Bulletin 100S-C/104S-C Safety Contactors. Bulletin 700S-CF Safety Control Relays. Table of Contents. Selection Guide

Size: px
Start display at page:

Download "Bulletin 100S-C/104S-C Safety Contactors. Bulletin 700S-CF Safety Control Relays. Table of Contents. Selection Guide"

Transcription

1 Bulletin S-C/S-C Safety Contactors Bulletin 7S-CF Safety Control Relays Selection Guide Table of Contents Description Page Bulletin S-C/S-C Safety Contactors Product Selection Bulletin 7S-CF Safety Control Relays Product Selection Accessories Specifications Dimensions

2 Bulletin S-C/S-C Safety Contactors Bulletin S-C/S-C Positively Guided/ Mechanically Linked Auxiliary Contacts Front-Mounted Auxiliary Contacts: Permanently Fixed Protective Cover to Prevent Manual Operation Red Contact Housing for Easy Identification Incorporates IEC 97-- Mechanically Linked Symbol AC and DC Operating Coils SUVA Third-Party Certification Description Bulletin S-C/S-C safety contactors provide mechanically linked, positively guided contacts, which are required in feedback circuits for modern safety applications. The positively guided N.C. auxiliary contacts will not change state when a power contact welds. For additional information and selection of overload relays, mounting systems, and other MCS components, please see Publication C-... Consult your local sales office or price list for pricing information. Your order must include: Conformity to Standards Approvals IEC 97- SUVA Third-Party Certified IEC 97 Type Coordination CE IEC 97-- Annex H (Pending) Special Requirements for Auxiliary Contacts Mechanically Linked with Power Contacts (Mirror Contacts) CSA Certified (Cert. No. LR98) IEC 97-- Annex L Special Requirements for Mechanically Linked Contact Elements EN UL 8 CSA. No. UL Listed (File No. E, Guide No. NLDX) of contactor selected with coil voltage code. If required, of any accessories. If required, of replacement coils.

3 Bulletin S-C/S-C Safety Contactors Product Selection -Pole AC-Operated Contactors AC Operating Mechanism Main Contacts Ie Ratings for Switching AC Motors - AC-, AC-, AC- [A] kw ( Hz) AC- AC- V 8V V V V Aux. Contacts HP (6 Hz) 69V V V V V 6V 7V 9 / 7-/... / 7-/ / 7-/ / / 6 6 N.O. N.C. ➊ S-C9 C S-C9 C S-C C S-C C S-C6 C S-C6 C S-C C S-C C S-C C S-C C S-C7 C S-C7 C S-C C S-C C S-C6 C S-C6 C S-C7 C S-C7 C S-C8 C S-C8 C ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. Voltage Suffix Code and Terminal Position The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V, 6Hz: S-C9 C becomes S-C9DC. V Hz Hz 6Hz /6 R K V Q J KJ W V X Y KP X KY KP KP D KD P D S KG KG L KG H L F KF VA T A KA T I E N KN G B N KB B M C C Coil Terminal Position All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a U prior to the coil voltage code. Ordering example: S-C9UDC. S-C9 C Line Side S-C9U C Load Side

4 Bulletin S-C/S-C Safety Contactors Product Selection, Continued -Pole AC-Operated Contactors AC Operating Mechanism Main Contacts Ratings for Switching AC Motors Ie AC-, AC-, AC- Contact Configuration [A] kw ( Hz) HP (6 Hz) Main Pole Auxiliary Contacts AC- AC- V 8V V V V 69V V V V V 6V 7V N.O. N.C. N.O. N.C. 9 / 7-/... / 7-/ / ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. ➊ S-C9 C S-C9 C S-C C S-C C S-C6 C S-C6 C S-C C S-C C Voltage Suffix Code The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V, 6 Hz: S-C9 C becomes S-C9DC. Hz V Hz R K V W X Y KP D P S KG L F VA T N G B M C 6 Hz Q J V X KP D KG H L A T I E N B C /6 Hz KJ KY KP KD KG KF KA KN KB Accessories Page Specifications Page Approximate Dimensions Page 9

5 Bulletin S-C/S-C Safety Contactors Product Selection, Continued -Pole DC-Operated Contactors DC Operating Mechanism Main Contacts Ie Ratings for Switching AC Motors - AC-, AC-, AC- [A] AC- kw ( Hz) AC- V 8V V V V Auxiliary Contacts HP (6 Hz) 69V V V V V 6V 7V 9 / 7-/... / 7-/ / 7-/ / / 6 6 N.O. N.C. ➊ S-C9 C S-C9 C S-C C S-C C S-C6 C S-C6 C S-C C S-C C S-C C S-C C S-C7 C S-C7 C S-C C S-C C S-C6 C S-C6 C S-C7 C S-C7 C S-C8 C S-C8 C ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. Voltage Suffix Code and Terminal Position The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V DC: S-C9 C becomes S-C9ZJC. DC Voltages S-C9 C S-C6 C8 Standard with Integrated Diode with Integrated Diode ZR DR ZQ DQ ZJ DJ DJ ZW DW ZY DY ZZ DZ ZB DB ZG DG ZE DE ZD DD ZP DP ZS DS ZA DA ZF DF ZT DT Coil Terminal Position All contactors are delivered with the coil terminals located on the line side. For load side coil terminations, insert a U prior to the coil voltage code. Ordering example: S-C9UZJC. SC9Z C Line Side S-C9ZU C Load Side

6 Bulletin S-C/S-C Safety Contactors Product Selection, Continued -Pole DC-Operated Contactors DC Operating Mechanism Main Contacts Ratings for Switching AC Motors Ie AC-, AC-, AC- Contact Configuration [A] kw ( Hz) HP (6 Hz) Main Pole Auxiliary Contact AC- AC- V 8V V V V 69V V V V V 6V 7V N.O. N.C. N.O. N.C. 9 / 7-/... / 7-/ / ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. ➊ S-C9 C S-C9 C S-C C S-C C S-C6 C S-C6 C S-C C S-C C Voltage Suffix Code The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V DC: S- C9 C becomes S-C9ZJC. S-C9 C DC Voltages Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT with Integrated Diode DJ Accessories Page Specifications Page Approximate Dimensions Page 9 6

7 Reversing AC-Operated Contactors Bulletin S-C/S-C Safety Contactors Product Selection, Continued AC Operating Mechanism, Main Contacts Includes Mechanical/Electrical Interlock Includes Reversing Power Wiring Ratings for Switching AC Motors Ie AC-, AC-, AC- [A] kw ( Hz) HP (6 Hz) Auxiliary Contacts Installed per Contactor AC- AC- V 8V V V V 69V ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. ➊ Voltage Suffix Code The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V 6 Hz: S-C9 C becomes S-C9DC. V V V V 6V 7V N.O. N.C.➊ 9 / 7-/... / 7-/ / 7-/ / S-C9 C S-C9 C 6 S-C C S-C C 6 S-C6 C S-C6 C 6 S-C C S-C C S-C C S-C C S-C7 C S-C7 C S-C C S-C C S-C6 C S-C6 C S-C7 C S-C7 C S-C8 C S-C8 C Standard Coil - - Voltages Hz R K V W X Y KP D P S KG L F VA T N G B M C 6 Hz Q J V X KP D KG H L A T I E N B C /6 Hz KJ KY KP KD KG KF KA KN KB Accessories Page 7

