1 Low Voltage Products Enclosed Third Harmonic Filter and star Enclosed units Brochure S1GB 3_4 1SCC333C21

2 The Third Harmonic - a Growing Problem Today's electrical networks and plants are under much more stress than a decade ago. One reason for this is the increasing use of electric equipment that generate harmonics: in particular the third harmonic. This harmonic can generate exceptionally high neutral currents which can often exceed even the phase current. Equipment that generate harmonics: Fluorescent lighting systems Computers Welding equipment UPS Rectifiers TV monitors Microwave ovens 1,,, , 1,,4 3. -,4, , 1,,4 3. -,4, UPS -1, 1,,4, -,4, , 1, S1521A S248A, -1,, The third harmonics are accumulated in the neutral conductor. The Third Harmonic Causes Many Problems Problems are directly related to the harmonic content. The third harmonic found in the phase current appears neutral thus increasing the neutral current. See illustration above. In network: Overheating Increased power losses Poor quality of electricity Electromagnetic fields Malfunctions in earth fault control Failure in remote control systems In plants: Malfunction in electronics Damage to capacitors Power losses Increased magnetic fields Overload in neutral conductor Cable fires Abnormal temperature changes and noise in transformers uisance tripping in circuit-breakers Shorter life time 2 Low Voltage Products

3 The Solution- The Third Harmonic Filter star The third harmonic filter star removes the third harmonic current from the network. The third harmonic currents generated by the single phase loads flowing in the phase conductors sum up in the neutral conductor. The neutral current may be higher than the phase current. The filter mitigates the third harmonic current from the whole network from the luminances to the distribution panel, main switchboard up to the supply transformers medium voltage winding. The mitigation effect is the same both at the line and load side. The filtering application is patented. patented application S1528B Example on how Third Harmonic Filter effects on third harmonic currents. Transformer Transformer 21A _ 11A 13A 16A 32A 8A 6A 7A 21A Load Load Benefits of for lighting and mixed load Increased efficiency in low voltage network Reduction in transmission losses Increased loadability of the existing network and switchboards Lower temperature of cables, switchboards and transformers Elimination of third harmonic current in neutral and phase conductor S25A TS Increased efficiency in lighting appliance and pc-load Less power or more lighting Less maintenance Longer lifetime of the lamps and capacitors 3,5 3 2,5 Reduced Magnetic fields The reduction of third harmonic component of the current reduces the total magnetic field Diagram indicating an example of the total magnetic field spectrum typically in various locations 2 3,5 1 S1527A,5 Without With Diagram indicating the level of magnetic field with and without Third Harmonic Filter, Hospital building. Low Voltage Products 3

4 Selection and dimensioning of the product range Third harmonic filters star and The size of the -filters is selected according to the supply transformer or back up fuses. The protection unit needs to be used, in case the dimensioning exceeds the thermal rating of the filter. S1544A () The basis of dimensioning is that the filter withstands the 15Hz voltage and the fundamental neutral current generated by the phase unbalance. The star filters are tested according to the highest possible short circuit current or back up fuse. The filter is not suitable for applications including largely dimmer loads. Please consult with us. S1545A Installation to the transformer star point, enclosed filters and system components,star The new generation third harmonic filter star is designed for small size and economical solutions to places, which are especially exposed by third harmonic currents. The filter can be installed outdoor in vicinity of transformer stations, as retrofitting to existing transformer station or as additional field of main switchboard. It is recommended to install the filter star in conductor, whenever possible, equipped with appropriate protection unit 1S_. DIMESIOIG: According to the supply transformer PROTECTIO: Protection unit S1_S, 5Hz and 15 Hz measurement according to the mounting instruction etwork Rated current Transformer Enclosed Units System Input-Output Internal of the size components cable/ busbar connection to T-C, T-S transformer kva Indoor Outdoor IP the filter A IP3 IP34 8 1) 63 S5US1 S4A1 Acc. to phase 33% of phase 9 63 S63S1 S63U1 + 1_S conductors conductor S1544A () S63A1 Acc. to phase 33% of phase S1S1 S1U1 + 1_S conductors conductor S1A1 Acc. to phase 33% of phase S16S1 S16U1 + 1_S conductors conductor 32 2 S16S1x2 S16U1x2 S63A1x2 Acc. to phase 33% of phase conductors conductor ote: System components in brochure S 2 GB Installation for distribution boards in T-S-system, enclosed filter and system components, filters are designed in T-S-systems to provide selective mitigation of isolated groups with local or central compensation. The is normally installed in the load side neutral output of UPS-devise. is dimensioned according to the group fuses. In case the dimensioning is below 1% it is recommended to use additional protection unit. The filter types V include guard units to keep track of the -current in the area of A. DIMESIOIG: According to the group fuse- rated current = rated current of the fuse link PROTECTIO: Guard unit (_V), 15Hz measurement from -conductor of the group etwork Rated current Enclosed Units System Cross-section Internal of the components Input-Output connection to T-S group fuse Indoor IP3 IP cable the filter A mm 2 mm V 63B V 63B V 63B x V 63B x LV B x S1545A ote: System components in brochure S 2 GB 4 Low Voltage Products

