B MTS Systems Corp., Model Function Generator

Size: px
Start display at page:

Download "B MTS Systems Corp., Model Function Generator"

Transcription

1 B MTS Systems Corp., 1988 Model Function Generator

2 Table of Contents Section 1 Introduction 1.1 Functional Description Specifications 1-2 Section 2 Operation 2.1 Control Mode Selection Output Mode Selecting and Programming Waveforms Programming Cyclic Waveforms Programming Ramps Program (Null) Pacing Limit Programming 2-12 Section 3 Service 3.1 Power Supply Voltages Output Calibration Breakpoint Calibration Cosine Calibration (Option A) Voltage Controlled Oscillator Calibration (Option B) 3-8 Section 4 Installation 4.1 Function Generator Installation Equipment Rack Installation Voltage and Grounding Line Voltage Chassis Common and Grounding Switch and Jumper Descriptions S1 Program (Null) Pacing Enable S2 Output Scaling Internal/External S3 Breakpoint Source X1 Cosine Calibration X2 VCO Enable X3, X4 Cosine Output Enable X5, X6 Testing X7 Remote Stop/Hold Select X8 Remote Start X9, X10 Emergency Stop Rear Panel Connectors J1 Main Output J2 Sync Output J3 Gate Input J4 VCO External Input J5 Remote Cosine Option Installation VCO Option Installation 4-13 iii

3 Section 5 Theory of Operation 5.1 Front Panel Interface Waveform Select Thumbwheel Switches Breakpoint Return to Zero Waveform Generation Clock Signals Accumulators DACs Ramp Mode Cyclic Mode Cosine Output (Option A) Voltage Controlled Oscillator (Option B) Power Supply Vdc Supply ±15 Vdc Supply 5-7 List of Figures Figure 1-1 Model Function Generator 1-1 Figure 2-1 Function Generator Front Panel Controls and Indicators 2-1 Figure 2-2 Control Mode Switches 2-2 Figure 2-3 Output Mode Switches 2-3 Figure 2-4 Waveform Controls and Indicators 2-4 Figure 2-5 Limit Programming Example 2-13 Figure 3-1 Main Circuit Card Service Locations 3-2 Figure 3-2 Cosine Circuit Card Service Locations 3-6 Figure 3-3 VCO Circuit Card Service Locations 3-8 Figure 4-1 Rack Mounting the Female Slide Assembly (Top View) 4-3 Figure 4-2 Rear Panel Switch Locations 4-5 Figure 4-3 Main Circuit Card Jumper Locations 4-6 Figure 4-4 VCO Enable Jumper 4-7 Figure 4-5 Cosine Enable Jumpers 4-7 Figure 4-6 Remote Stop/Hold Jumper 4-8 Figure 4-7 Gate Input Jumper 4-8 Figure 4-8 Emergency Stop Configurations 4-9 Figure 4-9 Rear Panel Connectors 4-10 Figure 4-10 J5 Remote Signals 4-11 iv

4 List of Tables Table 1-1 Model Function Generator Specifications 1-2 Table 2-1 Control Mode Switch Descriptions 2-2 Table 2-2 Output Mode Switch Descriptions 2-3 Table 2-3 Waveform Controls and Indicators 2-4 Table 2-4 Waveform Descriptions 2-5 Table 2-5 Switch Setting and Frequency Range 2-8 Table 2-6 VCO Frequency Range 2-9 Table 2-7 Switch Setting and Ramp Range 2-10 Table 3-1 Power Supply Voltages 3-1 Table 4-1 Input Voltage and Corresponding PWB Legend 4-4 Table 5-1 PROM Program 5-4 v

5 Section 1 Introduction The MTS Model Function Generator (shown in Figure 1-1) is designed to provide a variety of programming capabilities for use in MTS testing systems Function Generator Output Main Sync Select Waveform Normal Invert Control Mode Local Single Remote Local Cycle Output Mode Finish Local Cycle Start & Stop Ret to Zero Output to 0 Trigger Manual Bkpt Hold Ramp Time 1 (sec) FS 0 t +100% FS % FS Ramp Time 2 (sec) FS 0 t Hold Time (sec) FS t 0 Frequency (Hz) Breakpt 5-05% Full Scale Figure 1-1. Model Function Generator 1.1 Functional Description The Function Generator can output cyclic waveforms or ramps. The cyclic waveforms include sine, haversine and haversquare programs. Twelve ramp functions provide combinations of dual ramps, hold times and adjustable break points which can produce triangle, saw tooth, trapezoid and custom waveforms. The Function Generator produces cyclic waveform frequencies from Hz to 990 Hz and full-scale ramps can be programmed from seconds to 990,000 seconds (11.45 days). All of the waveforms start and stop at zero and may be started positive (normal) or negative (invert). The breakpoint capabilities allow a ramp to change to a second ramp rate or a hold time. The breakpoint can be triggered automatically when the program reaches a preset level (as adjusted by a front panel control), manually (with a front panel switch) or remotely (from an external device). The hold capabilities can be used in conjunction with program null pacing or limit programming. Program null pacing ensures each program level is reached before proceeding to a new level. Limit programming allows transducer feedback limits to trigger breakpoints and/or release hold times of the waveform (Model Limit Detector required). 1-1

6 1.2 Specifications Table 1-1 lists the specifications for the Function Generator. Table 1-1. Model Function Generator Specifications Parameter Specification Environmental: Temperature 50 F(10 C ) to 104 F (40 C ) Relative Humidity 0 to 85%, noncondensing Program Output: Waveforms Maximum Voltage Maximum Load sine, haversine, haversquare, ramp and hold time ±10 volts 600 Ω Resolution: Ramp 0.05 mv (approximate) at 10 5, 10 4, 10 3, 10 2, 10 1,10 0 rates; 5.0 mv (approximate) at 10-1, 10-2 rates Sine/Haversine 1.2 mv (approximate) at 10-4, 10-3, 10-2, 10-1, 10 0 ranges; 120 mv (approximate) at 10 1, 10 2 ranges Step Accuracy Noise ±2.5 mv less than 63 mv p-p Ramp: Rates (0 to full-scale) Linearity Hold Drift to 990,000 seconds ±0.1% from best straight line within ±5 mv for 24 hours Sine wave Harmonic Distortion less than 0.5% Square wave Characteristics flat to within 0.1% of full amplitude, rise time less than 50 µsec Preset Breakpoint: Accuracy Range 0.5% of full-scale between 5% and 95% of full-scale 5 to 95% of full-scale 1-2

7 Table 1-1. Model Function Generator Specifications (continued) Parameter Specification Frequency: Accuracy Range ±0.1% of range (±1% w/vco option) to 990 Hz Stability 1 hour ±0.05%; 24 hours ±0.1% (±0.5%; ±1% w/vco option) Amplitude Variation (w/freq) Sync Output Gating Input VCO Input Range External Reference Input Range Line Voltage less than 10 mv RMS +5 Vdc 500 µsec pulse (max load 2 kω) jumper selectable, 5 volt logic or relay contacts 0.1 to 10 volts 2 to 10 volts 115/230 Vac (±10%), 50/60 Hz, 40 W Specifications are subject to change without notice. Contact MTS for verification of critical specifications. 1-3

8 Section 2 Operation This section provides a functional description of the Function Generator front panel controls and indicators. Figure 2-1 shows the Function Generator front panel controls and indicators. Operation of the Function Generator requires the following: Selecting a control mode, Subsection 2.1. Controlling the waveform output, Subsection 2.2. Selecting and programming a waveform, Subsection 2.3. The following are optional operation information: Program pacing information, Subsection 2.4. Limit programming information, Subsection Function Generator Output Main Sync Select Waveform Normal Invert Control Mode Local Single Remote Local Cycle Output Mode Finish Local Cycle Start & Stop Ret to Zero Output to 0 Trigger Manual Bkpt Hold Ramp Time 1 (sec) FS 0 t +100% FS % FS Ramp Time 2 (sec) FS 0 t Hold Time (sec) FS t 0 Frequency (Hz) Breakpt 5-05% Full Scale Figure 2-1. Function Generator Front Panel Controls and Indicators 2-1

9 2.1 Control Mode Selection The Function Generator provides three modes of operation to start and stop the waveform output. Figure 2-2 shows the controls associated with control mode selection. Table 2-1 describes the control modes. Control Mode Remote Local Local Single Cycle ➊ ➋ ➌ Figure 2-2. Control Mode Switches Table 2-1. Control Mode Switch Descriptions Item Control Description 1 Remote The Remote switch allows an external device (input at the J3 Gate connector) to start and stop the Function Generator output. 2 Local The Local switch allows the front panel controls to start and stop the Function Generator output. 3 Local Single Cycle The Local Single Cycle switch allows one cycle of the Function Generator output after the Local Start switch is pressed. 2-2

10 2.2 Output Mode The Output Mode section provides controls to start, stop and manually override the waveform output. Output Mode Output to 0 Local Start Finish Cycle & Stop Ret to Zero Trigger Manual Bkpt Hold ➊ ➋ ➌ ➍ ➎ Figure 2-3. Output Mode Switches Table 2-2. Output Mode Switch Descriptions Item Control Description 1 Local Start The Local Start switch begins the waveform output in the Local and Local Single Cycle modes. 2 Finish Cycle & Stop The Finish Cycle & Stop switch allows the waveform to continue until it completes the current cycle, then it stops. 3 Ret to Zero The Ret to Zero switch ramps the waveform from its current value to zero at the Ramp Time 2 setting when in the ramp mode. The sine and haversine modes will stop at the next zero crossing. 4 Trigger Manual Bkpt The Trigger Manual Bkpt switch overrides the programmed breakpoint setting and triggers an immediate breakpoint. One breakpoint can be executed in each waveform quadrant (e.g., 0 to 10V, 10 to 0V, 0 to -10V and -10 to 0V). The breakpoint can be generated by the Trigger Manual Bkpt switch, a preset level or a remote breakpoint signal. 5 Hold The Hold switch stops the waveform at the current level until the Hold switch is pressed again. 6 Main The Main BNC connector provides the waveform output for monitoring. 7 Sync The Sync BNC connector outputs a signal each cycle to trigger an external device (i.e, counting cycles). 8 Output at 0 The Output at 0 indicator lights when the program output is at 0.00 volts. 2-3