8 Bulletin S-C/S-C Safety Contactors Product Selection, Continued Reversing DC-Operated Contactors DC Operating Mechanism, Main Contacts, Line Side Coil Terminations Includes Mechanical/Electrical Interlock Includes Reversing Power Wiring Ratings for Switching AC Motors Ie AC-, AC-, AC- [A] kw ( Hz) HP (6 Hz) Auxiliary Contacts Installed per Contactor ➊ For other contact configurations, please contact your local Rockwell Automation/Allen-Bradley sales office. Voltage Suffix Code The as listed is incomplete. Select a voltage suffix code from the table below to complete the Example: V 6 Hz: S-C9 C becomes S-C9ZJC. 8 AC- AC- V 8V V V V 69V V V V V 6V 7V N.O. N.C. 9 / 7-/... / 7-/ / 7-/ / 6 6 S- C9 C S- C6 C8 ➊ 6 S-C9 C S-C9 C 6 S-C C S-C C 6 S-C6 C S-C6 C 6 S-C C S-C C S-C C S-C C S-C7 C S-C7 C S-C C S-C C S-C6 C S-C6 C S-C7 C S-C7 C S-C8 C S-C8 C DC Voltages Standard ZR ZQ ZJ ZW ZY ZZ ZB ZG ZE ZD ZP ZS ZA ZF ZT with Integrated Diode DJ with Integrated Diode DR DQ DJ DW DY DZ DB DG DE DD DP DS DA DF DT Accessories Page Specifications Page Approximate Dimensions Page 9

9 Bulletin 7S-CF Safety Control Relays Bulletin 7S-CF Positively Guided/ Mechanically Linked Auxiliary Contacts Front-Mounted Auxiliary Contacts: Permanently Fixed Protective Cover to Prevent Manual Operation Red Contact Housing for Easy Identification Incorporates IEC 97-- Mechanically Linked Symbol AC and DC Operating Coils SUVA Third-Party Certification Description Bulletin 7S-CF Safety Control Relays provide mechanically linked, positively guided contacts, which are required in feedback circuits for modern safety applications. The positively guided N.C. auxiliary contacts will not change state if a N.O. contact welds. Consult your local sales office or price list for pricing information. Conformity to Standards IEC 97-- IEC 97-- Annex L Special Requirements for Mechanically Linked Contact Elements EN, EN, EN UL 8 VDE 66 CSA C. Part Approvals SUVA Third-Party Certified CE Certified CSA Certified UL Listed, File E8, Guide NKCR Your order must include: of the relays required, complete with coil suffix. of adder decks, timers and accessories required. If required, the part number of replacement coils. 9

10 Bulletin 7S-CF Safety Control Relays Product Selection Type CF Control Relays 8-Pole AC Voltage AC- AC- and AC- Connection Diagrams Contacts I e [A] I e [A] Main Auxiliary C 6 C /8V V V V V 6V 69V Contacts Contacts N.O. N.C. 7S-CF C S-CF C 6 7S-CF6 C Voltage Suffix Code The as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Example: 7-CF C becomes 7-CFDC. Voltage Hz R K V W X Y KP D P S KG F VA T N G B M C 6 Hz Q J V X KP D KG H L A T I E N B C /6 Hz KJ KY KP KD KG KF KA KN KB Accessories Page Specifications Page Approximate Dimensions Page 9

11 Type CF Control Relays 8-Pole DC Voltage Bulletin 7S-CF Safety Control Relays Product Selection AC- AC- and AC- Connection Diagrams Contacts I e [A] I e [A] Auxiliary Main Contacts C 6 C /8V V V V V 6V 69V Contacts N.O. N.C. 7S-CFZ C S-CFZ C 6 7S-CF6Z C Voltage Suffix Code The as listed is incomplete. Select a Voltage Suffix Code from the table below to complete the Example: 7-CFZ C becomes 7-CFZJC for V DC. Voltage Standard R Q J W Y Z B G E D P S A F T With diode suppressor ➊ DJ ➊ When ordering DJ coil with built-in surge suppression, remove Z from the Example: 7S-CFZ C becomes 7S-CFDJC Accessories Page Specifications Page Approximate Dimensions Page 9

12 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Accessories Auxiliary Contacts Description N.O. N.C. Connection Diagrams For Use With Auxiliary Contact Blocks for Side Mounting without Sequence Terminal Designations ➊ - and -pole Two-way numbering for right or left mounting on the contactor Quick and easy mounting without tools Electronic-compatible contacts down to 7V, ma Mutual positive guidance to the main contactor poles (except for L types) -SA -SA S-C all 7S-CF all S-C AC only 7S-CF AC only -SA -SA Auxiliary Contact Blocks for Side Mounting with Sequence Terminal Designations ➊ - and -pole Two-way numbering for right or left mounting on the contactor Quick and easy mounting without tools Electronic compatible contacts down to 7V, ma Mutual positive guidance to the main contactor poles (except for L types) L = Late break/early make -SB -SB S-C9 C 7S-CF all➋ S-C9 C AC only 7S-CF AC only➋ -SB -SB ➊ AC Coils: Max. N.O. auxiliary contacts may be mounted on the side. DC coils: Max. N.O. auxiliary contact may be mounted on the side. No additional N.C. auxiliary contacts may be added to safety contactors and control relays listed in this publication. For additional contact configurations, consult your local Allen-Bradley sales office. ➋ Double Numbering Left-side mounting only is recommended for 7S-CF due to double numbering. Marking Systems Uniform labeling materials for contactors, motor starting equipment, timing relays and circuit breakers Description Pkg. Qty. Label Sheet sheet with self-adhesive paper labels, 6 x 7 mm -FMS Marking Tag Sheet sheet with 6 perforated paper labels, 6 x 7 mm To be used with a transparent cover Transparent Cover To be used with marking tag sheets Marking Tag Adapters each To be used with marking tag: System V / V System Bul. 9W -FMP -FMC -FMA -FMA

13 Control Modules Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Accessories, Continued Description Connection Diagrams For Use With DC Interface (electronic) Interface between the DC control signal (PLC) and the contactor AC operating mechanism. Control voltage 8 V DC (V DC nominal) For coil voltages of V AC Suitable for all S-C contactor sizes, 9 8 A Requires no additional surge suppression for the coils Power consumption. W at 8V DC. W at V DC. W at V DC Surge Suppressors For limitation of coil switching transients. Plug-in, coil mounted Suitable for all S-C contactor sizes, 9 8 A RC, Varistor and Diode Versions RC Module AC Operating Mechanism Varistor Module AC/DC Operating Mechanism Diode Module DC Operating Mechanism 8V, /6 Hz 8V, /6 Hz 8 8V, /6 Hz V AC/ 77V DC 6 6V AC / 78 8V DC 7 77V AC / 8 V DC 78 7V AC V DC KM (KM) S-C with AC coils 7S-CF with AC coils S-C with AC coils 7S-CF with AC coils S-C all 7S-CF all S-C with DC coils 7S-CF with DC coils -JE -FSC8 -FSC8 -FSC8 -FSV -FSV6 -FSV77 -FSV7 -FSD

