ITP16. Temperature indicator. User guide

Similar documents
ITP14. Universal process indicator. User guide

MU110-16R(K) Digital output module 16 channel. User guide

MU110-8R(K) Digital output module 8 channel. User guide

MV110-8A. Analog input module 8 channel. User guide

MV110-8AS. Analog input module 8 channel. User guide

MK110-8D.4R. Digital I/O-Module 12 channel 8 DI, 4 DO. User guide

TRM channel on-off controller. User guide

FC Series Signal Conditioners

OPTITEMP TT 20 Technical Datasheet

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

Power supply CP-E 24/2.5

3B SCIENTIFIC PHYSICS

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Transducer transmitter BILT 4 II 2(1) G. Technical Manual

Temperature Input Module for Zone 1 Series 9482/32

itemp PA TMT184 Technical information

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

CX105 Conductivity/Resistivity Transmitter

B850 Boiler House Energy Monitor

0 2 1 â Ó. itemp HART TMT182. Technical Information

OPERATING INSTRUCTIONS

Power supply CP-E 24/20.0

Temperature transmitter itemp PCP DIN rail TMT 121

ProfiScale MULTI Multimeter

OPTITEMP TT 10 C/R Technical Datasheet

Power supply CP-E 24/2.5

High-quality digital indicator for panel mounting Model DI35-M, with multi-function input Model DI35-D, with two inputs for standard signals

Temperature Transmitters - DIN Rail Mounted

Signal converter for electromagnetic flowmeters

Instruction Manual. Digital Panel Meter Model 3153B

itemp HART DIN rail TMT112

INSTRUCTION MANUAL FOR PROGRAMMABLE CONTROLLER PCD-33A

AC/DC Clamp Meter. Owner's Manual. Model No Safety Operation Maintenance Español

RSMFX-2R MULTIFUNCTIONAL

Documentation. Content. Measurement and Control. Type: ELT-GP1. 1. Installation instructions 2. Data sheets 3. Declarations of conformity

QUINT-PS AC/24DC/40

Power supply CP-E 24/0.75

SmartBlock I/O Module - HE579DAC107/HE579DAC207 8/4 Channel Current and Voltage Output 0-5V / 0-10V / 4-20mA / 0-20mA - CsCAN

FC-33, DC SELECTABLE SIGNAL CONDITIONER

Rosemount 248 Wireless Temperature Transmitter

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES

P5201 Universal Programmable Transmitters with Galvanic Isolation

B850 Boiler House Energy Monitor

Additel 875 Series Dry Well Calibrators

0 2 1 â Ó. itemp HART TMT182. Technical Information

MINI MCR-SL-UI-I-LP-NC

Power supply CP-T 48/5.0 Primary switch mode power supply

Universal Alarm Indicator

CONTA-ELECTRONICS. Converter Units

Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Power supply CP-T 24/10.0 Primary switch mode power supply

Temperature Transmitters - Head Mounted

Power supply CP-T 24/40.0 Primary switch mode power supply

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

Models UT350/UT320 Digital Indicating Controllers

+GF+ SIGNET Temperature Transmitter Instructions

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

Electronic Thermostat TE-1 Version according to EN

Operating manual GTL 241 GTL 251. Temperature probe. Please keep the manual for future use.

Models UT550/UT520 Digital Indicating Controllers User s Manual for Loop Control for Backup

Operating Manual MU2000K

Digital indicator for panel mounting With multi-function input Model DI25

Level Switch NRS 2-50 NRS Original Installation Instructions English

PROCESS & TEMPERATURE CONTROLLERS

AI 043 S-DIAS Analog Input Module

Power supply CP-D 24/1.3

MINI-PS AC/24DC/1.3

Paperless Recorder PR20

Power supply CP-T 48/20.0 Primary switch mode power supply

TRANSDUCER of TEMPERATURE and STANDARD SIGNALS P20 type

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

Temperature Measurement Transmitters for mounting in sensor head

Power supply CP-T 24/20.0 Primary switch mode power supply

PHOENIX CONTACT - 09/2009

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

MD 200A High voltage differential probe

Model UP350 Program Controller

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

5 years! Modular Housings. VariTrans P Warranty

ATS22C21Q soft starter-ats22-control 220V-power 230V(55kW)/ V(110kW)

Out 1 sin / cos 1Vpp. sin / cos 1Vpp. Out 3. sin / cos 1Vpp. Out 4 sin / cos 1Vpp. Interface type SV211 SinCos signal splitter with 4 SinCos outputs

Temperature Measurement Transmitters for mounting in sensor head

Electronic Circuit Protector ESX10-T

Operator Manual. Transmitter Model RT - R and RT - RH. Programmable transmitter in 2 wire - technique

