1 NEC 2014 Code Changes Articles CHANGES FROM 2011 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 200 Use and Identification of Grounded Conductors General Grounded Conductors will act as stated in section Further Information: For information on the conformability of grounded conductors used in multi-wire branch circuits refer to section (B). (A) Insulation: The grounded conductor, if insulated, shall have insulation that is (1) suitable, other than color, for any ungrounded conductor of the same circuit for systems of 1000 volts or less, or impedance grounded neutral systems of over 1000 volts, or (2) rated not less than 600 volts for solidly grounded neutral systems of over 1000 volts as described in (A) Neutral Conductors (A) Installation: You will not use Neutral Conductors for more than one branch circuit, for more than one multiwire branch circuit, or for more than one group of ungrounded feeder conductors. Exception: Use of Neutral Conductors is allowed if shown elsewhere in the Code All Star Training, Inc. 1

2 (B) Multiple Circuits. Where multiple neutral conductors associated with different circuits are in an enclosure, grounded circuit conductors of each circuit shall be identified or grouped to correspond with the ungrounded circuit conductor(s) by wire markers, cable ties, or similar means in one or more within the enclosure. Exception No. 1: The requirement for grouping or identifying shall not apply if the branch-circuit or feeder conductors which enter from a cable or a raceway unique to the circuit that makes the grouping obvious. Exception No. 2: The requirement for grouping or identifying shall not apply where branch-circuit conductors pass though a box or conduit body without a loop or without a splice or termination Means of Identifying Grounded Conductors (A) Sizes 6 AWG or Smaller: Insulated grounded conductors of 6 AWG or smaller will be identified in one of the following ways. (1) A continuous white outer finish (2) A continuous gray outer finish 2014 All Star Training, Inc. 2

3 (3) Three continuous white or gray stripes along the conductor s entire length on other than green installations. (1) Three continuous white stripes along the conductor s full length. Use of green insulation will not be allowed. (2) Wires with insulation of a white or gray color, but have colored tracer threads in the braid identifying the place of manufacture, will meet the directives of this section. (B) Sizes 4 AWG or Larger: Insulated grounded conductors that are 4 AWG or larger will be identified by one of the following means: (1) A continuous white outer finish. (2) A continuous gray outer finish. Identification will be documented in a way that is easily available. It must also be displayed where the conductors of different systems originate Use of Insulation of a White or Gray Color or with Three Continuous White or Gray Stripes. (C) Circuits of 50 Volts or More: Insulation that is white, gray, or that has three continuous white or gray stripes for other than a grounded conductor for circuits of 50 volts or more will be allowed only in the following circumstances: (1) If part of a cable assembly that has the insulation re-identified by marking tape or painting at its end, to indicate its use as an ungrounded conductor and also where the conductor is visible All Star Training, Inc. 3

4 Identification will surround the insulation. Use of insulation that is white, gray, or green in color will not be allowed. If used for single pole, 3-way or 4-way switch loops, the re-identified conductor with allowed markings will be used only for the supply to the switch and not as a return conductor from the switch to the outlet. (2) A flexible cord, having one conductor identified by any means allowed here or in section that is used for connecting an appliance or equipment allowed in section This provision will also apply to flexible cords connected to outlets whether or not the outlet is supplied by a circuit with a grounded conductor. ARTICLE 210 Branch Circuits I. General Provisions Multiwire Branch Circuits (B) Discounting Means Each multi-wire branch circuit will have a means of disengaging immediately all ungrounded conductors at the branch circuit s origin. Further Information: See section (B) for information on the use of single-pole circuit breakers as the means of disconnecting All Star Training, Inc. 4

5 (D) Grouping The ungrounded and grounded circuit conductors of each multi-wire branch circuit will be organized by cable ties or other means in at least one place within the panelboard or other point of origin. Exception: The requirement for grouping shall not apply if the circuit enters from a cable or raceway unique to the circuit that makes the grouping obvious or if the conductors are identified at their terminations with numbered wire markers corresponding to the appropriate circuit number Identification for Branch Circuits (C) Identification of Ungrounded Conductors Ungrounded conductors will be identified according to section 210.5(C)(1) or (2) as applicable (1) Branch Circuits Supplied from More Than One Nominal Voltage System Where the location wiring system has branch circuits provided from more than one small voltage system each ungrounded conductor of a branch circuit will be identified by phase or line and system at all termination, connection, and splice points in compliance with 210.5(C)(1)(a) and (b). (2) Branch Circuits Supplied From Direct-Current Systems. Where a branch circuit is supplied from a D/C system operating at greater than 50 volts, each ungrounded conductor of 4 AWG or larger shall be identified by polarity at all termination, 2014 All Star Training, Inc. 5

