Hitachi P1 Closed Loop Hoist Basic Instruc on Manual

Similar documents
SJ100 Series Inverter Quick Reference Guide. Single-phase Input 200V Class Three-phase Input 200V Class Three-phase Input 400V Class

HITACHI. L100-M Series Inverter Quick Reference Guide. Hitachi Industrial Equipment Systems Co., Ltd. Single-phase Input 100V Class

INDEX. i 1. B Braking Resistor Dimensions: A 24 Braking Resistors: A 20 Braking Units: A 20. DURAPULSE AC Drive User Manual

GS1 Parameter Summary Detailed Parameter Listings...4 9

6.9 Jump frequency - Avoiding frequency resonance

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

CHAPTER MAINTENANCE AND TROUBLESHOOTING. In This Chapter... Maintenance and Inspection Troubleshooting...6 3

VFD - D700 Series Specifications. The latest low-cost variable speed control solution for centrifugal pumps.

S11 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification

Index 2. G Gain settings 4 31 Glossary of terms A 2 Grommets 2 13

BACnet- MS/TP COMMUNICATION V

Invertek Optidrive E3 Frequency Inverter (IP20, 3ph output) Easy Start Guide

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

The GS1 Digital Keypad LED Display Function Keys Displaying the Status of the GS1 AC Drive Programming the GS1 AC Drive...

HPVFP High Performance Full Function Vector Frequency Inverter

Multi-function, Compact Inverters. 3G3MV Series

Troubleshooting 12. This section explains the items to check when problems occur, and troubleshooting by the use of error displays or operation state.

CHAPTER 8 PARAMETER SUMMARY

Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW)

3. Be aware of the ambient temperature. Use the unit within the specified ambient temperature only.

[ 4 ] Using pulse train input (F01 = 12)

Manual Overview...1 2

NX series Constant and variable torque Variable Speed Drives for induction motors

Operating Instructions

13. Before making a service call Trip information and remedies

ADTECH Solar inverter

Before you operate the inverter, the parameters that you must first program are the basic parameters.

SJ300 Series Inverter Quick Reference Guide

MD310 Quick Start Manual. General-Purpose AC Drive

In the event of a failure, the inverter switches off and a fault code appears on the display.

OPC-E1-PG3 Specifications

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

NX Series Inverters. HVAC Pocket Programming Guide

INTERNATIONAL SERVICE BULLETIN - I #2-319 Liberty - Delta M+ VFD parameter list. A VFD parameter list is required when replacing a DELTA M+ VFD.

FUJI Inverter. Standard Specifications

E3 Adjustable Speed Drive Engineering Specification

CHAPTER KEYPAD OPERATION AND QUICKSTART. In This Chapter... The GS2 Digital Keypad GS2 Quickstart...3 6

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

ROLL TO ROLL FUNCTION MANUAL FR-A (0.4K)-04750(90K)-R2R FR-A (0.4K)-06830(280K)-R2R FR-A (315K)-12120(500K)-R2R

Inverter Drive /Vector Drive Motors & Controls

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

ADJUSTABLE SPEED DRIVES. AS1 Drive

NICE900 -Door Drive Setup Manual for Asynchronous / Synchronous Motor with Encoder Feedback (Document Release Dt ) Sr. No

Phoenix DX Clean Power (18 Pulse) AC Drive

Troubleshooting Alarm Displays Warning Displays

vacon nx all in one application manual ac drives Phone: Fax: Web: -

TOSVERT TM VF-nC3 Parameter List

user's manual nx frequency converters beam pump application asfiff13

Drives 101 Lesson 3. Parts of a Variable Frequency Drive (VFD)

Compact & Powerful Inverter STARVERT ig5a 0.4~1.5kW 1phase 200~230Volts 0.4~22kW 3Phase 200~230Volts 0.4~22kW 3Phase 380~480Volts

General Specifications FECA-TE /2010. Phone: Fax: Web:

Operation Instructions NORDAC SK 400E. Frequency Inverter. SK 400E B / SK 400E B (0.4kW / 0.7kW, 1~ 115V)

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

Configuring Drive Parameters

General-Purpose AC Servo. MELSERVO-JE Servo amplifier INSTRUCTION MANUAL (TROUBLE SHOOTING)

Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards

Users Manual SM5 INVERTER. Subject to changes without notice December, 2001

AF91 Adjustable Frequency Drives Series B

Copyright 2014 YASKAWA ELECTRIC CORPORATION All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or

Operating Instructions VLT Extended Relay Card MCB 113

VS1SM Single Phase AC Drive

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB. For Immediate Delivery call KMParts.com at (866)

Installation Servo Drive Dimensions

VFD 101 Lesson 1. Functions of an Variable Frequency Drive (VFD)

Warning!! 2. The drive contains high voltage that can cause electric shock resulting in personal injury or loss of life.

G320X MANUAL DC BRUSH SERVO MOTOR DRIVE

MA7200 PLUS INVERTER SERIES PID Quick Start Manual For Fan and Pump Applications

Chapter 8 Troubleshooting

A700 VFD with SSCNET III eth1000_large.jpg

vacon nxp arfiff30 user manual generator application ac drives

NXL HVAC APPLICATION MANUAL Programming manual for NXL HVAC drives

THYFREC-VT110S 200V 1PH System 0.4 to 2.2kW 400V 3PH System 0.75 to 2.2kW QUICK START GUIDE

VFS9 Parameter List for Version110 or later

SRVODRV REV7 INSTALLATION NOTES

Design Specifications Operator Keypad Environmental and Operating Conditions

ECET 211 Electric Machines & Controls Lecture 9-1 Adjustable-Speed Drives and PLC Installations (1 of 2)

MTY (81)

MASTER/SLAVE TENSION CONTROL

Variable Frequency Drive / Inverter (0.4 ~ 280kW)

SV9000 SVReady USER MANUAL CONTENTS OPEN SV9000 USER MANUAL. SV9000 Page 0-1

ACH550 HVAC Drive Submittal

AV-300i Specifications. GE Industrial Systems. Product Specifications. A New Concept in Automation. AV-300i

40 Amp Digital Bidirectional PWM Motor Controller with Regenerative Braking BIDIR-340-DR

Troubleshooting and Maintenance

HITACHI INVERTER SJ700-2 SERIES SERVICE MANUAL. After reading this manual, keep it handy for future reference. NTS204X

SJ700-2 SERIES HITACHI INVERTER SERVICE MANUAL. Phone: Fax: Web: -

Lock Cracker S. Lust, E. Skjel, R. LeBlanc, C. Kim

MTY (81)

VLT MICRO Series Adjustable Frequency Drive Instruction Manual

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

VS-616G5 Series (Revision F) Programming Manual. Constant Torque Inverter with Adaptive Vector Control (AVC )

BOSTON GEAR CONTROLLERS. ACE 20 Series 1/8 through 10 HP Adjustable Frequency AC Motor Controllers. MTY (81)

KBDA SERIES STANDARD FEATURES DESCRIPTION PERFORMANCE FEATURES PROTECTION FEATURES

Speed Feedback and Current Control in PWM DC Motor Drives

CHAPTER 5 DESCRIPTION OF PARAMETER SETTINGS

Transcription:

Hitachi P1 Closed Loop Hoist Basic Instruc on Manual DH Firmware V.18 DETROIT HOIST AND CRANE LLC, CO. 6650 STERLING DRIVE NORTH STERLING HEIGHTS MICHIGAN 48312