5 Auto A B A1 A A B A1 A2 4 2 A1 A A B V~ 5/6Hz SM V~ 5/6Hz SM Aut I O Enclosed third harmonic filters star, Ordering information Technical information S1552A FILTER BYBASS O OFF MS Enclosed third harmonic filters star Installation to transformer star point. The delivery includes protection unit, by-pass contactor and switch as well as the overload proof current transformer. Indoor use IP 3. Cabling from bottom or top Transformer size Dimensions Input-Output Type Order Weight [kva] [A] L x S x K [mm] Cabling /Busbar Code [kg] x 36 x 12 2 x 15 mm 2 Cu S 5US1 1) x 654 x x 15 mm 2 Cu S 63S1 4 (max 4 cables) x 654 x x 15 mm 2 Cu S 1S1 52 (max 6 cables) x 654 x 226 Busbar 2x1x12 S 16S x 15 mmm 2 Cu 1) Cabling from bottom S_S1 Outdoor use IP 34. Includes base element, cabling from bottom Transformer size Dimensions Input-Output Type Weight [kva] [A] L x S x K [mm] Cabling / Busbar [kg] x 36 x 12 2 x 15mm 2 Cu S 63U1 31 (max 4 cables) x 72 x 12 4 x 15mm 2 Cu S 1U1 45 (max 6 cables) x 72 x 12 Busbar 2x1x12 S 16U x 15 mmm 2 Cu S_U1 Example on 16kVA filter joints S1536A Reset R Strömberg OK ByPass Enclosed third harmonic filters Installation to T-S-system. Filter suitable for voltage 69V. Steel sheet enclosure. Group Connection Dimensions Protection Type Order Weight fuse cable (Cu) (LxSxK) degree Code [A] [mm 2 ] [mm] [kg] Third harmonic filters including guard unit and by-pass contactor Current transformer of the relay, cable diameter max. 27 mm, is included in the delivery x18x4 IP 3 25V 1SCA22388R x23x6 IP 3 63V 1SCA22374R x23x1 IP 3 125V 1SCA22374R and 15 4x23x14 IP 3 125LV 1SCA22378R and 7 8x23x1 IP 3 16V 1SCA22374R Third harmonic filters without guard unit and by-pass contactor Can be used parallel with V- and LV- types x23x6 IP SCA22325R x23x1 IP SCA22325R and 15 4x23x14 IP 3 125L 1SCA22358R and 7 8x23x1 IP SCA22325R OTE: 125 L include space for parallel connection of several filters. 63V S978A 1BS For increased protection of Protection unit Back up Terminals Dimensions Protection Type Order Weight fuse (HxWxD) degree Code [mm 2 ] / Cu [mm] [kg] Open type 1A x35x15 IP 1BS 1SCA22457R x4x15 1BSMS 1SCA22437R Enclosed 1A 2.5 4x35x15 IP44 1S 1SCA22468R (Sheet steel) Current transformers 5/6Hz Error R Reset OK ByPass 5/6Hz 15/18Hz 15/18Hz Error Current Overload Type Order ratio value code S977A 25/1 8A KORE 6F1-25/1 1SCA22458R426 Strömberg 1S Low Voltage Products 5