6 connection, and splice points by marking tape, tagging, or other approved means; each ungrounded conductor of 6 AWG or smaller shall be identified by polarity at all termination, connection, and splice points in compliance with 210.5(C)(2)(a) and (b). The identification methods utilized for conductors beginning from within each branch circuit panelboard or similar branch-circuit distribution equipment shall be documented in a manner that is readily available or shall be permanently posted at each branch circuit panelboard or similar branch-circuit distribution equipment. (a) Positive Polarity, Sizes 6 AWG or Smaller. Where the positive polarity of a D/C system does not serve as the connection point for the grounded conductor, each positive ungrounded conductor shall be identified by one of the following means: (1) A continuous red outer finish (2) A continuous red stripe durably marked along the conductor s entire length on insulation of a color other than green, white, gray, or black (3) Imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color that is not green, white, gray, or black, and repeated at intervals no more than 610 mm (24 in.) in accordance with (b) (b) Negative Polarity, Sizes 6 AWG or Smaller. Where the negative polarity of a D/C system does not serve as the connection point for the grounded conductor, each negative ungrounded conductor shall be identified by one of the following means: (1) A continuous black outer finish (2) A continuous black stripe durably marked along the conductor s entire length on insulation of a color that is not green, white, gray, or red 2014 All Star Training, Inc. 6

7 (3) Imprinted minus signs ( ) or the word NEGATIVE or NEG durably marked on insulation of a color other than green, white, gray, or red, and repeated at intervals not exceeding 610 mm (24 in.) in accordance with (B) (3) Deleted (1) Listed electric-discharge luminaries Branch-circuit Voltage Limitations. (C) 277 Volts to Ground (1) Listed electric-discharge or listed light-emitting diode-type luminaries Branch-Circuit Requirements for Device Connections and Locations. A) Receptacle Outlet Location Receptacle outlets will be located in branch circuits according to Part III of Article 210. (B) Multiple branch Circuits Where two or more branch-circuits supply devices or equipment on the same yoke, there must be also installed a means of simultaneously disconnecting the ungrounded conductors and it must be available at the point where the branch circuits begin Multiple Branch Circuits 2014 All Star Training, Inc. 7

8 Where two or more branch circuits supply devices or equipment on the same yoke or mounting strap, there must be a means available to simultaneously disconnect the ungrounded conductors supplying those devices and it must be available at the point at which the branch circuits begin Ground Fault Circuit-Interrupter Protection for Personnel Ground-fault circuit interrupter protection for personnel shall be provided as required in (A) through (D). (A) Dwelling Units: (3) Outdoors Exception to #3: Receptacles that are not easily accessible and are supplied by a dedicated branch circuit for electric snow removal, deicing, or pipeline and vessel heating equipment will be allowed according to section or section (7) Sinks located in areas other than kitchens where the receptacles are installed within 1.8 m (6 ft.) of the outside edge of the sink (8) Boathouses (9) Bathtubs or shower stalls where receptacles are installed within 1.8 m (6 ft) of the outside edge of the bathtub or shower stall (10) laundry areas (B) Other Than Dwelling Units. (3) Rooftops 2014 All Star Training, Inc. 8

9 (4) Outdoors Exception #1: To (3) and (4) Receptacles that are not easily reached and are supplied by a dedicated branch circuit for electric snow removal, deicing, or pipeline and vessel heating equipment will be installed according to section or section (5) Sinks Exception #2 to #5: For receptacles found in patient care areas of health care facilities, other than those sheltered under section 210.8(B)(1), GFCI protection will not be essential. (6) Indoor Wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas where electrical diagnostic equipment, electrical hand tools, or portable lighting are to be used Branch Circuits Required. (B) Load Evenly Proportioned Among Branch Circuits. When the load is calculated on the basis of volt-amperes per square meter or per square foot, the wiring system, up to and including the branch-circuit panelboards, will be provided to serve at no less than the calculated load. This load will be evenly distributed throughout multi-outlet branch circuits within the panelboards. Branch circuit over-current devices and circuits will be installed only to serve the connected load Arc-Fault Circuit-Interrupter Protection. (A) Dwelling Units: 2014 All Star Training, Inc. 9

10 All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets or devices installed in dwelling unit kitchens, laundry areas, or similar rooms or areas shall be protected by any of the means described in (A)(1) through (6) (1) A listed combination-type arc-fault circuit interrupter, installed to provide protection of the entire branch circuit (2) A listed branch/feeder-type AFCI installed at the origin of the branch-circuit in combination with a listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet box on the branch circuit. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit. (3) A listed supplemental arc protection circuit breaker installed at the origin of the branch circuit in combination with a listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet box on the branch circuit where all of the following conditions are met: a. The branch-circuit wiring shall be continuous from the branch-circuit over-current device to the outlet branch-circuit arc-fault circuit interrupter. b. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 15.2 m (50 ft) for a 14 AWG conductor or 21.3 m (70 ft) for a 12 AWG conductor. c. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit. (4) A listed outlet branch-circuit type arc-fault circuit interrupter installed at the first outlet on the branch circuit in combination with a listed branch-circuit over-current protective device where all of the following conditions are met: 2014 All Star Training, Inc. 10

