High-Speed DC Circuit-Breaker for Fixed Installation Type UR26, UR36 & UR40

Similar documents
High-Speed DC Circuit-Breakers for Fixed Installation Type UR26, UR36, UR40 & UR46

COMPONENTS. Power contactor Type BMS09.08 / BMS18.08

COMPONENTS. High power contactor Type BMS09.15 / BMS18.15 BMS09.18 / BMS18.18

C20.en. Power contactors for AC and DC CT1115 and CT1130. Connect - Contact - Control

C20.en. Power contactors for AC and DC CT1115 and CT1130. Connect - Contact - Control

Contactors. Series C137, C163, C164, C165 Single pole contactors for battery voltages Catalogue B60.en

NS..S contactor relays - with spring terminals AC operated

Technical features table for miniature circuit-breakers SH 200 Series

3 - Protection components Circuit-breakers

Contactors and Contactor Assemblies

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition

B 80.en. Single pole cam contactors for DC and AC applications C160, C162 Series. Connect - Contact - Control max. ED: 100% U 14,4V.

Page 13-2 Page Page 13-7

LC1D12BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

LC1D32BD TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 24 V DC coil

Controls Contactors and Contactor Assemblies Special Applications

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Semiconductor (AC) fuses

Snap Action Switches Technical Guide

Capacitor Switching Contactors

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Description Basic devices with positive operation contacts. Connection to SmartWire-DT yes in conjunction with DIL-SWD SmartWire DT contactor module

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

LC1D12BD TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 12 A - 24 V DC coil

Characteristics 5 TeSys k contactors and reversing contactors


CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil

Mini Contactors. Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 10 Auxiliary Contact Blocks

)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics

FM series position switches

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X

Circuit Breakers FAZ / FAZ6. Installation Products for Industrial Applications

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

MK-S (New Models) General-purpose Relays. New Super MK Relays. Models with Latching Lever Added to the Series. Features. Model Number Structure

Inductive sensor slot-type SI2-K08-AP7

MSV200 - Hall effect transducer

(1,5 modules per pole)

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

KCS-U200 relay - Latching, 2 pole

SPAE 010, 011 High Impedance Protection Relay

LC1D32ED TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 32 A - 48 V DC coil

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

Overcurrent Protection / 7SJ45

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Detecting Devices. 8/2 Introduction

QUINT-PS/ 1AC/24DC/20

RXG21BD interface plug-in relay - Zelio RXG - 2 C/O standard - 24V DC - 5A - with LTB

POWER TRANSDUCERS FOR SINGLE-PHASE AND THREE-PHASE NETWORK ISO P11P, P13P and P13B mm SERVICE MANUAL

VI 3 - i TABLE OF CONTENTS

Medium voltage circuit breaker technical guide

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Add-on modules DX 3 63A for MCBs DX 3 1,5 modules per pole

TS RES - OUTSTANDING ISSUES

Classification Enclosure rating Contact form Model Standard Flux protection SPST-NO G6RL-1A

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

VEO. V2PF480Y/277VS01 Art.Nr.: B TECHNICAL DATA

Industrial Controls. Catalog IC SIRIUS. Answers for industry.

For ultra-high precision measurement of current: DC, AC, pulsed..., with galvanic separation between primary and secondary. Applications.

EA16, EB16, EA17, EA19, EA12 MOVING-IRON METERS Ammeters and Voltmeters

Residual Current Operated Circuit-Breakers (RCCBs)

Time over/underfrequency relay with protection assemblies

Utilization category DC-1 DC-3 DC-5 L/R 1 ms L/R 2 ms L/R 7.5 ms

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

N. TEST TEST DESCRIPTION

MK-S (New Models) General-purpose Relays. New Super MK Relays. Models with Latching Lever Added to the Series. Features. Model Number Structure

Customer: Standard type Page 1 of 7 Description Fluxgate current sensor with toroidal core PCB mounting

QUINT-PS-24DC/24DC/10

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

AF AF V50/60HZ-DC Contactor. General Information. Ordering. Popular Downloads. Dimensions. Technical AF

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Theta 20A / 20V. Technical Data Sheet. Special Features

Power supply CP-D 24/4.2 Primary switch mode power supply

Instructions Contact numbers to EN Coil terminal markings to EN Integrated diode-resistor combination Coil rating 2.