11 2.3 Selecting and Programming Waveforms ➊ Select Waveform Normal Invert ➋ The controls and indicators associated with selecting and programming a waveform are shown in Figure 2-4 and described in Table 2-3. Descriptions of the waveforms are provided in Table 2-4. Operational procedures to program waveforms are provided in Subsections (cyclic) and (ramp). ➍ ➎ +100% FS % FS ➌ Breakpt 5-05% Full Scale Ramp Time 1 (sec) FS Ramp Time 2 (sec) FS t 0 0 t Hold Time (sec) FS t 0 Frequency (Hz) Figure 2-4. Waveform Controls and Indicators Table 2-3 Waveform Controls and Indicators Item Control Description 1 Select Waveform (16-position switch) 2 Normal/Invert (switch) 3 Breakpt 5-95% Full Scale (10-turn potentiometer) 4 Ramp Time 1 (sec) (thumbwheel switch) Thumbwheel switch The Select Waveform switch selects the desired waveform. Each switch position lights an indicator above the selected waveform along with the appropriate thumbwheel indicator(s). Refer to Table 2-3 for descriptions of the waveforms. The Normal/Invert switch selects the initial polarity of the waveform. The Normal selection starts the waveform positive and the Invert selection starts negative. The Breakpt (breakpoint) control sets a breakpoint level within the range of 5% to 95% of full-scale. The breakpoint level is a point at which the waveform changes to another ramp rate or hold time. The control is scaled from 00 to 100 representing 0% to 100% full-scale (the upper and lower 5% are not used). The Ramp Time 1 (sec) control sets the ramp time (in seconds) for the output to go from zero (0.0 volts) to fullscale (10 volts). The control allows a two-digit number and multiplier to be entered. The function of this control is determined by the waveform selection. The control can set a second ramp time, a hold time or a frequency. The appropriate function indicator lights according to the waveform selection. The control allows a two-digit number and multiplier to be entered. 2-4

12 Table 2-3 Waveform Controls and Indicators (continued) Item Control Description 5 Ramp Time 2 (sec) (indicator) Hold Time (sec) (indicator) Frequency (Hz) (indicator) When the Ramp Time 2 (sec) indicator lights, the thumbwheel switch sets a ramp time (in seconds) for a second ramp rate to go from zero (0.0 volts) to full-scale (10 volts). The ramp is begins at the breakpoint level. When the Hold Time (sec) indicator lights, the thumbwheel switch sets a hold time (in seconds) required for some waveforms. The hold time is applied at the breakpoint level. When the Frequency (Hz) indicator lights, the thumbwheel switch sets a frequency (in hertz) for the cyclic waveforms. 6 Waveforms The waveforms illustrated on the front panel are color coded. The colors indicate which controls set-up the components of the waveform. Refer to Table 2-4 for descriptions of the waveforms. Table 2-4 provides descriptions of the front panel waveform selections. The waveform descriptions assume the Normal/Invert switch is set for Normal operation. Waveform illustrations with black dots indicate the use of the Breakpt control. Table 2-4. Waveform Descriptions Waveform Description Sine The program output is a ±10 volt sine wave. The Frequency (Hz) indicator lights to show which thumbwheel switch sets the frequency of the waveform. Haversine Haversquare The program output is a 0 to 10 volt sine wave (haversine). The Frequency (Hz) indicator lights to show which thumbwheel switch sets the frequency of the waveform. The program output is a 0 to 10 volt square wave (haversquare). The Frequency (Hz) indicator lights to show which thumbwheel switch sets the frequency of the waveform. 2-5

13 Table 2-4. Waveform Descriptions (continued) Waveform Description Ramp A Ramp B Ramp C Ramp D The program output increases from zero to the breakpoint level at ramp rate 1. Then the program output decreases to zero at ramp rate 1 to complete one cycle of the waveform. The program output increases from zero to 10 volts at ramp rate 1. Then the output decreases to zero at ramp rate 1 to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to the breakpoint level. The output decreases through zero to the negative breakpoint level and increases to zero to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to 10 volts. Then the output decreases through zero to -10 volts. The output increases to zero to complete one cycle of the waveform. Ramp E Ramp F Ramp G Ramp H The program output increases at ramp rate 1 from zero to the breakpoint level. Then the output increases at ramp rate 2 to 10 volts and holds the output at 10 volts until the Ret to Zero switch pushed. The program output increases at ramp rate 1 from zero to the breakpoint level. Then the output decreases at ramp rate 2 to zero to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to the breakpoint level. The output increases at ramp rate 2 to 10 volts. Then the output decreases at ramp rate 2 from 10 volts to the breakpoint level and changes to ramp rate 1 through zero to the negative breakpoint level. The output decreases at ramp rate 2 to -10 volts. Then the output increases at ramp rate 2 to the negative breakpoint level and changes to ramp rate 1 to zero to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to the breakpoint level. The output decreases at ramp rate 2 from the breakpoint level through zero to the negative breakpoint level. Then the output increases at ramp rate 1 to zero to complete one cycle of the waveform. 2-6

14 Table 2-4. Waveform Descriptions (continued) Waveform Description Ramp I Ramp J Ramp K Ramp L The program output increases at ramp rate 1 from zero to the the breakpoint level and holds the output. When the hold time is over, the output decreases at ramp rate 1 to zero to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to the breakpoint level and holds the output. When the hold time is over, the output increases at ramp rate 1 to 10 volts. Then the output decreases to the breakpoint level and applies the hold time again. When the hold time is over, the output decreases at ramp rate 1 to zero to complete one cycle. The program output increases at ramp rate 1 from zero to the breakpoint level and holds the output. When the hold time is over, the output decreases at ramp rate 1 through zero to the negative breakpoint level and holds the output again. When the hold time is over, the output increases at ramp rate 1 to zero to complete one cycle of the waveform. The program output increases at ramp rate 1 from zero to the breakpoint level and holds the output. When the hold time is over, the output increases at ramp rate 1 to 10 volts and decreases to the breakpoint level at ramp rate 1 and applies the hold time. When the hold time is over, the output decreases at ramp rate 1 through zero to the negative breakpoint level and applies the hold time. When the hold time is over, the output decreases at ramp rate 1 to -10 volts then increases to the negative breakpoint level and applies the hold time. When the hold time is over the output increases at ramp rate 1 to zero to complete one cycle of the waveform. 2-7

15 2.3.1 Programming Cyclic Waveforms The Function Generator includes the cyclic waveforms: sine, haversine and haversquare. The cyclic waveform selections are color coded green and lights the Frequency (Hz) indicator of the thumbwheel switches. The VCO (voltage controlled oscillator) option allows an external device to control the frequency. The waveform frequency (within a selected range) is controlled by an external device connected to the rear panel VCO EXT input. The input voltage determines the waveform frequency. When using the VCO input, the front panel thumbwheel switches are normally set to 0.0 (only the multiplier is set). This scales the VCO input so that a 0.1 volt input causes the minimum frequency in a given range and a 10 volt input causes the maximum frequency of the range. If desired, the thumbwheel switches may be set to a value other than zero. For example; a thumbwheel setting of 4.0 X 10 2 (400 Hz) and a VCO input of 2.5 volts (250 Hz) will result with a 650 Hz output. Perform the following to program a cyclic waveform: 1. Select the desired waveform with the Select Waveform switch to light the appropriate green indicator. The Frequency (Hz )control indicator will also light. NOTE: The maximum frequency for a cyclic waveform is 990 Hz. The maximum frequency using the VCO option is 1000 Hz. Tables 2-5 and 2-6 do not include the ranges 10 3, 10 4 and 10 5 ; these ranges provide the same frequencies as the 10 2 range. 2. Set the Frequency Hz switches to the desired program frequency (a two- digit number and multiplier). Table 2-5 shows the frequency range of the corresponding thumbwheel switch settings. Table 2-6 shows the frequency range and corresponding thumbwheel switch settings for the VCO option, only the multiplier is normally set for VCO operation. Table 2-5. Switch Setting and Frequency Range Switch Setting Frequency Range x Hz x Hz x Hz x Hz x Hz x Hz x Hz 2-8

16 Table 2-6. VCO Frequency Range Switch Setting Frequency Range 0.0 x Hz 0.0 x Hz 0.0 x Hz 0.0 x Hz 0.0 x Hz 0.0 x Hz 0.0 x Hz 3. Select the initial waveform polarity with the Normal/Invert switch. Normal selects a positive waveform. Invert selects a negative waveform. 4. Press the desired Control Mode switch. The control mode determines how the Function Generator program is started; perform one of the following: A. If Local or Local Single Cycle is selected, press the Local Start switch to begin the cyclic waveform program. B. If Remote is selected, refer to the product manual of the remote device for operation procedures to start/stop the program (ensure the remote device is properly connected to the Function Generator). 5. To stop the waveform, press the Finish Cycle & Stop or Ret to Zero switch, or the appropriate stop control on the remote device. 2-9

17 2.3.2 Programming Ramps The Function Generator includes twelve ramp waveforms (A through L) as described in Table 2-4. Waveforms A through D are programmed with one thumbwheel switch. Waveforms E through L require are programmed with both thumbwheel switches. The ramp rate setting defines the slope of the ramp. A ramp is programmed in seconds to cause the Function Generator output to go from zero (0.0 volts) to full-scale (10.0 volts) even though the ramp may change at a breakpoint. Perform the following to program a ramp. 1. Select the desired ramp with the Select Waveform switch to light the desired indicator (A through L). If waveform A through D is selected, the Ramp Time 1 (sec) indicator will light. If waveform E through L is selected, the Ramp Time 1 (sec) indicator will light along with the Ramp Time 2 (sec) or Hold Time (sec) indicator. NOTE: The minimum ramp period is seconds. Table 2-7 does not include the ranges 10-3 and 10-4 ; these ranges provide the same frequencies as the 10-2 range. 2. Set the thumbwheel switches of Ramp Time 1 (sec) to the desired ramp time. A two digit number and a multiplier can be set. Table 2-7 shows the ramp range and corresponding switch settings. Table 2-7. Switch Setting and Ramp Range Switch Setting Ramp Range (in seconds) x , , x ,000-99, x , x x x x x