11 a. The branch-circuit wiring shall be continuous from the branch-circuit overcurrent device to the outlet branch-circuit arc-fault circuit interrupter. b. The maximum length of the branch-circuit wiring from the branch-circuit overcurrent device to the first outlet shall not exceed 15.2 m (50 ft) for a 14 AWG conductor or 21.3 m (70 ft) for a 12 AWG conductor. c. The first outlet box in the branch circuit shall be marked to indicate that it is the first outlet of the circuit. d. The combination of the branch-circuit overcurrent device and outlet branch-circuit AFCI shall be identified as meeting the requirements for a system combination type AFCI and shall be listed as such. (5) If RMC, IMC, EMT, Type MC, or steel-armored Type AC cables meeting the requirements of , metal wireways, metal auxiliary gutters, and metal outlet and junction boxes are installed for the portion of the branch circuit between the branch-circuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branch-circuit type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit. (6) Where a listed metal or nonmetallic conduit or tubing or Type MC cable is encased in not less than 50 mm (2 in.) of concrete for the portion of the branch circuit between the branchcircuit overcurrent device and the first outlet, it shall be permitted to install a listed outlet branchcircuit type AFCI at the first outlet to provide protection for the remaining portion of the branch circuit. (B) Branch Circuit Extensions or Modifications Branch circuits shall be protected by: 2014 All Star Training, Inc. 11

12 (1) A Listed combination-type AFCI located at the origin of the branch circuit (2) A listed outlet branch-circuit type AFCI located at the first receptacle outlet of the existing branch circuit Exception: AFCI protection shall not be required where the extension of the existing conductors is not more than 1.8 m (6 ft) and does not include any additional outlets or devices. (C) Dormitory Units: All 120-volt, single-phase, 15- and 20-ampere branch circuits supplying outlets installed in dormitory unit rooms shall be protected by a listed arc-fault circuit Ground-Fault Protection of Equipment. Each branch-circuit disconnect rated 1000 amps or more and installed on solidly grounded wye electrical systems of more than 150 volts to ground, but not exceeding 600 volts phase-tophase, shall be provided with ground-fault protection of equipment in accordance with the provisions of Exception No. 1: The provisions of this section shall not apply to a disconnecting means for a continuous industrial process where a non-orderly shutdown will introduce additional or increased hazards. Exception No. 2: The provisions of this section shall not apply if ground-fault protection of equipment is provided on the supply side of the branch circuit and on the load side of any transformer supplying the branch circuit Electric Vehicle Branch Circuit. An outlet(s) installed for the purpose of charging electric vehicles shall be supplied by a separate branch circuit. This circuit shall have 2014 All Star Training, Inc. 12

13 no other outlets. Informational Note: See for the definition of Electric Vehicle Conductors Minimum Ampacity and Size. (A) Branch Circuits Not More Than 600 Volts: (1) General General: Branch-circuit conductors must have an ampacity at least the maximum load to be served. Conductors shall be sized to carry not less than the larger of (A)(1)(a) or (b). (a) When a branch circuit supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum branch-circuit conductor size shall have an allowable ampacity at least the non-continuous load plus 125 percent of the continuous load. (b) The minimum branch-circuit conductor size shall have an allowable ampacity at least the maximum load to be served after applying any adjustment or correction factors. Exception: If the assembly, including the over-current devices protecting the branch circuits, is listed for operation at 100 percent of its rating, the allowed Ampacity of the branch circuit conductors will be no less than the sum of the continuous load plus the non-continuous load Outlet Devices. (3) Receptacle Ratings: 2014 All Star Training, Inc. 13

14 Where connected to a branch circuit supplying two or more receptacles or outlets, receptacle ratings will adhere to the values listed in Table (B)(3), or where rated higher than 50 amperes, the receptacle rating will be no less than the branch circuit rating Permissible Loads, Individual Branch Circuits: An individual branch circuit is allowed to supply any load for which it is rated, but the load must not exceed the branch-circuit ampere rating Branch-Circuit Requirements Summary. The requirements for circuits that have two or more outlets or receptacles, other than the receptacle circuits of section (C)(1), (C)(2) and (C)(3, are summarized in Table Table (C)(1) and (C)(2) provides only a summary of minimum requirements. See sections , , and section for the specific requirements applied to branch circuits Branch-Circuits in Buildings with More Than One Occupancy. (B) Common Area Branch Circuits: Branch circuits installed for the purpose of, lighting, central alarm, signal, communications or other purposes to meet the needs of the public, or familiar areas of two family dwelling, a multifamily dwelling, or a multi-occupancy building will not be supplied from mechanisms used in an individual dwelling unit. III. Required Outlets Dwelling Unit Receptacle Outlets (A) General Provisions: 2014 All Star Training, Inc. 14