Safety light curtain to safeguard the hinge edge IMPORTANT NOTE

USER MANUAL ENGLISH 1450 COIN COUNTER & SORTER

Process/Mini. English IMPORTANT NOTE. Installation and Operation Manual. General Purpose Light Curtain with 30 mm resolution

USER'S MANUAL DMR-4350

TC 34 MICROPROCESSOR-BASED DIGITAL ELECTRONIC PULSE COUNTER. OPERATING INSTRUCTIONS Vr. 02 (ENG) - cod.: ISTR-MTC34ENG02

USER'S MANUAL DMR-4300

User Manual Laser distance sensor. series OWLE. Welotec GmbH Zum Hagenbach Laer Manual_OWLE _EN 1/20

SUNNY BEAM REPEATER Transmission Range Increase for Sunny Beam

Isolators A3/1.

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

Models UT550/UT520 Digital Indicating Controllers User s Manual for Single-loop Control

User s Manual Current Probe. IM E 2nd Edition IM E

U S E R S M A N U A L

NI REM Remote I/O Overview DATASHEET. Temperature Input Module for Remote I/O

Transcription:

ITP16 Temperature indicator User guide ITP16_2018.05_0280_EN All rights reserved Subject to technical changes and misprints akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0) 511 16 59 672-0 www.akytec.de

Contents 1 Overview... 2 2 Specifications... 2 2.1 Galvanic isolation... 3 2.2 Environmental conditions... 3 3 Intended use... 4 4 Functions... 4 5 Installation... 4 5.1 Wiring... 4 5.1.1 Input... 5 5.1.2 Output... 6 6 Operation... 6 6.1 Control... 6 6.2 Alarm... 7 6.3 Filter... 7 6.4 Square root function... 8 6.5 Error... 8 7 Programming... 8 8 Maintenance... 10 9 Transportation and storage... 11 10 Scope of delivery... 11 Appendix A. Dimensions... 11 akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0) 511 16 59 672-0 www.akytec.de 1

1 Overview ITP16 is a universally applicable process indicator and can be used with various input signals: RTD, TC, linear voltage signal. The device requires 24V DC auxiliary voltage. It is designed for control and monitoring of industrial processes. 2 Specifications ITP14 can be ordered in two versions. They differ in the display color. Ordering key: Table 2.1 Technical data Power supply 24 (10 30) V DC Power consumption, max. 1 W Input 1 Input signal See Table 2.2 Sampling time, max. 2 s Accuracy ± 0.25% FS Temperature influence 0.2% / 10 C Input resistance 0-1 V, -50 +50mV 250 kohm Output 1 Type NPN transistor Loading capacity 200 ma, 42 V DC Enclosure for panel mounting Character height 14 mm Dimensions 48 x 26 x 65 mm Weight approx. 30 g Table 2.2 Input signal Display Measurement Signal type range, C RTD according to IEC 60751:2008 Temperature coefficient, C -1 P50 Pt50-200 +850 0.00385 P100 Pt100-200 +850 0.00385 P500 Pt500-200 +850 0.00385 P1E3 Pt1000-200 +850 0.00385 RTD according to GOST 6651 c50 Cu50-50 +200 0.00426 c.50 50M -180 +200 0.00428 P.50 50P -200 +850 0.00391 c100 Cu100-50 +200 0.00426 c.100 100M -180 +200 0.00428 P.100 100P -200 +850 0.00391 N100 Ni100-60 +180 0.00617 c500 Cu500-50 +200 0.00426 c.500 500M -180 +200 0.00428 P.500 500P -200 +850 0.00391 n500 Ni500-60 +180 0.00617 c1e3 Cu1000-50 +200 0.00426 akytec GmbH Vahrenwalder Str. 269 A 30179 Hannover Germany Tel.: +49 (0) 511 16 59 672-0 www.akytec.de 2

Display Signal type Measurement range, C Temperature coefficient, C -1 c.1e3 1000M -180 +200 0.00428 P.1E3 1000P -200 +850 0.00391 n1e3 Ni1000-60 +180 0.00617 TC according to IEC 60584-1:2013 tp.ka K 200 +1300 tp.j J 200 +1200 tp.n N 200 +1300 tp.t T 250 +400 tp.s S 50 +1750 tp.r R 50 +1750 tp.b B +200 +1800 tp.a1 A 0 +2500 TC according to GOST 8.585 tp.l L -200 +800 tp.a2 A-2 0 +1800 tp.a3 A-3 0 +1800 TC according to DIN 43710 tp.tl L -200 +900 - Linear signals 50.50-50 50 mv 0 100 % 0-1 0-1 V 0 100 % Reserved PK15 PK20 PC20 2.1 Galvanic isolation not used - - - - - The ITP16 has three potential groups: Power supply 24 V DC Analog input Digital output Galvanic isolation from each group to enclosure Galvanic isolation between groups 2.2 Environmental conditions 500 V 500 V The device is designed for natural convection cooling. It should be taken into account when choosing the installation site. The following environment conditions must be observed: clean, dry and controlled environment, low dust level closed non-hazardous areas, free of corrosive or flammable gases Table 2.3 Conditions Permissible range Ambient temperature -40 +60 C Storage temperature -25 +55 C IP Code front IP65, rear IP20 Protection class III Relative humidity up to 80% (at +35 C, non-condensing) 3

