1 OHearne Associates: Architecture - Site - Planning P. O. Box 598, Harrisville, RI Fax: OHearneAssociates.com North Smithfield Town Hall 1 Main Street Flashing & Slate Roof Repair Work Scope September 21, 2017 Scope of Work: Also Refer to photos and drawings. Refit and reattach existing coper hip ridge copings. Under Option 1: Preplace copper box gutter lining. Under Option 2: Line existing box gutters with EPDM. Rework/repair right front copper valley connection at box gutter. Repair isolated copper snow guards.

2 MATERIALS Sheet Copper: Sheet copper shall be Revere standard copper for building construction or equivalent. Only domestic materials shall be used when available. Any sheet metal shown on drawings and not otherwise specified shall be 16 oz. cold rolled copper. Sheets shall conform to ASTM specifications B370 or Federal Specification QQ-C-576. Fasteners: Nails used for fastening copper shall be copper or hardware bronze of Stronghold type, or equal, with large flat head. They shall not be smaller than No. 12 Stubs gauge (0.109") and of sufficient length to penetrate roof boarding not less than ¾ Rivets shall be of hard copper, brass, or bronze. Screws and bolts used for fastening copper shall be copper, bronze, brass or stainless steel (passive). Expansion Inserts: Expansion inserts shall be nylon or suitable plastic. Cleats: Cleats shall be 2" wide by about 3" long and shall be made of 16 oz. cold rolled copper, unless otherwise specified. One end shall be locked into seams or into folded edge of copper sheets. Other end shall be nailed with two nails and folded back over nail heads, unless otherwise noted on drawings. When expansion cleats are used, they shall be the same overall dimensions as fixed cleats. Solder: Where used on plain copper, solder composition shall be 50% block tin. Solder shall conform to ASTM specification B32 or Federal Specification QQ-S-571. Flux: Flux shall be muriatic acid killed with zinc, or approved brand of soldering flux. Acid shall be thoroughly washed off after soldering is completed. Synthetic or Rubber Base Sealants: Butyl sealants shall be those conforming to Federal Specification TT-S Use shall be in conformance with manufacturer s recommendations.

3 One part polysulfide sealants shall be those conforming with Federal Specification TT-S-00230C Type II, Class A. Use shall be in conformance with manufacturer s recommendation. One part polyurethane sealants shall be those conforming with Federal Specification TT-S C Type II, Class B. Use shall be in conformance with manufacturer s recommendations. Silicone sealants shall be those conforming to Federal Specification TT-S-00230C Type II, Class & Use shall be in conformance with manufacturer s recommendations. Butyl tape shall be of a type produced and recommended by a reputable manufacturer for architectural copper applications, and shall be used in conformance with that manufacturer s recommendations. Elastic Cement: Elastic cement shall fulfill requirements of Federal Specification SS-C-153. Roofing Felt: Roofing felt shall be saturated with asphalt or pitch and shall have a min. weight of 15 lbs. Per 100 sq. ft. Rosin-Sized Paper: Rosin-sized paper shall be smooth, unsaturated building paper weighing approximately 5 to lbs. per 100 sq. ft. INSTALLATION Surfaces: Surfaces to be covered with sheet metal shall be smooth and free from defects of every description. All such surfaces shall be cleaned of dirt, rubbish and other foreign materials before sheet metal work is started. All projecting nails shall be driven flush with roof boarding. Tinning: Edges of all sheets of uncoated copper to be soldered shall be tinned with solder on both sides for width not less than 1 ½. Soldering: All soldering shall be done slowly with well heated coppers - to heat sheet thoroughly and to sweat solder completely through full width of seam. Ample solder shall be used and seam shall show at least one full inch of evenly flowed solder. Wherever possible, all soldering shall be done in flat Position. Seams on slopes steeper than 45 deg. shall be soldered a second time. Soldering Coppers: Soldering shall be done with heavy soldering coppers of blunt design, properly tinned before using. For flat seam work, and gutters, they shall weigh not less than 10 lbs. per pair except, when gas-heated soldering torch is used, copper itself shall weigh not less than 3lbs. Roofing Underlayment: Surfaces to receive copper roofing shall be covered with roofing felt. Each ply shall lap not less than 2" in the direction of flow and shall be fastened with copper or bronze nails driven through sheet copper washers not less than 1" square. Nails in roofing felts shall be not more than 6 inches apart on all lapped seams.

4 Building Paper: Rosin-sized building paper shall be placed over roofing felts immediately preceding the application of copper roofing. Rosin-sized building paper is omitted for flat seam roofing. FLASHINGS Thru-wall Flashing: Not applicable Stepped Base Flashing: Not applicable Chimney on Roof Slope: Not applicable Chimney Cap: Not applicable On Brick Parapet Walls: Not applicable On Concrete Parapet and Walls: Not applicable Standing Seam Parapet Lining: Not applicable BASE FLASHING Base flashings shall be provided where roofing abuts vertical surface. On built-up roofing: Not applicable Base flashing units shall be made from cold rolled copper in (8') (10') lengths, Maximum length of each unit for 16 oz. copper shall be 16 ft.; for 20 oz. copper, 24 ft. Seams shall be 3/4" locked and soldered. Units shall be joined together with loose-lock seam, 3" wide, filled with sealant before units are hooked together. Loose lock slip joints shall be made as specified under cross folded loose seams. On long straight runs, there shall also be slip joints not more than 8' from any external or internal corner. Straight runs between 20' and 48' in length shall have slip joint at center of run. All seams shall be soldered in flat position. Cleated Edge: Horizontal leg of base flashing shall terminate with 1/2" folded edge. Cleats spaced 8" apart shall be hooked into folded edge with other end nailed to roof deck or wood nailer in roof slab. Over horizontal flange on roof deck a layer of roofing plastic shall be troweled. Into this roofing plastic, strip of fabric shall be embedded. Top strip of fabric shall be similarly applied. (Alternate: First strip of fabric shall be covered with hot pitch into which a top strip of saturated felt shall be embedded.) Top strip shall be surfaced same as adjacent built-up roofing. Nailed Edge: Horizontal leg of base flashing may be nailed along outer edge with copper or bronze nails spaced 3" apart, optional. On other than wood decks, wood nailers shall be provided. Strip horizontal flange into built-up roofing as specified under "cleated edge base flashing." NEW CAP FLASHING: Mot applicable NEW VALLEY FLASHING SYSTEM: Mot applicable NEW COPING COVERS: Not applicable COPING COVER REPAIR: Remove existing fastening pieces. Uniformly straighten the existing coping as much as practical to get them to fit more uniformly and with a greater degree of friction against the copper at the outside edge of the flashing piece. One section of flashing is severely bent. Remove and re-straighten on a brake machine prior to reinstalling. Refasten the piece to the existing wood blocking as sown on the attached diagram. Allow in the bid to replace approximately 30% of the balking which may be rotted.