15 (1) Spacing Receptacles will be installed so that no point measured horizontally along the floor line of any wall space is more than 1.8 m (6 ft.) from receptacle outlet. (2) Wall Space: (1) Any space 600 mm (2 ft.) or more in width (including corners) and unbroken along the floor line by doorways and similar openings, fireplaces and fixed cabinets. (3) Floor Receptacles: Receptacle outlets in or on floors shall are not to be counted as part of the number of receptacle outlets unless they are within 450 mm (18 inches) of the wall. (4) Countertop Receptacles Receptacles installed for countertops as shown in section (C) will not be considered as the receptacles required by section (A) (C) Countertops (3) Balconies, Decks and Porches: Balconies, decks, and porches that are attached to the dwelling unit and can be accessed from inside the dwelling unit must have one receptacle or more outlet accessible from the balcony, deck, or porch. The receptacle outlet must not be located more than 2.0 m (61 2 ft) above the balcony, deck, or porch walking surface. (4) Separate Spaces 2014 All Star Training, Inc. 15

16 Counter top spaces separated by range tops, refrigerators, or sinks will be considered as separate spaces in applying the requirements of section (C)(1). If a range, counter-mounted cooking unit, or sink is installed in an island counter top and the depth of the counter top behind the range, counter-mounted cooking unit, or sink is less than 300 mm (12 in.), the range, countermounted cooking unit, or sink must be considered as separating the counter top space into two distinct spaces. Each counter top space will adhere to the requirements in section (C). (5) Receptacle Outlet Location Receptacle outlets will be located on or above, but not more than 500 mm (20 in.) above, the counter top. Receptacle outlet assemblies listed for the application will be allowed to be installed in counter tops. Receptacle outlets rendered not easily reached by appliances fastened in place as covered in the section (C)(1) exception or appliances occupying dedicated space will not be considered as these required outlets. (D) Bathrooms At least one receptacle outlet will be installed in the bathroom within 900 mm (3 ft.) of the outside edge of each basin. The receptacle outlet will be located on a wall that is next to the basin counter top, located on the counter top, or installed on the side of the basin not more than 300 mm (12 in.) below the counter top. Receptacle outlet assemblies listed for the application will be allowed to be installed in the counter top. Further Information: See section 406.5(E) for requirements for installation of receptacles in counter tops All Star Training, Inc. 16

17 (G) Basements, Garages and Accessory Buildings: (1) Garages: In each attached garage and in each detached garage with electric power. The branch circuit that supplies this receptacle(s) must not supply outlets outside of the garage. A minimum of one receptacle outlet must be installed for each car space. (H) Hallways In homes, hallways of 3.0 m (10 ft.) or more in length will have at least one receptacle outlet. As stated in this subsection, the hallway length will be considered the length along the centerline of the hallway without passing through a doorway. (I) Foyers Foyers that are not part of a hallway in according to section (H) and that have an area that is greater than 5.6 m 2 (60 ft. 2 ) will have a receptacle located in each wall space 900 mm (3ft.) or more in width. Doorways, door-side windows that extend to the floor and unbroken by doorways, floor-to-ceiling windows, and other openings must not be counted as wall space. ARTICLE 215 Feeders Minimum Rating and Size. (A) Feeders Not More Than 600 Volts: (1) General: 2014 All Star Training, Inc. 17

18 Exception #1: If the assembly is listed for operation at 100 percent of its rating, the allowed ampacity of the feeder conductors will be no less than the sum of the continuous load plus the non-continuous load. (a) When a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the minimum feeder conductor size must have an allowable ampacity at least the non-continuous load plus 125 percent of the continuous load. (b) The minimum feeder conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of any adjustment or correction factors. (2) Grounded Conductor: The size of the feeder circuit grounded conductor will be no smaller than that required by section , except that section (F) will not apply where grounded conductors are run parallel. Additional minimum sizes will be as specified in section 215.2(A)(2) and section 215.2(A)(3). (3) Ampacity Relative to Service Conductors The feeder conductor ampacity will be no less than the service conductors where the feeder conductors carry the total load supplied by service conductors with an ampacity of 55 amperes or less. (4) Individual Dwelling Unit or Mobile Home Conductors Feeder conductors for individual homes or mobile homes do not need to be larger than the service conductors. Use Paragraph (B)(6) for finding required conductor size Over-current Protection All Star Training, Inc. 18

19 Exception #2: Over-current protection for feeders over 600 volts, nominal, will adhere to Part IX of Article All Star Training, Inc. 19