14 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Contactor Specifications General Ratings S-C9...S-C8 Rated Insulation Voltage U i IEC, AS, BS, SEV, VDE 66 UL; CSA Rated Impulse Voltage U imp Rated Voltage U e Main Contacts AC /6Hz DC Operating Frequency for AC Loads Switching Motor Loads 69V 6V 8 kv,, 8,,, 8,,, 6,, 7, 69V, 8,,,,,, V 6 Hz S- C9 S- C S- C6 Standard Ratings AC-, AC-, AC- - Hz V [A] DOL & Reversing V [A] IEC 8V [A] V [A] V [A] V [A] V [A] V [kw] V [kw] V [kw] V [kw] V [kw] V [kw] V [kw] AC-, AC-, AC- - 6Hz -Ph V [A] DOL & Reversing V [A] UL/CSA/IEC V [HP] /. 7-/ V [HP] 7-/ -Ph V [A] V [A] V [A] V [A] V [HP] 7-/ V [HP] 7-/ 6 V [HP] 7-/ 6 7 V [HP] 7-/ 6 Max. Operating Rate S- C S- C S- C7 S- C S- C6 S- C7 AC (ops/hr) S- C8 AC (ops/hr) AC (ops/hr) Product Selection Page Accessories Page Approximate Dimensions Page 9

15 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Contactor Specifications, Continued Coil Data S- C9 S- C S- C6 S- C Voltage Range AC: Hz, 6Hz, Pickup [x U s ].8. /6 Hz Dropout [x U s ]..6 DC Pickup [x U s ].8. Dropout [x U s ]..6 Coil Consumption AC: Hz, 6 Hz, Pickup [VA/W] 7/ 7/ 7/ 7/ 7/ 8/6 /9 / / / /6 Hz Hold-in [VA/W] 8/.6 8/.7 8/.8 9/ 9/ 9/ /. 6/. 6/. 6/. DC Pickup [W] Hold-in [W] Operating Times AC: Hz, 6 Hz, Pickup [ms] /6 Hz Dropout [ms] w/ RC Suppressor Dropout [ms] DC Pickup [ms] Dropout [ms] w/ Integ. Suppres. Dropout [ms] w/ Diode Suppres. Dropout [ms] ➊ DC- ratings of -F auxiliary contacts are the same as the ratings of the auxiliary contact in S-C9...S-C contactors. S- C S- C7 S- C S- C6 S- C7 S- C8

16 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Contactor Accessory Specifications Auxiliary Contacts Auxiliary Contacts in Contactor S-C9...S-C Auxiliary Contacts in Accessories -S, -F➊, -MC Current Switching AC- I th at C [A] at 6 C [A] 6 AC- at Rated Operating Voltage [V],8,,,,, 6, 69, 8,,,,, 6, 69 [A] 6, 6,,,.,.8, 6, 6, 6,,,.,.,.7 DC- at Rated Operating Voltage [V], 8,,,, 8,,, [A],,.7,.,.,.,.6,.,. Short-Circuit Protection gg Fuse Type Coordination [A] Rated Impulse Voltage U imp [kv] 8 6 Insulation Voltage (between control and load circuit) per DIN, VDE 6, Part (NAMUR recommendation) Contact reliability per DIN9 without contamination, normal industrial atmosphere Positively Guided Contacts Terminals [V] Terminal Type x A x A Wire Size per IEC 97- Flexible with Wire- Conductor [mm ].. End Ferrule Conductor [mm ].7. Solid/Stranded Conductor [mm ]. 6.. Conductor Conductor [mm ] Recommended Tightening Torque (min...max) [Nm].... Wire Size per UL/CSA [AWG] 6 8 Recommended Tightening Torque (min...max) [lb-in] ➊ DC- ratings of -F auxiliary contacts are the same as the ratings of the auxiliary contact in S-C9...S-C contactors. Between auxiliary circuits: V, Between load and direct-connected aux. circuits: 69 V 7V, ma, > 8 operations per error 7V, ma, > 8 operations per error Yes, N.O. and N.C. mutually unrestricted Yes, N.O. and N.C. mutually unrestricted, including N.C. in relation to N.O. main contacts. Product Selection Page Specifications Page Approximate Dimensions Page 9 6

17 General 7S-CF Aux. Contact (Frontmounted) Contact Ratings NEMA A6, P6 A6, Q6 Minimum Contact Rating 7-9.9V ma -V ma V 6A 6A Contact Ratings IEC 8V 6A 6A AC- (solenoids, contactors) V A 6A at rated voltage IEC 97, EN 697 V A A V A A 8V/V.A.6A 6V.8A.A 69V A.A C I th A A AC- (Non-inductive, V kw or slightly inductive V 7 kw loads, resistance furnaces) 69V kw 6 C I th A 6A IEC 97, EN 697 V 8 kw V kw 69V kw Switching DC Loads / R < ms, Resistive Loads V A A 8V 9A 9A V.A.A V.A.A V.A.A L / R < ms, Inductive Loads with economy resistor in series DC- IEC 97, EN 697, Solenoids and contactors Mechanically Linked Contacts ➋ Location of welded N.O. contacts V 9A 9A 8V A A V A A V.A.A V.6A.6A V A A 8V A A V.7A.7A V.A.A V.A.A Left side aux. Open Open ➊ Open Open Right side aux. Open Open ➊ Open Open ➊ If the accessory is a pneumatic timer or latch, there is no positive guidance; the accessory contacts are independent ➋ Defined in IEC 97-- annex L. Positive guidance is a relationship between contacts of opposite types (i.e., N.O. and N.C.). Yes Yes ➊ State of N.C. Contacts if N.O. contact welds Main Front aux. Left side aux. Main Open Open ➊ Open Open Front aux. Open Open ➊ Open Open Right side aux. Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Control Relay Specifications 7S-CF Aux. Contact (Frontmounted) Mechanical Life [Mil] Electrical Life AC- (V, A) AC Op. Weight Mechanism Terminal Cross-Sections Terminal Type [Mil].. [g] 9 Terminal Size per IEC 97- x A x A Flexible with Wire End Ferrule Solid Conductor Conductor Conductor Conductor [mm] [mm] [mm] [mm] Max. Wire Size per UL/CSA [AWG] 6 8 Tightening Torque [lb-in] Tightening Torque [Nm].. Contact Ratings IEC AC- (solenoids, contactors) at rated voltage IEC 97, EN 697 Aux.Contact (Side-mounted) V V 8V/V AC- (Non-inductive, or C I th A slightly inductive loads, resistance furnaces) IEC 97, EN C I th 6A DC- IEC 97, EN 697, Solenoids and contactors V A 8V.A V.6A V.A V.A Max. Wire Size per UL/CSA [AWG] 8 Tightening Torque [lb-in] 8.9. Tightening Torque [Nm]. 7