Introduction This manual only applies to Hitachi P1 VFD s programmed with firmware version 18. Please verify the version by checking parameter db-02 Each Detroit Hoist comes equipped with Hitachi variable frequency drives to control each supplied motion and in most cases will not require any field adjustment. If adjustments or different configurations are required, use this manual to make those changes or contact Detroit Hoist technical department 1 (800) 521-9126. Pushbutton VFD Operation Explanation. P2 Wiring in Pushbutton Controls.. P3 Configuring Speed Control Methods... P4 Configuring Speeds Parameters.. P5 125% Load Testing. P6 Setting Hoist Over-Weight. P7 Setting Upper & Lower Operational Encoder Limits * Closed Loop P1 Only *.....P8 Motor Overload Protection..P9 Encoder Input & Parameters* Closed Loop P1 Only *.. P9 Acceleration and Deceleration Parameters. P10 Load Float * Closed Loop Only *... P11 Motor Brake Wait Delay * Closed Loop Only *..... P11 Start of Run Motor Check * Closed Loop Only *.... P12 End of Run Brake Check * Closed Loop Only *... P13 Auto Speed.... P14 VFD Monitor Parameters... P15 Troubleshooting Common VFD Error Codes P16-P17 Clearing Trip Data. P18 Temporarily Switching Closed Loop Vector To Sensorless Vector....P18 Navigating using the front display P19-20 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 1

Pushbutton VFD Operation Explanation Pushbutton Action VFD Action 2-Speed 2-Speed Inf.Var 3-Speed 3-Speed Inf.Var 0-10V POT Press to 1st step Accelerates to 1st speed frequency. Accelerates to 1st speed frequency. Accelerates to 1st speed frequency. Accelerates to 1st speed frequency. Accelerates to 1st speed frequency or frequency determined by 0-10V reference Press to 2nd step Accelerates to 2nd speed frequency. Accelerates to 2nd speed frequency. Accelerates to 2nd speed frequency. Maintains the speed frequency before the button was pushed to the 2nd step. N/A Press to 3rd step N/A N/A Accelerates to 3rd speed frequency. Accelerates to 3rd speed frequency. N/A Release to 2nd step N/A N/A Decelerates 2nd speed frequency. Maintains speed before the button was released to the 2nd step. N/A Release to 1st step Decelerates to 1st speed frequency. Maintains speed frequency before the button was released to the 1st Step. Decelerates to 1st speed frequency. Decelerates to 1st speed frequency. N/A Complete release from any step Decelerates to 0Hz frequency and floats then sets motor brake Decelerates to 0Hz frequency and floats then sets motor brake Decelerates to 0Hz frequency and floats then sets motor brake Decelerates to 0Hz frequency and floats then sets motor brake Decelerates to 0Hz frequency and floats then sets motor brake 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 2

Wiring in Pushbutton Controls Please use the chart as a reference for connecting the pushbutton wires to the corresponding control terminals. Please refer to supplied electrical schematic for proper installation. Terminals may vary based on model. 2-Step & 3-Step Control Wiring Pushbutton Wires Hoist Up Direction Hoist Down Direction Hoist 2 nd Speed / 2 nd Step Hoist 3 rd Speed / 3 rd Step Control Terminals On Control Panel HU HD H2 110vac to input 6 on interface card 24vdc to input 6 on VFD if no interface card Micro Speed Break HIC Input 4 (hoist interface card) or input 4 on hoist VFD. Analog 0-10V Potentiometer Controller Hoist Up Direction Hoist Down Direction Hoist Analog 10V Reference Hoist Analog Ground Reference Hoist Analog Input Reference Cb-05 Cb-06 Control Terminals On Control Panel HU HD Terminal H on Hoist VFD Terminal L bottom row on Hoist VFD Terminal Ai1 on Hoist VFD Start Rate Of Terminal Ai1 End Rate Of Terminal Ai1 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 3