18 3. For waveforms E through L, set the thumbwheel switches of Ramp Time 2 (sec)/hold Time (sec) to the desired time. A two digit number and multiplier can be set. 4. Adjust the Breakpt control to the desired percent of full-scale (within 5 to 95% full-scale) where the second ramp or hold time is to be applied. 5. Select the initial waveform polarity with the Normal/Invert switch. Normal starts the waveform positive and Invert starts the waveform negative. 6. Press the desired Control Mode switch. The control mode determines how the Function Generator program is started; perform one of the following: A. If Local or Local Single Cycle is selected, press the Local Start switch to begin the cyclic waveform program. B. If Remote is selected, refer to the product manual of the remote device for operation procedures to start the program (ensure the remote device is properly connected to the Function Generator). 7. To stop the waveform, press the Finish Cycle & Stop or Ret to Zero switch, or the appropriate stop control on the remote device. 2-11

19 2.4 Program (Null) Pacing Program (null) pacing holds the Function Generator output at the breakpoint level to allow the servohydraulic system to reduce any error before continuing the waveform program. This is accomplished by sending a dwell signal from the Function Generator to the servohydraulic controller to check the difference (dc error) between the program command and the transducer feedback. The dwell signal is sent when the output reaches the breakpoint level. If the level of dc error exceeds the limit adjusted on the system controller, the Function Generator holds the program level to allow the system to reduce the dc error. When the dc error reaches an acceptable level, the system controller outputs a null signal to the Function Generator and the program continues. Program pacing can only be used with waveforms containing hold times (waveforms I through L). To enable the program pacing function ensure the system controller is properly connected to the Function Generator (Subsection 4.5.5) and set the rear panel Null Pacing switch to the In position (Subsection 4.4.1). NOTE: For program pacing, the setting of the Hold Time switch should exceed the anticipated dwell time. The Function Generator resumes the program when the null signal is received or the end of the hold time is reached. 2.5 Limit Programming Limit programming is similar to program pacing except it is used in systems containing a Model Limit Detector. The Limit Detector monitors the output of three transducers. An upper and lower limit is adjusted for each transducer output. If a transducer output exceeds the adjusted limit, the Function Generator will change the program output according to the waveform selected. Each of the transducer feedback signals of the Model Limit Detector can be configured to initiate a breakpoint or release a hold time. Observe the following considerations when operating in the limit programming mode: Adjust the Breakpt control to 1000 (100% full-scale). The breakpoint function will be performed by the Limit Detector module. If the breakpoint level is below full-scale, the program output may change prematurely causing the remaining program changes to occur out of sequence. 2-12

20 If a waveform with a hold time is selected, ensure to program a hold time of sufficient duration to allow a limit to be detected. If the hold time is completed before a limit is detected, the program output will resume prematurely causing the remaining program changes to occur out of sequence. Figure 2-5 illustrates an example of limit programming. In the example shown, waveform J and normal are selected. The Limit Detector is set-up with the load limit detector set for a breakpoint and the strain limit detector set for release (refer to the Limit Detector product manual). Function Generator Output (Waveform L) Upper Limit Load Feedback Lower Limit Upper Limit Strain Feedback Lower Limit Figure 2-5. Limit Programming Example 2-13

21 The program output increases at ramp rate 1 until the upper load limit is detected. The upper load limit causes the output to hold until the upper strain limit is detected. When the upper strain limit is detected, the output increases at ramp rate 1 until full-scale (+10 volts) is reached and the output decreases (at ramp rate 1) until the lower load limit is detected. The lower load limit causes the output to hold until the lower strain limit is detected. When the lower strain limit is detected, the output decreases at ramp rate 1 until zero (0.00 volts) is reached and another cycle begins. 2-14

22 Section 3 Service This section provides calibration information for the Model Function Generator. In cases where the Function Generator unit is supplied as part of an MTS Systems Corporation testing system, the Function Generator unit will have been calibrated at the factory. Field calibration may be necessary when a new Function Generator is installed, a replacement unit is required, or calibration is deemed necessary after checking calibration accuracy. The procedures in the following subsections assume the person performing calibration is familiar with the use of electronic test equipment and the operation of system components. NOTES: The adjustment values specified in the following procedures provide for optimum calibration accuracy. The adjustment tolerances of these procedures during field calibration are dependent on system requirements and available test equipment. All calibration procedures are performed with hydraulic pressure turned off and the Function Generator set for Local Start control. 3.1 Power Supply Voltages Table 3-1 lists the monitoring point to check the power supply voltages. Figure 3-1 shows the locations of the monitoring points. Remove the top cover to access the test points. The +5 volt power supply is adjusted with R1 on the power supply circuit card assembly. The ±15 volt power supplies, -12 volt supply and the +10 volt reference are not adjustable. Common is TP10. Table 3-1. Power Supply Voltages Voltage Test Point + 5 Vdc; ±10 mv TP7 +15 Vdc; ±0.6 V TP8-15 Vdc; ±0.6 V TP9 +10 Vdc; ±0.1 V TP5-12 Vdc; ±0.6 V TP11 3-1

23 TP7 +5V TP9-15V TP10 COM TP8 +15V R45 TP12 BRKPT REF 1 R83 2 R46 R R48 R42 TP5 10V REF R A B R41 R21 X2 TP11 E J K -12 V C D L M N TP6 MAIN OUTPUT TP4 BRKPT REF TP13 10V BRKPT REF Figure 3-1. Main Circuit Card Service Locations 3.2 Output Calibration The Function Generator includes three digital-to-analog converters (DAC). The accuracy of the Function Generator output depends on the calibration of the DACs. The main 12-bit DAC is calibrated for a fullscale output of +10 volts using the internal reference voltage. The two 8-bit fill-in DACs are calibrated to smooth out the steps of the main DAC. The fill-in circuit is active for cyclic frequencies below 9.9 Hz (frequency multipliers 10 0 through 10-4 ) and ramps above 10 seconds (ramp multipliers 10 0 through 10 5 ). Perform the following procedure to calibrate the output of the Function Generator. Refer to Figure 3-1 for the adjustment locations. NOTE: Ensure the 10 volt reference voltage is within the specifications defined in Subsection

24 1. If mounted in an equipment rack, pull the Function Generator out and remove the top cover. 2. Set the rear panel Output Scaling switch to Int to establish a fullscale output of +10 volts. Set the rear panel Output Scaling switch to Ext to establish a fullscale output representing the external reference voltage. If external scaling is selected, change the voltage levels in the following steps to reflect the reference voltage input through the Remote connector J5. 3. Apply power to the Function Generator. 4. Connect a digital voltmeter (DVM) to TP6 (MAIN OUTPUT) and TP10 (COM). 5. Select the square waveform. Set the Frequency Hz switch to 1.0 x 10 0 (1 Hz). 6. Press the Hold switch, this allows the DACs to increment only one step when the Local Start switch is pressed. 7. Set the Normal/Invert switch to the Invert position. 8. Press the Local Start switch. The output will go negative fullscale (-10 volts) and hold. 9. Adjust R42 (ZERO) for a DVM reading of Vdc. 10. Set the Normal/Invert switch to the Normal position. 11. Press the Local Start switch. The output will go positive fullscale (+10 volts) and hold. 12. Adjust R41 (GAIN) for a DVM reading of Vdc. 13. Press the Ret to Zero switch. The DVM reading should be volts (±2.5 mv). Note the actual reading. 14. Connect the DVM to the front panel Main output. 15. Adjust R110 for the same reading noted in step Connect a DVM to TP6 (MAIN OUTPUT) and TP10 (COM). 17. Select the sine waveform. 18. Set the Normal/Invert switch to the Invert position. 19. Press the Local Start switch; this causes the DAC to decrease 1 step. Note the DVM reading, the voltage should be a few millivolts. 3-3

25 20. Set the Normal/Invert switch to the Normal position. 21. Press the Local Start switch; this causes the DAC to increase 1 step. Note the DVM reading. 22. The voltage noted in steps 19 and 21 should be the same. If not, adjust R46 (SINE FILL IN) for a DVM readout to reflect the same voltage noted in step Return to step 18 and recheck the symmetry between a positive step and a negative step. Repeat this step until both DVM readings are within 1 mv. 24. Press the Return to Zero switch. Adjust R48 (MIN OFFSET) for a DVM readout of volts (±1 mv). 25. Repeat steps 18 through 24 as necessary to balance the voltages to less than 1 mv. 26. Select the Ramp A waveform. Set the Ramp Time 1 (sec) switch to 1.0 x 10 1 (10 second ramp rate). 27. Set the Normal/Invert switch to the Invert position. 28. Press the Local Start switch; this causes the DAC to decrease 1 step. Note the DVM reading, the voltage should be a few millivolts. 29. Set the Normal/Invert switch to the Normal position. 30. Press the Local Start switch; this causes the DAC to increase 1 step. Note the DVM reading. 31. The voltage noted in steps 28 and 30 should be the same. If not, adjust R45 (RAMP FILL IN) for a DVM readout to reflect the same voltage noted in step Repeat steps 27 through 31 as necessary until the symmetry between a positive step and a negative step is within 1 mv. 33. Install the top cover removed in step 1 then push the Function Generator back into the equipment rack. 3-4

26 3.3 Breakpoint Calibration The breakpoint calibration procedure establishes the accuracy of the front panel Breakpt 5-95% Full Scale control. Perform the following procedure to calibrate the Breakpt control. NOTE: The adjustment range of the front panel Breakpt control is 5 to 95% full-scale. The first and last 50 increments of the control dial do not function. 1. If mounted in an equipment rack, pull the Function Generator out and remove the top cover. 1. Adjust the front panel Breakpt control to exactly 1000 (100% fullscale). 2. Connect a DVM to the wiper of the Breakpt control and TP10 (COM). 3. Adjust R82 (BRKPT 10V REF ADJUST) for Vdc. 4. Connect the DVM to TP4 (BRKPT REF). 5. Adjust R19 (BRKPT REF UPPER CLAMP) for Vdc. 6. Set the Breakpt control for 900 (90% full-scale) note the DVM reading. 7. Connect the DVM to TP12 (INV BRKPT REF). 8. Adjust R83 (BRKPT BAL) for a DVM reading of the negative voltage noted in step Connect the DVM to TP4 (BRKPT REF) 10. Set the Breakpt contro to l 000 (0% full-scale). 11. Adjust R21 (BRKPT REF LOWER CLAMP) for a DVM reading of Vdc. 3-5