6 Enclosed third harmonic filters star Installation to the transformer star point The third harmonic filters star are installed in the neutral- or -conductor between the unearthed transformer star point and the neutral busbar of the distribution board. All neutral and earth currents need to be conducted through the current transformer of the protection unit. The protection unit is connected to reliable auxiliary voltage source. S_ 1 A S161A I O Protection unit 23 VAC 3 X 1,5 mm 2 TRASFORMER IPUT OUTPUT MAI DISTRIBUTIO BOARD () Installation of star filters in transformer circuits in T-C system In T-C -system the star filter is installed in the transformer star point. There must be no earthing between the starpoint of the transformer and the incoming terminal of star filter. S1522A Incorrect installation Because of earth current, star filters cannot be installed in the conductor of a four-conductor system. Incorrect installation Earthing is allowed only after star filter. Approvals SGS-FIMKO Oy' s certification on use in neutral conductor. o standards available sofar. Approval in EU area acc. to CEELEC Memorandum 7. CE certificate Standards IEC IEC 76-1 IEC 289 IEC 831-1/2 6 Low Voltage Products

7 Protection unit The purpose of the protection unit is to limit the fundamental unbalance current, protect star for overloading and to detect the increased third harmonic current due to network failure or failure of star. The protection unit 1_S and current transformer are included in the delivery. The protection unit include 5Hz and 15Hz measurement circuits. The current transformer need to be installed so that all neutral and vagabonding currents pass through it to the star point of the transformer. In case of failure the protection unit is closing the by-pass contactor of the filter. S985A I > K1 Installation of star in the star points of parallel transformers or generators star is installed between points A and B. The isolation resistance after the point B needs to be measured over R e > 5 kω. The filters in both star points, -conductors- need to be controlled simultaneously. Alternative ways of installation: D GE. A1 A2 A1 A2 B1 B2 B1 B2 A S982A S983A S984A B Low Voltage Products 7

8 Installation of filter for distribution boards T-S -system T-S -system In T-S system the filter can be installed in the neutral conductor. The network must be a pure T-S system. Fault current monitoring is recommended. Before the installation the state of T-S-system shall be verified by measuring the isolation resistance in the poles where is to be installed. It is advisable to install the filter in the transformer star point even in T-S-system. In that case there is no 15 Hz voltage between and. See installation of star filter for transformer circuits on page 6. SUPPLY ETWORK UPS L BATTERY ~ = ~ = STATIC BYPASS SWITCH S1523A MAUAL BYPASS SWITCH In T-S system the neutral and shall be connected in one point only, when the filter is installed in the neutral conductor, there cannot be any connections between and in the loadside. S118A UPS ETWORK L Installation example UPS. -filter is installed in the load side output terminal of the neutral conductor. Selection of filter for distribution boards in the T-S-system The filter is installed in the neutral conductor. A filter is sized according to the distribution board or the fuse, which is supplying the group. The basis of the factory dimensioning of the filter is the fact that a filter installed in the neutral conductor bears, in addition to the 15 Hz current, a 5 Hz component which may reach 1 % of the phase current (fully asymmetrical load). Size of Recommended cable size of neutral conductors feeding Quantity & Type eutral Cables between fuse conductor filters in-out Cross section [A] Cross section 25 1 x 25V 6 mm x 63V 16 mm x 125V 35 mm x 16V 5 mm x 16V + 1 x 63 7 mm 2 16 mm 2 8 Low Voltage Products

9 Guard unit The -units for T-S-system include guard unit (_V). The purpose of guard unit is to supervise the network condition by measuring the level of the current of the -conductor of the group. In case the -current exceeding the set level in the area of 4A 1A, the guard unit closes the by-pass contactor of and can give an alarm. If increased protection is needed, the group fuse is bigger than the rated current of the filter, or in case of large cable diameters, the -filters can be provided with an extra protection unit and current transformer. In those cases the star is recommended. The protection unit is controlling the by-pass contactor of the in case of large 5 Hz current or when the 15Hz current exceeds the set limit. The current transformer is installed in the -conductor alt. the -conductor depending on the installation. S1536A Reset R Aut Strömberg OK ByPass equipped with quard unit. equipped with optional protection unit. _V 1A GUARD star Protection unit 1A K1 S1525A S1524B installed in neutral conductor of T-S system equipped with quard unit. Measurement from conductor. star filter installed in neutral conductor of T-S system equipped with optional protection unit. Measurement from and conductors. Connection example: filter with guard unit 25V 63V 125V 16V 125LV F1 1A S1 K2 9 S2 8 I > t 6 S2 21 R 22 5 S1 Aut F1 1A 1 K2 1 K11 2 S1 9 S2 8 I > t 6 S2 21 R 22 5 S1 Aut S1533A K OK Load Load Load S1534A K1 A1 A2 K11 A1 A ByPass OK Load Load Load Low Voltage Products 9