Configuring Speed Control Methods All Detroit Hoist controls come pre-configured for 2-Step speed control unless otherwise specified. Detroit Hoist controls are designed to be easily configured for 2-Step, 2-Step Infinitely Variable, 3- Step, 3-Step Infinitely Variable, and an External Potentiometer speed control methods. The following will guide you in changing the speed control methods. Speed Control Methods 2-Step Changes To Make Default From Factory (1) Turn switch located on the side of the enclosure from INF VAR to TWO SPEED (2) If no switch is available Set VFD Parameter UE-18 = 00 (3) Set VFD Parameter CA-06 = NO / 000 (4) Set VFD Parameter UE-12 = 2 nd Speed Frequency (see note) 2-Step Infinitely Variable (1) Turn switch located on the side of the enclosure from TWO SPEED to INF VAR. (2) If no switch is available Set VFD Parameter UE-18 = 01 (1) Change VFD Parameter CA-06 = 91 3-Step (2) Set VFD Parameter UE-12 = 2 nd Speed Frequency (see note) (3) Set VFD Parameter UE-13 = 3 rd Speed Frequency (see note) (1) Turn switch located on the side of the enclosure from TWO SPEED to INF VAR 3-Step Infinitely Variable (2) If no switch is available Set VFD Parameter UE-18 = 01 (3) Set VFD Parameter CA-06 = 91 (4) Set VFD Parameter UE-13 = 3 rd Speed Frequency (see note) Analog 0-10V (1) Change VFD Parameter UE-16 = 01 0V = Low Speed VFD Parameter UE-11 (see note) 10V = High Speed VFD Parameter UE-12 (see note) Note Speed frequency parameters UE-10 thru UE-14 are represented as a whole number. See example below to understand how to set the speed parameters. Example: 10.00 Hz / UE-10 = 1000 Example: 15.00 Hz / UE-11 = 1500 Example: 39.99 Hz / UE-12 = 3999 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 4

Configuring Speed Parameters Speeds VFD Parameters Micro 1 st Speed UE-10 Micro 2 nd Speed UE-15 1 st Step / 1 st Speed UE-11 2 nd Step / 2 nd Speed UE-12 3 rd Step / 3 Speed UE-13 Auto Speed UE-14 Micro 1 st Speed This is the 1 st speed / low speed frequency setting. This will be the 1 st speed frequency as long as input 4 is off. Note To use micro speed use a relay or switch to break the input 4 connection to the HIC (Hoist Interface Card) or the input 4 wire on the VFD. Micro 2 nd Speed This is the 2 nd speed / high speed frequency setting. This will be the 2 nd speed frequency as long as input 4 is off. 1 st Step / 1 st Speed This is the 1 st speed / low speed frequency setting. This will be the 1 st speed frequency as long as input 4 is on. 2 nd Step / 2 nd Speed This is the 2 nd speed / 2 nd step frequency setting. This is also the high speed setting for 0-10V external POT 3 rd Step / 3 Speed This is the 3 rd speed / 3 rd step frequency setting. Auto Speed This is the Auto speed frequency setting. This is used in hoisting only. This is the speed in which the hoist VFD will allow when lifting a light load or empty hook. (Do not exceed 90HZ) Note Speed frequency parameters UE-10 thru UE-14 are represented as a whole number. See example below to understand how to set the speed parameters. Example: 10.00 Hz / UE-10 = 1000 Example: 15.00 Hz / UE-11 = 1500 Example: 39.99 Hz / UE-12 = 3999 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 5

125% Load Testing Each hoist is live load tested at 125% at the Detroit Hoist factory prior to shipment, to pass inspection. If additional field testing is required, please use the provided instructions to do so. (Step 1) Locate over-weight bypass switch and open it (see images below for BPS switch example). (Step 2) Proceed to lift 125% of rated capacity. Once the 125% load is off the ground test all motions to ensure proper movement. (Step 3) If all motions had proper movement then go to step 4. If any of the motions did not move properly, please use the Manual Torque Boost parameters on the next page to increase the torque to attempt to move the load. If this is a closed loop application please contact Detroit Hoist for further assistance. If after adjusting the Manual Torque Boost parameters the load will still not move please contact Detroit Hoist for further assistance. (Step 4) Remove the 125% load and close the over-weight bypass switch. 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 6