5 Fascia- Flat Roofs: Not applicable Eave Snow Flashing: Not applicable BUILT-IN GUTTER Scope: Install new copper lining to match profile of existing galvanized. Lock into the existing lock seam of the existing copper counter flashing. Paper: Supporting surfaces under copper gutter linings shall be covered with roofing felt. Over this roofing felt, a ply of rosin-sized building paper shall be installed. Gutter Lining: Gutter lining shall be formed of cold rolled copper sheets conforming closely to profile of gutter. There shall be no longitudinal seams. If sectional contour of gutter is more than 36", cross seams shall be spaced 36" apart. If sectional contour is 36" or less, gutter lining may be formed of copper sheets in 8' or 10 lengths. Gutter linings constructed of 16 oz. or 20 oz. cold rolled copper shall have ends joined together by 3/4" wide locked and soldered cross seams. For copper linings heavier than 20 oz., ends shall be joined together by 1 1/2" lapped, riveted and soldered cross seams. Rivets shall be copper, 3/16 in diameter with copper burrs under peened heads. Rivets shall be spaced not more than 3" apart, in two staggered rows, with 1/2" edge distance. Hold Downs: Where flat or sloping sections of gutters have widths between 18" and 24", sections shall be held down by brass screws covered with 16 oz. copper cups soldered to lining. Hold downs shall be placed along center of section, spaced not more than 48" apart longitudinally. Flat or sloping sections exceeding 24" in width shall have brass screws spaced not more than 18" apart transversely and 48" apart longitudinally. Where used in wood, screws shall be No. 12 x 3/4" round head brass screws, Where used in stone, similar screws shall be set in expansion shields. Under each screw head, a brass or copper washer, 1/16 thick x 1 1/4" diameter, shall be provided. Holes in gutter lining shall be 1/2" larger than diameter of screw. Connection to Asphalt Shingle Slate or Tile Roofing: Top back edge of gutter lining shall terminate at roof edge in 3/4" loose lock seam and be secured with copper cleats spaced 24" apart. Separate apron strip made of 8' or 10 lengths of 16 oz. cold rolled copper, shall be hooked over top rear folded edge of gutter lining to form 3/4" wide loose lock seam bent down at 45 deg. This apron flashing shall extend up on roof under slate or tile roofing not less than 6" with upper edge folded 1/2" and secured by cleats spaced 24" apart. Adjacent lengths of apron flashing shall be lapped 4". Cant strips, as elsewhere specified, shall be attached to apron flashing. Connection To Copper Roofing: Method A: Where ends of batten or standing seams terminate at edge of roof, top rear edge of gutter lining shall be folded over 3/4" and shall terminate at edge of roof. Top edge of gutter lining shall be secured with copper cleats spaced 2' apart Under each standing or batten seam at roof edge, separate piece of copper, 6" wide x 10" long, shall be placed to hook over folded top edge of gutter lining; it shall be secured to roof deck by nails. Lower ends of copper roofing sheets shall hook over top rear folded edge of gutter lining to form 3/4" wide loose lock seam. Method B: Where ends of batten or standing seams do not terminate at edge of roof, rear edge of gutter lining shall extend up on roof deck under copper roofing sheets at least 6" and terminate in a 1/2" fold - where it shall be attached to roof boarding by copper cleats spaced 24" apart