10 I O Specification of harmonic filter Example star Type: S 16 S1 Rated voltage: 4V Dimensioning according to the transformer size:16 kva Removes the third harmonic current from the phase and neutral conductor Dimensioning current/ Max continuous current: 225A/ 8A Dimensioning voltage: 4V 15Hz The filter allows subsequent increasing of the harmonic load without retrofitting Short circuit dimensioning according to max. available short circuit The filter is stand along type and not influencing on the power factor compensation The filter is not influencing on carrier- wave-line. Main incoming breaker: Max. time delay:,2 s Terminations: Max six cables of 3mm 2 The filter is equipped with by-pass switch for commisoning S1552A FILTER BYBASS O OFF MS Stand along enclosure: indoor use IP3 outdoor use IP34 Accommodation: In the vicinity of transformer station Retrofitting to the transformer station In the main switchboard The star removes typically 95% of the third harmonic current from the whole network from line and load side independent of the magnitude of the third harmonic current. For example the neutral current reduces from 45A down to 25A and in the phase conductors from 15A to 1A. The same mitigation prevails in the whole network from the transformer windings to the lamps and computers. The magnetic field from the construction and earthing wiring reduces typically by 5% due to mitigation of the vagabonding currents ( 5% of magnetic field usually of 15 Hz origin). The iron, copper and resistance losses reduce the temperature and noise level of the supply transformer doubling the lifetime of the transformer by every 8 degrees C. The filter reduces the resistance losses (I 2 R) For example: Before: (45A) 2 x,1 Ω = 225 W Filter installed: (25A) 2 x,1 Ω = 62,5 W The filter include protection unit, which limit the 5Hz unbalance current and 15Hz fault current Check star filters Installation and commissioning: The installation of star is in theory easy but in practice certain points have to be checked : Ensure by measurement that there is no parallel current path to the filter Check up also the possible influence of parallel transformers or generators Ensure that the filter is installed in the right location. The neutral conductor from the star point of the transformer is the recommended place. Check up that the current measurement is right. The CT shall always measure the sum of all neutral and earth currents of the network. Check up the relay setting of the protection unit. Check up that there is no largely dimmer loads. Read mounting instruction 341S 1 Low Voltage Products

11 Installation examples T-S-system, where the original cabling to the transformer star point need to be displaced to fundamentally same position in the -conductor of the main switchboard. star installation. Transformer X -S S Main switchboard X S1541B Main earthing busbar Earthing electrode Concrete iron fitting Water meter T-C-S system Alternative installation examples when using star with protection unit(_s) or with guard unit(_v). Transformer -S S Main switchboard 1) -S S/ Distribution switchboard S1543B -V -V Earthing busbar of transformer station Main earthing busbar Distribution swtichboard Earthing electrode Concrete iron fitting Water meter T-S system Alternative installation example when using star with protection unit(_s) or with guard unit(_v). Transformer -S S Main switchboard 1) -S S/ Distribution switchboard S1542B -V -V Earthing busbar of transformer station Main earthing busbar Distribution swtichboard 1) In this installation model, the current transformer need to measure both - and -current, unless additional guard unit is used. S1549A S Earthing electrode Concrete iron fitting Water meter Low Voltage Products 11

12 The technical data and dimensions are valid at the time of printing. We reserve the right to subsequent alterations. Brochure S1GB 3_4 1SCC333C21 Waasa Graphics Oy, Vaasa Finland ABB Oy Low Voltage Products P.O. Box 622 FI-6511 VAASA, Finland Telephone Telefax The operations of the manufacturing plant have been certified.