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors

CHAPTER 2 Wiring and Protection. Article 200 Use and Identification of Grounded Conductors ARTICLE 200 USE AND IDENTIFICATION OF GROUNDED CONDUCTORS 70 35 CHAPTER 2 Wiring and Protection Article 200 Use and Identification of Grounded Conductors 200-1. Scope. This article provides requirements

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 9/8/10 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions conduit? 9/8/10 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. Can branch circuits of different services be installed in the same Yes, see 300.3(C)(1) for conductors of different systems

More information

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights

1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights 1 Exam Prep NFPA 70: National Electric Code 2011 Tabs and Highlights These 1 Exam Prep Tabs are based on NFPA 70: National Electrical Code, 2011. Each 1 Exam Prep Tabs sheet has five rows of Tabs. Start

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING 1 1 1 1 1 NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING NORTH CAROLINA BUILDING CODE COUNCIL Notice of Rule-making Proceedings is hereby given by NC Building Code Council in accordance with G.S.

More information

2017 NEC TABLE OF CONTENTS

2017 NEC TABLE OF CONTENTS Article 90 Introduction 90.1 Purpose (A) Practical Safeguarding (B) Adequacy (C) Relation to Other International Standards 90.2 Scope (A Covered (B) Not Covered (C) Special Permission 90.3 Code Arrangement

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

ECET Fall 2017 Name: _ Lab Assignment #01

ECET Fall 2017 Name: _ Lab Assignment #01 ECET 4520 - Fall 2017 Name: _ Lab Assignment #01 General Instructions: This assignment is to be completed individually. All answers/work required for each problem should be neatly written in the space

More information

Article 225: Outside Branch Circuits And Feeders

Article 225: Outside Branch Circuits And Feeders Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)

More information

American Electrical Institute

American Electrical Institute American Electrical Institute Oregon Electricians Continuing Education Grounding & Bonding (Article 250) 4 Hours American Electrical Institute PO Box 31131 Spokane, WA 99223 www.aeitraining.com Article

More information

2014 NEC Changes Part 1

2014 NEC Changes Part 1 www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms

More information

Journeyman's Practice Exam

Journeyman's Practice Exam Journeyman's Practice Exam [Time limit 4.0 hrs.] (The test is open book. I've started at the front of the Code Book and worked toward the back for instructional purposes. The real test will not be in order

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Code Check Electrical is a field guide to common code issues in residential

Code Check Electrical is a field guide to common code issues in residential INTRODUCTION u CODES u ABBREVIATIONS Code 3Check Electrical 5th Edition By Redwood Kardon & DOUGLAS HANSEN Illustrations & Layout: Paddy Morrissey 2008 by The Taunton Press, Inc. ISBN 978-1-60085-012-7

More information

Article 250 Grounding & Bonding

Article 250 Grounding & Bonding Article 250 Grounding & Bonding AMERICAN ELECTRICAL INSTITUTE N16 W23217 Stone Ridge Dr. Waukesha, WI 53188 855-780-5046 www.aeitraining.com DISCLAIMER NOTE: This course is APPROVED for continuing education

More information

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit.

a) Determine the smallest, standard-sized circuit breaker that should be used to protect this branch circuit. ECET4520 Exam II Sample Exam Problems Instructions: This exam is closed book, except for the reference booklet provided by your instructor and one (8.5 x11 ) sheet of handwritten notes that may not contain

More information

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math

Chapter 1 Electrical Theory and Part C Series Parallel and Code Questions Multiwire Branch Circuits Unit 1 Electrician s Math Chapter 1 Electrical Theory and Code Questions 1 Unit 1 Electrician s Math and Basic Electrical Formulas 3 Part A Electrician s Math 3 1 1 Fractions 3 1 2 Kilo 4 1 3 Knowing Your Answer 4 1 4 Multiplier

More information

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...

INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet... INTRODUCTION...xiii Author s Comments...xiii Exam Preparation...xiii Difficult Concepts...xiv Textbook Errors and Corrections...xv Internet...xv UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS...1

More information

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit Current will always try to return to its source In order for there to be current, there must be a complete circuit Current will take as many paths or circuits available to it to return to the source The

More information

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5 Applied Grounding and Bonding Paul Dobrowsky Member NEC Panel 5 1 Introduction This presentation is a representative sample from the following Chapters of Applied Grounding and Bonding. Chapter 1, Introduction

More information

Department of Labor and Industry Electrical Licensing

Department of Labor and Industry Electrical Licensing Department of Labor and Industry Electrical Licensing License Examination Guide The information in this guide is provided by the Licensing Unit of the Department of Labor and Industry to ensure that applicants

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings SOLAR MICROINVERTER/M STANDARD PLAN - COMPREHENSIVE Microinverter and M Systems for One- and Two- Family Dwellings SCOPE: Use this plan ONLY for systems using utility-interactive Microinverters or Modules

More information

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST

STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST STANDARD COMMENTS 2016 ELECTRICAL PLAN REVIEW CHECK LIST Item Comments 1. The electrical plan check is approved and ready to have the electrical permit issued, pending the building permit being issued.