3 Intended use The device may only be used in the manner described in this user guide, properly installed and in accordance with the specification. Damages caused by disregarding the instructions of this manual are without liability. Non-observance of the safety guidelines may result in damage to the device and injury to personal. Improper use Any other use is considered improper. Especially to note: The ITP16 may not be used for medical devices that sustain, monitor or otherwise affect human life or health. The device may not be used if the environmental conditions (temperature, humidity etc.) are not within the limits indicated in the specification. The device may not be used in potentially explosive environment or in an atmosphere with chemically active substances. 4 Functions A 4-digit LED display with 14 mm character height is located on the front of the device to display the process value or error messages in opera-tion (see 6) and programming parameters in programming mode (see 7). The function buttons are positioned on the rear part of the device. Main functions: Analog input signals according to Table 2.2 Measuring and displaying of a process value Linear voltage signal scaling Adjustable decimal point position Display range -999 9999 Square root function (for special transmitters) Digital filter Alarm function Error indication when the input signal is out of range Error indication when wire break or short circuit 5 Installation CAUTION CAUTION Improper installation can cause serious or minor injuries and damage the device. Installation must be performed only by fully qualified personnel. The device is designed for panel mounting in a borehole of Ø22.5 mm (see Appendix A for dimensional drawings). Carefully position the supplied gasket on the display rear surface. Insert the cylindrical body of the device into the borehole and tighten the nut from the rear side of the panel. 5.1 Wiring Switch on the power supply only after the wiring of the device has been completely performed NOTICE Switch off the device before checking the sensor and connection lines. For circuit integrity check use only the measuring device with the output voltage max. 4.5 V to prevent the device damage. Disconnect the sensor in case of higher voltage. NOTICE Signal cables should be routed separately or screened from the supply cables. Only a shielded cable may be used for signal lines. 4

5...7 Fig. 5.1 Wire preparation Do not use wire end ferrules to connect stranded wires. To connect fine-stranded wire, tin the wire end. Fig. 5.2 Connecting the wire to the terminal To connect solid wire, push the wire into the terminal. To connect stranded wire, press the release lever and push the wire into the terminal. Press the release lever to free the wire. Fig. 5.3 Disconnecting the wire Fig. 5.4 Mounting The electrical connections are shown in Fig. 5.5-5.8, the terminal assignments in Table 5.1. Ensure that the device is provided with its own power supply line and electric fuse I = 0.5 A. Solid conductor cross-section: 0.2 0.8 mm². Stranded conductor cross-section: 0.45 0.7 mm². Wires should be stripped for approx. 8 mm. 5.1.1 Input Fig. 5.5 RTD sensor wiring Fig. 5.6 TC sensor wiring 5

Table 5.1 Terminal assignment Table 5.2 Sensor cables Sensor type Cable length, max. Fig. 5.7 Voltage signal wiring Designation Description 24VDC - 24VDC + Power supply DO- Output - DO+ Output + AI1 + (three-wire RTD) AI2 + AI3 Resistance (each wire), max. Requirement RTD 100 m 30 ohm Equal length and crosssection for 3-wire TC 20 m 100 ohm Thermocouple cable 5.1.2 Output The NPN transistor output is designed to control the low voltage relay up to 42 V DC / 200 ma NOTICE As a precaution against inadvertent current reversal on output, a parallel diode (UVD 1.3U, IVD 1.3I) is usually included in the output circuit. DO- DO+ K VD _ U +U 6 Operation Fig. 5.8 NPN transistor output After the device is powered on the operating mode is activated. In this mode the measured signal is scaled and displayed. The signal type must be selected in the parameter in.t Input signal. The complete list of the programming parameters is shown in Table 7.2. The input signal is digitalised, the square root calculated (if the function is enabled), the signal scaled and displayed. The scale factor is calculated based on the parameters di.lo Lower measuring limit and di.hi Upper measuring limit. The display decimal point can be specified in the parameter di.p. For other signal processing functions see 6.2 and 6.3. For displayed errors see Table 6.1. 6.1 Control ON/ control is implemented with the NPN transistor output (see 5.1.2). The parameters SP.Lo Lower setpoint limit and SP.Hi Upper setpoint limit specify the control limits. The control function can be selected in the parameter Cnt: 6