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201

Low Voltage Products. Third Harmonic Filter THF and THF star System components for assembly and retrofitting. Catalogue THFS2GB 03_05 1SCC330004C0201 Low Voltage Products Third Harmonic Filter and star System components for assembly and retrofitting Catalogue SGB _ SCCC System components for assembly and retrofitting star, installation in the transformer

More information

Tuningintobetter power quality

Tuningintobetter power quality Technology Review Third harmonic filters Tuningintobetter power quality Jouko Jaakkola Your PC screen flickers, stops flickering, starts again... Irritating to be sure, and perhaps the first visible sign

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

LV Compensation & Filtering Products

LV Compensation & Filtering Products GE Grid Solutions LV Compensation & Filtering Products Providing Power Quality and Energy Efficiency Low (LV) reactive power compensation and harmonic filtering solutions help customers to improve the

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

Cahier technique no. 212

Cahier technique no. 212 Collection Technique... Cahier technique no. 212 The neutral: A live and unique conductor J. Schonek Building a ew Electric World "Cahiers Techniques" is a collection of documents intended for engineers

More information

ET 40 - Electrician Theory Examination Marking Schedule

ET 40 - Electrician Theory Examination Marking Schedule ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Active Harmonic Filter

Active Harmonic Filter Reactive Power and Harmonic Compensation Active Harmonic Filter The new StacoSine Plus active harmonic filter is available in 100, 150, 200 and 300 amp assemblies. Modules can be paralleled for a maximum

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Technical Data Sheets

Technical Data Sheets GE Consumer & Industrial Power Protection Technical Data Sheets Digital Energy Uninterruptible Power Supply SG Series 80 100 120 kva 400 Vac CE Series 0 Date of issue: 01.11.2007 SGSE_080_UPS_GE_01a SGSE_100-120_UPS_GE_01a

More information

Emicon Engineering Consultants L.L.C.

Emicon Engineering Consultants L.L.C. Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com

More information

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

Miniature circuit-breakers S 280 UC series. System pro M. Technical data Technical data 11 Robbie Rd. / Avon, MA 02322 T:(508)513-1000 F:(508)513-1100 70 Ernest St. / Providence, RI 02905 T:(401)781-7100 www.controllerservice.com System pro M Prior to connection of aluminum

More information

Magtech Voltage Booster MVB

Magtech Voltage Booster MVB Model overview MVB 27.03.08 EG.doc Magtech Voltage Booster Voltage fluctuations caused by unbalanced load in Y-ground grid? Low voltage part of the day due to high load? Quick and profitable solution with

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

Magtech Voltage Booster MVB

Magtech Voltage Booster MVB Model overview MVB 30.04.09 EG.doc Magtech Voltage Booster Voltage fluctuations caused by unbalanced load in Y-ground grid? Low voltage part of the day due to high load? Quick and profitable solution with

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Understanding Harmonics

Understanding Harmonics Understanding Harmonics Terry Gaiser Sensus What Are Harmonics? 1 » What is Power Quality?» Power quality is the degree to which both the utilization and delivery of electric power affects the performance

More information

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.

Harmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics

More information

Power IT LV Active Filters PQFA - PQFL - PQFT

Power IT LV Active Filters PQFA - PQFL - PQFT Power IT LV Active Filters PQFA - PQFL - PQFT The ABB comprehensive solution for active filtering of harmonics Pst Harmonics and Power Quality Harmonics caused by non-linear electrical loads such as variable

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with

More information

7P Series - Surge Protection Device (SPD) Features 7P P P

7P Series - Surge Protection Device (SPD) Features 7P P P Features 7P.09.1.255.0100 7P.01.8.260.1025 7P.02.8.260.1025 SPD Type 1+2 Surge arrester range - single phase system / three phase system Surge arresters suitable in low-voltage applications in order to

More information

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28 SPAD 6 C Stabilized Differential Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = A 5A ( I ) I n = A 5A ( I 0 ) I n = A 5A ( I 0 ) 5 I I d L L I L I > IRF I 0 > I 0

More information

StacoDVR-5 60kVA to 6000kVA

StacoDVR-5 60kVA to 6000kVA StacoDVR- 5: 3- ph. Voltage Regulator Why choose a voltage regulator The availability of steady voltage supply is critical for a number of situations involving voltage sensitive equipment. Whether because

More information

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL 1 Contents 1. Application... 5 2. meter set... 6 3. BASIC REQUIREMENTS, OPERATIONAL SAFETy... 6 4. installation... 10 4.1. Mounting... 10 4.2. External

More information

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS

2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS 2kVA EARTH TESTING CURRENT INJECTION SYSTEM 4046 / 4047 DATASHEET REDPHASE INSTRUMENTS Contents Section Brief Description... 1 Where and why it is used... 1.1 Induced Measureable Parameters... 1.2 Hardware

