F2 0 F2 3496 4.4 1041 5.4 1206 Unit L M F2 4425 F1 6991 F2 0 F2 4425 F1 6991 3.3 1041 4.3 1041 5.3 1206 Unit L M F2 5983 F1 8851 F1 10487 F2 0 F2 5983 F1 8851 F1 10487 2.2 1041 3.2 1041 4.2 1041 5.2 1206 Unit L M F1 10032 F1 11966 F1 13276 F1 13983 F2 0 F1 10032 F1 11966 F1 13276 F1 13983 1.1 1206 2.1 723 3.1 876 4.1 876 5.1 1041 F1 17000 F1 17000 F1 17000 F1 17000 F1 17000 Max moment for F1 Max moment for F2 Figure 1. Worst-case bending moments for 1, 2, 3, 4 and 5-unit arresters F1 and F2 indicate the two different end fitting types 1.1, 2.1, 2.2,..etc indicate porcelain housings Length is in mm, Moment is in Nm - 3 -

EU1517-H-09.1 Bending Moment (Nm) 20000 18000 16000 14000 12000 10000 8000 6000 4000 2000 0 0 50 100 150 200 250 Time (s) Figure 2. Bending moment at bottom end of unit, end fitting type F1 Max design moment at MPDSL: 17000 Nm 10000 9000 8000 7000 Moment (Nm) 6000 5000 4000 3000 2000 1000 0 0 50 100 150 200 250 Time (Sec) Figure 3. Bending moment at bottom end of unit, end fitting type F2 Max design moment at MPDSL: 5983 Nm - 4 -

EU1517-H-10.1 IEC Type Test Report Report No. EU1517-H-10.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Seal Leak Rate This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-10.1 IEC TYPE TEST REPORT Seal Leak Rate Clause 8.11 of IEC 60099-4 requires that one comp let e arrester be subject ed to a seal leak rate test, using any sensitive method suit able for the measurement of the sp ecified seal leak test. Using the adop ted method, the seal leak rate shall be lower than 1x10-6 Pa.m 3 s -1. Clause 9.1 d) of this same st andard requires that, for arrester unit s with sealed housing, all manufactured unit s be subject ed to a seal leak test as a rout ine test. In this test, the method us ed for H4 series arresters is the vacuum helium mass sp ectrometer method. With this method, the internal air sp ace of the arrester unit is evacuat ed, resulting in a one at mosphere pres sure different ial betw een outs ide and inside, under which conditions the outs ide of the arrester is flooded with helium. The evacuat ion port is monitored by a mass sp ectrometer tuned to detect helium, and any helium detected is quantit at ively measured to provide a leak rate. The maximum leak rate accepted for H4 series arrester unit s is 1x10-7 Pa.m 3 s -1, one order of magnitude below the maximum allowed by IEC 60099-4. Rout ine test reports are provided on request verifying that this requirement has been met. By performing the rout ine test ing of unit s according to Clause 9.1 d), the ty pe test requirements of Clause 8.11 are automat ically met. - 2 -

EU1517-H-11.1 IEC Type Test Report Report No. EU1517-H-11.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Radio Influence Voltage (RIV) This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-11.1 IEC TYPE TEST REPORT Radio Influence Voltage (RIV) TESTS PERFORMED: A fully-assembled arrester, with volt age rating U r of 396 kv and cont inuous op erating volt age U c of 318 kv, was subject ed to the RIV test as prescribed in Clause 8.11 of IEC 60099-4. The volt age ap plication was as follows: raised to 366 kv (1.15 U c ) lowered to 334 kv (1.05 U c ) held at 334 kv for 5 min lowered in st ep s of ap proximately 0.1 U c until reaching 0.5 U c increased in similar st ep s until reaching 334 kv (1.05 U c ) held at 334 kv for 5 min lowered again in st ep s of ap proximately 0.1 U c unt il reaching 0.5 U c RIV meas urements were made at each volt age level. The variable-frequency RIV meter was tuned to 1 MHz for the measurements. RESULTS : Prior to inst alling the arrester in the test circuit, an op en circuit test was run to determine the background nois e of the circuit. The arrester was inst alled and the sequence of volt age ap plications described above was ap plied. Figure 1 show s the arrester inst alled for test. Results of the RIV measurements are shown in Table 1. At all test volt age levels, the RIV was essentially at background noise level. IEC 60099-4 allows a maximum RIV level of 2500 µv. - 2 -