Heating Cooling Alarm within limits Alarm outside limits The safe output state can be selected in the parameter out.e. Note: Switching hysteresis: 0.05 x (SP.Hi SP.Lo). 6.2 Alarm If the control function Cnt is set and the alarm function d.fnc = ON, the display blinks with a frequency of about 2 Hz when the output is switched on (see Fig. 6.1). 6.3 Filter Fig. 6.1 Undesirable signal fluctuations can be suppressed through the adjustable filter in the parameter td Filter time constant (see Fig. 6.2 and Table 7.2). The filter time constant can be set within the range 0 10 seconds. The higher the value, the slower the display reaction to changes of the input signal and the lower the susceptibility to interference is. The filter is deactivated if td = 0. 7

Fig. 6.2 Filter time constant 6.4 Square root function The function is intended for transmitters with the square characteristic. To enable the function set the parameter Sqrt = ON. 6.5 Error Table 6.1 Displayed errors Display Possible cause Remedy Eг.1 Measured value error Check the input signal. Check the sensor and connection lines. Contact the Technical Support of akytec GmbH. LLLL HHHH Measured value is below the lower limit for the selected signal (see Table 2.2) Measured value is above the upper limit for the selected signal (see Table 2.2) Check the input signal Check the input signal ---- Sensor break or short circuit Check the signal line Er.Cj CJC sensor error 7 Programming Contact the Technical Support of akytec GmbH. Table 7.1 Function buttons Key + Description Press > 3 s: enter the programming mode exit the programming mode Press < 1 s: save the parameter Press > 3 s: enter the service menu Increase value or menu navigation Decrease value or menu navigation Press and hold the button or to activate the ramp function while changing parameter. 8

if no button was pressed within 20 s, the device returns to the operating mode automatically. Table 7.2 Programming parameters Name Display Parameter Valid value Description Default SP.Lo SP.Lo Setpoint lower limit -999...9999 affected by di.p 0 SP.Hi SP.Hi Setpoint upper limit -999...9999 affected by di.p 30 Cnt Cnt Control function off Heat CooL U П Heating Cooling Alarm outside limits Alarm within limits in.t in.t Input signal See Table 2.2 Pt100 td td 0BFilter time constant 0 10 s 0 out.e out.e Output safe state ON di.lo di.lo Signal lower limit* -999...9999 affected by di.p 0 di.hi di.hi Signal upper limit* -999...9999 affected by di.p 100 SQrt SQrt Square root function di.p di.p Decimal point 2u3u 2u3u RTD connection d.fnс d.fnс Alarm function * only for linear signals Table 7.3 Service menu ON ---- 0000 ---.- 000.0 --.-- 00.00 -.--- 0.000 3-Ln 3-wire 2-Ln 2-wire ON Display Comments Valid values U ---.- 3-Ln гes Restore factory settings 0 User settings 1 Factory settings Note: CLbг Service function - t.c Service function - SCj Service function SoFt Firmware version 1. The minus sign is displayed in the most significant digit, together with 1. The display range is -199.9...999.9 if di.p = ---.-, 2. When setting the signal limits, take into account that in some cases the correct value cannot be displayed though there is no error indication. Example 1: di.lo: -999 -> 4 ma di.hi: 9999 -> 20 ma For the input current of 3.8 ma the correct indication should be -1068. Actually 1068 will be displayed. 9

Example 2: di.lo: -999 -> 4 ma di.hi: 9999 -> 20 ma For the input current of 20.8 ma the correct indication should be 10548. Actually 0548 will be displayed. 8 Maintenance The maintenance includes: Fig. 7.1 Device menu cleaning the housing and the terminals from dust, dirt and debris checking the fastening of the device checking the wiring (connecting leads, fastenings, mechanical damage) The device should be cleaned with a damp cloth only. No abrasives or solvent-containing cleaners may be used. 10

9 Transportation and storage NOTICE Pack the device in such a way as to protect it reliably against impact for storage and transportation. The original packaging provides optimum protection. If the device is not taken immediately after delivery into operation, it must be carefully stored at a protected location. The device should not be stored in an atmosphere with chemically active substances. Permitted storage temperature: -25 +55 C The device may have been damaged during transportation. Check the device for transport damage and completeness! Report the transport damage immediately to the shipper and akytec GmbH! 10 Scope of delivery ITP16 1 Gasket 1 Mounting nut 1 User guide 1 Appendix A. Dimensions Fig. A1 Fig. A2 To prevent the device spinning, the borehole in the front panel must correspond to the dimensions in Fig. A.2. 11