Low profile safety relay with forcibly guided double contacts FEATURES. Relay height, 14.5mm. 4a2b

E-STOP relays, safety gate monitors

7P Series - Surge Protection Device (SPD) Features 7P P P

Instantaneous Overcurrent Relay

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13

QUINT-PS/ 3AC/24DC/10

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Thermistor motor protection relays

V2IM10AL10 Art.Nr.: V2IM10AL10P Art.Nr.: Control element. Tripping delay. Function selector. Status indication 24...

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Index N Line N Line Chapter Title Page

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Modeion OTHER ACCESSORIES OF MOULDED CASE CIRCUIT BREAKERS

Connect - Contact - Control. DC Contactors 600V / 750V / 1000V. F 215e

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

VEO. V2PF480Y/277VSY01 Art.Nr.: V2PF480Y/277VSY01P Art.Nr.: TECHNICAL DATA

Description Basic devices with positive operation contacts

Transcription:

High-Speed DC Circuit-Breaker for Fixed Installation Type UR26, UR36 & UR40 C O M P O N E N T S

The UR26, UR36 & UR40 are DC high-speed current limiting air Circuit-Breakers, trip free, single pole, bi-directional, with electromagnetic blow-out, electric control circuits and series direct instantaneous over-current release. Their simple design and high insulation level combined with their compliance to both standards EN50123/IEC61992 for Fixed Installations and EN/IEC60077 for Rolling Stock (more severe for what concerns the mechanical endurance and the vibrations & shocks), guarantee to the UR26, UR36 & UR40 range a very high reliability and an exceptionally long life time. With its proven worldwide experience and acceptance, Sécheron's range of Circuit-Breakers offers you the key product for such a strategic and critical application that is to guarantee the highest safety to your equipment as well as to the people operating it and using it. Applications Line Circuit-Breaker type* H/L/B/O for DC traction power substations Interconnecting Circuit-Breaker type* H/I/B/O for DC traction power substations Rectifier Circuit-Breaker type* H/R,lr,r/B/O for DC traction power substation Rolling mill plants, chemical plants, nuclear research centers, mines * Type designation according to standards EN50123-2 / IEC61992-2 Main features Conventional thermal current 2600 A (UR26), 3600 A (UR36) and 4000 A (UR40) Rated voltage 900 Vdc, 1800 Vdc and 3600 Vdc Rated insulation voltage up to 4800 Vdc for a rated voltage of 3600 Vdc Safe with a high insulation level: over-voltage category OV4 Limited maximum arc voltage High rated short-circuit making and breaking capacity Electro-magnetic closing with electric holding or magnetic latch Five double contacts auxiliary switches Low voltage 22-poles connector interface for auxiliary contacts and control coil High mechanical and electrical endurance Very low maintenance requirements Proven design with worldwide experience and acceptance Insulation material according to relevant BS, NF, ASTM, IEC and DIN standards Designed according to EN50123-1/2, IEC61992-1/2 A large number of different options to match the various applications requirements Technical diagrams 2 Track line supplied by a rectifier f e d d: duty d - distant fault e: duty e - maximum energy f: duty f - maximum fault current Breaking current parameters Îss>1.42Iss I Iss 0.63 Iss Icut off Id V Ûarc UNe t c t l di/dt Typical duty f Typical duty e and d t t Characteristics of the duties d, e and f t c /T Nc 1 0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 d >63 31.5 T Nc [ms] 16 0 0.4 0.6 0.8 1 2I Ne /I Nss e f I ss /I Nss I ss = Prospective sustained short-circuit current Î ss = Peak of I ss I Nss = Rated short-circuit current of the circuit-breaker I d = Setting of maximum current release I cut off = Cut off current Û arc = Maximum arc voltage U Ne = Rated operational voltage di/dt = Initial current rate of rise t c = Time-constant of the circuit t l = Opening time T Nc = Rated track time constant of the circuit-breaker