27 3.4 Cosine Calibration (Option A) This subsection provides the procedure to calibrate the cosine DACs for a full-scale output of ±10 volts. Unless otherwise noted, all test points, jumpers and adjustments are located on the cosine circuit card assembly shown in Figure 3-2. R9 R11 R8 R7 1 X1 TP3 TP2 TP1 J3 Figure 3-2. Cosine Circuit Card Service Locations 1. Set the rear panel Output Scaling switch to Int to establish a fullscale output of +10 volts or, set the rear panel Output Scaling switch to Ext to establish a full-scale output representing the external reference voltage. If external scaling is selected, change the voltage levels in the following steps to reflect the reference voltage input through the Remote connector J5. 2. Connect a DVM to TP1. Ensure the reference voltage selected in step 1 is within 0.1 volt of the selected level. 3. Position jumper X1 across pins 2 and 3 to select the calibration mode. 4. Connect a DVM to the rear panel J1A Cosine connector. 5. Select the haversquare waveform. Set the Frequency (Hz) switch to 9.9 x Set the Normal/Invert switch to the Invert position. 7. Select the Local mode of operation. 3-6

28 8. Press the Local Start switch. When the output reaches -10 volts, press the Hold switch. 9. Adjust R8 (-FULL SCALE) for a DVM reading of Vdc. 10. Set the Normal/Invert switch to the Normal position. 11. Press the Hold switch to release the hold function. Press the Local Start switch. When the output reaches 10 volts, press the Hold switch. 12. Adjust R7 (+FULL SCALE) for a DVM reading of Vdc. 13. Press the Hold switch to release the hold function. Press the Ret to Zero switch and verify a DVM reading of (±2.5 mv). 14. Select the sine waveform. Set the Frequency (Hz) switch to 9.9 x Remove the DVM and connect an oscilloscope to the rear panel J1A Cosine connector. 16. Press the Local Start switch. 17. Adjust R9 (FILL IN) for the smoothest waveform (i.e., to fill in the steps of the DAC). 18. Set-up the oscilloscope to trigger when TP3 goes high. 19. Adjust R11 (MIN OFFSET) for 0.0 volts at the start of a trace on the oscilloscope. 20. Position jumper X1 across pins 1 and 2 for normal operation. 3-7

29 3.5 Voltage Controlled Oscillator Calibration (Option B) The voltage controlled oscillator (VCO) option is calibrated so the output frequency tracks the internal or external frequency setting to within 1% of any range. Unless otherwise noted, all test points, jumpers and adjustments are located on the VCO circuit card assembly. R16 R13 R5 J8 Figure 3-3. VCO Circuit Card Service Locations 1. Select the haversquare waveform. 2. Ground the J4 VCO Ext connector on the rear panel. 3. Set the Frequency (Hz) switch to 0.1 X Connect a frequency counter to the rear panel J1 Main connector. 5. Adjust R13 (VCO ZERO) for a frequency counter reading of 100 ms (±0.1 ms). 6. Set the Frequency (Hz) switch to 9.9 x Adjust R5 (VCO GAIN) for a frequency counter reading of 1.01 ms (±0.001 ms). 8. Repeat steps 3 through 7 until no further adjustment is needed. 9. Connect a voltage source to the rear panel J4 VCO Ext connector. 10. Set the Frequency (Hz) switch to 0.0 X Set the voltage source to Vdc. 12. Adjust R16 (EXT VCO INPUT GAIN) for a frequency counter readout of 1.01 ms (±0.001 ms). 3-8

30 3-9

31 Section 4 Installation This section provides information for installing the Model Function Generator. The Function Generator installation involves mounting the chassis, configuring the power supply to the local line voltage, configuring the operational characteristics with jumpers and connecting the Function Generator to other system components. Read and observe the following note before installing the Function Generator. NOTES: The Model Function Generator contains components which are sensitive to static. Care should be exercised when handling these components to prevent circuit card and/or component damage. The following precautions are suggested: Do not install or remove a jumper while power is applied. Touch the console or other ground point before removing or installing a circuit card. When handling printed circuit cards, avoid making physical contact with any components or circuitry on the card. Hold the card by its sides. Maintain the same potential between the printed circuit card and the equipment or surfaces it will contact by touching the surfaces first. Handle the integrated circuits by the edges. Avoid touching the pins themselves. Any circuit card repairs should be made at a static-free work station by personnel familiar with repairing such devices. 4-1

32 4.1 Function Generator Installation The installation of the Function Generator is subject to specific system requirements. Perform the following to install the Function Generator. 1. Ensure the Function Generator has arrived with no shipping damage. If damaged, contact the Customer Service Division of MTS Corporation. 2. Refer to Subsection 4.2 to install the Function Generator in an equipment rack. 3. Perform the line voltage and grounding procedures in Subsection Circuit card switches and jumpers establish the operational characteristics of the Function Generator. To determine if any configuration changes are needed, refer to Subsection 4.4 for descriptions of the switches and jumpers. 5. Subsection 4.5 provides information for the rear panel connections. Each subsection includes signal identification, signal levels, I/O indication and pin numbers. Review the possible connections to determine which connections are required. 6. If the Cosine option is to be installed, refer to Subsection If the VCO option is to be installed, refer to Subsection Equipment Rack Installation The Function Generator chassis is installed in an equipment rack with slide rails. Perform the following procedure to rack-mount the Function Generator: 1. Determine a mounting position in the equipment rack for the Function Generator. Note which two holes on each of the equipment rack front hole strips will be used to mount the slide rails (refer to Figure 4-1). Ensure the slide rails are positioned at the same level. 2. Separate the female slide assembly (outer slide) from the male slide assembly (attached to the chassis) by pulling the female slide to the rear of the chassis and unlocking the spring latch. 3. Install the female slide assembly to the console as shown in Figure 4-1 using the hex head screws and bar nuts from the slide rail mounting hardware. 4. Repeat steps 2 and 3 to mount the other female slide assembly on the opposite side of the console. 4-2

33 5. Fully extend the female slides from the console. Insert the male slides mounted on the chassis into the female slides until the spring latch locks. 6. Press the spring latch releases and slide the chassis into the console. Rear Equipment Rack Hole Strap Hex Head Screw Chassis Slide Mounting Bracket Female Slides Male Slide attached to Chassis Front Panel Hex Head Screw Equipment Rack Front Equipment Rack Hole Strap Bar Nut Figure 4-1. Rack Mounting the Female Slide Assembly (Top View) 4.3 Voltage and Grounding The following subsections provide information to match the Function Generator to local line voltages and to properly ground the chassis Line Voltage The Function Generator receives power from a detachable, three-wire power cord. The power cord plugs into an input power connector block located on the Function Generator rear panel. Located in the input power connector block are the input power fuse and a PWB to adapt the Function Generator to various input line voltages. The power switch is located on the rear panel, on is labeled and off is labeled O. Perform the following procedure to change the setting to the available line voltage: 1. Disconnect the input power cord from the input power connector. 2. Slide the plastic cover over the input power connector to access the fuse and PWB. 3. Lift the FUSE PULL lever outward and toward the input power connector and remove the fuse. 4. Remove the PWB by inserting a hook in the hole through the PWB to pull it out. 4-3

34 5. Refer to Table 4-1. Position the PWB such that the appropriate input voltage selection legend will be visible and push the PWB back into the input power connector block. Table 4-1. Input Voltage and Corresponding PWB Legend Input Voltage PWB Legend Vac Vac 240 NOTE: The Function Generator specifications are maintained providing the line frequency is within 48 to 63 Hz. Table 4-1 shows the recommended PWB selections for optimum operation. 6. Install a 1 amp, slo-blo fuse for 120 Vac operation. Install a 0.5 amp, slo-blo fuse for 240 Vac operation. 7. If necessary, replace the main power cord with one having the appropriate wall receptacle connector Chassis Common and Grounding The external connections for circuit common (black terminal) and chassis common (metallic terminal) are located on the rear panel of the Function Generator. The Function Generator is manufactured with both terminals connected together (for stand alone applications). For equipment rack installations remove the commoning wire from the ground terminals. The circuit common terminal is connected to a single power ground or earth ground with a braided wire (typically connected to a single point with the circuit common of other equipment). The chassis common terminal is connected to the equipment rack frame with a braided wire. Both wires should be long enough to allow the chassis to be pulled out of the console for testing and calibration. 4-4

35 4.4 Switch and Jumper Descriptions The following subsections provide information on the effect of the rear panel switches and circuit card jumpers on the operation of the Function Generator. The rear panel switches are shown in Figure 4-2 and the location of the circuit card jumpers are shown in Figure 4-3. To access the circuit card jumpers, remove the top cover of the chassis (secured with four screws). Configure the Function Generator rear panel switches and circuit card jumpers per system requirements. NOTE: The jumper illustrations show a jumper block as a shaded rectangle. Figure 4-2. Rear Panel Switch Locations S1 Program (Null) Pacing Enable Switch S1 enables or disables the Function Generator for program null pacing. Setting the Null Pacing switch to Out disables program (null) pacing; setting the Null Pacing switch to In enables program (null) pacing. Program (null) pacing ensures programed levels are reached by the feedback signal of the servocontroller before continuing the program. This is accomplished by sending a dwell signal to the servohydraulic controller; the controller returns a null signal when the transducer feedback is within an acceptable limit of the program command. Refer to Subsection 2.4 for additional information. 4-5

36 4.4.2 S2 Output Scaling Internal/External Switch S2 selects the source of the reference voltage to scale the Function Generator output. The internal selection (Int) provides a fullscale output of ±10 volts. The external selection (Ext) allows an external reference voltage to be input through the Remote connector J5 to establish a full-scale output equal to the external reference voltage. The external reference voltage can be from 2 to 10 volts S3 Breakpoint Source Switch S3 selects the source of the breakpoint reference voltage. The internal selection (Int) enables the front panel Breakpt control. The external selection (Ext) provides an external level input through the Remote connector J5. The external breakpoint reference voltage can be from 0.5 to 9.5 volts. E F G H J K 1 X X9 X6 X X X8 X3 X7 X5 11 A B C D L M N MP-E003B Figure 4-3. Main Circuit Card Jumper Locations X1 Cosine Calibration Jumper X1 (not shown) is located on the cosine option circuit card assembly. The jumper is provided to calibrate the cosine circuit. The jumper is positioned across pins 1 and 2 for normal operation. 4-6

