1 Engineering Recommendation G83/2 Type Approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G83/2. Type reference number STL 300 Type System Supplier name PHOTOVOLTAIC GRID TIED INVERTER SELCO s.r.l. Address Via Palladio Onara di Tombolo (PADOVA) ITALY Tel Fax E:mail Web site Connection Option 3 kw single phase, single, split or three phase system Maximum rated capacity, use separate sheet if more than one connection option. kw three phase kw two phases in three phase system kw two phases split phase system manufacturer/supplier declaration. I certify on behalf of the company named above as a manufacturer/supplier of Small Scale Embedded Generators, that all products manufactured/supplied by the company with the above Type reference number will be manufactured and tested to ensure that they perform as stated in this Type Verification Test Report, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G83/2. Signed Date: 28/2/2013 Lino Frasson Chief Executive SELCO s.r.l. Via Palladio Onara di Tombolo (PD) - ITALY STL300_G83-2_ _rev. 1.0.docx Pagina 1/5
2 G83/2 - Appendix 4 - Type Verification Test Report Power Quality. Harmonics. The requirement is specified in section 5.4.1, test procedure in Annex A or B rating per phase (rpp) 3 kw NV=MV*3.68/rpp Harmonic At 45-55% of rated 100% of rated Value (MV) in Amps Normalised Value (NV) in Amps Value (MV) in Amps Normalised Value (NV) in Amps Limit in BS EN in Amps Higher limit for odd harmonics 21 and above 2 0,026 0,032 0,039 0, ,024 0,029 0,032 0, ,010 0,012 0,014 0, ,044 0,054 0,050 0, ,007 0,009 0,010 0, ,010 0,012 0,041 0, ,007 0,009 0,009 0, ,034 0,042 0,035 0, ,008 0,010 0,011 0, ,051 0,063 0,040 0, ,011 0,013 0,013 0, ,016 0,020 0,028 0, ,021 0,026 0,019 0, ,079 0,097 0,027 0, ,019 0,023 0,020 0, ,045 0,055 0,018 0, ,047 0,058 0,050 0, ,017 0,021 0,042 0, ,033 0,040 0,037 0, ,040 0,049 0,015 0, ,014 0,017 0,014 0, ,017 0,021 0,050 0, ,010 0,012 0,011 0, ,015 0,018 0,028 0, ,010 0,012 0,009 0, ,028 0,034 0,029 0, ,010 0,012 0,009 0, ,009 0,011 0,026 0, ,009 0,011 0,008 0, ,020 0,025 0,012 0, ,006 0,007 0,008 0, ,005 0,006 0,012 0, ,005 0,006 0,008 0, ,009 0,011 0,012 0, ,007 0,009 0,009 0, ,008 0,010 0,007 0, ,004 0,005 0,006 0, ,004 0,005 0,007 0, ,003 0,004 0,005 0, STL300_G83-2_ _rev. 1.0.docx Pagina 2/5
3 Power Quality. Voltage fluctuations and Flicker. The requirement is specified in section 5.4.2, test procedure in Annex A or B Starting Stopping Running d max d c d (t) d max d c d (t) P st P lt 2 hours Values 2.833% 2.311% % 2.311% Normalised to standard impedance and 3.68kW for multiple units Limits set under BS EN % 2.835% % 2.835% % 3.3% 3.3% 500ms 4% 3.3% 3.3% 500ms Power quality. DC injection. The requirement is specified in section 5.5, test procedure in Annex A or B Test power level Recorded value as % of rated AC current 10% 55% 100% 5mA 10mA 10mA 0.04% 0,08% 0.08% Limit 0.25% 0.25% 0.25% Power Quality. Power factor. The requirement is specified in section 5.6, test procedure in Annex A or B value 216.2V 230V 253V at three voltage levels and at full >0.99 >0.99 >0.99. Voltage to be maintained within ±1.5% of the stated level during the test. Limit >0.95 >0.95 >0.95 Protection. Frequency tests The requirement is specified in section 5.3.1, test procedure in Annex A or B Function Setting Trip test tests Frequency Time Frequency Time Frequency /time Confirm no trip U/F stage Hz 20s 47.4Hz s 47.7Hz / 25s U/F stage 2 47Hz 0.5s 46.9Hz s 47.2Hz / 19.98s 46.8Hz / 0.48s O/F stage Hz 90s 51.6Hz s 51.3Hz / 95s O/F stage 2 52Hz 0.5s 52.1Hz s 51.8Hz / 89.98s 52.2Hz / 0.48s STL300_G83-2_ _rev. 1.0.docx Pagina 3/5