18 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Control Relay Specifications, Continued Control Circuit 7S-CF Operating Voltage AC /6 Hz Pickup [x U s ].8. Dropout [x U s ]..6 DC➊ Pickup [x U s ].8. Dropout [x U s ]..6 Coil Consumption AC /6 Hz Inrush [VA/W] 7/ Seal [VA/W] 8/.6 DC Inrush/Seal [W] 6.7 Operating Times AC- /6 Hz Pickup Time [ms] Dropout Time [ms] 6 DC Pickup Time [ms] 7 Dropout Time [ms] 7 ➊ For 9V DC, code ZR, use operating voltage.6. x U s. For V DC, code ZJ or DJ, use operating voltage.7. x U s. General Rated Insulation Voltage U i 7S-CF IEC 69V UL; CSA 6V Rated Impulse Strength U imp 8 kv High Test Voltage minute (per IEC 97-) V Rated Voltage U e AC DC Short-Circuit Protection IEC 8- Fuse Rated Frequency Ambient Temperature Storage Operation at nominal current Conditioned % current reduction after AC- at > 6 C Corrosion Resistance Altitude Type of Protection IP LX (IEC 9 and DIN ) Finger Protection,,,, 69V, 8,,, V /6 Hz, DC +8 C (67 76 F) +6 C ( F) +7 C ( 8 F) humid-alternating climate, cyclic, per IEC 68-- and DIN 6, 6 cycles m above mean sea level, per IEC 97- in connected state safe from touch by fingers and back of hand per VDE 6, Part 8

19 Bulletin S-C/S-C/7S-CF Safety Contactors and Control Relays Contactors, Control Relays, and Accessories Dimensions are shown in millimeters (inches). Dimensions are not intended for manufacturing purposes. c Mounting Position Approximate Dimensions ➊ AC Contactors and Control Relays c c DC Contactors and Control Relays AC Contactors and Control Relays a b c c c d d d S-C9 S-C, 7S-CF S-C, S-C7 S-C S-C6 S-C8 (-/) (-/) (-/8) 7 (-/6) 8 (-/6) 8 (-/6) 8 (-/6) (-/6) 9. (-/) 6. (-7/6) 9. (-/6) 6 (6-/). (-/6).6 (-/).6 (-9/6). (6-/8) 6 (/) 6. (7/6) 6. (7/6) 8. (/6) -. ( - /6) -. ( - /6) -. ( - /6) -. ( - 7/) 6 (-/6) 6 (-/6) 6 (-/6) (-/6) (-/6) (-/6) (-/) (-/6) DC Contactors and Control Relays Accessories a b c c c d d d S-C9Z...S-C6Z, 7S-CF S-CZ S-C...S-C7 S-CZ S-C6D...S-C8D (-/) (-/) (-/) (-/8) 7 (-/6) 8 (-/6) 8 (-/6) 8 (-/6) 8 (-/6) (-/6). (-9/6) 6. (6-7/6) 8. (7-/) 8. (7-7/6) 6 (6-/). (-7/6) 8 (6-/) 7. (6-6/6) 79 (7-/). (6-/8) 6 (/) 6 (/) 6. (7/6) 6. (7/6) 8. (/6) -. ( -/6) -. ( -/6) -. ( -/6) -. ( -/6) -. ( -7/) 6 (-/6) 6 (-/6) 6 (-/6) 6 (-/6) (-/6) (-/6) (-/6) (-/6) (-/) (-/6) Contactors with mm (inches) Auxiliary contact block for side mounting - or -pole a + 9 (a + /6) Electronic Timing Module on coil terminal side b + (b + /6) Mechanical Interlock on side of contactor a + 9 (a + /6) Interface Module on coil terminal side b + 9 (b + /6) Surge Suppressor on coil terminal side b + (b + /8) ➊ Labeling with label sheet marking tag sheet with clear cover marking tag adapter for System V / V marking tag adapter for System Bul. 9W (+ ) (+ ) (+ 7/) (+ 7/) 9

20 Terminal Markings -Pole Safety Contactors S-C9 C...C C S-C9 C...C C S-C C...C8 C -Pole Safety Contactors 7 R R8 S-C9 C...C C Reversing Safety Contactors S-C9 C...C C S-C9 C...C C S-C C...C8 C Publication S-SGA-US-P - November Rockwell International. All Rights Reserved. Printed in USA

Connection Diagrams. Auxiliary 40 C 60 C 24/48V 120V 240V 400V 500V 600V 690V Contacts Contacts N.O. N.C. Contacts 43 K

Connection Diagrams. Auxiliary 40 C 60 C 24/48V 120V 240V 400V 500V 600V 690V Contacts Contacts N.O. N.C. Contacts 43 K Bulletin Overview/Product Selection Προδυχτ Σελεχτιον Bulletin IEC Industrial Safety Relay Positively Guided/Mechanically Linked as Per IEC 947-5-1 Annex L Third Party Certification By SUA Red Cover and

More information

Ratings for Switching AC Motors AC-2, AC-3, AC / /

Ratings for Switching AC Motors AC-2, AC-3, AC / / Bulletin -C/-C Overview/Product Selection Product Selection -Pole AC- and DC-Operated Contactors Ie [A] Bulletin -C/-C Compact sizes from kw/ Hp ( A) AC and DC coil control Common accessories for all contactor

More information

Ratings for Switching AC Motors AC-2, AC-3, AC / /

Ratings for Switching AC Motors AC-2, AC-3, AC / / Bulletin S-C/S-C IEC Safety Contactors Overview/Product Selection Product Selection -Pole AC- and DC-Operated Contactors Bulletin S-C/S-C IEC Safety Contactors Mechanically linked N.C. auxiliary contacts

More information

AC-3 AC-1 230V 400/415V 500V 690V 115V 230V 200V 230V 460V 575V N.O. N.C. Qty. Cat. No. Screw Terminals. Spring Clamp Terminals. 40 C Pkg.

AC-3 AC-1 230V 400/415V 500V 690V 115V 230V 200V 230V 460V 575V N.O. N.C. Qty. Cat. No. Screw Terminals. Spring Clamp Terminals. 40 C Pkg. Bulletin -K, -K IEC Miniature Contactors Overview/Product Selection Product Selection -Pole AC- and DC-Operated Contactors Bulletin -K/-K IEC Miniature Contactors Compact size Same dimensions for AC and

More information

190S A N D 2 C A16 C TE

190S A N D 2 C A16 C TE Bulletin / Eco and Catalog Number Explanation Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for product selection; not all combinations

More information

190S A N D 2 C A16 C TE

190S A N D 2 C A16 C TE Bulletin / Eco and Compact Combination Starters Catalog Number Explanation Cat. No. Explanation Examples given in this section are for reference purposes. This basic explanation should not be used for

More information

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(24V60HZ) Catalog No. 276390 Eaton Catalog No. XTRE10B22B6 Delivery program Product range DILA relays Application Contactor relays Description Basic devices

More information

Instructions Contact numbers to EN Coil terminal markings to EN Integrated diode-resistor combination Coil rating 2.