6 Separate 16 oz. cold rolled copper locking strip, made from 8' or 10' lengths, shall be continuously soldered to gutter lining on roof slope. Lower edges of copper roofing sheets shall be folded 3/4" and hook into lock strip to form 3/4" wide loose lock seam. Gutter at Cornices: Outer edge of gutter linings shall extend over top of cornice and be folded 3/4" to hook over previously placed continuous edge strip. Edge strip shall be made of 20 oz. cold rolled copper in 8' or 10' lengths; ends of each length shall lap 1". Edge strips shall be attached to wood construction with either nails spaced 3" apart or bronze screws spaced 10" apart On stone cornices, edge strips shall be secured with brass screws in plastic inserts spaced 10" apart or (alternately) formed to fit into reglet cut in stone.-edge strip shall be secured by brass screws and expansion sleeves spaced 10" apart and regrets filled with sealant. Expansion Joints: Expansion joints shall be provided midway between all outlet tubes (unless otherwise shown on the drawings); also at exterior corners, and where ends of gutters abut masonry walls. Ends of each gutter section shall be closed with cold rolled copper of same thickness as gutter lining copper and shall be flanged, riveted and soldered to gutter lining. Top edge of gutter ends shall have horizontal flange of 1 1/2" wide for connection to expansion joint cover strip. Expansion joint shall have open space - 1" wide between adjacent gutter ends, 1/2" between gutter end and adjacent wall. Cover strip, formed from 16 oz. cold rolled copper, shall be provided over expansion joint and shall be loose locked into horizontal flanges at top of gutter ends. Loose lock joints shall provide for gutter lining movement of 1/2" in either direction. Where ends of gutter abut masonry wall, there shall be 1/2" open space between gutter end and masonry wall - and cover strip shall extend under counter flashing built into masonry. Ends of cover strips shall so terminate to provide watertight connections and permit freedom of movement of gutter lining. L-type water diversion baffle shall be soldered across top of cover strip on line with centerline of gutter. HUNG MOLDED GUTTERS: Not applicable Outlet Tubes: Outlet tubes that connect to outside leaders or downspouts shall be formed of 16 oz. cold rolled copper, with locked and soldered longitudinal seam. Upper end of tube shall be flanged 1/2" and soldered to gutter lining. Tube shall extend into leader at least 3". Strainers: Strainers shall be provided at all outlet tubes. They shall be wire basket type formed of No. 14 B&S gauge copper wire, or cast bronze, and shall fit snugly in outlet tube. BUILDING EXPANSION JOINTS Not applicable. Snow Guard: Re-secure below slate with adhesive. Isolated Slate Replacement: Submit replacement slate to match existing for review and approval. To cover the event that an exact match is not achievable, include in the base bid the provision the harvesting of existing slate from the left side roof toward he rear, and replacing those along a uniform line along the roof edge with the new slate for aesthetic reasons. Carefully remove broken or cracked existing slate or missing slate. Base bid on 6 such locations. Work with surrounding slate to achieve the clearance necessary to slide the new slate up into position and to fasten. The Contractor shall include in the bid the labor and materials to replace

7 slates that may be broken during this process which could involve several slates per slate repair. Include in the bid the same harvesting operation. Copper Valley Repair: Repair the bottom of the copper valley at its termination at the box gutter at the front left side of the roof. Re-work existing copper and add slip sheet of copper under the direction of the water flow to close the gap. End

8 Photo #1: Existing Box Gutter

9 Photo #2: View of right half of the building copper hip ridges: Typical existing copper valley:

10 Photo #3: Typical copper hip ridge: Drawings are attached.

Slate Shingle Specifications

Slate Shingle Specifications Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural

More information

Ekoroof LiteTile Dimensions

Ekoroof LiteTile Dimensions Ekoroof LiteTile Dimensions 7 3 3.5 Height 40 Width 20 Length Weight per Panel: 3 kg / 6.61 lbs 2 2 Area per panel 800 in / 5.55 ft 2 Panels per Square: 20 (including overlap, for a 100 ft covered area)

More information

eco-shake INSTALLATION INSTRUCTION

eco-shake INSTALLATION INSTRUCTION 1 eco-shake INSTALLATION INSTRUCTION NOTE: Shuffling the eco-shakes during installation may be necessary to obtain a uniform color throughout the roof. Due to the natural wood content in the ecoshakes,

More information

SECTION SHEET METAL FLASHING AND TRIM

SECTION SHEET METAL FLASHING AND TRIM SECTION 07620 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Formed roof drainage sheet metal fabrications. 2. Formed low-slope roof sheet metal fabrications. 1.2 SUBMITTALS A. Shop Drawings: Show

More information

SHEET METAL FLASHING AND TRIM Christ on the Mountain

SHEET METAL FLASHING AND TRIM Christ on the Mountain SECTION 076200 - SHEET METAL FLASHING AND TRIM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Compatibly with the bumping of flashings and trim as identified in the Membrane Roofing Section 075000.

More information

AIA Specification. Section Slate Shingles PART 1 GENERAL

AIA Specification. Section Slate Shingles PART 1 GENERAL AIA Specification Section 07315 Slate Shingles PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

SECTION SHEET METAL FLASHING AND TRIM

SECTION SHEET METAL FLASHING AND TRIM SECTION 07620 SHEET METAL FLASHING AND TRIM PART 1 GENERAL 1.1 SUMMARY A. Section includes flashings and counterflashings, sheet metal roofing and fabricated sheet metal items, as indicated in Schedule.

More information

Inspire Aledora Slate Application Guidelines

Inspire Aledora Slate Application Guidelines July 2014 Inspire Aledora Slate Application Guidelines Only Basic Roofing Tools Required Hand fastened or fastened with a pneumatic nail gun Utility knife or a standard circular saw Tape measure, pry bar,

More information

REGAL. Installation Manual

REGAL. Installation Manual REGAL Installation Manual General Information The details shown on the following pages are suggestions or guidelines for installing the Regal system. The installation details shown here are proven methods

More information

SECTION SLATE SHINGLES. 1.1 SUMMARY A. Section Includes: 1. Slate shingles over underlayment nailed to roof sheathing.

SECTION SLATE SHINGLES. 1.1 SUMMARY A. Section Includes: 1. Slate shingles over underlayment nailed to roof sheathing. SECTION 07 31 26 SLATE SHINGLES SPEC WRITER NOTES: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Slate shingles

More information

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive

More information

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION

ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive

More information

Turada Hardwood Shingles and Shakes Installation instructions

Turada Hardwood Shingles and Shakes Installation instructions 1. General 1.1 Maximum Exposure: Maximum exposure for wood shingles and shakes shall comply with Table 1 herein, unless specifically specified in the roof assemblies Product Approval. 1.2 Solid and Spaced

More information

C e r t a i n T e e d S h i n g l e A p p l i c a t o r s M a n u a l. and Carriage House STEEP. Slope Application. (over 21/12)

C e r t a i n T e e d S h i n g l e A p p l i c a t o r s M a n u a l. and Carriage House STEEP. Slope Application. (over 21/12) C e r t a i n T e e d S h i n g l e A p p l i c a t o r s M a n u a l Grand Manor 16 and Carriage House YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products. These shingles

More information

Table of Contents. Fasteners... 4 Venting Preparation Installation with Battens - DECRA Tile & DECRA Shake 1

Table of Contents. Fasteners... 4 Venting Preparation Installation with Battens - DECRA Tile & DECRA Shake 1 Table of Contents DECRA Tile & Shake Roof Overview... 2 Introduction... 3 Safety... 3 Tools.... 3 Estimating Sheets... 4 Codes & Requirements... 4 Roof Slope... 4 Underlayment... 4 Deck Preparation....