4 Protection. Voltage tests The requirement is specified in section 5.3.1, test procedure in Annex A or B Function Setting Trip test tests Voltage Time Voltage Time Voltage /time Confirm no trip U/V stage V 2.5s 196.5V s 204.1V / 3.5s U/V stage 2 184V 0.5s 180.4V s 188V / 2.48s 180V / 0.48s O/V stage V 1.0s 265.7V s 258.2V / 2.0s O/V stage V 0.5s 277.2V s 269.7V / 0.98s 277.7V / 0.48s Protection. Loss of Mains test. The requirement is specified in section 5.3.2, test procedure in Annex A or B Test power 10% 55% 100% 10% 55% 100% Balancing load on islanded network Trip time. Limit is 0.5s < 0.5s < 0.5s < 0.5s < 0.5s < 0.5s < 0.5s Protection. Frequency change, Stability test The requirement is specified in section 5.3.3, test procedure in Annex A or B Start Frequency Change End Frequency Positive Vector Shift 49.5Hz +9 degrees Negative Vector Shift 50.5Hz - 9 degrees Positive Frequency drift 49.5Hz +0.19Hz/sec 51.5Hz Negative Frequency drift 50.5Hz -0.19Hz/sec 47.5Hz Confirm no trip Protection. Re-connection timer. The requirement is specified in section 5.3.4, test procedure in Annex A or B Test should prove that the reconnection sequence starts after a minimum of 20 seconds for restoration of voltage and frequency to within the stage 1 settings of table 1. Time setting Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of table s >190s At 266.2V At 196.1V At 47.4Hz At 51.6Hz Confirmation that the does not reconnect. No connection No connection No connection No connection STL300_G83-2_ _rev. 1.0.docx Pagina 4/5
5 Fault level contribution. The requirement is specified in section 5.7, test procedure in Annex A or B For a directly coupled For a Inverter Parameter Symbol Value Time after fault Volts Peak Short Circuit current i p 20ms 34V 0A Initial Value of aperiodic current A 100ms 34V 0A Initial symmetrical short-circuit current* Decaying (aperiodic) component of short circuit current* Reactance/Resistance Ratio of source* I k i DC X / R 250ms 34V 0A 500ms 34V 0A Time to trip < 0.5s Amps In seconds Self-Monitoring solid state switching The requirement is specified in section 5.3.1, No specified test requirements. It has been verified that in the event of the solid state switching device failing to disconnect the, the voltage on the side of the switching device is reduced to a value below 50 volts within 0.5 seconds. Yes or NA NA Additional comments STL300_G83-2_ _rev. 1.0.docx Pagina 5/5
G59/3 TYPE TEST VERIFICATION REPORT. Photovoltaic Microinverter. Tel Fax
Type Tested reference number Unit technology System supplier name Address M250-60-230-S22 Photovoltaic Microinverter Enphase Energy Inc. 1420 North McDowell Blvd. Petaluma, CA USA Tel +1-707-763-4784 Fax
More informationENA G59/3 TYPE VERIFICATION TEST REPORT
ENA G59/3 TYPE VERIFICATION TEST REPORT Type approval and manufacturer/supplier declaration of compliance with the requirements of Engineering Recommendation G59/3. Unit Type reference number Unit Type
More informationG59/3 TYPE TEST VERIFICATION REPORT
G59/3 TYPE TEST VERIFICATION REPORT Type Tested reference number GW3048-EM, GW3648-EM,GW5048-EM System supplier name Jiangsu GoodWe Power Supply Technology Co.,Ltd. Address NO.189 Kun Lun Shan Road, Suzhou
More informationG59/3 TYPE TEST VERIFICATION REPORT
MATERIALS & SAFETY R&D TR 141110T Page 1 of 10 G59/3 TYPE TEST VERIFICATION REPORT This Type Test sheet shall be used to record the results of the type testing of Generating Unit between 16A per phase
More informationG59/3 Generating Unit Type Test Sheet
G59/3 Unit Type Test Sheet Type Tested Unit(>16A per phase but 50kW 3 phase or 17kW 1 phase) This Type Test sheet shall be used to record the results of the type testing of Unit between16a per phase and
More informationIt includes the Generating Units supplier declaration of compliance with the requirements of Engineering Recommendation G59/3
