The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Size: px
Start display at page:

Download "The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc."

Transcription

1 The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency Injection BY STEVE TURNER, Beckwith Electric Company, Inc. This paper covers practical considerations for proper application and commissioning of this special protection. The total capacitance to ground of the generator stator windings, bus work, and delta-connected unit transformer windings is a very important factor as will be shown. This protection can: Detect a stator ground when the winding insulation first starts to break down and trip the unit before catastrophic damage occurs Be set to trip in the order of cycles since the 20 Hz signal is decoupled from the 50 or 60 Hz power system Detect grounds close to the machine neutral or even right at the neutral thus providing 100 percent coverage of the stator windings Detect grounds when the machine is starting up or offline Reliably operate with the generator in various operating modes such as a synchronous condenser and at all levels of real and reactive power output. Special steps should be taken in the design of this protection as there are cases when it is difficult to distinguish between normal operating conditions and an actual ground fault. The protection must reject fundamental frequency (50 or 60 Hz) voltage and current signals that are present during ground faults on the stator windings. A real life example for a pump storage facility is included. STATOR GROUND FAULTS ROOT CAUSES In-service stator winding failure to ground is a common generator failure, and there are many possible causes such as mechanical damage to the ground wall insulation (category #1) and fracturing of the current carrying conductor that result in the ground wall insulation burning away (category #2). Examples of category #1 failures: ground wall insulation wear-through from a foreign object or loose component 68 SUMMER 2014

2 FEATURE fracture of the ground wall due to a sudden short circuit deficient ground wall insulation system partial discharge combined with vibration vibration sparking, inadvertent damage during maintenance wet insulation due to strand header water leak, bar vibration in the slot Examples of category #2 failures: fracture of stator bar copper conductors due to high cycle fatigue associated with vibration fracture of bar copper due to gross overheating of the copper core iron melting, failure of a bolted connection failure of a brazed or welded joint failure of a series or phase connection Category #1 failures are typically benign, unless a second ground occurs, in which case there is massive arcing. Category #2 failures are always highly destructive to the generator. Current will temporarily continue to flow uninterrupted within the stator bar ground wall insulation (i.e., welding arc) when a conductor breaks and the heat generated is extremely high. This current will flow inside the insulation until it is mechanically destroyed. Experience has shown that the copper is vaporized for perhaps 8 to 12 inches before the internal arcing breaks through the insulation wall and arcs to ground as shown in Figures 1-3. Conventional neutral overvoltage protection (59N) cannot detect grounds in the last 5 to 10 percent of the stator winding. If a failure occurs in a lower voltage portion of the winding near the neutral, a generator trip will not typically occur until some other relay protection detects there is a problem, (e.g., arcing becomes so widespread that other portions of the winding become involved). There has been recent experience with four such failures in large generators that demonstrate the lack of proper protection can be disastrous. Each of the four failures caused massive damage NETA_InteriorPages_SUM14.indb 69 Figure 1: Typical Winding Damage Resulting from Broken Stator Winding Conductor Figure 2: Typical Core and Winding Damage Resulting from a Burned Open Bar in a Slot Figure 3: Burned Away Copper Fractured Connection Ring NETAWORLD 69 5/21/14 1:27 PM

3 to the generator and collectively had a total cost, including repair and loss of generation, close to $500,000, This demonstrates that failure of stator windings in the last five percent of the winding is not uncommon. One hundred percent stator ground fault protection is provided by injecting a 20 Hz voltage signal (64S) into the secondary of the generator neutral grounding transformer through a band-pass filter. The band-pass filter passes only the 20 Hz signal and rejects out of band signals. The main advantage of this protection is it provides 100 percent protection of the stator windings for ground faults including when the machine is off-line (provided that the 20 Hz signal is present). APPLICATION Figure 4 illustrates a typical application. A 20 Hz voltage signal is impressed across the grounding resistor ( ) by the 20 Hz signal generator. The band-pass filter only passes the 20 Hz signal and rejects out of band signals. The voltage across the grounding resistor is also connected across the voltage input (V N ) of the 64S function. The current input (I N ) of the 64S function measures the 20 Hz current flowing on the secondary side of the grounding transformer and is stepped down through a CT. It is important to note that the relay does not measure the 20 Hz current flowing through the grounding resistor; it measures the 20 Hz current flowing into the power system. The 20 Hz current magnitude increases during ground faults on the stator winding and an overcurrent element that operates on this low frequency current provides the protection. 20 Hz Voltage and Current 64S Relay Measurements The following method shows how to calculate the 20 Hz voltage and current measured by the 64S function. Figure 4: 20 Hz Injection Grounding Network 70 SUMMER 2014