Instructions Contact numbers to EN Coil terminal markings to EN Integrated diode-resistor combination Coil rating 2. Delivery program Contactor relay, 2N/O+2N/C, DC current Part no. DILER-22-G(24VDC) Catalog No. 010042 Eaton Catalog No. XTRM10A22TD EL-Nummer 4130354 (Norway) Product range DILER Mini-contactors Application

More information

Mini Contactors. Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 10 Auxiliary Contact Blocks

Mini Contactors. Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks. Interface Contactor Relays. Mini Contactors 10 Auxiliary Contact Blocks Mini Contactors Mini Contactor Relays 4-pole 8 Auxiliary Contact Blocks Interface Contactor Relays Mini Contactors 10 Auxiliary Contact Blocks Mini Contactors With Fast On Tab Connectors 12 Mini Contactors

More information

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA

Description Basic devices with positive operation contacts. Standards IEC/EN 60947, EN , VDE 0660, UL, CSA DATASHEET - DILA-22(230V50HZ,240V60HZ) Delivery program Contactor relay, 2N/O+2N/C, AC Part no. DILA-22(230V50HZ,240V60HZ) Catalog No. 276399 Eaton Catalog No. XTRE10B22F EL-Nummer 0004130208 (Norway)

More information

AC-Operated Latch Units PKLL11. Reset Input. DC-Operated Latch Units DC-PKLL10

AC-Operated Latch Units PKLL11. Reset Input. DC-Operated Latch Units DC-PKLL10 Bulletin -P Product Selection/ Accessories Units Description DX Arrangement DX K Continuous Carrying Current [A] No cartridge Cat. No. -PLL -PLL AC-Operated Units -PKLL DY DY K DX Reset Input DX K No cartridge

More information

Type: DILEM 10 G(24VDC) Article No.:

Type: DILEM 10 G(24VDC) Article No.: Type: DILEM 10 G(24VDC) Article No.: 010213 Ordering information Description Connection technique Rated operational current AC 3 380 V 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 220

More information

Description Basic devices with positive operation contacts

Description Basic devices with positive operation contacts Contactorrelay,3N/O+1N/C,DCcurrent Partno. DILA-31(24VDC) Articleno. 276379 CatalogNo. XTRE10B31TD Deliveryprogramme Product range DILA relays Application Contactor relays Description Basic devices with

More information

Controls Contactors and Contactor Assemblies Special Applications

Controls Contactors and Contactor Assemblies Special Applications Controls Contactors and Contactor Assemblies Special Applications Price groups 1B, 1H /2 Introduction More information can be found on the Internet: see the opening information, page 13 - Contactors for

More information

Description Basic devices with positive operation contacts. Connection to SmartWire-DT yes in conjunction with DIL-SWD SmartWire DT contactor module

Description Basic devices with positive operation contacts. Connection to SmartWire-DT yes in conjunction with DIL-SWD SmartWire DT contactor module DATASHEET - DILA-22(24VDC) Delivery program Contactor relay, 2N/O+2N/C, DC current Part no. DILA-22(24VDC) Catalog No. 276414 Eaton Catalog No. XTRE10B22TD EL-Nummer 4130211 (Norway) Product range DILA

More information

Characteristics 5 TeSys k contactors and reversing contactors

Characteristics 5 TeSys k contactors and reversing contactors 90 Characteristics contactors k contactors and reversing contactors Environment characteristics Conforming to standards IEC 60947, NF C 63-110, VDE 0660, BS 424 Product certifications LCp and LPp K06 to

More information

AF AF V50/60HZ-DC Contactor. General Information. Ordering. Popular Downloads. Dimensions. Technical AF

AF AF V50/60HZ-DC Contactor. General Information. Ordering. Popular Downloads. Dimensions. Technical AF ABB AF12-30-01-14 250-500V50/60HZ-DC Contactor General Information Extended Product Type Product ID AF12-30-01-14 1SBL157001R1401 EAN 3471523110441 Catalog Description Long Description AF12-30-01-14 250-500V50/60HZ-DC

More information

PKZ 2 Manual Motor Protectors Technical Data

PKZ 2 Manual Motor Protectors Technical Data 08/066 PKZ 2 Manual Motor Protectors General Standards UL 508, CSA C 22.2 No. 14, IEC/EN 60 947, VDE 0660 GL, LR, DNV, PRS, BV, RINA, RS, EZU, MEEI Climatic proofing Damp heat, constant, to IEC 60 068-2-3

More information

Accessories Field Installable

Accessories Field Installable ccessories Field Installable Top (Front) Mount uxiliary Contact Blocks ➊ Contact Block NO NC 0 2 Contact rrangement 51 61 52 62 For use with... Standard Contacts Bifurcated Contacts ➋ C7 all CS7-PV-02

More information

Type: DILEM 10(220V50HZ,240V60HZ) Article No.:

Type: DILEM 10(220V50HZ,240V60HZ) Article No.: Type: DILEM 10(220V50HZ,240V60HZ) Article No.: 051785 Ordering information Actuating voltage Description Connection technique 380 V 400 V I e A 8.8 Max. rating for three phase motors, 50 AC 3 220 V 230

More information

Miniature Contactors & Starters. Series CA8 family of Contactors, Starters, and Overload & Industrial Relays

Miniature Contactors & Starters. Series CA8 family of Contactors, Starters, and Overload & Industrial Relays Miniature & Starters Series family of, Starters, and Overload & Industrial Relays Miniature, Starters, Overload Relays & Industrial Controls List Prices shown in this selection guide are for use in the

More information

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X

TeSys contactors. TeSys D contactors. IEC/EN , IEC/EN , UL 508, CSA C22.2 n 14. Protection against direct fi nger contact IP 2X Characteristics Contactor type LC1 D09 D18 DT20 and DT25 Environment Rated insulation voltage (Ui) Conforming to IEC 097--1, overvoltage category III, degree of pollution: 3 Conforming to UL, CSA V 00

More information

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13

Micro Contactors. Micro Contactor Relays 10. Micro Contactors 11. Micro Contactors With Solder Pins 12. Coil voltages 12. Micro Reversing Contactor 13 Micro Contactor Relays 10 Micro Contactors 11 Micro Contactors With Solder Pins 12 Coil voltages 12 Micro Reversing Contactor 13 Technical Data 14 Dimensions 18 D946E 9 Micro Contactor Relays 4-pole AC

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product

More information

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment

Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment Artisan Technology Group is your source for quality new and certified-used/pre-owned equipment FAST SHIPPING AND DELIVERY TENS OF THOUSANDS OF IN-STOCK ITEMS EQUIPMENT DEMOS HUNDREDS OF MANUFACTURERS SUPPORTED

More information

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information Type: DILM80(110V50HZ,120V60HZ) Article No.: 239399 Sales text Contactor,37kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current AC 3 380 V 400

More information

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information Type: DILM95(230V50HZ,240V60HZ) Article No.: 239480 Sales text Contactor,45kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current AC 3 380 V 400

More information

Industrial Controls. Catalog IC SIRIUS. Answers for industry.