37 4.4.5 X2 VCO Enable Jumper X2 enables the voltage controlled oscillator (VCO) option. The jumper determines if the operating frequency is established with the front panel thumbwheel switches or the VCO option. The VCO option is used with the sine, haversine and haversquare waveforms only. Refer to Figure 4-4 and configure jumper X2 per system requirements. VCO Enable X2 VCO Disable X2 Figure 4-4. VCO Enable Jumper X3, X4 Cosine Output Enable Jumpers X3 and X4 configures the Function Generator to operate with the cosine option. Jumper X3 allows the cosine output to finish its cycle when the program is stopped (after the sine wave program stops). Jumper X4 enables the cosine output to be routed to the rear panel connector J1A. Refer to Figure 4-5 and configure jumpers X3 and X4 per system requirements. Cosine Enable X4 Cosine Disable X X3 1 X3 Figure 4-5. Cosine Enable Jumpers X5, X6 Testing Jumpers X5 and X6 are provided for factory testing purposes. Both jumpers should be positioned across pins 1 and 2 for normal operation. 4-7

38 4.4.8 X7 Remote Stop/Hold Select Jumper X7 determines if the Function Generator output returns to zero or is held at the current level when the remote stop signal is detected. Refer to Figure 4-6 and configure jumper X7 per system requirements. Remote Stop Remote Hold/Resume X7 X Figure 4-6. Remote Stop/Hold Jumper X8 Remote Start Jumper X8 configures the input electronics to accept a 5 volt logic signal or switch contacts from an external gate signal. The gate signal is input through the rear panel Gate connector J3 (refer to Subsection 4.5.3). Refer to Figure 4-7 and configure jumper X8 per system requirements. 5 Volt Logic Switch Contacts 1 X8 1 X8 Figure 4-7. Gate Input Jumper X9, X10 Emergency Stop Jumpers X9 and X10 configure the Function Generator operation for an emergency stop signal. Jumper X9 enables an emergency stop signal to control the Function Generator output (return to zero or hold). Jumper X10 determines how the Function Generator output returns to zero (if necessary) when the emergency stop signal is reset. When an emergency stop signal is detected, jumper X9 can be configured to execute a return to zero, hold the output at the current level then return the output to zero according to jumper X10 or the emergency stop function can be disabled. When the emergency stop signal is reset (interlock reset), jumper X10 can be configured to execute a return to zero (according to the setting of the Ramp Time 2 switch) or step the output directly to zero. 4-8

39 NOTE: When the Function Generator executes a return to zero for a sine, haversine or haversquare waveform; the output will continue until it reaches the next zero crossing. Refer to Figure 4-8 and configure jumpers X9 and X10 per system requirements. Return to Zero Hold Output and X10 No E-Stop X9 4 X9 X9 Ramp to Zero Intlk Reset X Step to Zero Intlk Reset X ' Figure 4-8. Emergency Stop Configurations 4.5 Rear Panel Connectors All input and output signals that interface the Function Generator with other system components are connected to, or available at the rear panel connectors shown in Figure 4-9. This section provides information on all input/output signals at the rear panel. The sequence of the following subsections is in the numerical order of the rear panel connectors. Figure 4-9. Rear Panel Connectors 4-9

40 4.5.1 J1 Main Output Two J1 Main connectors are on the rear panel and one Main connector is on the front panel. These BNC connectors provide the Function Generator program output (within ±10 volts). When the cosine option is installed, rear panel connector J1A provides the 90 (phase lag) program output. The front panel Main Output connector is buffered and provided for monitoring purposes J2 Sync Output The Sync connector outputs a sync pulse at the beginning of each cycle. The sync pulse is a 5 volt, 500 µs signal which can be used for cycle counting. Connector J2 is a BNC connector J3 Gate Input The Gate BNC connector allows an external device to start and stop the Function Generator. The input signal can be from switch contacts or a 5 volt logic signal (refer to Subsection to configure the input). The Function Generator program starts when closed contacts or a high logic signal is detected; the output stops when open contacts or a low logic signal is detected. The gate function operates in conjunction with the front panel Remote switch. NOTE: A 25 Vdc signal through a 22k resistor can also be used when jumper X8 is configured for switch contacts J4 VCO External Input The VCO Ext (Voltage Controlled Oscillator) connector provides an input to control the frequency of a cyclic waveform when option B is installed. The input signal can be within 0.1 volts to 10.0 volts. Refer to Subsection 4.7 for installation information and Subsection for operational information. 4-10

FMR622S DUAL NARROW BAND SLIDING DE-EMPHASIS DEMODULATOR INSTRUCTION BOOK IB

FMR622S DUAL NARROW BAND SLIDING DE-EMPHASIS DEMODULATOR INSTRUCTION BOOK IB FMR622S DUAL NARROW BAND SLIDING DE-EMPHASIS DEMODULATOR INSTRUCTION BOOK IB 1222-22 TABLE OF CONTENTS SECTION 1.0 INTRODUCTION 2.0 INSTALLATION & OPERATING INSTRUCTIONS 3.0 SPECIFICATIONS 4.0 FUNCTIONAL

More information

Model Hz to 10MHz Precision Phasemeter. Operating Manual

Model Hz to 10MHz Precision Phasemeter. Operating Manual Model 6610 1Hz to 10MHz Precision Phasemeter Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give long

More information

INSTRUCTION MANUAL. March 11, 2003, Revision 3

INSTRUCTION MANUAL. March 11, 2003, Revision 3 INSTRUCTION MANUAL Model 701A Stimulator March 11, 2003, Revision 3 Copyright 2003 Aurora Scientific Inc. Aurora Scientific Inc. 360 Industrial Parkway S., Unit 4 Aurora, Ontario, Canada L4G 3V7 Tel: 1-905-727-5161

More information

CIRCUIT-TEST ELECTRONICS

CIRCUIT-TEST ELECTRONICS USER'S MANUAL Sweep Function Generator with Counter SWF-8030 CIRCUIT-TEST ELECTRONICS www.circuittest.com TABLE OF CONTENTS SAFETY INFORMATION...page 3 INTRODUCTION... 4 SPECIFICATIONS... 5 FRONT PANEL

More information

Model LIA100. Lock-in Amplifier

Model LIA100. Lock-in Amplifier Model LIA100 Lock-in Amplifier Operations Manual Thorlabs, Inc 435 Route 206 Newton, NJ 07860 P-(973) 579-7227 F-(973) 300-3600 www.thorlabs.com Doc. Page 1 of 10 Table of Contents Chapter Description

More information

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module

Product overview. Features. Product specifications. Order codes. 1kΩ Resistance Output Module Product overview The AX-ROM135 and the AX-ROM1000 Modules enable an Analogue, Pulse or Floating point signal and convert to either a 0-135Ω or a 1KΩ Proportional Resistive output signal. The output resistance

More information

EXAMPLE. Use this jack for the red test lead when measuring. current from 0 to 200mA. Figure P-1

EXAMPLE. Use this jack for the red test lead when measuring. current from 0 to 200mA. Figure P-1 Digital Multimeters ON / OFF power switch Continuity / Diode Test Function Resistance Function Ranges from 200Ω to 200MΩ Transistor Test Function DC Current Function Ranges from 2mA to 20A. AC Current

More information

CHAPTER 6 DIGITAL INSTRUMENTS

CHAPTER 6 DIGITAL INSTRUMENTS CHAPTER 6 DIGITAL INSTRUMENTS 1 LECTURE CONTENTS 6.1 Logic Gates 6.2 Digital Instruments 6.3 Analog to Digital Converter 6.4 Electronic Counter 6.6 Digital Multimeters 2 6.1 Logic Gates 3 AND Gate The

More information

WESTREX RA-1712 PHOTOGRAPHIC SOUND RECORD ELECTRONICS

WESTREX RA-1712 PHOTOGRAPHIC SOUND RECORD ELECTRONICS INTRODUCTION The RA-1712 solid state Record Electronics is an integrated system for recording photographic sound tracks on a Westrex photographic sound recorder. It accepts a 600Ω input signal level from

More information

DLVP A OPERATOR S MANUAL

DLVP A OPERATOR S MANUAL DLVP-50-300-3000A OPERATOR S MANUAL DYNALOAD DIVISION 36 NEWBURGH RD. HACKETTSTOWN, NJ 07840 PHONE (908) 850-5088 FAX (908) 908-0679 TABLE OF CONTENTS INTRODUCTION...3 SPECIFICATIONS...5 MODE SELECTOR

More information

SixPac Series of SCR AC Controller and DC Converters

SixPac Series of SCR AC Controller and DC Converters SixPac Series of SCR AC Controller and DC Converters Complete Series of SCR Three-Phase Power Control Units Features Include: Compact, rugged construction Applications include: Windmill Converters Motor

More information

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE. ISO-STIM 01D STIMULUS ISOLATION UNIT ±100 V / ±10 ma, bipolar output

OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE. ISO-STIM 01D STIMULUS ISOLATION UNIT ±100 V / ±10 ma, bipolar output OPERATING INSTRUCTIONS AND SYSTEM DESCRIPTION FOR THE ISO-STIM 01D STIMULUS ISOLATION UNIT ±100 V / ±10 ma, bipolar output VERSION 4.0 npi 2014 npi electronic GmbH, Bauhofring 16, D-71732 Tamm, Germany

More information

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR

Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model XR Harris IRT Enterprises Multi-Channel Digital Resistance Tester Model 6012-06XR Specifications & Dimensions 2 Theory of Operation 3 System Block Diagram 4 Operator Controls & Connectors 5 Test Connections

More information

Model 4402B. Ultra-Pure Sinewave Oscillator 1Hz to 110kHz Typical Distortion of % Serial No. Operating Manual

Model 4402B. Ultra-Pure Sinewave Oscillator 1Hz to 110kHz Typical Distortion of % Serial No. Operating Manual Model 4402B Ultra-Pure Sinewave Oscillator 1Hz to 110kHz Typical Distortion of 0.0005% Serial No. Operating Manual 15 Jonathan Drive, Unit 4, Brockton, MA 02301 U.S.A. Tel: (508) 580-1660; Fax: (508) 583-8989

More information

Signal Conditioning Amplifier

Signal Conditioning Amplifier 2300 System Micro-Measurements FEATURES Accepts all strain gage inputs (foil and piezoresistive), potentiometers, DCDT s, etc Selectable bridge excitation, 0.7 to 15 VDC (11 steps), plus 0.2 to 7 VDC continuously

More information

OPERATING MANUAL FOR A 6-SCR GENERAL PURPOSE GATE FIRING BOARD, PART NO. FCOG6100 REV. J, J', J", K INTRODUCTION PRODUCT DESCRIPTION

OPERATING MANUAL FOR A 6-SCR GENERAL PURPOSE GATE FIRING BOARD, PART NO. FCOG6100 REV. J, J', J, K INTRODUCTION PRODUCT DESCRIPTION 5780 Thornwood Drive Goleta, California 93117 Report No. R054 October 14, 1993 OPERATING MANUAL FOR A 6-SCR GENERAL PURPOSE GATE FIRING BOARD, PART NO. FCOG6100 REV. J, J', J", K INTRODUCTION This manual

More information

5MHz FUNCTION GENERATOR

5MHz FUNCTION GENERATOR 5MHz FUNCTION GENERATOR MODEL GF-8056 User s Manual Elenco TM Electronics, Inc. Copyright 2004 by Elenco TM Electronics, Inc. All rights reserved. 753117 No part of this book shall be reproduced by any

More information

5MHz FUNCTION GENERATOR

5MHz FUNCTION GENERATOR 5MHz FUNCTION GENERATOR MODEL GF-8056 99 Washington Street Melrose, MA 02176 Phone 781-665-1400 Toll Free 1-800-517-8431 Visit us at www.testequipmentdepot.com User s Manual Elenco TM Electronics, Inc.