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

Sensor Technology. Applications for medium voltage

Sensor Technology. Applications for medium voltage Sensor Technology Applications for medium voltage Contents Introduction to sensor technology... 3 Sensors versus instrument transformers... 6 Advantages for builders and users of switchgear... 7 The impact

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Current Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other

More information

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications Electrical Power Systems PSL2 Investigates the principles and operating characteristics of single-phase and three-phase power and distribution transformers Key Features Educational transformers with fully

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

Electromagnetic Harmonic Filters Technical Guide

Electromagnetic Harmonic Filters Technical Guide Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Active Harmonic Filters IPC150 AHF Series

Active Harmonic Filters IPC150 AHF Series IPC150 AHF Series Multi Function Ultra Fast Power Quality Compensation Harmonics Power Factor Correction Unbalance Compensation www.inphase.in ISO 9001:2008 Certified THE CHALLENGE To increase the productivity,

More information

General Requirements. Technical Specification LVAC Systems

General Requirements. Technical Specification LVAC Systems Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks LVAC Systems NO: 423-1

More information

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A) IRI1-ER - Stabilized Earth Fault Current Relay Manual IRI1-ER (Revision A) Woodward Manual IRI-ER GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

The future of installation testing is here. The Fluke 1650 Series Multifunction Testers

The future of installation testing is here. The Fluke 1650 Series Multifunction Testers The future of installation testing is here The Fluke 50 Series Multifunction Testers Fluke 50 Series Safer, easier installation testing. The 50 Series testers verify the safety of electrical installations

More information

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale

Specifications. S&C BankGuard Plus Controls. For Substation Capacitor Banks and Shunt Reactors. Conditions of Sale For Substation Capacitor Banks and Shunt Reactors Specifications Conditions of Sale STANDARD: Seller s standard conditions of sale set forth in Price Sheet 150 apply, except as modified by the SPE CIAL

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters Power factor correction and harmonic filtering 5 R. /6 Automatic capacitor banks with detuned filters R. 5 /6 Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 - Automatic capacitor

More information

IRI1-ER - Stabilized Earth Fault Current Relay

IRI1-ER - Stabilized Earth Fault Current Relay IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters الکتروه م ند Power factor correction and harmonic filtering Automatic capacitor banks with detuned filters www.electrohamand.com Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 -

More information

Section 3. Test Procedures

Section 3. Test Procedures Section 3. Information contained within this section shall be read in conjunction with all sections of this manual Non - Compliant Test Results Where acceptable results are not attained in accordance with

More information

I -limiter The world s fastest switching device

I -limiter The world s fastest switching device I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection

More information

Wireless multizone receiver RDE-MZ6

Wireless multizone receiver RDE-MZ6 s 1 428 Wireless multizone receiver RDE-MZ6 for floor heating / zone heating systems Mains-powered RDE-MZ6 multizone wireless receiver (AC 230 V) DIN rail mounting 2-position control with On/Off output

More information

ABB n.v. Power Quality Products, October 2014

ABB n.v. Power Quality Products, October 2014 ABB n.v. Power Quality Products, October 2014 Power Quality Harmonic Basics Problems and solutions March 19, 2015 Slide 1 828m high 160 floors in total Total 113 PQF in this tower, 12000A PQFS 45M IP30

More information

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS

Liebert Hipulse-U. Fully Digital Dual DSP Controlled Transformer Based UPS Liebert Hipulse-U Fully Digital Dual DSP Controlled Transformer Based UPS Addressing a Variety of Needs The Liebert Hipulse-U offers a reliable, scalable and user-friendly solution to ensure availability

More information

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str. 65 35305 Grünberg Tel.: 0640 807-0 Fax: 0640 807-259 IT system floor-standing distribution cabinet Series -IPS-F/EDS for supplying power to medical locations

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

QUINT-PS/ 3AC/24DC/10

QUINT-PS/ 3AC/24DC/10 Primary-switched power supply with SFB technology, 3 AC, output current 10 A INTERFACE Data sheet 103131_en_01 1 Description PHOENIX CONTACT - 09/2009 Features QUINT POWER power supply units Maximum system

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

CONTENTS XV300K GB r doc XV300K 2/13

CONTENTS XV300K GB r doc XV300K 2/13 XV300K CONTENTS 1 PRELIMINARY CHECK GUARANTEE RECYCLING... 3 2 XV300K SPECIFICATIONS OF USE... 3 3 CODES - MODELS... 4 4 TECHNICAL SPECIFICATIONS... 4 5 STANDARD REFERENCES... 5 6 MECHANICAL INSTALLATION...