Opening time t l t l Relationship between opening time t l and the initial rate of rise of current di/dt for direct instantaneous over-current release. Example for an initial rate of rise of current of 3. 10 6 A/s: the opening time is about 3.5 ms for UR26 and about 4.7 ms for UR36 and UR40. Remark: for a shorter opening time the indirect release option can be used (refer to option section). Designation code (standard version) Type designation URS 36 81 A E 024 0 DS1 310 0 A 0 0 0 0 UR Breaker type - Execution UR - Fixed installation URS Conventional thermal current 2600 A 26 3600 A 36 4000 A 40 Rated voltage 900 Vdc 81 1800 Vdc 82 3600 Vdc 64 Arc chute execution Standard for 81/82 arc chute A Standard type SE (1) for 64 arc chute B Closing device type Electric holding E Magnetic holding M Nominal control voltage 24 Vdc 024 36 Vdc 036 48 Vdc 048 72 Vdc 072 110 Vdc 110 220 Vdc 220 Varistor on coil No 0 Direct over-current instantaneous release (2) 1.4-2.7 ka (3) DV1 2.0-8.0 ka DS1 4.0-15.0 ka (4) DS2 Pre-set over-current setting x 10 (A) 310 310 Example: 310 x 10 = 3100 A Indirect release No 0 Auxiliary contact configuration 5a (NO) + 5b (NC) A Manual tripping No 0 Manual closing device No 0 Position Indicator No 0 Overcurrent release indicator No 0 (1) Includes only the arc chute locking mechanism but no arc chute lifting lever and no additional insulating panels around the arc chute. (2) DV type has a single trip setting range with the setting from underneath; DS type has a double trip setting range with the setting from underneath. (3) Only for UR26. (4) Only for UR36 & UR40.

Technical data Symbol Unit UR26 UR36 UR40 MAIN CIRCUIT Conventional free air thermal current (T amb =+40 C) I th [A] - acc to EN50123-2 / IEC61992-2 2600 3600 4000 - acc. to ANSI C37.14-2002 2150 2900 3200 - acc. to IEC60947 2600 3600 4000 Rated service current I Ne [A] 2600 3600 4000 Rated voltage U Ne [Vdc] - arc chute type 81 900 900 900 - arc chute type 82 1800 1800 1800 - arc chute type 64 3600 3600 3600 Rated insulation voltage: - arc chute type 81 U Nm [Vdc] 3000 3000 3000 - arc chute type 82 3000 3000 3000 - arc chute type 64 4800 4800 4800 Rated impulse withstand voltage: - arc chute type 81 U Ni [kvdc] 20 20 20 - arc chute type 82 20 20 20 - arc chute type 64 40 40 40 Rated short-circuit making & breaking capacity I NSS / T Nc: - at U Ne 900 Vdc [ka]/[ms] 125/100 125/100 125/100 - at U Ne 1800 Vdc [ka]/[ms] 80/31.5 80/31.5 80 /31.5 - at U Ne 3600 Vdc [ka]/[ms] 40/31.5 40/31.5 40/31.5 Direct over-current instantaneous release [ka] 1.4-2.7 2.0-8.0 2.0-8.0 [ka] 2.0-8.0 4.0-15.0 4.0-15.0 Power frequency withstand voltage (50 Hz, 1 min) : - arc chute type 81 U a [kv] 12 12 12 - arc chute type 82 12 12 12 - arc chute type 64 18.5 18.5 18.5 CONTROL CIRCUIT Nominal voltage U n [Vdc] 24, 36, 48, 72, 96, 110, 220 Nominal closing power (T amb =+20 C) [W]/[s] 1300/1 Nominal holding power for electric holding (T amb =+20 C) [W] 2.3 Nominal holding power for magnetic holding (T amb =+20 C) [W] 0 Nominal opening power for magnetic holding (T amb =+20 C) [W]/[s] 25/1 Mechanical opening time* at U n and T amb =+20 C t o [ms] 15 to 30 Mechanical closing time* at U n and T amb =+20 C t c [ms] ~ 150 * starting when the signal is received by the coil AUXILIARY CONTACTS CIRCUIT Number of contacts 5a (NO)+5b (NC) Rated voltage (potential free contacts) [Vdc] 24 to 110 Rated current [A] 10 Maximum breaking current - Ohmic load at 110 Vdc [A] 1 - Inductive load τ = 15 ms at 110 Vdc [A] 0.3 Minimum let through current at 24 Vdc (1) [ma] 10 (1) For a dry and clean environment OPERATING CONDITIONS Ambient temperature T amb [ C] -25 to +40 Minimum mechanical durability N Operations 8x25000 Altitude [m] <1400 Humidity Class 5K2 Pollution degree PD4