More information

ROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION

ROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION ROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION 1. 2. 3. Scope 1.1 This application standard provides the minimum installation criteria for wood

More information

b) Symphony comes pre-packaged in color and width blends. There is no need to mix Symphony at the job site. Currently Symphony is available in the

b) Symphony comes pre-packaged in color and width blends. There is no need to mix Symphony at the job site. Currently Symphony is available in the PART 1 GENERAL 1) DESCRIPTION a) CertainTeed Symphony TM composite slate is an innovative roofing product that simulates the appearance, texture, and contours of traditional natural slate. It is a carefully

More information

ROOFING APPLICATION STANDARD (RAS) No. 130

ROOFING APPLICATION STANDARD (RAS) No. 130 ROOFING APPLICATION STANDARD (RAS) No. 130 1. Scope 1.1 This application Standard provides the minimum installation criteria for wood shingles and shakes. 2. Definitions 2.1 For definitions of terms used

More information

Basic Fitting Details No. 1

Basic Fitting Details No. 1 No. 1 Fixing free edges of flashings A. Clips for flashings over interlocking tiles B. Clip to ridge or hip roll C. Clip to apron flashings Clips should be made from quarter hard copper, 0.6mm thick, terne

More information

Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications.

Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications. Best Materials LLC distributes backer rod, caulking and sealants for all types of EIFS joints and penetration sealing applications. EXTERIOR INSULATION & FINISH SYSTEM CONSTRUCTION Data Published Courtesy

More information

Brava Old World Slate Installation Guide

Brava Old World Slate Installation Guide Brava Old World Slate Installation Guide Brava Roof Tile Phone: 844-290-4196 www.bravarooftile.com This document includes the recommended and suggested installation procedures for Brava Old World Slate

More information

IRONSTONE SLATE & FLASHING SPECIFICATIONS IRONSTONE SLATE

IRONSTONE SLATE & FLASHING SPECIFICATIONS IRONSTONE SLATE 8 5/8" A) 1 5/8" 5/8" 1 10" 10 1 5 50" 9 7/8" IRONSTONE SLATE & FLASHING SPECIFICATIONS IRONSTONE SLATE 1/8" 1 B) 3/8" 2 7/8" 1 3/8" 3/8" 3/8" 3/8" 1" 1 5/8" 1 5/8" 1 2 1 8.3" 3/4" Overall Length 52 Length

More information

Inspire Slate Starter Piece Hip and Ridge. 13 1/2" Height: 13 ½" Width: 12" Squares/ Pallet. Bundles/ Square

Inspire Slate Starter Piece Hip and Ridge. 13 1/2 Height: 13 ½ Width: 12 Squares/ Pallet. Bundles/ Square December 2017 Classic Slate Application Guidelines Only Basic Roofing Tools Required Hand fastened or fastened with a pneumatic nail gun Utility knife or a standard circular saw Tape measure, pry bar,

More information

Installation Guide. Cedar Shake. Distributed by: BEST MATERIALS LLC, Phoenx AZ

Installation Guide. Cedar Shake. Distributed by: BEST MATERIALS LLC, Phoenx AZ RPM ROOFING Installation Guide Cedar Shake Distributed by: BEST MATERIALS LLC, Phoenx AZ 602-272-8128 800-474-7570 www.bestmaterials.com Table of Contents OVERVIEW... 1 CAUTION... 1 DISCLAIMER... 1 PRODUCT

More information

Installation Guide. Step 3. Valley Flashing. Step 7. Transition Flashings and Accessories. Step 6. Hip and Ridge Installation

Installation Guide.   Step 3. Valley Flashing. Step 7. Transition Flashings and Accessories. Step 6. Hip and Ridge Installation Step 7. Transition s and Accessories Step 3. Valley Step 6. Hip and Ridge Installation Step 2. Rake Trim Step 5. Installing the Shingles Step 1. Eave Starter Installation Step 4. Endwall s Installation

More information

installation guide Villa

installation guide Villa installation guide Villa Table of Contents Introduction............................. 2 Safety................................... 2 Tools.................................... 2 Codes & Requirements....................

More information

PROJECT INSTRUCTIONS Roofing

PROJECT INSTRUCTIONS Roofing PROJECT INSTRUCTIONS Roofing This handout outlines some basic regulations contained within the 2015 Minnesota State Building Code, as well as other good building practices. However, this handout is not

More information

1 Exam Prep NRCA Roofing Manual: Steep-Slope Roof Systems 2013 Tabs and Highlights

1 Exam Prep NRCA Roofing Manual: Steep-Slope Roof Systems 2013 Tabs and Highlights 1 Exam Prep NRCA Roofing Manual: Steep-Slope Roof Systems 2013 Tabs and s These 1 Exam Prep Tabs are based on the National Roofing Contractors Association (NRCA) manual listed below: Steep-Slope Roof Systems

More information

SG-30 A P P L I C A T I O N I N S T R U C T I O N S. Directions For Application

SG-30 A P P L I C A T I O N I N S T R U C T I O N S. Directions For Application 1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE

More information

Grand Manor Carriage House and Centennial Slate 16 YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products.