Industrial Controls. Catalog IC SIRIUS. Answers for industry. Industrial Controls Catalog IC 10 2012 SIRIUS Answers for industry. Contactor Relays Siemens AG 2012 Overview Standards IEC 60947-1, EN 60947-1, IEC 60947--1, EN 60947--1 The 3TH42 and 3TH43 contactor

More information

Output of three-phase motors at 50 Hz and 400 V

Output of three-phase motors at 50 Hz and 400 V RT0, RH Coupling Relays (Interfaces) Description DC operation IEC 0 947 and EN 0 947 (VDE 00) The RT0 coupling relays for switching motors and RH for auxiliary circuits are laid out to the special requirements

More information

Capacitor Switching Contactors

Capacitor Switching Contactors Capacitor Switching D385E51 Technical catalogues and news under: www.benedict.at Motor-Starter Mini- Overload Relays Capacitor Switching Motor-Starters Modular Circuit Breakers M4-32T... up to 32A M4-32R..

More information

XT IEC Power Control Miniature Controls

XT IEC Power Control Miniature Controls Product Family Overview May 07 Contents Description Page Selection................ Product Selection.......... Non-reversing Mini Contactors......... Reversing Mini Contactors............. Star-Delta (Wye-Delta)

More information

Contactors and Contactor Assemblies

Contactors and Contactor Assemblies s for Switching Motors Technical data General data Permissible mounting position The contactors are designed for operation on a vertical mounting surface. C and DC operation S3 3RT14 46 For DC operation

More information

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations

Top wiring permanent magnet latching For non-motor loads, lighting, heating NEMA sizes to 300 A 2-, 3-, and 4-pole configurations Bulletin LP NEMA AC Permanent Magnet-Latching Lighting Contactors Product Overview/Product Selection/Wiring Diagram A, -Pole Open Type without Enclosure Bulletin LP Top wiring permanent magnet latching

More information

NS..S contactor relays - with spring terminals AC operated

NS..S contactor relays - with spring terminals AC operated NS..S contactor relays - with spring terminals AC operated NSES 1SBC101015F00 Description NS..S contactor relays are used for switching auxiliary and control circuits. These contactor relays are designed

More information

3 - Protection components Circuit-breakers

3 - Protection components Circuit-breakers Contents - Protection components Circuit-breakers for the motor protection Selection guide..............................................page /2 Thermal-magnetic motor circuit-breakers Selection guide..............................................page

More information

Approved Standards. Ordering Information. Mini Contactor Relays 4-pole J7KNA-AR. Model Number Legend. Main contactor. Accessories

Approved Standards. Ordering Information. Mini Contactor Relays 4-pole J7KNA-AR. Model Number Legend. Main contactor. Accessories Mini Contactor Relays 4-pole J7KN-R ) Main contactor C & DC operated 4-, 6- and 8-pole versions in different configurations Mirror contacts Screw fixing and snap fitting (35 mm DIN rail) Rated current

More information

General 2 Approvals 3 Technical Information 5 Mounting Information 6

General 2 Approvals 3 Technical Information 5 Mounting Information 6 Index Page General 2 Approvals 3 Technical Information 5 Mounting Information 6 Mini Contactors 7 Mini Contactors 8 Interface Contactors 8 Mini Reversing Contactors 4 Technical Information 5 Dimensions

More information

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6

Index. Capacitor Switching - 2 Contactors. Typical Circuit Diagram 2. Auxiliary Contact Blocks 2. Contactors 3. Dimensions 3. Technical Data 4,5,6 Index Index Page Capacitor Switching - 2 Contactors Typical Circuit Diagram 2 Auxiliary Contact Blocks 2 Contactors 3 Dimensions 3 Technical Data 4,5,6 Contactor operation 7 Function 8 Construction 9 Oscillogram

More information

3RF A A 0 2. Switching function. Control voltage Operating voltage with heat sink 10 = 10.5 A. A = Zero-point switching

3RF A A 0 2. Switching function. Control voltage Operating voltage with heat sink 10 = 10.5 A. A = Zero-point switching Main Characteristics: Zero-point switching LED display Various connection technologies Plug-in control terminal Degree of protection IP 2 Insulated mounting foot Standards / Approvals: DIN EN 697--3 UL

More information

Small but rugged DRAFT

Small but rugged DRAFT Series C8 and CT8 Starters n ingenious miniature contactor and starter system Sprecher + Schuh s New C8 Series of miniature contactors and starters provide an extremely compact and reliable method of controlling

More information

The CWC0 compact contactors are offered as a complete solution for switching and controlling motors.

The CWC0 compact contactors are offered as a complete solution for switching and controlling motors. Compact Contactors The CWC compact contactors are offered as a complete solution for switching and controlling motors. Main Features Contactors with screw s for C-3 operation up to Contactors with spring

More information

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet CDC 0 F0t07 Features Rated control supply voltage -8 V DC, -0 V AC Single-function timer with star-delta change-over One device includes 7 time ranges (0.0 s - 0 min) n/o contacts LEDs for status indication

More information

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A

Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection. Product range PKZM4 motor protective circuit-breakers up to 65 A DATASHEET - PKZM4-50 Delivery program Motor-protective circuit-breaker, 3p, Ir=40-50A, screw connection Part no. PKZM4-50 Catalog No. 222355 Eaton Catalog No. XTPR050DC1NL EL-Nummer 0004355161 (Norway)

More information

NZMH4, NZM(H)6(B), NZM(H)9, NZM12 Technical Data

NZMH4, NZM(H)6(B), NZM(H)9, NZM12 Technical Data Circuit Breakers, 09/098 Molded case circuit breakers 3 pole NZMH 4-...-C 1) NZM6B.../ZM6A...- Frame size A 80 125 125 IEC 60 947-2 Electrical Ratings Rated impulse withstand voltage U imp V 8000 8000

More information

IDEC RJ22 Series Slim Power Relays (Bifurcated Contacts)

IDEC RJ22 Series Slim Power Relays (Bifurcated Contacts) IDEC RJ22 Series Slim Relays (Bifurcated Contacts) Phone: 00.94.042 - Fax:.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com RJ Series Slim Relay Plug-in Terminal (Bifurcated Contacts) High contact

More information

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Modular equipment. Presentation, standards. Standard contactors TeSys GC Presentation, standards Standard contactors TeSys GC Presentation TeSys GC contactors are designed for use in modular panels and enclosures. These contactors feature: b Easy installation v quick clip-on

More information

Bulletin 700-R -RM Sealed Switch Relays

Bulletin 700-R -RM Sealed Switch Relays Bulletin 700-R -RM Sealed Switch Relays Bulletin 700 R, RM Sealed Switch Relays Sealed contacts Extremely long mechanical and electrical life Hazardous locations Class 1, Div Groups A, B, C, D Harsh environments