MATERIALS & SAFETY R&D TR170801S Page 1 of 8 G59/3 Type Verification Test Report This Type Test sheet shall be used to record the results of the type testing of Generating Unit between 16A per phase and
More informationGrid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 10 th February 2015
Seite 1 von 7 Page 1 of 7 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference test
More informationENA Engineering Recommendation G59/3 Type Verification Test Report
ref. PVI-4.2(3.6)(3.0)-TL-OUTD & Derived Models (UK G59/3 Type Verification Test Report) ENA Engineering Recommendation G59/3 Type Verification Test Report Type Approval and manufacturer/supplier declaration
More informationmmenda 012 erification n Test Rep port e reference number W3600S BP upplier name oodwe Powe Jiangsu Go O.189 Kun Lun w District, Jian ngsu,china
ENA Engineeringg Recom mmenda ation G883 Isssue 2 20 012 erification n Test Rep port roval and maanufacturer/ssupplier declaaration of co ompliance with the requirrements of Engineering ndation G83/2.
More informationPVI l-OUTD(-S)-400 PvI10.04CuTD(.s)400 SOLAR GRID TIED INVERTER. Power-One Italy S.p.A.
Power and productivity for a better 11 II II tm FID ref PVI-]2.O(1O.O-I-OUTD( -S,)-4OO & Derived Models (UK G59/3 Type VerUication Test Report,) ENA Engineering Recommendation G59/3 Type Verification Test
More informationGrid tied inverter. Reference test report: Issued by TÜV Rheinland Italia S.r.l. on 19 th Janury 2015
Seite 1 von 5 Page 1 of 5 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference test
More informationCertificate. Inverter with integrated automatic disconnection device between a generator and the public low-voltage grid
Certificate Applicant: Product: Victron Energy B.V. De Paal 35 1351 JG Almere-Haven The Netherlands Inverter with integrated automatic disconnection device between a generator and the public low-voltage
More informationTR % L Not stated L % L % L3 2.67% L % L % L3 0.
TR 09 Page 2 of 10 Power Quality. Harmonics. SolarLake 20000TLPM Generating Unit rating per phase (rpp) Harmonic At 4555% of rated r outputt 6.6 kva % of rated outpu Harmonic % = Measured Value(Amps) *23/rating
More informationSeite 1 von 8 Page 1 of 8 Appendix 4 Type Verification Test Report (G83/2) Grid tied inverter
Seite 1 von 8 Page 1 of 8 Appendix 4 Type of System: System Manufacturer: Manufacturer data: Grid tied inverter Power-One Italy S.p.A. Via S. Giorgio 642, 52028 Terranuova Bracciolini (AR) - Italy Reference
More informationHarmonic current emissions as per EN
POWER QUALITY Harmonic current emissions as per EN 61000-3-2 Harmonic Test Value in Amps % of fund Limit in Amps 2 0.014 0.16 1.080 3 0.099 1.14 2.300 4 0.009 0.10 0.430 5 0.040 0.46 1.140 6 0.015 0.17
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationMANUFACTURER AND TEST HOUSE DETAILS
Certificate UK G83/1 The results of tests performed according to reference standard UK G83/1 are summarized in this certificate. Power-One Italy S.p.a. declares that the units set for UK G83/1 operations
More informationSSEG DETAILS (Small-Scale Embedded Generator) SSEG Type Reference: SSEG Model Reference:
Certificate BELGIUM C10/11 Pmax=100% The results of tests performed according to reference standard BELGIUM C10/11 Pmax=100% are summarized in this certificate. Power-One Italy S.p.a. declares that the
More informationSSEG DETAILS (Small-Scale Embedded Generator) SSEG Type Reference: SSEG Model Reference:
Certificate UK G59/2-1 The results of tests performed according to reference standard UK G59/2-1 are summarized in this certificate. Power-One Italy S.p.a. declares that the units set for UK G59/2-1 operations
More informationGrid Converters for Photovoltaic
Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements
More informationPhase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.
Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationCompany Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes
Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation
More informationPage 1 of 28. Ingo Röhr. Frank Hesmer
Page 1 of 28 TEST REPORT Engineering recommendation G83/1 Recommendation for the connection of small-scale embedded generators (up to 16 A per phase) in parallel with public low-voltage distribution networks.
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationImplementation of Revised IEEE Standard 1547
MAY 31, 2017 HOLYOKE, MASSACHUSETTS Implementation of Revised IEEE Standard 1547 Presentation to ISO-TO Operations Committee David Forrest Key Points As New England adds significant amounts of Distributed
More informationAC Sources for IEC 1000 Harmonics and Flicker Testing
APPLICATION NOTE #101 IEC 1000-3-2 and IEC 1000-3-3 The IEC 1000-3 standard is concerned with the quality of the utility line power. To ensure good power quality, this standard specifies limits for the
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationTEST REPORT DIN V VDE V :2006 Automatic disconnecting device
age 1 of 23 TEST REORT Automatic disconnecting device Report Reference No...: GZ10080033-1 Date of issue...: August 18, 2010 Total number of pages... 23 pages Testing Laboratory...: Address...: Tested
More informationProtective Relaying for DER
Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationTEST REPORT AS :2005 and AS :2005 Grid connection of energy systems via inverters Grid protection requirements
TEST REPORT AS 4777.2:2005 and AS 4777.3:2005 Grid connection of energy systems via inverters Grid protection requirements Report reference No...: 09TH0459-AS4777_2 Tested by (printed name and signature)...:
More informationOwner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:
Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete
More information7051Plus / 5051Plus. Extended Specification
7051Plus / 5051Plus Extended Specification V1.1 Time Electronics, Botany Industrial Estate,Tonbridge, Kent, TN9 1RH England Tel: 44 (0)1732 355993 Fax: 44 (0) 1732 770312. E-mail: mail@timeelectronics.co.uk
More informationImprovement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications
FEATURED TOPIC Improvement of Islanding Detector Using Interharmonics Current Injection Method and Its Applications Sadayuki ISHIKURA*, Hideyuki NAKATANI, Junya TAKAGI, Tsutomu FUKADA, Shoji NISHIMURA
More informationCompany Directive STANDARD TECHNIQUE: SD5F. Relating to connecting multiple small low voltage connections with limited network analysis
Company Directive STANDARD TECHNIQUE: SD5F Relating to connecting multiple small low voltage connections with limited network analysis Policy Summary This document specifies the procedure for connecting
More informationInverter Source Requirement Document of ISO New England (ISO-NE)
Inverter Source Requirement Document of ISO New England (ISO-NE) This Source Requirement Document applies to inverters associated with specific types of generation for projects that have applied for interconnection
More informationAmeren Illinois Company d/b/a Ameren Illinois Smart Inverter Specifications
1. SCOPE OF WORK 1.1 Purpose This document is formulated to provide guidance to SMART inverter installers in Illinois. The document provides the minimum specification for inverters that interconnect with
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationGRID INTERCONNECTION OF EMBEDDED GENERATION. Part 2: Small-scale embedded generation
ISBN 978-0-626-29938-5 NRS 097-2-3:2014 Edition 1 GRID INTERCONNECTION OF EMBEDDED GENERATION Part 2: Small-scale embedded generation Section 3: Simplified utility connection criteria for low-voltage connected
More informationTripping of circuit breakers in PV installations due to zero sequence field impedance
Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be
More informationLOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION
EN K09LV LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION General Description The K09LV instrument is a three points galvanic insulator, with input on high sensitivity voltage, and active output.