Grand Manor Carriage House and Centennial Slate 16 YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products. CertainTeed Shingle Applicator s Manual Grand Manor Carriage House and Centennial Slate 16 YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products. 90 STEEP Slope Application

More information

StormMaster Slate General Instructions 1.) GENERAL INSTRUCTIONS 2.) ROOF DECK VENTILATION 3.) ROOF DECK

StormMaster Slate General Instructions 1.) GENERAL INSTRUCTIONS 2.) ROOF DECK VENTILATION 3.) ROOF DECK StormMaster Slate General Instructions IMPORTANT: THE STATEMENTS EXPRESSED ON THIS PAGE ARE THE RECOMMENDATIONS FOR THE APPLICATION OF THE ROOFING PRODUCTS AS OUTLINED AND ILLUSTRATED. ANY DEVIATION FROM

More information

SLATE & SHINGLE INSTALLATION

SLATE & SHINGLE INSTALLATION EAVE EDGE Apply a small strip of roofing paper to the bottom of eave. Eave flashing is attached to substrate with roofing nails every 9". Install underlayment over entire roof. (See Fig. 1) PAGE 1 Bend

More information

RED DIAMOND SHINGLES Roof Installation Introduction:

RED DIAMOND SHINGLES Roof Installation Introduction: RED DIAMOND SHINGLES Roof Installation Introduction: The guidelines set forth in this manual are intended for use with the application of Red Diamond shingles. Wallaba specie (Eperua Falcata) shingles

More information

ROOFING City of Grand Rapids Building Safety Division

ROOFING City of Grand Rapids Building Safety Division ROOFING City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Grand

More information

4. Metal roof jacks at penetrations and attachments

4. Metal roof jacks at penetrations and attachments - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - SECTION 07 61 00 METAL SHINGLE ROOFING - - - - - - - - - - -

More information

Cambridge English Application Instructions

Cambridge English Application Instructions Cambridge English Application Instructions ROOF SLOPE: Never apply asphalt shingles to roof slopes less than 2:12. For slopes 2:12 to 4:12 (LOW SLOPE), see special underlayment requirements outlined below.

More information

IRONWOOD SHAKE & FLASHING SPECIFICATIONS

IRONWOOD SHAKE & FLASHING SPECIFICATIONS 3 1-51 3-3/4 1 IRONWOOD SHAKE & FLASHING SPECIFICATIONS 6 1-13- 1-1-1/4 2-1.5 Drip Edge 2.5 Drip Edge 2-7/8 1-1-1/4 3/4 1 2-1 IRONWOOD SHAKE Overall Length 51 Length of Coverage 48 Width of Coverage 1

More information

BARRELL VAULT BATTENLESS

BARRELL VAULT BATTENLESS i BARRELL VAULT BATTENLESS INSTALLATION GUIDE INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation of the Gerard Barrel Vault battenless

More information

Installation Manual. Future Roof Shingle / Slate Products

Installation Manual. Future Roof Shingle / Slate Products Installation Manual Future Roof Shingle / Slate Products REVISED 14/09/2010 Future Roof Shingle Installation Manual is a component of Future Roof, Inc. and as such is intended to be used with Future Roof

More information

Installation Guide. Titan Old World Slate REV Titan Manufacturing Phone: (407) Fax: (866)

Installation Guide. Titan Old World Slate REV Titan Manufacturing Phone: (407) Fax: (866) Installation Guide Titan Old World Slate REV70908 Titan Manufacturing Phone: (407) 587-5492 Fax: (866) 741-2147 www.titanroofsystems.com This document includes the recommended and suggested installation

More information

Hatteras Shingles. CertainTeed Shingle Applicator s Manual. YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles

Hatteras Shingles. CertainTeed Shingle Applicator s Manual. YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles CertainTeed Applicator s Manual Hatteras s 14 YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles HATTERAS SHINGLES Hatteras shingles are a premium oversize (18" x 36") roofing

More information

DESIGNER SERIES GUTTER SYSTEM INSTALLATION INSTRUCTIONS

DESIGNER SERIES GUTTER SYSTEM INSTALLATION INSTRUCTIONS DESIGNER SERIES GUTTER SYSTEM INSTALLATION INSTRUCTIONS GENERAL DESCRIPTION: The Designer Series Gutter System is a specially designed roof edge drainage product for industrial, commercial, and high end

More information

The City of Winnipeg SHINGLE ROOF REPLACEMENT Section Replacement of Shingle Roof - Louis Riel Library Page 1 of 5 Bid Opp. No.

The City of Winnipeg SHINGLE ROOF REPLACEMENT Section Replacement of Shingle Roof - Louis Riel Library Page 1 of 5 Bid Opp. No. Replacement of Shingle Roof - Louis Riel Library Page 1 of 5 PART 1 GENERAL 1.1 SCOPE OF WORK.1 Total roof area approximately 1,312 m 2. The Work includes, but is not limited to:.1 Removal and disposal

More information

Unless otherwise directed, traditionally cast lead sheet is required.