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Electrical Occupations

Electrical Occupations Job Ready Assessment Blueprint Electrical Occupations Test Code: 3029 / Version: 01 Copyright 2011. All Rights Reserved. General Assessment Information Blueprint Contents General Assessment Information

More information

Continued from Part 1 Rules 1 25.

Continued from Part 1 Rules 1 25. Continued from Part 1 Rules 1 25. 26 225.32 Disconnect Location The disconnecting means for a building or structure must be installed at a readily accessible location, either outside the building or structure

More information

Electrical Inspectors

Electrical Inspectors International Association of Electrical Inspectors Western Section 114th Annual Meeting September 16-19, 2018 Appleton, Wisconsin The answers to these questions are the opinion of the person that answered

More information

We have 3 ways to help you prepare

We have 3 ways to help you prepare P a g e 2 Texas Electrical Excel is your source for obtaining your license state exam. Call us if you have questions regarding your applications, exam preparation, exam registration and more. We have reached

More information

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate.

Article 700: Emergency Systems. 2.! Audible and visual signal devices shall be provided, where practicable to indicate. Part N: Code Book Questions Article 700: Emergency Systems 1.! For emergency systems, the authority having jurisdiction shall conduct or witness a test on the! complete system upon installation and periodically

More information

A. Product Description: Stranded conductor insulated wire.

A. Product Description: Stranded conductor insulated wire. SECTION 16120CPPR CONDUCTORS AND CABLE PART 1 - GENERAL 1.1 SYSTEM DESCRIPTION A. Product Requirements: Provide products as follows: 1. All building wire shall be stranded copper (no aluminum wire). 2.

More information

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS

UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS UNION COUNTY ENGINEER DIVISION OF BUILDING REGULATIONS Residential Pool Permit Requirements FEES: A nonrefundable permit application fee of $25.25 and a nonrefundable plan review fee of $40.40 will be

More information

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL BELL SYSTEM PRACTICES Plant Series SECTION 508-100-100 Issue 3, October 1970 AT&TCo Standard ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL I. GENERAL 1.01 This section is reissued to: Revise

More information

Canadian Standards Association Mississauga, Ontario To the Part I Committee

Canadian Standards Association Mississauga, Ontario To the Part I Committee Canadian Standards Association Mississauga, Ontario To the Part I Committee Subject No. 3130 Chair: R. Leduc Date: December 24, 2003 Title: Receptacles in Residential Occupancies, Rules 26-710, 26-712,

More information

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. SECTION 26 05 19 PART 1 - GENERAL 1.1 THE REQUIREMENT A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents. 1.2 CONTRACTOR SUBMITTALS A. The

More information

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL

SECTION LOW-VOLTAGE ELECT. DIST. DESIGN AND CONSTRUCTION STANDARDS _ February 2015 PART I: GENERAL PART I: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. a.

More information

Electrical Wiring: Commercial, Seventh Canadian Edition

Electrical Wiring: Commercial, Seventh Canadian Edition Electrical Wiring Commercial Canadian 7th Edition Mullin SOLUTIONS MANUAL Full download at: https://testbankreal.com/download/electrical-wiring-commercialcanadian-7th-edition-mullin-solutions-manual/ Unit

More information

Bulletin Voltage drop in single dwelling units Rule 8-102

Bulletin Voltage drop in single dwelling units Rule 8-102 Bulletin 8-6-0 Voltage drop in single dwelling units Rule 8-102 Scope Issued February 2014 (1) Background (2) Application of voltage drop for branch circuits in single dwelling units a) Determination of

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Home Electrical Wiring. Types of Receptacles and Wiring them for 120v 15Amp/20Amp

Home Electrical Wiring. Types of Receptacles and Wiring them for 120v 15Amp/20Amp Home Electrical Wiring Types of Receptacles and Wiring them for 120v 15Amp/20Amp Understanding the wires You have 3 wires in a home electrical system; Hot (Black wire) - dangerous one Neutral (White wire)

More information

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition

Jake Leahy s Electrical Code Connection. A look at Grounding and Bonding of Electrical Services Article Florida Building Code 5 th Edition Jake Leahy s Electrical Code Connection A look at Grounding and Bonding of Electrical Services Article 250 2014 Florida Building Code 5 th Edition Wiring Integrity. Completed wiring installations shall

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION

SECTION COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION SECTION 16715 COMMUNICATIONS ELECTRICAL POWER DISTRIBUTION PART 1 - GENERAL 1.01 SECTION DESCRIPTION AND BASIC REQUIREMENTS A. The Electrical Power Distribution System provides power distribution from