4 Grounding Transformer Turns Ratio (N) Assume that the turns ratio of the grounding transformer is equal to: N 8, (1) Capacitive Reactance The total capacitance to ground of the generator stator windings, bus work, and delta connected transformer windings of the unit transformer is expressed as C 0. Generator step up transformers have delta connected windings facing the generator so capacitance on the high side is ignored. The corresponding capacitive reactance is calculated as follows: X CO 1 2π f o C o (2) Assume the capacitance to ground is 1 microfarad: X CO 1 2 π (20Hz) (10 6 F) 7,958Ω primary Reflect the capacitive reactance to the secondary of the grounding transformer: X CO 7,958Ω N 2 7, 958Ω ( ) 8, Ω secondary Grounding Resistor ( ) The ohmic value of the grounding resistor can be sized as follows so as to avoid high transient overvoltage due to ferroresonance 2 : X c0 3 (3) Ω sec Ω secondary A value of 2.5 ohms secondary is used for this example. 20 Hz Signal Generator and Band-pass Filter Characteristics The 20 Hz signal generator output is 25 volts RMS and the band-pass filter has a resistance equal to eight ohms. V source 25 0 volts (4) R Filter 8Ω secondary (5) Stator Insulation Resistance ( ) is the total insulation resistance from the stator windings to ground. A typical value for nonfault conditions is 50,000 ohms primary. Reflect the insulation resistance to the secondary of the grounding transformer. R s 50,000Ω pri N 2 45Ω secondary 50,000Ω pri ( ) 2 8, Current Transformer The current input (I N ) of the 64S function measures the 20 Hz current flowing on the grounded side of the grounding transformer and is stepped down through a CT. CTR 400/5 80/1 (6) Grounding Network These are all of the elements needed to mathematically derive the grounding network and determine the 20 Hz signals measured by the 64S function. Figure 5A shows the insulation resistance and the stator windings referred to the primary of the grounding transformer. Figure 5B shows the insulation resistance and the stator windings reflected to the secondary of the grounding transformer. NETAWORLD 71

5 Figure 5A: 20 Hz Grounding Network Referred to Grounding Transformer Primary Figure 5B: 20 Hz Grounding Network Refl ected to Grounding Transformer Secondary X C total capacitance to ground R stator stator insulation resistance to ground neutral resistor R Filter band-pass filter resistance V N voltage drop across I N current from system I BANK current flow in I T I BANK + I N 20 Hz Current (I N ) Measured by 64S Function The current input (I N ) of the 64S function measures the 20 Hz current flowing in the secondary of the grounding transformer and is stepped down through a CT. As noted previously the relay does not measure the 20 Hz current flowing through the grounding resistor. Z T 8 + ( 2.5) / /( 45) / /( j) j Ω secondary The total 20 Hz current supplied by the signal generator is determined as follows: Total 20 Hz Current Supplied by Signal Generator The 20 Hz signal generator looks into the band pass filter resistance (R Filter ) which is in series with the parallel combination of the following: Z CO Rs I T I T V CTR Z T (8) V ( j Ω) Therefore, the total loop impedance of the 20 Hz grounding network can be expressed as follows: Z T R Filter + Z CO + Z CO + Z C O + Z CO (7) ma 20 Hz Current Measured by 64S Function (I N ) during Nonfaulted Conditions The 20 Hz current measured by the 64S function is the ratio of the total current that flows into the primary side of the grounding network (Z CO //R s ): 72 SUMMER 2014