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationENS31 Automatic Isolation Unit Product Description
ENS31 Automatic Isolation Unit Product Description Issue 09/2005 UfE Umweltfreundliche Energieanlagen GmbH Joachim-Jungius-Straße 9 D 18059 Rostock Tel.: +49 3 81 / 405 97 05 Fax: +49 3 81 / 405 97 03
More informationEN50160 Individual Report Summary
EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6)
More informationFuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)
Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there
More informationGrid Code 2015 for Small Scale Distributed Generation (SSDG) Net Metering Scheme Version June 2017 Central Electricity Board
Grid Code 2015 for Small Scale Distributed Generation (SSDG) Net Metering Scheme Version 2.2 - June 2017 Central Electricity Board Foreword The purpose of this document is to assist the public to better
More informationGreen LED (right of 'D' type connector)
3050A EXTENDED SPECIFICATIONS General Specifications TRANSMILLE LTD Warm Up Time Double the time since last used up to 20 minutes maximum Standard Interfaces USB Optional Interfaces GPIB (IEEE-488) : RS232
More informationTechnical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US
Technical information Grid Support Utility Interactive Inverters for Sunny Central-US and Sunny Central Storage-US ENGLISH SC-US-GridServices-TI-en-10 Version 1.0 Table of Contents SMA Solar Technology
More informationEMC TEST REPORT. According to
EMC TEST REPORT According to EN 55014-1: 2006 EN 55014-2: 1997+A1:2001 EN 61000-3-2: 2006 EN 61000-3-3: 1995+A1:2001+A2:2005 Test Report No. Equipment : BWS-08-EC-0001 : Air cleaner Model No : AIRVAX 33X2
More informationProject acronym: Multi-island
Technical report for The Experimental investigation on the performance characteristics of anti-islanding techniques in the prospect of high PV penetration level Project acronym: Multi-island USER PROJECT
More informationTechnical Documentation of (EU) No 617/2013
Technical Documentation of (EU) No 617/2013 Product type Product category Manufacturer name, address Notebook computer A Acer Italy srl Viale De Gasperi 88/A 20017 Mazzo di Rho ( MI) Italy Product model
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationDeclaration of Conformity
for SkyBox True Hybrid Energy System Purpose The intent of this document is to specify that the OutBack model listed below conforms to the following standards for grid-interactive inverter/chargers intended
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationAn input resistor suppresses noise and stray pickup developed across the high input impedance of the op amp.
When you have completed this exercise, you will be able to operate a voltage follower using dc voltages. You will verify your results with a multimeter. O I The polarity of V O is identical to the polarity
More informationParameters related to frequency stability
Parameters related to frequency stability EN-E guidance document for national implementation for network codes on grid connection 16 November 2016 EN-E AISBL Avenue de Cortenbergh 100 1000 Brussels Belgium
More informationOrbital GFI Inverter Series
Orbital GFI Inverter Series Datasheet Key Features One, split or three phases and up to 25 kva Superior efficiency of 95% CAN Bus control and DAQ Power quality and EMC compliance in accordance with European
More informationAutomatic connection/reconnection and admissible rate of change of active power
Automatic connection/reconnection and admissible rate of change of active power ENTSO-E guidance document for national implementation of conditions for automatic connection / reconnection after incidental
More informationTechnical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks
2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution
More informationIssued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY
WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable
More informationWe take care of it. Special Publication. Power Quality PQ-Box 100/200. Expert opinions: Emergency power supply for hospitals and computer centres.