Setting Hoist Over-weight (Step 1) (Step 2) (Step 3) (Step 4) (Step 5) (Step 6) (Step 7) (Step 8) (Step 9) - On the Hoist VFD home screen displays the output current to the motor. - Locate the over-weight bypass switch located on the control panel (BPS) and open it. This will ignore any over-weight signal given by the hoist VFD to the over-weight circuit. - Lift 100% of the rated capacity in 1st speed and wait for the output current to become stable, note that value and add 2%. - Lift 100% of the rated load in 2nd speed and wait for the output current to become stable, note that value and add 2%. - On the Hoist VFD navigate to parameter CE106 which is the over-weight current setting for low speed and set the value to the value determined in step 3. - On the Hoist VFD navigate to parameter CE107 which is the over-weight current setting for high speed and set the value to the value determined in step 4. - Verify lifting 100% of the rated capacity in 1st and 2nd speed does not create an overweight condition. - If the over-weight trips you will need to determine if the trip is in low or high speed and increment the value in the corresponding over-weight setting parameters. If the overweight trips due to inrush current increment parameter CC-20 to delay the over-weight output signal. - After the over-weight setting have been successfully set close the over-weight bypass switch located on the control panel (BPS). Over-Weight VFD Parameters Low Speed Over-Weight High Speed Over-Weight CE106 CE107 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 7

Setting Upper & Lower Operational Encoder Limits The Hitachi P1 can use the encoder pulses for electronic upper and lower hook block limits. Detroit Hoist has made this a simple process by using knife disconnect switches. To set the upper and lower limits follow the steps below in order. Note: The process cannot be reversed or limits will not work properly. Note: To disable the use of the electronic limits simply change parameter UE-33 = 0 and be sure to wire in a limit circuit. For assistance please contact Detroit Hoist for an updated electrical drawing. 1.) Simply open the PP knife disconnect to enter program mode. (Program Position Switch). 2.) Run hook block to desired upper limit. 3.) Simply open and then close the PR knife disconnect to clear the position counter memory. (Position Reset Switch) This is used as a momentary switch. (DO NOT LEAVE OPEN) 4.) Run hook block to desired lower limit. 5.) Simply close the PP knife disconnect once the motor brake has set to store the position data. Use image below for reference of PP & PR switch. 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 8

Motor Overload Protection The Hitachi VFD s have built in solid state motor overload protection which reacts up to 150% of max output current of the VFD. Please ensure that this parameter is set correctly to the application provided by the VFD. This is not the over-weight protection parameter. Hoisting applications bc110 = 125% hoist Motor FLA Encoder Inputs & Parameters The Hitachi P1 VFD s have a built in high speed encoder input located under the front cover. The supply voltage for the encoder is 24vdc. Please ensure that your encoder is rated for 24vdc. Be sure to terminate the encoder shield with 0vdc to act as a noise drain. Terminal A = Encoder Signal A Terminal B = Encoder Signal B Terminal COM = Encoder 24vdc Terminal CM1 = Encoder 0vdc & Shield Speeds Encoder PPR Encoder Position Selection VFD Parameters CA-81 (1024 Normal) CA-82 00 = Phase A Lead 01 = Phase B Lead 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 9

Acceleration & Deceleration Parameters Standard Accel & Decel Functions Acceleration Time (1) Deceleration Time (1) VFD Parameter AC120 AC122 The Hitachi VFD s features two-stage acceleration and deceleration ramps. This gives flexibility in the profile shape while running in the infinite variable method. This feature allows you to have more control in the accel and decel while transitioning your frequency. You can specify the frequency transition point, the point at which the standard acceleration (AC120) or deceleration (AC122) changes to the second acceleration (AC124) or deceleration (AC126). Use the table below to configure the 2-Stage Accel & Decel feature. 2-Stage Accel & Decel Function VFD Parameter Acceleration Time (2) Deceleration Time (2) Select method to switch to accel / decel (2) profile Accel (1) to Accel (2) frequency transition Decel (1) to Decel (2) frequency transition AC124 AC126 AC115 = 00 will require the use of CA-06 = 031 AC115 = 01 will use transition frequency AC115 = 02 will change when direction is reversed AC115 AC116 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 10