More information

M302RM OPERATING MANUAL

M302RM OPERATING MANUAL M302RM OPERATING MANUAL The Model 302RM is a Linear, high voltage, differential amplifier designed to drive a capacitive load such as Conoptics 350, 360, 370 series E.O. modulators. The amplifier is DC

More information

The MP SERIES CONTROLLER. User s Manual. ISE, Inc.

The MP SERIES CONTROLLER. User s Manual. ISE, Inc. The MP SERIES CONTROLLER User s Manual ISE, Inc. 10100 Royalton Rd. Cleveland, OH 44133 USA Tel: (440) 237-3200 Fax: (440) 237-1744 http://variac.com Form No, 003-1622 Rev G 02/25/2009 Form No. 003-1622

More information

OPERATING AND MAINTENANCE MANUAL

OPERATING AND MAINTENANCE MANUAL 5Hz to 1MHz WIDE RANGE FULLY AUTOMATIC DISTORTION ANALYZER MODEL 6900B SERIAL NO. OPERATING AND MAINTENANCE MANUAL Unit 4, 15 Jonathan Drive, Brockton, MA 02301-5566 Tel: (508) 580-1660; Fax: (508) 583-8989

More information

Model MHz Arbitrary Waveform / Function Generator

Model MHz Arbitrary Waveform / Function Generator Verification and Adjustment Manual 3390-905-01 Rev. B / May 2016 www.tek.com/keithley Model 3390 50 MHz Arbitrary Waveform / Function Generator *P3390-905-01B* 3390-905-01 A Greater Measure of Confidence

More information

INSTRUCTIONS PS2500 POWER SUPPLY

INSTRUCTIONS PS2500 POWER SUPPLY INSTRUCTIONS PS2500 POWER SUPPLY The Hoefer PS 2500 Power Supply will furnished power to Constant Voltage or Constant Power modes of operation. It will accurately supply 0-2500 volts, 0-300 ma or 0-375

More information

Dual Channel Function/Arbitrary Waveform Generators 4050 Series

Dual Channel Function/Arbitrary Waveform Generators 4050 Series Data Sheet Dual Channel Function/Arbitrary Waveform Generators The Dual Channel Function/Arbitrary Waveform Generators are capable of generating stable and precise sine, square, triangle, pulse, and arbitrary

More information

User s Manual for Integrator Short Pulse ISP16 10JUN2016

User s Manual for Integrator Short Pulse ISP16 10JUN2016 User s Manual for Integrator Short Pulse ISP16 10JUN2016 Specifications Exceeding any of the Maximum Ratings and/or failing to follow any of the Warnings and/or Operating Instructions may result in damage

More information

FFP-C Fiber Fabry-Perot Controller OPERATING INSTRUCTIONS. Version 1.0 MICRON OPTICS, INC.

FFP-C Fiber Fabry-Perot Controller OPERATING INSTRUCTIONS. Version 1.0 MICRON OPTICS, INC. FFP-C Fiber Fabry-Perot Controller OPERATING INSTRUCTIONS Version 1.0 MICRON OPTICS, INC. 1852 Century Place NE Atlanta, GA 30345 USA Tel (404) 325-0005 Fax (404) 325-4082 www.micronoptics.com Page 2 Table

More information

MULT SWP X1K K VERN START FREQ DURATION AMPLITUDE 0 TTL OUT RAMP

MULT SWP X1K K VERN START FREQ DURATION AMPLITUDE 0 TTL OUT RAMP Signal Generators This document is a quick reference guide to the operation of the signal generators available in the laboratories. Major functions will be covered, but some features such as their sweep

More information

EECS 318 Electronics Lab Laboratory #2 Electronic Test Equipment

EECS 318 Electronics Lab Laboratory #2 Electronic Test Equipment EECS 318 Electronics Lab Laboratory #2 Electronic Test Equipment Objectives: The purpose of this laboratory is to acquaint you with the electronic sources and measuring equipment you will be using throughout

More information

Peak Current. Continuous Current. See Part Numbering Information on last page of datasheet for additional ordering options.

Peak Current. Continuous Current. See Part Numbering Information on last page of datasheet for additional ordering options. Description Power Range The PWM servo drive is designed to drive brushless DC motors at a high switching frequency. A single red/green LED indicates operating status. The drive is fully protected against

More information

Model 305 Synchronous Countdown System

Model 305 Synchronous Countdown System Model 305 Synchronous Countdown System Introduction: The Model 305 pre-settable countdown electronics is a high-speed synchronous divider that generates an electronic trigger pulse, locked in time with

More information

AME140 Lab #2 INTRODUCTION TO ELECTRONIC TEST EQUIPMENT AND BASIC ELECTRONICS MEASUREMENTS

AME140 Lab #2 INTRODUCTION TO ELECTRONIC TEST EQUIPMENT AND BASIC ELECTRONICS MEASUREMENTS INTRODUCTION TO ELECTRONIC TEST EQUIPMENT AND BASIC ELECTRONICS MEASUREMENTS The purpose of this document is to guide students through a few simple activities to increase familiarity with basic electronics

More information

Models 900CT & 900BT. Tunable Active Single Channel Certified Filter Instrument

Models 900CT & 900BT. Tunable Active Single Channel Certified Filter Instrument Tunable Active Single Channel Certified Filter Instrument Description Frequency Devices instruments are single channel; 8-pole low-pass or high-pass, front panel tunable filter instruments. The controls

More information

Publication Number ATFxxB Series DDS FUNCTION WAVEFORM GENERATOR. User s Guide

Publication Number ATFxxB Series DDS FUNCTION WAVEFORM GENERATOR. User s Guide Publication Number 101201 ATFxxB Series DDS FUNCTION WAVEFORM GENERATOR User s Guide Introduction This user's guide is used for all models of ATFxxB series of DDS function generator. xx in the model number

More information

MODELS 5251/ MS/s PXIBus / PCIBus Arbitrary Waveform / Function Generators

MODELS 5251/ MS/s PXIBus / PCIBus Arbitrary Waveform / Function Generators 250MS/s PXIBus / PCIBus Arbitrary 5251: Single Channel PXIBus waveform generator 5351: Single Channel PCIBus waveform generator Sine waves to 100MHz and Square to 62.5MHz 16 Bit amplitude resolution 2M

More information

User s Manual Current Probe. IM E 2nd Edition IM E

User s Manual Current Probe. IM E 2nd Edition IM E User s Manual 700937 Current Probe 2nd Edition Introduction Thank you for purchasing the 700937 Current Probe. This Instruction Manual contains useful information about the instrument s functions and operating

More information

Applications of the LM392 Comparator Op Amp IC

Applications of the LM392 Comparator Op Amp IC Applications of the LM392 Comparator Op Amp IC The LM339 quad comparator and the LM324 op amp are among the most widely used linear ICs today. The combination of low cost, single or dual supply operation

More information

45EMD Portable Calibrator User Manual

45EMD Portable Calibrator User Manual Trig-Tek 45EMD Portable Calibrator User Manual Publication No. 980958 Rev. B Astronics Test Systems Inc. 4 Goodyear, Irvine, CA 92618 Tel: (800) 722-2528, (949) 859-8999; Fax: (949) 859-7139 atsinfo@astronics.com

More information

Arbitrary/Function Waveform Generators 4075B Series

Arbitrary/Function Waveform Generators 4075B Series Data Sheet Arbitrary/Function Waveform Generators Point-by-Point Signal Integrity The Arbitrary/Function Waveform Generators are versatile high-performance single- and dual-channel arbitrary waveform generators

More information

Agilent 8360B Series Synthesized Swept Signal Generators 8360L Series Synthesized Swept CW Generators Data Sheet

Agilent 8360B Series Synthesized Swept Signal Generators 8360L Series Synthesized Swept CW Generators Data Sheet Agilent 8360B Series Synthesized Swept Signal Generators 8360L Series Synthesized Swept CW Generators Data Sheet 10 MHz to 110 GHz Specifications apply after full user calibration, and in coupled attenuator

More information

Microprocessor Control Board Set Up Procedures (OR PLC)

Microprocessor Control Board Set Up Procedures (OR PLC) Microprocessor Control Board Set Up Procedures (OR-00 PLC) SWITCHES/PUSHBUTTONS Push Buttons at display SW Enter button SW Back button SW Down SW UP Back light on/off switch Rotary switches on main board

More information

Model 3102D 0-2 kv H.V. Power Supply

Model 3102D 0-2 kv H.V. Power Supply Features Compact single width NIM package Regulated up to ±2000 V dc. 1 ma output Noise and ripple 3 mv peak to peak Overload and short circuit protected Overload, inhibit and polarity status indicators

More information

MAINTENANCE MANUAL AUDIO MATRIX BOARD P29/

MAINTENANCE MANUAL AUDIO MATRIX BOARD P29/ MAINTENANCE MANUAL AUDIO MATRIX BOARD P29/5000056000 TABLE OF CONTENTS Page DESCRIPTION................................................ Front Cover CIRCUIT ANALYSIS.............................................