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

MODULAR DC POWER SUPPLIES & SYSTEMS. DC Power Systems DC/AC Inverters Static Switches DC/DC Converters. GAMATRONIC, A SolarEdge Division

MODULAR DC POWER SUPPLIES & SYSTEMS. DC Power Systems DC/AC Inverters Static Switches DC/DC Converters. GAMATRONIC, A SolarEdge Division MODULAR DC POWER SUPPLIES & SYSTEMS DC Power Systems DC/AC Inverters Static Switches DC/DC Converters GAMATRONIC, A SolarEdge Division 17 Hartom Street, Jerusalem 9777517, Israel 1-800-20-70-90 Tel: +972-2-5888277

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

PROJECT: SUPPLY & INSTALL ELECTRICAL SWITCHBOARD AT SENGKURONG EXCHANGE PHASE 1, JLN TUTONG, BSB. SCOPE OF WORK The scope of work under Electrical Services shall include but not limited to the supply,

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an

Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an EDS309 Portable equipment for insulation fault location for unearthed and earthed systems (IT and TN systems) to be used in conjunction with or without an equipment for insulation fault location EDS309x_D00012_02_D_XXEN/11.2018

More information

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter

PFCC-1000 series. Powerful Flexibility Durability - Quality. Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter PFCC-1000 series Medium Voltage Metal Enclose 5,15,25,35kV Power Factor Correction & Harmonic Filter Powerful Flexibility Durability - Quality email.us.at:.quotes@tanddproducts.com www.tanddproducts.com

More information

StatiVolt. Inverter UPS Systems. Features. Contents

StatiVolt. Inverter UPS Systems. Features. Contents Redundant, clean, sine-wave AC power ensures a high availability of mission-critical safety devices, instrumentation, alarms, controls and computers. Robust, StatiVolt UPS Systems are designed and built

More information

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd. High-Tech Range IRI1-ER- Stablized Earth Fault Current Relay C&S Protection & Control Ltd. Contents 1. Summary 7. Housing 2. Applications 3. Characteristics and features 4. Design 7.1 Individual housing

More information

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-50 Delivery program Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection Part no. PKZM4-50 Catalog No. 222355 Eaton Catalog No. XTPR050DC1NL EL-Nummer 0004355161 (Norway)

More information

B9000 FXS kVA B9600 FXS kVA

B9000 FXS kVA B9600 FXS kVA OF CONTINUOUS SERVICE YEARS WARRANTY B9000 FXS 60-300kVA B9600 FXS 400-800kVA BORRI B9000 FXS B9600 FXS With disturbances to the electrical supply being one of the major causes of IT downtime, the UPS

More information

High Technology Control

High Technology Control High Technology Control Michael Linden ABB National Drives Manager for High Technology Control Pty Ltd High Technology Control Variable Frequency Drives Variable Voltage Variable Frequency Drives Variable

More information

Frequently Asked Question on Isolated Power Supply(IPS)

Frequently Asked Question on Isolated Power Supply(IPS) Frequently Asked Question on Isolated Power Supply(IPS) Q: What is an IPS? A: IPS is called as Isolated Power Supply or System and is used in a Hospital to ensure safe power supply to OT Operation Theaters

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Description Basic devices with positive operation contacts. Connection to SmartWire-DT yes in conjunction with DIL-SWD SmartWire DT contactor module

Description Basic devices with positive operation contacts. Connection to SmartWire-DT yes in conjunction with DIL-SWD SmartWire DT contactor module DATASHEET - DILA-22(24VDC) Delivery program Contactor relay, 2N/O+2N/C, DC current Part no. DILA-22(24VDC) Catalog No. 276414 Eaton Catalog No. XTRE10B22TD EL-Nummer 4130211 (Norway) Product range DILA

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Frequency Converter SFX 10kVA - 10MVA Static Frequency Converter SFX 10kVA - 10MVA A Concept Thycon Static Frequency Converters (SFX) convert supply frequency to load requirement frequency.

More information