Load Float * Closed Loop Hoist Only * Load float makes use of the encoder feedback to hold the load at zero speed without setting the motor brake. This allows for extremely precise movement of a load as well as eliminating motor brake wear by always setting the motor brake at zero speed. Once the motor brake has been released and directional commands have been completely released the VFD will decelerate to zero speed and float the load for the set amount time in parameter UE-29. If a directional command is given before the load float timer has expired the load float timer will reset once the directional commands are released again. Once the timer has expired the VFD will close the motor brake and start the End of Run Motor Brake Check. The load float timer is adjustable please use the example below to set the desired float time. Example: 2.00 seconds / UE-29 = 200 Motor Brake Wait Delay * Closed Loop Hoist Only * In some cases a motor brake may react faster or slower when given the release or set command. To ensure the motor doesn t not run through the brake or prematurely slip during the End of Run Brake check the Motor Brake Delay parameter UE-28 has been introduced. This delay will allow for the motor brake to fully release before accepting a frequency command as well as allowing the motor brake to fully set before starting the End of Run Motor Brake Check. Please use the example below to adjust the motor brake delay time. Example: 0.3 seconds / UE-28 = 30 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 11

Start of Run Motor Check * Closed Loop Hoist Only * The Start of Run Motor Check is designed to check the motor torque at the beginning of each lift. On a power up cycle the VFD will test the motor at the default torque test value. Once the first check has successfully completed the VFD will check the motor at the torque required for the suspended load. If no load is suspended the VFD will check the motor torque at the minimum torque check value. During the Start of Run Motor Check the VFD will check to make sure the motor has produced sufficient torque before releasing the motor brake. If the motor fails to generate sufficient torque during the Start of Run Motor Check the VFD will trip with an E51 error. Please contact Detroit Hoist technical department 1 (800) 521-9126. Note Once the Start of Run Motor Check is complete the motor brake will release and if there is a light load or no load suspended the hoist may rotate slightly in the up direction due to a buildup of torque, this is normal. Function VFD Parameter Enable Feature UE-30 ( 0 = disabled / 1 = enabled ) Default Torque Check Value Motor Torque Check Time UE-31 UE-32 Example: 1.00 seconds / UE-32 = 100 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 12

End of Run Motor Brake Check * Closed Loop Hoist Only * Brake Torque Proving The End of Run Motor Check will check for motor brake slip at the end of each lift cycle. Once the load float timer has expired the VFD will lockout the directional commands. The VFD will then set the motor brake and wait until the Motor Brake Delay timer has expired. Once the Motor Brake Delay timer has expired the VFD will start controllably reducing the motor torque to 0%. While the VFD is controllably reducing the motor torque the VFD is checking for movement from the motor encoder. If movement is detected during the End of Run Motor Brake Check the VFD will restore full torque to the motor and will turn on the fault condition signal from output relay 16A. The forward direction and high speed commands will be locked out, and only the reverse direction will be enabled. The VFD will wait until a reverse command is given and then will proceed to lower the load in low speed while the reverse command is on. If the reverse command is removed the VFD will start the End of Run Motor Brake Check again. Once the load is safely on the ground and the End of Run Motor Brake Check passes then the VFD will restore all directional and speed commands and turn off the fault condition signal output relay 16A. Function VFD Parameter Enable Feature UE-34 ( 0 = disabled / 1 = enabled ) Motor Brake Slip Max Allowable Pulse Count UE-35 ( Please Contact Detroit Hoist ) 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 13