More information

SCC-FV01 Frequency Input Module

SCC-FV01 Frequency Input Module USER GUIDE SCC-FV01 Frequency Input Module Conventions The SCC-FV01 frequency input module is a frequency-to-voltage converter designed to measure signals from frequency-generating sensors and other periodic

More information

LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL

LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL LINCO MEASUREMENT MODEL CP-2B MASTER METER PROVER COUNTER INSTRUCTION MANUAL ENGINEERED AUTOMATED SYSTEMS DESIGNERS ENGINEERS MANUFACTURERS SALES REPRESENTATIVES 4580 W. HWY 80 P.O. BOX 4096 MIDLAND, TEXAS

More information

Maintenance Manual ERICSSONZ LBI-31552E

Maintenance Manual ERICSSONZ LBI-31552E E Maintenance Manual TONE REMOTE CONTROL BOARD 19A704686P4 (1-Frequency Transmit Receive with Channel Guard) 19A704686P6 (4-Frequency Transmit Receive with Channel Guard) ERICSSONZ Ericsson Inc. Private

More information

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation

User s Manual Current Probe. IM E 2nd Edition. Yokogawa Electric Corporation User s Manual 701930 Current Probe Yokogawa Electric Corporation 2nd Edition Foreword Revisions Thank you for purchasing the Current Probe (Model 701930). This instruction manual contains useful information

More information

HP 33120A Function Generator / Arbitrary Waveform Generator

HP 33120A Function Generator / Arbitrary Waveform Generator Note: Unless otherwise indicated, this manual applies to all Serial Numbers. The HP 33120A is a high-performance 15 MHz synthesized function generator with built-in arbitrary waveform capability. Its combination

More information

Instruction Manual. SSQ-2F Controller Board. For the. v1.41 For Rife Plasma Tube Systems. Manual v by Ralph Hartwell Spectrotek Services

Instruction Manual. SSQ-2F Controller Board. For the. v1.41 For Rife Plasma Tube Systems. Manual v by Ralph Hartwell Spectrotek Services Instruction Manual For the SSQ-2F Controller Board v1.41 For Rife Plasma Tube Systems Manual v1.00 2012 by Ralph Hartwell Spectrotek Services This page intentionally blank. 2 Index and Table of Contents

More information

2775AM4 Signal conditioner Instruction manual. IM2775AM4, Revision BC

2775AM4 Signal conditioner Instruction manual. IM2775AM4, Revision BC 2775AM4 Signal conditioner Instruction manual, Revision BC TABLE OF CONTENTS SECTION 1: INTRODUCTION PAGE 1. INTRODUCTION 1-1 2. EQUIPMENT USE 1-2 SECTION 2: CONTROLS AND CONNECTORS 1. INTRODUCTION 2-1

More information

Agilent 33250A 80 MHz Function / Arbitrary Waveform Generator. User s Guide

Agilent 33250A 80 MHz Function / Arbitrary Waveform Generator. User s Guide User s Guide Publication Number 33250-90002 (order as 33250-90100 manual set) Edition 2, March 2003 Copyright Agilent Technologies, Inc. 2000, 2003 For Safety information, Warranties, and Regulatory information,

More information

Laboratory Equipment Instruction Manual 2011

Laboratory Equipment Instruction Manual 2011 University of Toronto Department of Electrical and Computer Engineering Instrumentation Laboratory GB341 Laboratory Equipment Instruction Manual 2011 Page 1. Wires and Cables A-2 2. Protoboard A-3 3. DC

More information

Dual Channel Function/Arbitrary Waveform Generators 4050 Series

Dual Channel Function/Arbitrary Waveform Generators 4050 Series Data Sheet Dual Channel Function/Arbitrary Waveform Generators The Dual Channel Function/Arbitrary Waveform Generators are capable of generating stable and precise sine, square, triangle, pulse, and arbitrary

More information

Installation and Operating Manual

Installation and Operating Manual GB Analog Weight Transmitter PS-1000 Installation and Operating Manual LIST OF CONTENTS Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5 Section

More information

AMC-100 AMC-101 AMC-100 AMC-100B AMC-100D AMC-101 AMC-101B AMC-101D AMC-100A AMC-100C AMC-100E AMC-101A AMC-101C AMC-101E. AC Motor Controllers

AMC-100 AMC-101 AMC-100 AMC-100B AMC-100D AMC-101 AMC-101B AMC-101D AMC-100A AMC-100C AMC-100E AMC-101A AMC-101C AMC-101E. AC Motor Controllers The Indelac / AC Motor Controllers are used for proportional positioning of split phase AC actuator motors. An external command signal of 0-0V, -V, or -0mA can be used to compare to a feedback signal from

More information

RIGOL Data Sheet. DG3000 Series Function/Arbitrary Waveform Generator DG3121A, DG3101A, DG3061A. Product Overview. Easy to Use Design.

RIGOL Data Sheet. DG3000 Series Function/Arbitrary Waveform Generator DG3121A, DG3101A, DG3061A. Product Overview. Easy to Use Design. RIGOL Data Sheet DG3000 Series Function/Arbitrary Waveform Generator DG3121A, DG3101A, DG3061A Product Overview DG3000 Series Function/Arbitrary Waveform Generators adopt DDS technology, which enables

More information

Computer-Based Project on VLSI Design Co 3/7

Computer-Based Project on VLSI Design Co 3/7 Computer-Based Project on VLSI Design Co 3/7 Electrical Characterisation of CMOS Ring Oscillator This pamphlet describes a laboratory activity based on an integrated circuit originally designed and tested

More information

When you have completed this exercise, you will be able to relate the gain and bandwidth of an op amp

When you have completed this exercise, you will be able to relate the gain and bandwidth of an op amp Op Amp Fundamentals When you have completed this exercise, you will be able to relate the gain and bandwidth of an op amp In general, the parameters are interactive. However, in this unit, circuit input

More information

FREQUENCY SYNTHESIZERS, SIGNAL GENERATORS

FREQUENCY SYNTHESIZERS, SIGNAL GENERATORS SYNTHESIZED SIGNAL GENERATOR MG3641A/MG3642A 12 khz to 1040/2080 MHz NEW New Anritsu synthesizer technology permits frequency to be set with a resolution of 0.01 Hz across the full frequency range. And

More information

OPERATION & SERVICE MANUAL FOR FC 110 AC POWER SOURCE

OPERATION & SERVICE MANUAL FOR FC 110 AC POWER SOURCE OPERATION & SERVICE MANUAL FOR FC 100 SERIES AC POWER SOURCE FC 110 AC POWER SOURCE VERSION 1.3, April 2001. copyright reserved. DWG No. FC00001 TABLE OF CONTENTS CHAPTER 1 INTRODUCTION... 1 1.1 GENERAL...

More information

Dual Channel Function/Arbitrary Waveform Generators 4050B Series

Dual Channel Function/Arbitrary Waveform Generators 4050B Series Data Sheet Dual Channel Function/Arbitrary Waveform Generators The Dual Channel Function/ Arbitrary Waveform Generators are capable of generating stable and precise sine, square, triangle, pulse, and arbitrary

More information

The University of Jordan Mechatronics Engineering Department Electronics Lab.( ) Experiment 1: Lab Equipment Familiarization

The University of Jordan Mechatronics Engineering Department Electronics Lab.( ) Experiment 1: Lab Equipment Familiarization The University of Jordan Mechatronics Engineering Department Electronics Lab.(0908322) Experiment 1: Lab Equipment Familiarization Objectives To be familiar with the main blocks of the oscilloscope and

More information

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY Sheet 1 of 7 Order Number Serial Number PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY Issue Date Level D 12/12/1996 Initial issue. Summary of changes Due to RMS continuous product improvement policy

More information

Thornwood Drive Operating Manual: Two-SCR General Purpose Gate Firing Board FCRO2100 Revision H

Thornwood Drive Operating Manual: Two-SCR General Purpose Gate Firing Board FCRO2100 Revision H http://www.enerpro-inc.com info@enerpro-inc.com 5780 Thornwood Drive Report R188 Goleta, California 93117 February 2011 Operating Manual: Two-SCR General Purpose Gate Firing Board FCRO2100 Revision H Introduction

More information

Operation Manual February Opticom Infrared System

Operation Manual February Opticom Infrared System Operation Manual February 2008 Opticom Infrared System M195/196, M9192, M292, M9592, M592 Emitters M511, M521, M522 Detectors M262, M562 Phase Selectors M360, M560 System Chassis M5168, M5575 Interface

More information

MODEL AT-10 ANALOG TRANSMITTER

MODEL AT-10 ANALOG TRANSMITTER MODEL AT-10 ANALOG TRANSMITTER INSTALLATION & OPERATING MANUAL Industrial Weighing Systems 9 Richmond Street Picton, Ontario K0K 2T0 Phone: 613-921-0397 Fax: 613-476-5293 Web: www.iwsystems.ca info@iwsystems.ca

More information

Variable Gm Calibration Procedure

Variable Gm Calibration Procedure Variable Gm Calibration Procedure REV. 3 Sept. 16, 2018. Warm-up Power on the unit and let it warm for about 20-30 minutes, so that all circuitries stabilize. A.C. Check With a DMM (Digital Multi Meter)

More information

FMT633S STEREO SYNTHESIZER MODULATOR INSTRUCTION BOOK IB

FMT633S STEREO SYNTHESIZER MODULATOR INSTRUCTION BOOK IB FMT633S STEREO SYNTHESIZER MODULATOR INSTRUCTION BOOK IB 6114-01 TABLE OF CONTENTS GENERAL DESCRIPTION: 1 SPECIFICATIONS: 2 FUNCTIONAL DESCRIPTION: 3 INSTALLATION & OPERATING INSTRUCTIONS: 3-4 CAUTION:

More information

2 Oscilloscope Familiarization

2 Oscilloscope Familiarization Lab 2 Oscilloscope Familiarization What You Need To Know: Voltages and currents in an electronic circuit as in a CD player, mobile phone or TV set vary in time. Throughout the course you will investigate

More information

MODELS WW5061/2. 50MS/s Single/Dual Channel Arbitrary Waveform Generators

MODELS WW5061/2. 50MS/s Single/Dual Channel Arbitrary Waveform Generators Single / Dual Channel 50MS/s waveform generator Sine waves to 25MHz, Square to 15MHz SINE OUT to 50MHz, 1Vp-p 11 Built-in popular standard waveforms 14 Bit amplitude resolution 11 digits frequency resolution

More information

Analog-to-Digital-Converter User Manual

Analog-to-Digital-Converter User Manual 7070 Analog-to-Digital-Converter User Manual copyright FAST ComTec GmbH Grünwalder Weg 28a, D-82041 Oberhaching Germany Version 2.0, July 7, 2005 Software Warranty FAST ComTec warrants proper operation

More information

High Efficiency AC Input 12A 12V Laser Driver

High Efficiency AC Input 12A 12V Laser Driver Figure. Front View of the Figure 2. Top View of the FEATURES High efficiency: 70 % Maximum output current: 2A Wide output voltage: 0V ~ 2V Wide input voltage: 00VAC ~ 240VAC High speed digital modulation:

More information

Model 34A. 3Hz to 2MHz 2-Channel Butterworth/Bessel HP, LP, BP, BR Plug-In Filter Card for Model 3905/3916 Chassis.