6 Table 1: 20 Hz Current Measurements I N I T I N Z C o Z Co + (9) ( j) / /(45) ma ( Nonfaulted) 20 Hz Current Measured by 64S Function (I N ) during Ground Fault on Stator Windings A typical value to represent the insulation resistance of the stator windings when it is breaking down during a ground fault is 5,000 ohms primary. If the calculations for equations 7 through 9 are repeated for a fault resistance equal to 5,000 ohms primary (4.5 ohms secondary), then the 20 Hz current measured by the relay is as follows: I N ma (5,000 ohm primary ground fault) If the calculations for equations 7 through 9 are repeated for a fault resistance equal to 1,000 ohms primary (0.9 ohms secondary), then the 20 Hz current measured by the relay is as follows: (primary) I N (secondary) 50,000 Ω ma 5,000 Ω ma 1,000 Ω ma PRACTICAL CONSIDERATIONS Here are three important aspects to consider when applying 100 percent stator ground fault protection by 20 Hz injection: slight change in fault current measured by relay rejection of fundamental frequency (50 or 60 Hz) voltage and current signals under-frequency inhibition Slight Change in Fault Current A very large capacitance to ground (C 0 ) coupled with a small value for the grounding resistor ( ) can result in very little margin between the fault and nonfault current measured by the 64S function. Generator windings and isophase bus work (see Figure 6) are both sources of high capacitance to ground (ex., a long run of bus from the generator to the step-up transformer). I N ma (1,000 ohm primary ground fault) Table 1 summarizes the 20 Hz current measured by the relay for nonfaulted and faulted conditions. Often the 64S protection can detect the ground for insulation resistance is much higher than 5,000 ohms primary. The 64S function can easily distinguish between nonfault and stator ground faults for this example. Set the pickup of the 64S, 20 Hz tuned, overcurrent element above the current measured during normal operating conditions but below the current measured for a stator ground fault equal to 5,000 ohms primary. Figure 6: Iso-Phase Bus Work NETAWORLD 73

7 Figure 7: Primary Side Current Distribution Figure 8: Current Flow in Secondary Network Figure 7 illustrates why there is not a significant change in the magnitude of the total neutral current when there is high capacitance. If the capacitive reactance is low enough, then only a small portion of the total neutral current flows through the insulation resistance. To overcome this challenge, calculating the real component of the total neutral current can reliably detect a stator ground fault for such a system. Consider the following grounding network parameters: N 8, C 0 10µF Z CO 0.25 Ω secondary Table 2: 20 Hz Current Measurements for High Capacitance (primary) j Ω secondary Determine the 20 Hz current measured by the 64S function for nonfaulted and stator ground fault conditions using the equations presented in the previous application section as shown in Table 2 below. I N (secondary) 50,000Ω ma 5,000Ω ma 1,000Ω ma The 64S 20 Hz tuned overcurrent element pickup cannot be set such that it reliably discriminates between nonfaulted and stator ground fault conditions. The solution is for the relay to calculate the real component of the 20 Hz current with respect to the neutral voltage. To do so, first determine the 20 Hz voltage measured by the relay voltage input (V N ). The 20 Hz voltage is equal to the drop across the grounding resistor due to the portion of the total current flowing through this branch of the grounding network (i.e., I BANK ). Use Figure 8 above to determine the corresponding equations (10 13). 20 Hz Current Flowing through the Grounding Transformer I Bank I T I N (10) 20 Hz Voltage Drop Across the Grounding Resistor V N I Bank (11) Real Component of 20 Hz Current Measured by 64S Function Calculate the real component of the relay current based upon the angle between the relay neutral voltage (V N ) and current (I N ) as shown in Table 3. V N I N (12) I Real I N i COS( ) (13) 74 SUMMER 2014