More information

Bulletin Voltage drop in single dwelling units Rule 8-102

Bulletin Voltage drop in single dwelling units Rule 8-102 Bulletin 8-6-1 Voltage drop in single dwelling units Rule 8-102 Issued April 2014 Supersedes Bulletin 8-6-0 Scope (1) Background (2) Application of voltage drop for branch circuits in single dwelling units

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL

PROVINCE.OF BRITISH COLUMBIA. ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL PROVINCE.OF BRITISH COLUMBIA ORDER OF THE LIEUTENANfelOVERNOR IN COUNCIL Order in Council No. 0640 Approved and Oidered a -1.1995 cieuisvunigott3mor Executive Council Chambers, Victoria On the recommendation

More information

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4

SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: Document Number: KUCSH0039 Rev: 4 SAFETY AND HEALTH STANDARD ELECTRICAL GROUNDING Effective Date: 07/17/10 Standard: 16.10 Document Number: KUCSH0039 Rev: 4 16.10.1 INTRODUCTION 16.10.1.1 The intent of this standard is to ensure that continuity

More information

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard

Wiring Methods, Components, and Equipment for General Use -- OSHA Standard ABE285 Wiring Methods, Components, and Equipment for General Use -- OSHA Standard 1910.305 1 Carol J. Lehtola, Charles M. Brown, and William J. Becker 2 The Impact of Safety on Florida Agriculture Florida

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Electrical requirements for plans on all new homes, additions, remodels & Service upgrades

Electrical requirements for plans on all new homes, additions, remodels & Service upgrades CHERRY HILLS VILLAGE COLORADO Electrical requirements for plans on all new homes, additions, remodels & Service upgrades Due to the size and uniqueness of homes built in Cherry Hills Village, a policy

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

SECTION BUILDING WIRE AND CABLE

SECTION BUILDING WIRE AND CABLE SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION-16075 ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SECTION INCLUDES A. Electrical identification to identify all electrical items for easy operation and maintenance including, but not limited

More information

SECTION EQUIPMENT WIRING

SECTION EQUIPMENT WIRING PART 1 - GENERAL 1.01 RELATED DOCUMENTS: SECTION 26 27 17 EQUIPMENT WIRING A. The Conditions of the Contract and applicable requirements of Divisions 0 and 1 and Section 26 00 01, Electrical General Provisions,

More information

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage

More information

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT A. General In a hazardous location grounding of an electrical power system and bonding of enclosures of circuits and electrical equipment in the

More information

ELPT 1429 RESIDENTIAL WIRING

ELPT 1429 RESIDENTIAL WIRING SYLLABUS ELPT 1429 RESIDENTIAL WIRING INDUSTRIAL AND COMMERCIAL ELECTRICITY BRAZOSPORT COLLEGE LAKE JACKSON TEXAS PREPARED BY: Larry Grable DATE: September 13, 2005 INSTRUCTOR RECOMMENDED BY: RECOMMENDED

More information

Wiring of the Main Distribution Panelboard

Wiring of the Main Distribution Panelboard Job Sheet 4 Wiring of the Main Distribution Panelboard OBJECTIVE To connect the service-entrance conductors. To ground the main distribution panelboard (MDP). To wire a branch circuit supplying a three-phase

More information

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also, delete any other item or

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

Single-Family Dwelling Submittal Requirements

Single-Family Dwelling Submittal Requirements Single-Family Dwelling Submittal Requirements The purpose of this guideline is to assist our customers in preparing for plan submittal. The items listed must be included before your plans can be accepted

More information

SECTION 5 TRANSFORMERS

SECTION 5 TRANSFORMERS SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established

More information

Healthcare Isolation Power Systems. Presented by: David Knecht

Healthcare Isolation Power Systems. Presented by: David Knecht Healthcare Isolation Power Systems Presented by: David Knecht E-Mail: David.Knecht@Bender-us.com Healthcare Isolation Power Systems Theory Offer Codes & Standards FAQs Isolated Power System Purpose To

More information

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011 NATIONAL RULES FOR ELECTRICAL INSTALLATIONS Fourth Edition ET 101:2008 Extracts from Amendment No.1:2011 22 June 2011 Page vi: Insert after 1 st Paragraph: Section 710: Medical Locations was prepared by

More information

Electrical IP Red Seal Practice Exam

Electrical IP Red Seal Practice Exam Electrical IP Red Seal Practice Exam PRACTICE EXAM-3 1. What size 2 pole breaker must you use on a 3HP, 115V single phase motor? A. 40A B. 50A C. 80A. D. 100A. 2. An electrical equipment approved for use

More information

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax: National Fire Protection Association 1 Batterymarch Park, Quincy, MA 02169-7471 Phone: 617-770-3000 Fax: 617-770-0700 www.nfpa.org M E M O R A N D U M TO: Members of the NEC-Code Making Panel 16 FROM:

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Box Fill. We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies.