Unless otherwise directed, traditionally cast lead sheet is required. LEAD ROOFING 1.0 SPECIFICATION OF LEAD SHEETING Unless otherwise directed, traditionally cast lead sheet is required. 2.0 STRIPPING Carefully strip old defective lead and existing coverings from roofs

More information

PREMIUM LAMINATED ASPHALT SHINGLES Frederick, MD

PREMIUM LAMINATED ASPHALT SHINGLES Frederick, MD Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR

More information

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS

PREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR

More information

SPRINGLOK SPRINGLOK FLASHING SYSTEM PRODUCT BROCHURE ENGINEERED PRODUCT SYSTEMS

SPRINGLOK SPRINGLOK FLASHING SYSTEM PRODUCT BROCHURE ENGINEERED PRODUCT SYSTEMS FLASHING SYSTEM ENGINEERED PRODUCT SYSTEMS PRODUCT BROCHURE 2 ND EDITION FLASHING SYSTEM FUNCTIONALLY UNIQUE. ENGINEERED PRODUCT SYSTEMS / FLASHING Fry Reglet comprehensive selection of moisture prevention

More information

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590

More information

DIRECTIONS FOR APPLICATION

DIRECTIONS FOR APPLICATION Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS

More information

Terrabella Shake & Shingle Znap Ver. 2.0

Terrabella Shake & Shingle Znap Ver. 2.0 Terrabella Shake Znap Actual length = 52.6 Actual Width = 16.33 Coverage length = 49.7 Coverage width = 14 Terrabella Shingle Znap Actual Length = 52.375 Actual Width = 15.25 Coverage Length = 49.375 Coverage

More information

SECTION WOOD SHINGLES

SECTION WOOD SHINGLES SECTION 07 31 29.13 WOOD SHINGLES SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. This guide specification does not include requirements

More information

A P P L I C A T I O N I N S T R U C T I O N S

A P P L I C A T I O N I N S T R U C T I O N S 1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE

More information

SECTION ASPHALT SHINGLES

SECTION ASPHALT SHINGLES SECTION 07311 ASPHALT SHINGLES PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Asphalt shingle roofing. 2. Flexible sheet membranes for eave protection, underlayment, and valley protection. 3. Associated

More information

TABLE OF CONTENTS A-1

TABLE OF CONTENTS A-1 TABLE OF CONTENTS PAGE NUMBER: DETAIL DESCRIPTION A-1...TABLE OF CONTENTS A-2...GENERAL NOTES B-1...GENERAL INFORMATION C-1...EAVE DRIP DETAIL C-2...EAVE DRIP with GUTTER DETAIL C-3 & C-4...FIXED RIDGE

More information

DIRECTIONS FOR APPLICATION

DIRECTIONS FOR APPLICATION Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS

More information

TIOGA Table of Contents

TIOGA Table of Contents Table of Contents TABLE OF CONTENTS Product Data Sheet...2 Engineering Data...3 General Information...4 Handling...5 Roof Preparation...5 Fastening Recommendations...6 Field Cutting...7 Touch-up Paint...7

More information

Table of Contents. Notes to Designer/User Map of Typical Roof Conditions Fastener Placement Fastener Selection...

Table of Contents. Notes to Designer/User Map of Typical Roof Conditions Fastener Placement Fastener Selection... Table of Contents Section Page Notes to Designer/User... 2-3 Map of Typical Roof Conditions... 4 Fastener Placement... 5 Fastener Selection... 6 Ridge/Hip Flashing... 7 Valley Flashing... 8 Eave Flashings...

More information

Barrel Vault Counter Batten and Batten

Barrel Vault Counter Batten and Batten Barrel Vault Counter Batten and Batten INSTALLATION GUIDE www.gerardusa.com INSTALLATION NOTIFICATION The installation procedures demonstrated in this manual are recommended methods for the installation

More information

ENGINEERED SLATE 2018 INSTALLATION GUIDE

ENGINEERED SLATE 2018 INSTALLATION GUIDE ENGINEERED SLATE 2018 INSTALLATION GUIDE Table of Contents Contact Information Page 2 General Product Details Page 3 Code Compliance Page 3 Adhesives and Sealants Page 3 General Design Details Page 3

More information

HERITAGE LAMINATED ASPHALT SHINGLES Frederick, MD

HERITAGE LAMINATED ASPHALT SHINGLES Frederick, MD Application Instructions for FORMERLY 30 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR

More information

Installation Manual. For Gerard Shingle Products

Installation Manual. For Gerard Shingle Products Installation Manual For Gerard Shingle Products Gerard Shingle Installation Manual is a component of Gerard roofing products and as such is intended to be used with Gerard products only. All information

More information

DaVinci SlateTM INSTALLATION

DaVinci SlateTM INSTALLATION DaVinci SlateTM INSTALLATION GUIDE DaVinci Slate is a synthetic slate carefully engineered to provide the authentic look and durability of natural slate... at a fraction of the cost and weight. Special

More information

ONDUVILLA. The Attractive Alternative to Shingles I N S T A L L A T I O N I N S T R U C T I O N S

ONDUVILLA. The Attractive Alternative to Shingles I N S T A L L A T I O N I N S T R U C T I O N S ONDUVILLA The Attractive Alternative to Shingles I N S T A L L A T I O N I N S T R U C T I O N S 1 INSTALLATION INSTRUCTIONS Even though ONDUVILLA is easy to install, it is important to read through these

More information

Construction details: Master-C type profiles and joints:

Construction details: Master-C type profiles and joints: Construction details: Master-C type profiles and joints: Master-C 3g 32 mm. (1 1/4 ) 1000 mm. (39 3/8 ) outer face inner face 10.5 fixing details: sealing washers shall be installed through a 2-3/8 x 1-9/16

More information

Installation guide for 20/20

Installation guide for 20/20 Introduction The following installation instructions are recommended minimum requirements for the 20/20. The designer and fixer should ensure that tiles are installed in accordance with BS 5534; The British

More information

DIRECTIONS FOR APPLICATION

DIRECTIONS FOR APPLICATION Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS

More information

MetroCOTTAGE Shingle

MetroCOTTAGE Shingle Batten-less Installation Sept. 14, 2017 INSTALLATION WARNING! These install details are provided to demonstrate a recommended installation method for Metro Roof panels and accessories. used in the United

More information

ROOF FLASHING FEATURES & BENEFITS PRODUCT DESCRIPTION

ROOF FLASHING FEATURES & BENEFITS PRODUCT DESCRIPTION SPRINGLOK SYSTEM PRODUCT DESCRIPTION FEATURES & BENEFITS Fry Reglet offers five flashing systems, each tailored for a particular type of substrate so you can get exactly what you need. SM Surface mounted