More information

Control module CP-A CM

Control module CP-A CM 2CDC 271 002 F0t05 Features Pluggable onto redundancy unit CP A RU Threshold values adjustable (14 28 V) One relay output per monitored input / channel Approvals H UL 508, CAN/CSA C22.2 No.14 H UL 60950,

More information

Control relays. K mini-control relays. 2 or 4 for CA2-K and CA3-K: 2 for CA4-K. Conforming to VDE 0110 group C V 750

Control relays. K mini-control relays. 2 or 4 for CA2-K and CA3-K: 2 for CA4-K. Conforming to VDE 0110 group C V 750 Characteristics Contact characteristics of mini-control relays and instantaneous contact blocks Number of contacts On CAp-K 4 On L-K 2 or 4 for C-K and CA3-K: 2 for CA4-K Rated operational voltage (Ue)

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

Mini contactors B 6 and B 7 Mini contactor relays K.. Compact reversing contactors VB.. Thermal overload relay T 7 DU

Mini contactors B 6 and B 7 Mini contactor relays K.. Compact reversing contactors VB.. Thermal overload relay T 7 DU /0 Mini contactors B and B 7 Mini contactor relays K.. Compact reversing contactors VB.. Thermal overload relay T 7 DU Contents Mini Contactors B, BC, B 7, BC 7 Ordering Details... /2 Compact Reversing

More information

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC

LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC Product datasheet Characteristics LC2D09BL REVERSING CONTACTOR 575VAC 9A IEC Price* : 107.62 GBP Main Range Product name Product or component type Device short name Contactor application Utilisation category

More information

3RH1 contactor relays, 4- and 8-pole

3RH1 contactor relays, 4- and 8-pole Siemens AG 2010 RH, TH Contactor Relays RH1 contactor relays, 4- and 8-pole Overview AC and DC operation IEC 60947, EN 60947. The RH1 contactor relays are suitable for use in any climate. They are finger-safe

More information

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz HPL11002EN DILETTiming relays Rated operational current AC-11 230 V 400 V I th I e I e A A A A A Conventional thermal current Time Range Voltage Article No. See price list Std. pack On-delayed Timing functions

More information

Open Type Without Enclosure

Open Type Without Enclosure Bulletin L NEMA AC Electrically Held Lighting Contactors Product Selection Top Wiring for Non-Motor and Lighting Loads Tungsten Lamp Loads (Max. V Line, V Load) Maximum Continuous Ampere Ratings [A] General

More information

Breakcontact,Front. Articleno Deliveryprogramme. Product range RMQ-Titan (drilling dimensions 22.5 mm) Basic function Accessories

Breakcontact,Front. Articleno Deliveryprogramme. Product range RMQ-Titan (drilling dimensions 22.5 mm) Basic function Accessories Breakcontact,Front Partno. M22-K01 Articleno. 216378 Deliveryprogramme Product range RMQ-Titan (drilling dimensions 22.5 mm) Basic function Accessories Standard/Approval UL/CSA, IEC Construction size NZM1/2/3/4

More information

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition

LC2D09BD. Main. Device short name. Utilisation category. Poles description Pole contact composition Product datasheet Characteristics Main Range Product name Product or component type Device short name Contactor application Utilisation category Device presentation Poles description Pole contact composition

More information

Type: EASY719 AC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC. Description

Type: EASY719 AC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC. Description Type: EASY719 AC RC Article No.: 274115 Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC Description 12 digital inputs 6 relay outputs LCD display Operating buttons Screw terminals

More information

Block Contactors. Contents. Panorama 3-pole Contactors... 2/2 4-pole Contactors... 2/4

Block Contactors. Contents. Panorama 3-pole Contactors... 2/2 4-pole Contactors... 2/4 /0 Block Contactors Contents Panorama -pole Contactors... / 4-pole Contactors... /4 -pole Contactors: Description and Ordering Details A 9... A 0 Contactors (a.c. Operated)... /6 A 4... AF 60 Contactors

More information

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact Data sheet Electronic timer CT-YDE Star-delta change-over with c/o (SPDT) contact The CT-YDE is an electronic time relay with star-delta change-over. It is from the CT-E range. The CT-E range is the economic

More information

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil

LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 25 A - 24 V DC coil Product data sheet Characteristics LC1D25BL TeSys D contactor - 3P(3 NO) - AC-3 -

More information

48 Series - Relay interface modules A. Features

48 Series - Relay interface modules A. Features Series - Relay interface modules 8-0 - 6 A Features & Pole relay interface modules, 5.8 mm wide. Ideal interface for PLC and electronic systems.3 - Pole 0 A.5 - Pole 8 A.6 - Pole 6 A coils or sensitive

More information

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards APPROVED IGS Iranian Gas Standards Contactors. Fax:(9821)-8131-5679 --. /012 34-52673892 :;395- 8? /@A7 B;CD /E FGH 34-52673892I2

More information

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages Data sheet Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages For the monitoring of voltages in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

Type: DILM40(RDC24) Article No.:

Type: DILM40(RDC24) Article No.: Type: DILM40(RDC24) Article No.: 277780 Ordering information Rated operational current AC 3 400 V I e A 40 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50

More information

Electronic timer CT-SDS.22

Electronic timer CT-SDS.22 CDC 0 F0t07 Features Rated control supply voltage 8 V DC, 0 V AC Single function timer with star delta change over One device includes 7 time ranges (0.0 s 0 min) n/o contacts LEDs for status indication

More information

Electronic timer CT-SDD.22

Electronic timer CT-SDD.22 CDC 099 F0t0 a Rotary switch for the preselection of the time range b Potentiometer with direct reading scale for the fine adjustment of the time delay c U: green LED V control supply voltage applied W

More information

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents Data sheet Current monitoring relays CM-SRS.2 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

Supplemental Motor Protection Devices Table of Contents

Supplemental Motor Protection Devices Table of Contents Supplemental Motor Protection Devices Table of Contents Supplemental Motor Protection Devices Bulletin 0S/S//... Page - Bulletin 0 Arcing Ground Fault Detection System: Adjustable Trip from A... Page -

More information

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC 2CDC 251 244 F0t05 Characteristics Monitoring of DC and AC currents: RMS measuring principle One device includes 3 measuring ranges Over- or undercurrent monitoring configurable Hysteresis adjustable from

More information

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947 Motor--protective circuit--breaker system J7M -AM System Rated operational current 25 A. Switching capacity up to 10 A, 100 ka/415 V. Switching capacity 16 A, 20 A, 25 A, 16 ka/415 V. Fixed short--circuit

More information

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4

58 SERIES. Relay interface modules 7-10 A 58.P3 58.P4 58 58 3 & 4 CO relay interface modules, 31 mm wide with Push-in terminals Ideal interface for PLC and electronic systems 58.P3 58.P4 Type 58.P3 3 CO 10 A Push-in terminals Type 58.P4 4 CO 7 A Push-in terminals

More information

Protection components

Protection components Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &

More information

Open Type Without Enclosure

Open Type Without Enclosure Bulletin L NEMA AC Electrically Held Lighting Contactors Product Selection Top Wiring for Non-Motor and Lighting Loads Tungsten Lamp Loads (Max. V Line, V Load) Maximum Continuous Ampere Ratings [A] General