We take care of it. Special Publication Power Quality PQ-Box 100/200 Expert opinions: Emergency power supply for hospitals and computer centres. Power Quality PQ-Box 100/200 Emergency power supply for
More informationTEST REPORT IEC Uninterruptible power systems Part 3: Method of specifying the performance and test requirements
Test Report issued under the responsibility of: TEST REORT IEC 62040-3 Uninterruptible power systems art 3: Method of specifying the performance and test requirements Report reference No...: 11-EL-0026.06
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationImpact of High PV Penetration on Grid Operation. Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas
Impact of High PV Penetration on Grid Operation Yahia Baghzouz Professor of Electrical engineering University of Nevada Las Vegas Overview Introduction/Background Effects of High PV Penetration on Distribution
More informationThe development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08
The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges
More informationSmall-scale PV Inverters EEA Conference, Wellington. Bill Heffernan, Patrick Chen and Ankur Mishra June 2016
Small-scale PV Inverters EEA Conference, Wellington Bill Heffernan, Patrick Chen and Ankur Mishra June 2016 Introduction Concern exists regarding the effects of many inverters connecting to the LV system
More informationIntermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)
Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected
More informationKurz Instruments Inc. December 27, 2007
BUILT-IN ZERO-MIDSPAN-SPAN DRIFT CHECK/CALIBRATOR Introduction Continuous Emissions monitoring systems (CEMS) have a long term stability verification requirement. Most of the equipment is verified using
More informationEASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation
EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin
More informationDual Precision, Low Cost, High Speed BiFET Op Amp AD712-EP
Dual Precision, Low Cost, High Speed BiFET Op Amp FEATURES Supports defense and aerospace applications (AQEC standard) Military temperature range ( 55 C to +125 C) Controlled manufacturing baseline One
More informationSection 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General
Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently
More informationRevision Control. 0 18/07/2012 Initial Document Creation. STAKEHOLDERS The following positions shall be consulted if an update or review is required:
Standard: Technical Requirements for Bumpless Transfer of Customer Load between Embedded Generators and the Distribution Network Standard Number: HPC-9OJ-13-0001-2012 * Shall be the Process Owner and is
More informationThe Connecticut Light and Power Company
The Connecticut Light and Power Company and The United Illuminating Company Exhibit B - Generator Interconnection Technical Requirements May 12, 2010 Page 1 of 26 Table of Contents 1. SCOPE... 3 2. GENERAL
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationReport no GZU-001. Growatt 30000TL3-S, Growatt 30000TL3-SE. Max. input current: 34A/34A 38A/38A
age 2 of 27 Rating : Model Max. DC input Voltage: 30000TL3-S, 30000TL3-SE 33000TL3-S, 33000TL3-SE Input 1000Vdc 40000TL3- NS, 40000TL3- NSE 50000TL3-S, 50000TL3-SE Max. input current: 34A/34A 38A/38A DC
More informationSMK & STK. Voltage Stabilizer TO SOLVE TROUBLES DUE AT LARGE LOAD INSERTION OR DROP VOLTAGE WHEN THE UTILITIES ARE FAR FROM SOURCE
SMK & STK Voltage Stabilizer TO PROTECT AGAINST THE PEAK EFFECT AND LIGHTNING TO SOLVE TROUBLES DUE AT LARGE LOAD INSERTION OR DROP VOLTAGE WHEN THE UTILITIES ARE FAR FROM SOURCE TO REDUCE THE NOISE ON-LINE
More informationGRID CODE MEDIUM SCALE DISTRIBUTED GENERATION (MSDG) Greater than 50kW and not exceeding 200kW. (Version May 2016) CENTRAL ELECTRICITY BOARD
GRID CODE MEDIUM SCALE DISTRIBUTED GENERATION (MSDG) Greater than 50kW and not exceeding 200kW (Version 1.0 - May 2016) CENTRAL ELECTRICITY BOARD Corporate Office P.O Box 134 Rue du Savoir, Cybercity Ebène
More informationA Control Method of Parallel Inverter for Smart Islanding of a Microgrid
A Control Method of Parallel Inverter for Smart Islanding of a Microgrid M. Hojo 1, K. Amo 1, T. Funabashi 2 and Y. Ueda 2 1 Institute of Technology and Science, the University of Tokushima 2-1 Minami-josanjima,