Model 34A. 3Hz to 2MHz 2-Channel Butterworth/Bessel HP, LP, BP, BR Plug-In Filter Card for Model 3905/3916 Chassis. Model 34A 3Hz to 2MHz 2-Channel Butterworth/Bessel HP, LP, BP, BR Plug-In Filter Card for Model 3905/3916 Chassis Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured

More information

Circuit Applications of Multiplying CMOS D to A Converters

Circuit Applications of Multiplying CMOS D to A Converters Circuit Applications of Multiplying CMOS D to A Converters The 4-quadrant multiplying CMOS D to A converter (DAC) is among the most useful components available to the circuit designer Because CMOS DACs

More information

PEOPLE IN CONTROL OF MOTION

PEOPLE IN CONTROL OF MOTION MODEL 796500 RESOLVER TO ENCODER CONVERTER FOR MACHINE TOOL, POSITIONING, AND TRANSFER LINE APPLICATIONS *** APPLICATIONS *** Ideal For Closed Loop Positioning Systems Machine Tools Nuclear Applications

More information

Applications of the LM392 Comparator Op Amp IC

Applications of the LM392 Comparator Op Amp IC Applications of the LM392 Comparator Op Amp IC The LM339 quad comparator and the LM324 op amp are among the most widely used linear ICs today The combination of low cost single or dual supply operation

More information

ExacTime GPS Time & Frequency Generator

ExacTime GPS Time & Frequency Generator TIMING, TEST & MEASUREMENT ExacTime 6000 GPS Time & Frequency Generator KEY FEATURES GPS Time and Frequency Reference Disciplined Quartz Oscillator Time Base Optional Disciplined Rubidium Oscillator Rapid

More information

Analog Servo Drive 20A20

Analog Servo Drive 20A20 Description Power Range NOTE: This product has been replaced by the AxCent family of servo drives. Please visit our website at www.a-m-c.com or contact us for replacement model information and retrofit

More information

Exercise 2: FM Detection With a PLL

Exercise 2: FM Detection With a PLL Phase-Locked Loop Analog Communications Exercise 2: FM Detection With a PLL EXERCISE OBJECTIVE When you have completed this exercise, you will be able to explain how the phase detector s input frequencies

More information

A Simplified Test Set for Op Amp Characterization

A Simplified Test Set for Op Amp Characterization A Simplified Test Set for Op Amp Characterization INTRODUCTION The test set described in this paper allows complete quantitative characterization of all dc operational amplifier parameters quickly and

More information

Sealed Interface Control: EC20300

Sealed Interface Control: EC20300 ISO 9001:2000 WITH DESIGN Certificate #02.002.1 Sealed Interface Control: EC20300 FEATURES: Weather tight control package Pulse Width Modulated output Waterproof altitude pressure and vapor release vent

More information

4 K to 512 K words (2 n, n = 12 to 19) or 2 to 10,000 control points (linear interpolation between control points)

4 K to 512 K words (2 n, n = 12 to 19) or 2 to 10,000 control points (linear interpolation between control points) The values of items marked with *1 are guaranteed values. All other values are either nominal values or typical (typ.) values, and are not guaranteed. Conditions unless otherwise mentioned are as follows:

More information

LM13600 Dual Operational Transconductance Amplifiers with Linearizing Diodes and Buffers

LM13600 Dual Operational Transconductance Amplifiers with Linearizing Diodes and Buffers LM13600 Dual Operational Transconductance Amplifiers with Linearizing Diodes and Buffers General Description The LM13600 series consists of two current controlled transconductance amplifiers each with

More information

Standard Configuration

Standard Configuration Radiant Technologies, Inc. 2835D Pan American Freeway NE Albuquerque, NM 87107 Tel: 505-842-8007 Fax: 505-842-0366 e-mail: radiant@ferrodevices.com 9 April, 2009 From: Scott P. Chapman Radiant Technologies,

More information

MASTERFLEX L/S ECONOMY 200 RPM DRIVE 115 VOLT MASTERFLEX L/S ECONOMY 200 RPM DRIVE 230 VOLT

MASTERFLEX L/S ECONOMY 200 RPM DRIVE 115 VOLT MASTERFLEX L/S ECONOMY 200 RPM DRIVE 230 VOLT MODELS: ********SERVICE MANUAL******** 7554-80 MASTERFLEX L/S ECONOMY 200 RPM DRIVE 115 VOLT 7554-85 MASTERFLEX L/S ECONOMY 200 RPM DRIVE 230 VOLT 7554-90 MASTERFLEX L/S ECONOMY 600 RPM DRIVE 115 VOLT

More information

High Efficiency AC Input 8A 19V Laser Driver

High Efficiency AC Input 8A 19V Laser Driver Figure 1. Front View of the Figure 2. Top View of the FEATURES High efficiency: 70% Maximum output current: 8A Wide output voltage: 0V ~ 19V Wide input voltage: 100VAC ~ 240VAC High speed digital modulation:

More information

Model Operating Manual

Model Operating Manual Model 7500 DC to 1MHz Wideband Power Amplifier Operating Manual Copyright 2004. All rights reserved. Contents of this publication may not be reproduced in any form without the written permission of Krohn-Hite

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate True RMS AC Voltage & Current Meter with 1 Cycle Update at 50/60 Hz Features True AC or AC plus DC RMS measurement with crest factor of 3.0 at FS Fast response: reading

More information

DIGITAL MULTIMETERS VIEW RECORDERS & 7562 Digital Multimeters FUNCTIONS FEATURES

DIGITAL MULTIMETERS VIEW RECORDERS & 7562 Digital Multimeters FUNCTIONS FEATURES 756 & 7562 Digital Multimeters 756 (6-/2 digits) 23 88 330 mm 3 kg (8-3/8 3-/2 3" 6.6 lbs) 7562 (6-/2 digits) 23 88 330 mm 3 kg (8-3/8 3-/2 3" 6.6 lbs) The 7560 (6-/2 digit display) Series is a high-accuracy,

More information

Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW)

Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW) Yaskawa Electric America Unit Troubleshooting Manual Section Two: Power Checks GPD 506/P5 and GPD 515/G5 (0.4 ~ 160kW) Page 1 Section Two: Power Checks Page 2 Check box when completed Power Checks TEST

More information

6-Bit A/D converter (parallel outputs)

6-Bit A/D converter (parallel outputs) DESCRIPTION The is a low cost, complete successive-approximation analog-to-digital (A/D) converter, fabricated using Bipolar/I L technology. With an external reference voltage, the will accept input voltages

More information

EE431 Lab 1 Operational Amplifiers

EE431 Lab 1 Operational Amplifiers Feb. 10, 2015 Report all measured data and show all calculations Introduction The purpose of this laboratory exercise is for the student to gain experience with measuring and observing the effects of common

More information

OPERATION MANUAL LDM-1000

OPERATION MANUAL LDM-1000 OPERATION MANUAL LDM-1000 TE CONNECTIVITY SENSORS /// LDM-1000 OPERATION MANUAL P/N 09290100-000 REV. C 05/2016 Page 1 Table of Contents 1. Introduction...3 2. Product Specifications...3 3. Product Description...4

More information

Electronic regulator for PWM controlled proportional solenoid valves FABER -

Electronic regulator for PWM controlled proportional solenoid valves FABER - Electronic regulator for PWM controlled proportional solenoid valves STU Control Unit FABER - COM DESCRIPTION STU-PWM electronic card is a regulator for proportional solenoid valves, which can drive up

More information

Model 7000 Low Noise Differential Preamplifier

Model 7000 Low Noise Differential Preamplifier Model 7000 Low Noise Differential Preamplifier Operating Manual Service and Warranty Krohn-Hite Instruments are designed and manufactured in accordance with sound engineering practices and should give

More information

MC133C/133Ci. Electric Power/Energy Calibrator. Operation manual

MC133C/133Ci. Electric Power/Energy Calibrator. Operation manual MC133C/133Ci Electric Power/Energy Calibrator Operation manual MC133C Electric Power/Energy Calibrator Powertek Content 1 Basic information... 5 2 Preparation for operation... 6 2.1 Inspecting package

More information

BC145 SIGNAL ISOLATOR BOARD

BC145 SIGNAL ISOLATOR BOARD BC145 SIGNAL ISOLATOR BOARD 4/17 Installation & Operating Manual MN1373 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com to download

More information

DG5000 series Waveform Generators

DG5000 series Waveform Generators DG5000 series Waveform Generators DG5000 is a multifunctional generator that combines many functions in one, including Function Generator, Arbitrary Waveform Generator, IQ Baseband /IQ IF, Frequency Hopping

More information

1047A Refractive Index Detector. Service Handbook

1047A Refractive Index Detector. Service Handbook 1047A Refractive Index Detector Service Handbook Copyright Agilent Technologies 2001 All rights reserved. Reproduction, adaption, or translation without prior written permission is prohibited, except as

More information

General Application Notes Remote Sense Remote On / Off Output Trim Series Operation Parallel Operation...

General Application Notes Remote Sense Remote On / Off Output Trim Series Operation Parallel Operation... General... 28 Remote Sense... 29 Remote On / Off... 30 Output Trim... 30 Series Operation... 32 Parallel Operation... 33 Synchronization... 33 Power Good Signal... 34 Electro Magnetic Filter (EMI)... 34

More information

DG4000 Series Waveform Generators

DG4000 Series Waveform Generators No.1 DG4000 DG4000 series is a multifunctional generator that combines many functions in one, including Function Generator, Arbitrary Waveform Generator, Pulse Generator, Harmonic Generator, Analog/Digital

More information