EU1517-H-11.1 Test conditi on Fi gure 1. 396 kv rated arre ster Tabl e 1. Me asure d RIV values Test volt age (kv rms) RIV (µv) Open ci rcuit 334 6 Open ci rcuit 400 10 Arrester ins talled 366 6 Arrester ins talled 334 6 Arrester ins talled 318 6 Arrester ins talled 286 6 Arrester ins talled 254 6 Arrester ins talled 223 6 Arrester ins talled 191 6 Arrester ins talled 159 6 Arrester ins talled 191 6 Arrester ins talled 223 6 Arrester ins talled 254 6 Arrester ins talled 286 6 Arrester ins talled 318 6 Arrester ins talled 334 6 Arrester ins talled 318 6 Arrester ins talled 286 6 Arrester ins talled 254 6 Arrester ins talled 223 6 Arrester ins talled 191 6 Arrester ins talled 159 6-3 -

EU1517-H-12.1 IEC Type Test Report Report No. EU1517-H-12.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 Power Frequency Voltage Versus Time This report records the results of type tests made on H4 series 20 ka Line Discharge Class 4 arresters, rated up to 420 kv. Tests were performed in accordance with procedures of IEC Standard 60099-4, Ed. 2.1, 2006, Surge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems. To the best of our knowledge and within the usual limits of testing practice, tests performed on these arresters demonstrate compliance with the relevant clauses of the referenced standard. M.G. Comber Manager, Engineering Date: 4/11/2007

EU1517-H-12.1 IEC TYPE TEST REPORT Power Frequency Voltage Versus Time TESTS PERFORMED: Power frequency voltage versus time tests were performed on prorated test sections prepared based on the results of the tests to verify heat dissipation behavior of test sample. Each section consisted of two resistors in series, and with U r of approximately 12kV. The resistors were selected to represent the lowest acceptable reference voltage level. The tests were conducted in accordance with Annex D of IEC 60099-4. Prior to the test, measurements were made of the reference voltage of the section to determine its rated voltage U r and continuous operating voltage U c. Additional measurements were made of power dissipation at U c, and an adjusted value U c was determined such that the power dissipation of the sample represented the maximum power dissipation of resistors that could be used in arrester assembly. The adjusted value Uc was used in the thermal recovery portion of the test. Tests were made for three different time durations of elevated voltage application. For each test, the section was placed in an oven and heated overnight to 60 ± 3 C. After removal from the oven, the section was subjected to two long duration current impulses, with time between impulses being between 50 and 60 seconds. The parameters of the transmission line used to generate these impulses conformed to the requirements for Line Discharge Class 4 in Table 5 of Clause 8.4.2 of IEC 60099-4. Within 100 milliseconds of the second long duration current impulse, an elevated power frequency voltage (above U r ) was applied for a measured period of time, following which the voltage was reduced to the adjusted value U c for 30 min. During the 30 min period at U c the power dissipation was monitored to verify thermal stability. Table 1 lists the parameters of the test section and the corresponding transmission line parameters used for the test. Table 1. Test section and transmission line parameters Parameter Reference Current (ma) I ref Reference Voltage (kv c ) V ref COV ( kv rms) U c Adjusted COV 9kVrms) Uc Rating (kv rms) U r Arrester Classification (ka) Line Discharge Class Virtual Duration of Peak (µs, 90-90%) - min Surge Impedance (Ω) Z g - max (0.8 U r ) Charging Voltage (kv) U L min (2.6 U r ) Value 17 17.55 9.68 9.93 12.10 20 4 2800 9.68 31.46-2 -