More information

TremLock T-138 INSTALLATION MANUAL T-138 www.tremcoroofing.com 3735 Green Road Beachwood, Ohio 44122 1.800.852.6013 50 Beth Nealson Drive Toronto, Ontario M4H 1M6 1.800.668.9879 7241 6/8/18 TABLE OF CONTENTS

More information

Tuff-Rib Install Guide

Tuff-Rib Install Guide Install Guide bestbuymetalroof.com Page 2 of 27 Page 3 of 27 1. Page 4 2. a. Installation Guide b. Panel Squaring Pages 5, 6 Pages 7, 8 3. Pages 9, 10 4. a. Fascia (optional) b. Eave / 1.5x3.5 Angle c.

More information

INSTALLATION GUIDE LEARN MORE AT DECRA.COM

INSTALLATION GUIDE LEARN MORE AT DECRA.COM Villa Tile INSTALLATION GUIDE LEARN MORE AT DECRA.COM Table of Contents DECRA Villa Tile Roof Overview... 2 Introduction... 3 Safety... 3 Tools.... 3 Estimating Sheet... 3 Codes & Requirements... 3 Roof

More information

Asphalt Shingle Installation at Roof Edges, Intersections and Valleys

Asphalt Shingle Installation at Roof Edges, Intersections and Valleys & Asphalt Shingle Installation at Roof Edges, Intersections and Valleys Abstract This updated document is intended to provide additional guidance and options for asphalt shingle installations at roof edges,

More information

Installation Manual. Future Shingle Products

Installation Manual. Future Shingle Products Installation Manual Future Shingle Products TITLE REVISED 7/4/2011 Future Shingle Installation Manual is a component of Future Roof, Inc. and as such is intended to be used with Future Roof products only.

More information

Section 914. JOINT AND WATERPROOFING MATERIALS

Section 914. JOINT AND WATERPROOFING MATERIALS 914.01 Section 914. JOINT AND WATERPROOFING MATERIALS 914.01. General Requirements. Joint and waterproofing material for use in concrete construction must meet the requirements of this section. 914.02.

More information

SECTION ASPHALT SHINGLES

SECTION ASPHALT SHINGLES SECTION 073110 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Asphalt shingles. 2. Felt underlayment. 3. Self-adhering sheet underlayment. 4. Ice Shield Underlayment

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

Table of Contents. Roof to Head Wall w/ Side Flashing DECRA Shake XD Roof Overview Roof Penetration - Pipes & Vents...

Table of Contents. Roof to Head Wall w/ Side Flashing DECRA Shake XD Roof Overview Roof Penetration - Pipes & Vents... Table of Contents DECRA Shake XD Roof Overview.... 2 DECRA Shingle XD Roof Overview.... 3 Introduction... 4 Safety... 4 Tools.... 4 Estimating Sheet... 4 Codes & Requirements... 4 Roof Slope... 4 Underlayment...

More information

ARMORTAB R SUPER TM Shingles Installation Instructions

ARMORTAB R SUPER TM Shingles Installation Instructions ARMORTAB R SUPER Shingles Installation Instructions ARMORTAB SUPER DO NOT REMOVE THE RELEASE TAPE The release tape on the top of the ARMORTAB SUPER is designed to prevent adhesion between the shingles,

More information

Re-Roofing Policy SPECIAL REQUIREMENTS AND NOTES

Re-Roofing Policy SPECIAL REQUIREMENTS AND NOTES CITY OF MANTECA COMMUNITY DEVELOPMENT DEPARTMENT 1001 West Center Street Manteca, CA 95337 FAX (209) 923-8949 Building Safety Division (209) 456-8550 Planning Division (209) 456-8500 Public Works/Engineering

More information

INSTALLATION DETAILS

INSTALLATION DETAILS INSTALLATION DETAILS Front Issued January 23rd, 2005 These install details are provided to demonstrate the recommended installation method for Metro Roof products and accessories. The details and information

More information

METAL ROOFING INSTALLATION GUIDE

METAL ROOFING INSTALLATION GUIDE METAL ROOFING INSTALLATION GUIDE STANDING SEAM ROOFING PANELS Horizon 16 and Climaguard 16 Regardless of whether your roofing project is a new installation or a re-roof, and whether your building is residential,

More information

GLOSSARY OF TERMS SECTION 8

GLOSSARY OF TERMS SECTION 8 GLOSSARY OF TERMS SECTION 8 Anchor Bolt Angle Base Plate Bay Blocking CCB Centerline Chord Cladding Clip Closure Strip An A-307 steel bolt embedded in the concrete footing to anchor the base plate of the

More information

DW HORIZONTAL INSTALLATION

DW HORIZONTAL INSTALLATION AR-PJ-01-DW2H 2" HORIZONTAL PANEL JOINT AR-PJ-02-DW2H 2" VERTICAL PANEL JOINT AR-PJ-03-DW2H 3" HORIZONTAL PANEL JOINT AR-PJ-04-DW2H 3" VERTICAL PANEL JOINT AR-PJ-05-DW2H CUSTOM REVEAL AR-PJ-06-DW2H DW-2000S

More information

DETAIL CROFT FARM OUTBUILDING RESTORATION TOWNSHIP OF CHERRY HILL, NEW JERSEY

DETAIL CROFT FARM OUTBUILDING RESTORATION TOWNSHIP OF CHERRY HILL, NEW JERSEY 2x DIMENSIONAL LUMBER SISTER/SCAB REINFORCEMENT MEMBER 060523 3/8" A304 BOLT @ 8" O.C., STAGGERED EXISTING FRAMING MEMBER SECTION PROVIDE MIN EDGE DISTANCES AS SHOWN, TYP. ELEVATION REFER TO IFICATION