8 Table 3: 20 Hz Current Measurements for High Capacitance Including Real Component (primary) I N (secondary) R e (I N ) 50,000Ω ma ma 5,000Ω ma ma 1,000Ω ma ma A 20 Hz tuned overcurrent element that operates on the real component of 20 Hz current measured by the 64S function can reliably distinguish between nonfaulted and stator ground fault conditions when there is high-capacitive coupling to ground on the stator winding. A good rule of thumb is to use the real component of 20-Hz current for sensitive protection if C 0 is greater than 1.5 microfarads and the grounding resistor is less than 0.3 ohms secondary. The user can follow the commissioning instructions that appear at the end of this paper to determine the total capacitance to ground (C 0 ). If the values for and C 0 do not clearly fall under the category defined by this rule of thumb, then use the equations provided earlier in this paper to determine if use of the real component of neutral current is necessary. Figure 9 illustrates the fundamental voltage drop (50 or 60 Hz) across the grounding resistor as a function of the ground fault location along the stator windings. Table 4 shows the voltage drop as the fault location moves from the neutral end of the stator windings to the output terminals. Thegrounding transformer is rated 110 volts secondary; the grounding resistor is sized 0.32 ohms secondary; and the CT ratio is 400:5 (80:1). The corresponding fundamental component circulating current is shown as well. If the fundamental current is not well rejected, then high magnitude circulating current can saturate the neutral current input and, as a result, the protection will measure a value of 20 Hz current less than the actual value. Saturation causes the following problems: delayed operation or, even worse, no operation at all less than 100% coverage of the stator windings as the ground fault location moves towards the generator output terminals. NOTE Saturation is most likely to occur when the grounding resistor is sized less than one ohm secondary. NOTE If the 64S function uses the real component, it should also use the total neutral current as a backup for the case of a solid short circuit located right at the machine neutral (i.e., the real component equals zero for this case since there is no reference voltage). Rejection of Fundamental Frequency (50 or 60 Hz) Voltage and Current Signals Fundamental component voltage and current present at the relay measuring inputs during stator ground faults can prevent the 64S function from operating properly unless they are well rejected. Note that these signals are not eliminated by the band-pass filter since they are due to the fundamental voltage drop across the secondary of the grounding transformer. Figure 9: Fundamental Voltage across as Function of Ground Fault Location NETAWORLD 75

9 Table 4: Fundamental Voltage Drop Across Grounding Resistor and Circulating Current ( 0.32 Ω) Fault Location V S I S I S /CTR 100% (phase side) 110 V (110 V)/0.32 Ω amps amps 90% 99 V (99 V)/0.32 Ω amps amps 80% 88 V (88 V)/0.32 Ω 275 amps amps 70% 77 V (77 V)/0.32 Ω amps amps 60% 66 V (66 V)/0.32 Ω amps amps 50% 55 V (55 V)/0.32 Ω amps amps 40% 44 V (44 V)/0.32 Ω amps amps 30% 33 V (33 V)/0.32 Ω amps amps 20% 22 V (22 V)/0.32 Ω amps amps 10% 11 V (11 V/0.32 Ω amps amps 0% (neutral side) Table 4 provides magnitudes of the variables at various fault locations along the winding. Underfrequency Inhibition Sometimes it is necessary to block the 64S function during conditions such as startup when the system voltage measured by the relay is 40 Hz or lower. The third harmonic of 7 Hz is very close to 20 Hz during startup when the generator is transitionally through the lower frequencies and can cause unwanted operation. COMMISSIONING INSTRUCTIONS Figure 10 illustrates how to configure the 64S protection for commissioning. NOTE Use the 20 Hz signals captured during normal operating conditions to determine appropriate overcurrent pickup settings. Determine the total capacitance to ground and calculate the overcurrent pickup setting based upon these field measurements as a check. Stator Ground Fault at Machine Neutral Configure the power system as follows: High side breaker is open. The generator is offl ine. Generator terminals are connected to delta windings of the generator step up transformer. Switch F 1 is closed. Switch F 2 is open. 20 Hz signal generator is online. Place a single line-to-ground fault at location F 1 (switch F 1 closed) and measure the 20 Hz I N. This measurement corresponds to a short circuit applied at the neutral of the machine (see Figure 11 on the following page). The total 20 Hz neutral current (I N ) should be very close in magnitude to 39 ma. 76 SUMMER 2014