More informationBE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2
BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude
More informationChapter-5. Adaptive Fixed Duty Cycle (AFDC) MPPT Algorithm for Photovoltaic System
88 Chapter-5 Adaptive Fixed Duty Cycle (AFDC) MPPT Algorithm for Photovoltaic System 5.1 Introduction Optimum power point tracker (OPPT), despite its drawback of low efficiency, is a technique to achieve
More informationModel Hz to 10MHz Precision Phasemeter. Operating Manual
Model 6610 1Hz to 10MHz Precision Phasemeter Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give long
More informationMicro DC-DC Converter Family Isolated Remote Sense
APPLICATION NOTE AN:205 Micro DC-DC Converter Family Isolated Remote Sense Application Engineering Vicor Corporation Contents Page Introduction 1 Design Considerations 1 Remote Sense Circuit Functional
More informationMagtech Voltage Booster MVB
Model overview MVB 30.04.09 EG.doc Magtech Voltage Booster Voltage fluctuations caused by unbalanced load in Y-ground grid? Low voltage part of the day due to high load? Quick and profitable solution with
More information5320A. Multifunction Electrical Tester Calibrator. Extended Specifications
5320A Multifunction Electrical Tester Calibrator Extended Specifications General Specifications Warm-Up Time...30 minutes Specifications Confidence Level...99 % Specifications Interval...1 year Temperature
More informationTechnical Documentation of (EU) No 617/2013
Technical Documentation of (EU) No 617/2013 Product type Notebook computer Product category A B Manufacturer name, address Product model number Acer Italy s.r.l, Via Lepetit, 40, 20020 Lainate (MI) Italy
More informationTHE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES
THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES C.E.T. Foote*, G.W. Ault*, J.R. McDonald*, A.J. Beddoes *University of Strathclyde, UK EA Technology Limited, UK c.foote@eee.strath.ac.uk
More informationPOWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER
POWER QUALITY IMPACTS AND MITIGATION OF DISTRIBUTED SOLAR POWER Presented by Ric Austria, Principal at Pterra Consulting to the IEEE San Francisco Chapter Feb 17, 2016 California Public Utilities Commission,
More informationSIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side
www.siemens.com/protection SIPROTEC 5 Application SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT in the delta connection of the compensation Answers for infrastructure and cities. Autotransformer
More informationKurz Instruments Inc. 19 August 2010
BUILT-IN ZERO-MIDSPAN-SPAN DRIFT CHECK/CALIBRATOR Introduction Continuous Emissions Monitoring Systems (CEMS) have a long term stability verification requirement. Most of the equipment is verified using
More informationDistributed Generation Application Form (Generation of Greater than 20 kw to 15 MW)
Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW) PSC-6028 R(03-04-04) Name & Address Distributed By Name & Address Supplied By Public Service Commission of Wisconsin
More informationEMC Test report for LED Panel Light Models , , , , ,
4326247.50 EMC Test report for LED Panel Light Models 000529, 000530, 000531, 000532, 000535, 000536 Guangzhou, date of issue: 2016-02-24 Author:Jazz Liang By order of Marvo Verlichting B.V. at Hoogeveen,
More informationHybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation
Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation Maher G. M. Abdolrasol maher_photo@yahoo.com Dept. of Electrical Engineering University of Malaya Lembah Pantai, 50603
More informationSummary of testing: Testing location: Intertek Testing Services Taiwan Ltd.
age 2 of 40 Summary of testing: Tests performed (name of test and test clause): 5.4.3 System reactions flicker 5.4.4 System reactions harmonics and interharmonics 5.4.9 System reactions precautionary measures
More informationTechnical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US
Technical information SUNNY BOY 3.0-US / 3.8-US / 5.0-US / 6.0-US / 7.0-US / 7.7-US Grid Support Utility Interactive Inverters ENGLISH SBxx-1XP-US-40-GridServices-TI-en-15 Version 1.5 Table of Contents
More information