More information

YUKON PATIO COVER INSTALLATION INSTRUCTIONS

YUKON PATIO COVER INSTALLATION INSTRUCTIONS YUKON PATIO COVER INSTALLATION INSTRUCTIONS Before You Begin: Consult your local building department for any required permits You may be required to obtain a building permit for this structure. Contact

More information

Multi-Width Shake. Widths: 9", 8", 7", 6", 4" Length: 22" Thickness at butt: 5/8" Single-Width Shake. Widths: 9" Length: 22" Thickness at butt: 5/8"

Multi-Width Shake. Widths: 9, 8, 7, 6, 4 Length: 22 Thickness at butt: 5/8 Single-Width Shake. Widths: 9 Length: 22 Thickness at butt: 5/8 N DaVinci Shake Multi-Width Shake Single-Width Shake INSTALLATION GUIDE DaVinci polymer shakes are carefully engineered to provide the authentic look of hand-split shakes with dramatically increased durability

More information

PROFESSIONAL PITCHED ROOFING ANCILLARIES

PROFESSIONAL PITCHED ROOFING ANCILLARIES PROFESSIONAL PITCHED ROOFING ANCILLARIES MADE IN BRITAIN Before installing the Easy Roof System, please be aware of the following guidelines: The roof should be installed in the traditional way, with the

More information

CONTENTS. Transitions Board and Batten Vertical Installation... 10,11

CONTENTS. Transitions Board and Batten Vertical Installation... 10,11 INSTALLATION MANUAL CONTENTS Important Notes... 2-4 Weather Protective Barriers... 2 Storage and Transportation... 2 Tools and Equipment... 2 Fastener Choices... 3 Wall Preparation... 3,4 Flashing... 4

More information

Granite Ridge Shingle Guardian Shingle

Granite Ridge Shingle Guardian Shingle Allmet Installation Manual Shingle Profiles Granite Ridge Shingle Guardian Shingle March 2017 This Installation Manual is designed as an instructional tool to clearly depict to the contractor, installer,

More information

Dura-Lock Roof System

Dura-Lock Roof System DLR-14 Dura-Lock Roof System Assembly and Installation Instructions Read the instructions before starting the job. They explain the steps required to produce a finished product that will meet factory specifications.

More information

Shingle Installation Guide

Shingle Installation Guide Installation Guide Roof Framing Information Installation Installation Accessory Installation Estimating Data General Information Roof Framing Information It is the responsibility or roofers, building contractors

More information

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013.

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1790 Reissued September 1, 2012 This report is subject to renewal September 1, 2013. A Subsidiary of the International Code Council

More information

KS SERIES - VERTICAL INSTALLATION

KS SERIES - VERTICAL INSTALLATION CS-DS-01-KSV CS DISCLAIMER CS-PJ-01-KSV KS42SL EXPANDED PANEL JOINT CS-PJ-02-KSV KS42SL ENGAGED PANEL JOINT CS-PJ-03-KSV KS45SL EXPANDED PANEL JOINT CS-PJ-04-KSV KS45 FLAT ENGAGED PANEL JOINT CS-PJ-05-KSV

More information

Installing Quick Mount PV Products on. Metal Shingle Roofs RESPECT THE ROOF

Installing Quick Mount PV Products on. Metal Shingle Roofs RESPECT THE ROOF Installing Quick Mount PV Products on Metal Shingle Roofs RESPECT THE ROOF Getting Started Steel Shingle Roofing Flashing Method and Product Type Terminology Flashing QBase Mount Interlocking Steel Shingle

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 07311 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

Installation Guidelines

Installation Guidelines Installation Guidelines Tando Building Products provides these instructions as general guidelines only. Tando Building Products neither installs exterior cladding nor has any control over any installation.

More information

Panel Guard Installation For Adhesive Attachment

Panel Guard Installation For Adhesive Attachment For Adhesive Attachment 1. Clean roof surface with isopropyl alcohol where snow guard is to be attached-ensure area is completely dry before attaching snow guard 2. Cut tip of adhesive nozzle (Surebond

More information

I n s t a l l i n g Enviroshingle APPLICATION INSTALLATION GUIDELINE

I n s t a l l i n g Enviroshingle APPLICATION INSTALLATION GUIDELINE I n s t a l l i n g Enviroshingle APPLICATION INSTALLATION GUIDELINE home This Guideline and Installation Diagram have been designed for printability for your convenience. To ensure this we have maintained

More information

900 SERIES PANEL SHEET INDEX STAGGERED ENDLAP STAGGERED MALE LEG AT ENDLAP CONTINUOUS FEMALE ENDLAP INSTALLATION SEQUENCE CI-WR

900 SERIES PANEL SHEET INDEX STAGGERED ENDLAP STAGGERED MALE LEG AT ENDLAP CONTINUOUS FEMALE ENDLAP INSTALLATION SEQUENCE CI-WR 900 SERIES PANEL CI-DS-01-900 CI-PJ-01-900 CI-PJ-02-900 CI-EL-01-900 CI-EL-02-900 CI-EL-03-900 CI-EL-04-900 CI-EL-05-900 CI-EL-06-900 CI-EL-07-900 CI-EL-08-900 CI-RD-01-900 CI-RD-02-900 CI-RD-03-900 CI-EV-01-900

More information

METRO PANELS (EXPOSED

METRO PANELS (EXPOSED METRO PANELS 001EX-METRO-PANELS.VSD STARTER EAVE Detail Metro V-Bat RISER METAL (1) PANELS (2) FASTENERS (5) BOTTOM ROW fastening 0.75in. (4) METRO RISER Metal, With Integral Batten Riser & Locator-Lip.

More information