Auto Speed * Closed Loop Hoist * The Auto Speed feature will automatically increase the high speed frequency to the frequency value of UE-14 when the forward driving torque % at the high speed frequency is less than the Auto Speed output torque % threshold set in UE-21. The output current must not exceed the motor FLA and or the VFD FLA while in Auto Speed and the output torque must not exceed 150%. (Warning do not set the Auto Speed frequency above 90.0 Hz) Normal setting for UE-21 is 40 Use the table below to configure the Auto Speed feature. Function Enable Feature / Auto Speed Output Torque Threshold Auto Speed Frequency VFD Parameter UE-21 ( 0 = disabled ) UE-21 > 0 = The Auto Speed torque threshold % UE-14 Note UE-14 & UE-21 are represented as a whole number, see example below to understand how to set the parameters. Example1: 40% Torque / UE-21 = 40 (Do not set this value above 50) Example2: 90.00 Hz / UE-14 = 9000 (Do not set this value above 9000) 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 14

VFD Monitor Parameters This is a listing of the most common monitor parameters. To see all monitor parameters please use the Hitachi reference manual provided with the VFD. Monitor Parameter Monitor Description da-01 Output frequency da-02 Output current da-03 Rotation direction da-51 Digital input terminal status da-54 Digital output terminal status da-08 Actual output frequency from Encoder da-17 Output torque da-18 Output voltage da-20 Current Position da-30 Input power (kw) da-32 Accumulation Input Power (kwh) da-34 Output Power (kw) da-36 Accumulation Output Power (kwh) da-40 DC Buss Voltage da-41 Dynamic braking usage % db-02 Firmware Version db-14 Calculated Speed Deviation Monitor db-16 End Of Run Brake Slip Pulse Count Monitor 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 15

Troubleshooting Common VFD Error Codes This is a listing of the most common error codes. For a complete listing of all error codes please refer to the Hitachi reference manual provided with the VFD. Error Code Error Name Causes E001 Overcurrent During Constant Speed The VFD has detected excessive current so the inverter output is turned off, caused by the motor being constrained or suddenly accelerated or decelerated. E005 Overload Protection The VFD has detected a motor overload on the internal electronic thermal protection circuit (bc110) which is set for 125% of the FLA on the motor. E006 Braking Resistor Overload Protection The allowable dynamic braking usage ratio ba-60 has been reached. Check load brake for slip, or decrease high speed. E007 Over voltage When the DC bus voltage exceeds a threshold, due to regenerative energy from the motor. Check to see if DB resistor is connected and is not shorted open. E009 Under Voltage If the input voltage drops, the VFD cannot function normally. It will trip when the DC bus voltage drops below a specified voltage. E014 Ground Fault The VFD detected a ground fault between the motor and VFD output circuit on power up. E016 Instantaneous power failure If an instantaneous power failure lasts 15 ms or more, the inverter will shut off its output. E030 IGBT Error The VFD detects an instantaneous overcurrent, main circuit temperature is abnormal or the main circuit element drive power drops, it will trip. Check motor and VFD for shorts to ground. E038 Low Speed Overload Protection If overload occurs during the motor operation at a very low speed at 0.2 Hz or less, the electronic thermal protection circuit in the inverter will detect the overload and shut off the inverter output 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 16

Troubleshooting Common VFD Error Codes Cont.1 Error Code Error Name Causes E043 Program Error (Consult Detroit Hoist) E045 Program Error (Consult Detroit Hoist) E051 E052 / E105 Start of Run Motor Torque Proving Failed Speed Deviation Error During the Start of Run Motor Check the VFD has detected the motor did not generate sufficient torque to current. Check motor or contact Detroit Hoist. The VFD has detected a speed deviation error. This is caused when the commanded frequency does not match the actual frequency. Check to see if encoder has come loose from motor shaft. Check to see if motor is locked up. Check to see if motor brake is releasing. Check operation of encoder. E053 Over-Torque Over-Torque detected. Check to make sure motor brake is releasing and encoder is phased and operating correctly. Also check to make sure motor phasing is correct. E060 (E070) Encoder Line Break The VFD has detected a line break from the encoder or disconnection of encoder line or encoder failure. Check electrical connection from encoder to SJ-FB encoder card. E107 Over-speed Detect when the motor rotation speed exceeds the maximum frequency times the over-speed detection error level P026 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 17