Box Fill. We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies. Box Fill We have learned how to fill or NOT overfill a conduit. We must also determine how to fill boxes and conduit bodies. Box Fill This falls into four categories: 1. Small box fill (NEC 314.16) 2.

More information

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC

EFCOG BEST PRACTICE # 211. Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC EFCOG BEST PRACTICE # 211 Best Practice Title: Managing Hazards of Multiwire Branch Circuits Installed Before the 2008 NEC Facility: DOE Complex Point of Contact: John (Jackie) McAlhaney, Savannah River

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Customer Connection Guide Updates Effective May 2017

Customer Connection Guide Updates Effective May 2017 This document provides a list of the updates to the EPCOR Distribution and Transmission Inc. (EDTI) Customer Connection Guide. If you have any questions, please contact EDTI Customer Engineering Services

More information

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians.

Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. Continuing Education, For UDC Electrical Inspectors, Commercial Electrical Inspectors, Master Electricians and Journeyman Electricians. The following test is for Continuing Education Credits for the abovementioned

More information

1. Name the horizontal member that rests on the foundation wall to support other wood members.

1. Name the horizontal member that rests on the foundation wall to support other wood members. Student Name: Teacher: Date: District: Rowan Assessment: 9_12 T and I IC62 - Drafting - Architr II Test 1 Description: Unit C - Floorplans - Test 3 (ALL) Form: 501 1. Name the horizontal member that rests

More information

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2

Construction Electrician/Industrial Electrician/Power Electrician Common Core Level 2 Common Core Level 2 Unit: B1 Commercial Electrical Code Level: Two Duration: 60 hours Theory: Practical: 60 hours 0 hours Overview: This unit is designed to provide the apprentice with the knowledge about

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

Bulletin Filming in Minnesota

Bulletin Filming in Minnesota 443 Lafayette Road N. St. Paul, Minnesota 55155 www.doli.state.mn.us www.electricity.state.mn.us MINNESOTA DEPARTMENT OF LABOR & INDUSTRY (651) 284-5064 1-800-DIAL-DLI Fax: (651) 284-5749 TTY: (651) 297-4198

More information

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY

AN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC

More information

Electrical Standards Division 16

Electrical Standards Division 16 Design Guidelines and Standards Electrical Standards Division 16 November 2004 Office of the University Architect Construction Management P.O. Box 210181 Cincinnati, Ohio 45221-0181 ELECTRICAL SPECIFICATIONS

More information

Ground Fault Location. Turbo Sleuth. Instruction Manual

Ground Fault Location. Turbo Sleuth. Instruction Manual Ground Fault Location Turbo Sleuth Instruction Manual 7615 Kimbel Street, Mississauga, Ontario Canada L5S 1A8 Tel: (905)673-1553 Fax: (905)673-8472 Toll Free: 1-888-RESISTR 737-4787 www.ipc-resistors.com

More information

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance

Table of Contents. Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings. Technical Assistance Power Distribution Blocks & Terminal Blocks with High Short-Circuit Current Ratings Table of Contents Page Selection Table.... 2 Power Distribution Blocks PDBFS Series....................................3-8

More information

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.1 SUMMARY DISCONTINUED PRODUCT GUIDE SPECIFICATIONS 15-75 kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL These specifications describe requirements for a complete power conditioning and

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

Grounding and Bonding

Grounding and Bonding Grounding and Bonding 2017 Communications Academy Joe Blaschka Jr., PE Grounding/Bonding What is it? Why do we do it? What does the National Electrical Code say? What about fixed locations? What about

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

Alternating Current Power

Alternating Current Power Chapter 4 Alternating Current Power MElec-Ch4-1 Overview What is Alternating Current AC Hazards AC Power Requirements Shoreside Utility System On-Board Generators MElec-Ch4-2 What is Alternating Current

More information

UNSIGNED HARDCOPY NOT CONTROLLED. Reference Designation Marking and Miscellaneous Coding

UNSIGNED HARDCOPY NOT CONTROLLED. Reference Designation Marking and Miscellaneous Coding Subject: APPROVED BY STATUS PURPOSE Reference Designation Marking and Miscellaneous Coding Manager, Hardware Engineering Maintenance Revision Establish marking instructions for reference designations for

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

at Fiddler s Creek Offered by

at Fiddler s Creek Offered by at Fiddler s Creek at Fiddler s Creek hawthorne Elevation E Elevation F WWW.FIDDLERSCREEK.COM hawthorne 1 Story, 3 Bedrooms, 3 Baths, Den, 3 Car Garage Total A/C... 2,583 sq. ft. Entry...51 sq. ft. Garage...618

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 13 DISTRIBUTION SWITCHBOARDS SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also delete any other item or paragraph not applicable

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information