More information

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW Characteristics soft starter for asynchronous motor - ATS01-25 A - 110..480V - 2.2..11 KW Main Range of product Altistart 01 Product or component type Product destination Product specific application Device

More information

Utilization category DC-1 DC-3 DC-5 L/R 1 ms L/R 2 ms L/R 7.5 ms

Utilization category DC-1 DC-3 DC-5 L/R 1 ms L/R 2 ms L/R 7.5 ms controls IEC Technical data D.C. Power circuit switching Utilization category DC- DC- DC- L/R ms L/R ms L/R 7. ms + + + V A 6.0 6.0 6.0 8 V A 6.0 8.0.0 60 V A 6.0.0. V A 7.0. 0. 0 V A 0.8 0. V A 6.0 6.0

More information

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW Characteristics soft starter for asynchronous motor - ATS01-12 A - 110..480V - 1.5..5.5 KW Main Range of product Altistart 01 Product or component type Product destination Product specific application

More information

General Catalogue. Quality made in D946E182

General Catalogue. Quality made in D946E182 General Catalogue Quality made in D946E182 Index Page Contactors, Motor-Starter (D677E) 3 Micro Contactors 11 Mini Contactors 25 Contactor Relays 39 Contactors 45 Starters 91 D.O.L. Starters 111 Overload

More information

Relays & Sockets. RF1V Force Guided Relays/SF1V Relay Sockets. Certification Organization/ File Number. UL/c-UL File No.

Relays & Sockets. RF1V Force Guided Relays/SF1V Relay Sockets. Certification Organization/ File Number. UL/c-UL File No. RFV Key features: Compact and EN compliant RFV force guided relays Force guided contact mechanism (EN00 Type A TÜV approved) Contact configuration -pole (NO-NC, 3NO-NC) 6-pole (NO-NC, NO-NC, 3NO-3NC) Built-in

More information

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly

More information

Type: EASY719 DA RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC. Description

Type: EASY719 DA RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC. Description Type: EASY719 DA RC Article.: 274117 Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display

More information

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact Data sheet Electronic timer CT-SDE Star-delta change-over with n/c + n/o contact The CT-SDE is an electronic time relay with star-delta change-over. It is from the CT-E range. The CT-E range is the economic

More information

Thermistor motor protection relays

Thermistor motor protection relays Thermistor motor protection relays Content Benefits and advantages... / 68 Selection table... / 68 Ordering details CM-MSE... / 69 CM-MSS... / 69 CM-MSN... / 7 PTC sensor C0... / 7 Technical data... /

More information

RJ Series Slim Power Relays

RJ Series Slim Power Relays RJ Series RJ Series Slim Relays Circuit Breakers Terminal Blocks Timers Display Lights Switches & Pilot Lights Compact and rugged power relays. Large switching capacity. Compact housing only.7-mm wide.

More information

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents Data sheet Current monitoring relays CM-SRS.1 for single-phase AC/DC currents For the monitoring of currents in single-phase AC/DC systems, ABB s CM range comprises a wide selection of powerful and compact

More information

Components for safety applications

Components for safety applications Metal, turret head, types CS-A, CS-C and CS-E Double insulated, turret head, types CS-PA, CS-TA and CS-TE Presentation Metal, types CS-A, CS-C, CS-E Switches with or without locking of the actuator Pages

More information

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

ATV12H018F1 variable speed drive ATV kW hp V - 1ph Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component

More information

Auxiliary Contact (10 600V) Auxiliary Contact (10 5V DC)

Auxiliary Contact (10 600V) Auxiliary Contact (10 5V DC) Bulletin C,, C Accessories Accessories Auxiliary Contacts Contactors are supplied with one normally open and one normally closed auxiliary contact (A rating) as standard. Additional auxiliary contacts,

More information

ATS01N103FT soft starter for asynchronous motor - ATS01-3 A V KW

ATS01N103FT soft starter for asynchronous motor - ATS01-3 A V KW Characteristics soft starter for asynchronous motor - ATS01-3 A - 110..480V - 0.55..1.1 KW Main Range of product Altistart 01 Product or component type Product destination Product specific application

More information

Relays & Sockets. RF2V 2-Pole Force Guided Relays/SJ Series Relay Sockets. UL/Recogntion File No. E55996 TÜV SÜD. EU Low Voltage Directive

Relays & Sockets. RF2V 2-Pole Force Guided Relays/SJ Series Relay Sockets. UL/Recogntion File No. E55996 TÜV SÜD. EU Low Voltage Directive RFV RFV -Pole Force Guided Relays/SJ Series Relay Sockets Key features: -pole force guided relay to reduce cost and installation space. Force guided contact mechanism (EN00 Type A TÜV approved). Reinforced

More information

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks. 2CDC 251 052 F0t08 CM-MPS.23 2CDC 251 053 F0t08 CM-MPS.43 - relay status, timing - fault message - fault message Adjustment of the tripping delay t V Adjustment of the threshold value for overvoltage 6

More information

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application

More information

Control stations and enclosures Pendant control stations, for control circuits Double insulated or metal, types XAC-B and XAC-M

Control stations and enclosures Pendant control stations, for control circuits Double insulated or metal, types XAC-B and XAC-M Characteristics Pendant control stations, for control circuits Environment Conforming to standards IEC 947-5-1, EN 60947-5-1 XAC-B : standard version : NEMKO, CSA 300 V type 4 Approvals XAC-M : standard

More information

Standard voltages. Alternating current (V). Direct current (V) D F H J N Y Voltage For contactors type CL...

Standard voltages. Alternating current (V). Direct current (V) D F H J N Y Voltage For contactors type CL... Series CL Three and four pole contactors 9 to 05 (C3) 25 to 40 (C) Contactors lternating current up to 690V Direct current up to 440V Terminal numbering in accordance with EN 50005 and EN 5002 Fixing by

More information

Switching Devices Contactors and Contactor Assemblies for Switching Motors

Switching Devices Contactors and Contactor Assemblies for Switching Motors Switching Devices Contactors and Contactor Assemblies for Switching Motors groups 41B, 41H / Introduction Power contactors for switching motors /5 General data /11 SIRIUS RT10 contactors, -pole,... 50

More information

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC 2CDC 251 048 F0t08 CM-MPS.11 2CDC 251 049 F0t08 CM-MPS.21 Features Monitoring of three-phase mains for phase sequence (can be switched off), phase failure, over- and undervoltage as well as phase unbalance

More information

Circuit diagram. Applications. Function. Function (Continued) Page 23 SNO 4062K /K-A /KM /KM-A

Circuit diagram. Applications. Function. Function (Continued) Page 23 SNO 4062K /K-A /KM /KM-A SNO 4062K Basic unit for emergency stop and guard door applications Basic unit as per DIN EN 60204-1 and EN ISO 13849-1 for single or twin channel emergency stop monitoring. PL e and category 4 as per

More information