Clearing Trip Data Parameter Value Ub-01 01 Ub-05 01 * Do Not Set UB-01 to anything other than 01 or load may fall and VFD may need to be sent to Detroit Hoist * Temporarily Switching Closed Loop Vector to Sensorless Vector Switching a closed loop vector to sensorless vector should only be done for temporary purposes if the motor encoder has failed. All safety features will be disabled when operating in sensorless vector all motor and motor brake safety checks will be disabled. To switch to sensorless vector change parameter AA121 = 08 and cycle power to the VFD. To switch back to closed loop vector change parameter AA121 = 10 and cycle power to the VFD. Detroit Hoist does not endorse the decision to switch from closed loop vector to sensorless vector. 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 18

Operator Keypad Screen Types of main monitor screen RUN FW Three-line monitor screen "Multi-monitor" M H01 Output Frequency 29.51 Hz Output current 11.9 A Input ter m inal monitor LLLLLLLLLLL RUN FW Parameter setting screen "Concurrent monitor" Output Frequency FA-01 M1 29.51 Hz H03 46.49 Hz [0.00-60.00] RUN FW Monitor screen with large characters "Big monitor" da-01 Output Fr equency M 1 H04 29.51 Hz Menu ofw 46.49Hz Optional device Menu ofw 46.49Hz Optional device Menu o FW 46.49Hz Optional device RUN FW Trip history Total count Trip history screen "Total count monitor" M1 20 times H06 Retry history screen "Why retry onitor" RUN FW Retry history M1 H0 9 1. E007 16/07/15 10:10 2. E001 16/07/15 08:55 3. E001 16/07/15 08:52 4. E009 16/07/12 10:10 5. E012 16/07/10 22:52 1. r007 2. r009 3. r009 4. r009 5. r001 16/07/14 16/07/14 16/07/14 16/07/14 16/07/12 20 :10 18 :54 08 :32 06 :18 2 :49 Menu ofw 46.49Hz Optional device Menu ofw 46.49Hz Option a al device Menu screen Home screen option R UN FW Menu e 01 Scroll mode 02 R/W function 03 System settings M1 M01 RUN FW Home screen optio n M1 01 Controller name 02 Data displayed at the bottom center o01 Home ofw 46.49Hz ---- Home ofw 46.49Hz ----! You can switch between the main screen and menu screen using the F1(1) key.! You can navigate to the home screen option from the main screen by using the F2(2) key. To return to the home screen, press F1(1) key. 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 19

Scroll Mode TOP M H01 S Output Freq ency u 29.51 Hz Output current 11.9 A I put terminal monitor n LLLLLLLLLLL STOP Menu 01 Scroll mode 02 R/W function 03 System settings M1 M01 Menu ofw 46.49Hz Optional device Menu of 0.00Hz Option l device W Scroll menu - Parameter selection screen Set-up procedure STOP Scroll menu M1 All parameters d: Monitor F: Command monitor/setting A: Operation function b: Protective function L01 Action 3.1 Choose the croll mode on the system settings screen (M01) and press the SEL(O) key to show the scroll menu (L01). To 3.2. Back ofw 0.00Hz ---- STOP Scroll menu M1 F: Command R monitor/setting A: Operation function b: Protective function C: Terminal, S485 H: Motor control L01 3.2 Choose a group you want to browse using the up and down ) keys, and then press the SEL(O) key to move to the parameter list dis lay. For example, select "H: Motor control". Example: In the example shown below, the Hb group, which is a basic parameter of induction motor, is checked, and a parameter is changed. To 3.3. Back ofw 0.00Hz ---- 06/15/2018 Hitachi P1 Closed Loop Hoist Basic Instruc on Manual Firmware V.18 20