EU1517-H-12.1 RESULTS: A short circuit test was performed on the generator to confirm that generator impedance and duration of the current discharge met the requirements listed in Table 1. The oscillogram of Figure 1 shows Z g = 8,960 V / 936.89 A = 9.564 Ω Virtual Duration of Peak = 2885 µs Figure 1. Oscillogram of discharge current for generator short circuit set up test Tables 1 and 2, respectively, list measurements made during the application of elevated voltage and during the subsequent 30 min application of U c. Representative oscillograms made during this testing are shown in Figure 2 (beginning and end of 100 s application of elevated voltage) and Figure 3 (beginning and end of 30 min application of U c following 100 s application of elevated voltage). Figure 4 shows the three test points (elevated voltage s for 1s, 10 s and 100 s) superimposed on the characteristic of power frequency voltage vs. time for H4 series of arresters. - 3 -

EU1517-H-12.1 Figure 2. Oscillograms of voltage and current at the beginning and end of the 100 s application of elevated voltage - 4 -

EU1517-H-12.1 Figure 3. Oscillograms of voltage and current at the beginning and end of the 30 min application of U c following 100 s application of elevated voltage - 5 -

EU1517-H-12.1 Table 1. Measurements of voltage and current during application of elevated voltage 1 s elevated voltage 10 s elevated voltage 100 s elevated voltage Elapsed Elapsed Elapsed Applied voltage Current Applied voltage Current Time Time Time Applied voltage Current (s) (kv rms) (pu Ur) (ma peak) (s) (kv rms) (pu Ur) (ma peak) (s) (kv rms) (pu Ur) (ma peak) 0.0 14.02 1.16 3840 0.0 13.30 1.10 938 0 12.31 1.02 113 0.1 14.03 1.16 3780 1.0 13.31 1.10 1046 11 12.31 1.02 113 0.2 14.07 1.16 3790 2.0 13.30 1.10 1013 29 12.28 1.02 109 0.3 14.07 1.16 3850 3.0 13.29 1.10 1015 41 12.29 1.02 113 0.4 14.07 1.16 3730 4.0 13.30 1.10 1050 54 12.29 1.02 117 0.5 14.09 1.16 3830 5.0 13.30 1.10 1072 68 12.30 1.02 126 0.6 14.10 1.17 3810 6.0 13.28 1.10 1054 82 12.28 1.02 134 0.7 14.08 1.16 3850 7.0 13.30 1.10 1103 90 12.28 1.02 142 0.8 14.09 1.16 3970 8.0 13.28 1.10 1065 96 12.30 1.02 154 0.9 14.11 1.17 3810 9.0 13.29 1.10 1126 101 12.30 1.02 154 1.0 14.12 1.17 3940 10.0 13.29 1.10 1173 Table 2. Measurements of power dissipation and current made during 30 min at U c 1 s elevated voltage 10 s elevated voltage 100 s elevated voltage Elapsed Applied Power Elapsed Applied Power Elapsed Applied Power Current Current Time voltage dissipation ` Time voltage dissipation Time voltage dissipation Current (min) (kv rms) (W) (ma peak) (min) (kv rms) (W) (ma peak) (min) (kv rms) (W) (ma peak) 0 10.02 34.0 8.4 0 10.10 42.5 11.0 0 10.06 48.0 12.1 1 9.97 28.5 6.8 1 9.97 33.5 8.6 1 9.97 41.1 10.0 2 9.96 27.5 6.6 2 9.98 32.0 8.2 2 9.98 39.3 9.7 5 9.97 25.5 6.4 5 9.98 29.5 7.6 5 9.98 36.2 8.9 10 9.95 23.0 5.8 10 10.00 27.5 7.0 10 9.95 32.2 8.0 20 9.97 20.5 5.4 20 9.96 24.5 6.2 20 9.94 29.0 7.1 30 9.96 18.5 5.0 30 9.98 24.0 6.2 30 9.96 27.7 6.8 1.200 1.150 Per Unit of Ur 1.100 1.050 1.000 0.1 1 10 100 1000 Time - s Figure 4. Power frequency voltage vs. time characteristic for H4 series arresters, with test points for 1 s, 10 s and 100 s - 6 -