Main dimensions and weight (standard version) Circuit-breakers dimensions [mm] UR26 UR36 UR40 A 641 756 756 B 132 247 247 C 132 177 177 D 156 146 146 E 20 30 30 Circuit-breakers weight [kg] UR26 UR36 UR40 with arc chute type 81 77 94 98 with arc chute type 82 87 105 109 with arc chute type 64 148 150 154 UR..81/UR..82 238 617 (82) 419 (81) 168 65 784 51 4x Ø11 23 40 190 319 420 UR..64 140,5 1025 90 90 190 319

Insulating distances Minimum insulating distances [mm] (1) UR..81 UR..82 UR..64SE To insulating wall A 25 25 25 B 95 95 200 C (2) 750 750 875 To earth C (2) 750 750 1500 (1) At maximum short-circuit breaking capacity. For smaller short-circuit values, smaller distances can be used (2) Grid with 50% of surface opening Insulated grid 617 (82) 350 238 C 419 (81) UR..81/UR..82 B B A A C UR..64 B B A A

Options designation code (subject to additional costs) Type designation URS 36 64 C E 064 1 DV2 310 1 B 1 1 1 0 Description Designation Code Arc chute execution type S-CC for arc chute 64 C type S-OC for arc chute 64 D type SI-CC for arc chute 64 E type SI-OC for arc chute 64 F Nominal control voltage 64 Vdc 064 125 Vdc 125 Varistor on coil Yes 1 Direct over-current instantaneous release 2.0-5.0 ka DV2 4.0-10.0 ka DV3 2.0-5.0 ka DE1 4.0-8.0 ka DE2 6.0-10.0 ka DE3 9.0-15.0 ka DE4 Indirect release (including manual ralease) BIM 5 1 BIM 6 2 Auxiliary contact wiring 22 poles (5 change-over switches) B Manual release Yes 1 Manual closing device Yes 1 Position Indicator Yes 1 Over-current release indicator Yes 1 BIM5 & BIM6 indirect and manual releases DE direct over-current instantaneous release M3 manual release The indirect release enables to shorten the opening time when required by specific application. The choice of the relevant type has to be validated by Sécheron prior quoting. This device can also be manually activated. Mechanical reaction time Control mode - BIM 5 4.5-5.5 ms CID-1* - BIM 6 12-19 ms Direct battery 77-140 Vdc * Not included in the DC circuit-breaker - To be ordered separately Not available for 220 Vdc The DE type has a single trip range with a lateral setting.

Varistor on coil Position indicator Manual closing Over current release indicator Over current release indicator and manual closing device cannot be selected together for the same breaker. Arc chute 64 S execution S-OC type: arc chute lifting lever located on LV connector s opposite side. S-CC type: arc chute lifting lever located on LV connector s side. Arc chute 64 SI execution SI-OC type: with additional insulating panels and the arc chute lifting lever located on LV connector s opposite side. SI-CC type: with additional insulating panels and the arc chute lifting lever located on LV connector s side. SG101778BEN_A03-1/06 Sécheron SA Route des Moulières 5 1217 Meyrin - Geneva CH-Switzerland Tel: +41 (0)22 739 41 11 Fax: +41 (0)22 739 48 11 info@secheron.com www.secheron.com This document is not contractual and contains information corresponding to the level of technology at the date of printing. Sécheron reserves the right to modify and/or improve the product, whose characteristics are described in these documents, as required by new technology at any time. It is the purchaser's responsibility to inform himself, no matter what the circumstances, of the product's maintenance conditions and requirements. Sécheron reserves all rights, especially those arising from our "General Delivery Conditions". Printed in Switzerland