10 Figure 10: 20 Hz Grounding Network for Commissioning I sc 25 8ohmsX mA NOTE This is the first step and is a quick check to see if all the wiring is correct. Normal Operating Conditions Configure the power system as follows: High side breaker is open. Generator terminals are connected to delta windings of the generator step up transformer. Switch F1 is open. Switch F2 is open. 20 Hz signal generator is online. Preferably the generator is online. Measure the following 20 Hz signals: V N (neutral voltage) I N (neutral current) Re(I N )(real component of neutral current) These signals correspond to normal operating conditions. V N and I N are the 20 Hz signals applied to the relay inputs. Record V N, I N, and Re(I N ). Modern numerical generator relays can meter these values. The signals recorded in Figure 11 were captured while commissioning a large pumped storage hydroelectric unit while operating in the motoring (pumping) mode. Figure 11: Short Circuit at Machine Neutral Figure 12: Numerical Generator Relay 20 Hz Metering NETAWORLD 77

11 CONCLUSIONS This special protection provides 100 percent coverage of the stator windings for ground faults under all operating conditions including variable real and reactive power output and when off-line. Grounds on the last five percent of the stator windings do occur and can be disastrous if not quickly detected. Traditional protections (59N, 27TH, 27D) may not reliably operate for faults in the last five percent of the stator winding. The total capacitance-to-ground of the generator stator windings, bus work, and delta-connected unit transformer windings is a very important factor and must be known to ensure the protection settings are correctly determined. This value can be determined during commissioning. There are cases when it is difficult to distinguish between normal operating conditions and an actual stator ground fault unless special steps are taken in the design of this protection. A good rule of thumb to decide if the real component of 20 Hz current is necessary is when C 0 is greater than 1.5 microfarads and the grounding resistor is less than 0.3 ohms secondary. Use the real component of the 20 Hz current measured by the relay for these cases. The protection must reject fundamental frequency (50 or 60 Hz) voltage and current signals that are present at the relay measuring inputs during ground stator ground faults. Use an under-frequency element that operates on the system voltage to block the 64S function if nuisance tripping occurs during either startup or shutdown of the generator. REFERENCES 1. Maughan, Clyde V., Stator Winding Ground Protection Failures, ASME POWER Macon, Russell C., The Art and Science of Protective Relaying, Wiley , 1956 Steve Turner is a Senior Applications Engineer at Beckwith Electric Company, Inc. His previous experience includes working as an application engineer with GEC Alstom for five years, an application engineer in the international market for SEL, focusing on transmission line protection applications. Steve worked for Progress Energy, where he developed a patent for double-ended fault location on transmission lines and was in charge of all maintenance standards in the transmission department for protective relaying. Steve has both a BSEE and MSEE from Virginia Tech University. He has presented at numerous conferences including Georgia Tech Protective Relay Conference, Western Protective Relay Conference, ECNE, and Doble User Groups, as well as various international conferences. Steve Turner is also a senior member of the IEEE. 78 SUMMER 2014

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Steve Turner Senior Application Engineer Beckwith Electric Company Introduction Summarize conclusions from NERC

More information

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS BY STEVE TURNER, Beckwith Electric Company, Inc. This paper provides detailed technical analysis of two relay misoperations and demonstrates how to prevent them

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

DOUBLE-ENDED FAULT LOCATORS

DOUBLE-ENDED FAULT LOCATORS The InterNational Electrical Testing Association Journal FEATURE END-TO-END TESTING OF DOUBLE-ENDED FAULT LOCATORS BY STEVE TURNER, Beckwith Electric Company, Inc.. www.netaworld.org FOR HIGH VOLTAGE,

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Grounding System Theory and Practice

Grounding System Theory and Practice Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018 Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

Specialists in HV and MV test and diagnostics. Testing in Substations

Specialists in HV and MV test and diagnostics. Testing in Substations Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc. Bruce L. Graves A Defining a Power System A power system is an assembly of generators, transformers, power lines, fuses, circuit breakers, protective devices, cables, and associated apparatus used to generate

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

HARMONICS CAUSES AND EFFECTS

HARMONICS CAUSES AND EFFECTS HARMONICS CAUSES AND EFFECTS What is Harmonics? Harmonics is defined as the content of the signal whose frequency is an integral multiple of the system frequency of the fundamentals. Harmonics current

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Advanced Applications of Multifunction Digital Generator Protection

Advanced Applications of Multifunction Digital Generator Protection Advanced Applications of Multifunction Digital Generator Protection Charles J. Mozina Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A. Abstract: The protection of generators

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

ARC FLASH HAZARD ANALYSIS AND MITIGATION

ARC FLASH HAZARD ANALYSIS AND MITIGATION ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword

More information

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Advanced Paralleling of LTC Transformers by VAR TM Method

Advanced Paralleling of LTC Transformers by VAR TM Method TAPCHANGER CONTROLS Application Note #24 Advanced Paralleling of LTC Transformers by VAR TM Method 1.0 ABSTRACT Beckwith Electric Company Application Note #11, Introduction of Paralleling of LTC Transformers

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems This application should be completed as soon as possible and returned to the Cooperative in order to

More information

Overvoltage and undervoltage. Dr Audih 1

Overvoltage and undervoltage. Dr Audih 1 Overvoltage and undervoltage Dr Audih 1 A Overvoltage is defined as an increase in the r.m.s. value of the voltage up to a level between 1.1 pu to 1.8 pu at power frequency for periods ranging from a half

More information

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited

More information

1C.6.1 Voltage Disturbances

1C.6.1 Voltage Disturbances 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Journal of International Council on Electrical Engineering ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20 Optimal neutral ground resistor rating of the medium

More information

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation This application is to be completed and returned to the Cooperative member service representative in order to begin

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems WHITE PAPER Medium Voltage On-Site Generation Overview BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As our

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND

More information

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising Automation Rising Q U A R T E R LY First Quarter 2013 The Digital Magazine of Automation & Information Technology for Electric, Gas and Water Utilities Utility Automation & Information Technology... PLAN...

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power

More information

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions GE Grid Solutions GPM Field and Stator Ground Fault Protection Modules Instruction Manual Product version: 2.0x GE publication code: 1601-0256-AF1 (GEK-113231D) 1601-0256-AF1 Copyright 2017 GE Multilin

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012 SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

Verifying Transformer Differential Compensation Settings

Verifying Transformer Differential Compensation Settings Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers

More information

Grounding for Power Quality

Grounding for Power Quality Presents Grounding for Power Quality Grounding for Power Quality NEC 250.53 states that ground resistance should be less than 25 ohms. Is this true? Grounding for Power Quality No! NEC 250.53 states

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg. Aligarh College of Engineering & Technology (College Code: 19) Electrical Engg. (EE-11/21) Unit-I DC Network Theory 1. Distinguish the following terms: (a) Active and passive elements (b) Linearity and

More information

Transmission Line Fault Location Explained A review of single ended impedance based fault location methods, with real life examples

Transmission Line Fault Location Explained A review of single ended impedance based fault location methods, with real life examples Transmission Line Fault Location Explained A review of single ended impedance based fault location methods, with real life examples Presented at the 2018 Georgia Tech Fault and Disturbance Analysis Conference

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Abstract: A Thyristor Controlled Three Winding Transformer as a Static Var Compensator Vijay Bendre, Prof. Pat Bodger, Dr. Alan Wood. Department of Electrical and Computer Engineering, The University of

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

AC Power Instructor Notes

AC Power Instructor Notes Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

LOW-RESISTANCE grounding resistors (LRGs) appear

LOW-RESISTANCE grounding resistors (LRGs) appear IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 44, NO. 5, SEPTEMBER/OCTOBER 2008 1311 Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case Massimo

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

Fundamentals of Power Quality

Fundamentals of Power Quality NWEMS Fundamentals of Power Quality August 20 24, 2018 Seattle, WA Track D Anaisha Jaykumar (SEL) Class Content» Introduction to power quality (PQ)» Causes of poor PQ and impact of application» PQ characteristics»

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Three phase transformer 1

Three phase transformer 1 Three phase transformer 1 Electric Engineering Name Institution: Three phase transformer 2 Table of Contents Operation of transformer under no load... 3 Operation of transformer under load... 4 Circuit

More information

1. Introduction to Power Quality

1. Introduction to Power Quality 1.1. Define the term Quality A Standard IEEE1100 defines power quality (PQ) as the concept of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. A simpler and

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Automatic capacitor banks with detuned filters

Automatic capacitor banks with detuned filters الکتروه م ند Power factor correction and harmonic filtering Automatic capacitor banks with detuned filters www.electrohamand.com Automatic capacitor banks with detuned filters Introduction R5/6-3 R.5 -

More information