NIPSCO Energy Symposium

Size: px
Start display at page:

Download "NIPSCO Energy Symposium"

Transcription

1 Backup Power Automatic Transfer NIPSCO Energy Symposium symposium Backup Power Applications/Considerations Backup Power Types Automatic Transfer Switch Basics Presenters McGill Power - Jeremy Irmeger Eaton - Barry Graves 2007 Eaton Corporation. All rights reserved.

2 Objective & Agenda Bypass Isolation Magnum Front Access Objective Understanding the basics of how to identify and properly apply UPS s Uninterruptible Power Supplies) and ATS (Automatic Transfer Switches) for accommoding for seamless systems. Agenda What is a UPS UPS Types What is a Automatic Transfer Switch Transfer Switch Types Transfer Switch Application Categories Transition Types Basic Components of a Transfer Switch Application Considerations Questions

3 The 9 Common Power Problems Interruption Sag Swell Undervoltage Overvoltage Line Noise Frequency Variation Switching Transients Harmonic Distortion

4 3 (+1) Basic Types of UPS Standby Off Line Normal Operation Power Failure Event Powerware Series 3 The Series 3 (Stand-By) UPS delivers power protection from 3 of the most common power problems that threaten your equipment and data Interruption Sag Swell Line Interactive Buck/Boost Powerware Series 5 The Series 5 (Line-Interactive) UPS delivers power protection from 5 of the most common power problems that threaten your equipment and data Undervoltage Overvoltage Ferroresonant +1 Powerware Series Ferro The Series Ferro UPS delivers galvanic isolated power protection from 8 of the most common power problems that threaten equipment and data Harmonic distortion Line noise Switching transients On Line Double Conversion ( Powerware Series 9 The Series 9 (On-Line) UPS delivers power protection from all 9 of the most common power problems that threaten your equipment and data Frequency variation

5 What is a UPS System? Maintenance Bypass Panel System Input N.O. System Output To PDU AC DC AC UPS Power Module 1. Double Conversion 2. Online System Battery Cabinet

6 How Much Downtime is Acceptable? Power Availability Equivalent Power Disruptions (yr) % ISPs, e-business, Communications, Electronics mfg. N+ Redundancy < 3 seconds % Food Processing Server Operating Systems Generators and Some UPS 5.3 minutes 99.99% 99.9% Hospitals, Airports Generator Only Residential Homes Typical Grid Power 0.88 hours 8.8 hours

7 Automatic Transfer Switch A device which transfers electrical loads between two sources of power by using either manual or automatic controls. UTILITY LOAD GENERATOR UTILITY UTILITY

8 Bypass Isolation Transfer Switch An automatic transfer switch with an additional bypass isolation switch Provides ability to perform maintenance of the main transfer switch power device, without interruption of power to the load Applied in high reliability applications: Provides emergency power to life safety and other critical loads

9 Transfer Switch Types There are only two ways to transfer power: Automatic If loads are very critical, an automatic transfer switch would probably be used insure the fastest possible transfer. Non-Automatic (manual, or electrically operated) If loads are not quite as critical, but still cannot go for any extended period of time without power, a Non-Automatic or manual transfer switch could be used.

10 Non-automatic vs Manual Transfer Electrically operated non-automatic transfer switches. The switch electrically transfers power when a pushbutton, usually mounted on the switch s enclosure, is pushed. If necessary, the switch can also be manually operated. Manually initiated, Electrically operated Manually operated transfer switches provide all the mechanics to effect the transfer from source to source. The actual transfer of power, however, is by true hand operation of the transfer switch. Manually initiated, Manually operated

11 Application Category NFPA 70 National Electric Code NFPA 70 - National Electric Code Article Emergency Systems Article Legally Required Standby Systems Article Optional Standby Systems Article COPS Article Health Care Facilities NFPA 99 - Health Care Facilities NFPA Emergency & Standby Systems NFPA 20 - Fire Pumps NFPA 70E Workplace Safety

12 Article 700 Emergency Systems Article 701 Legally Required Article 702 Optional Systems Article 708 COPS Application examples include any system where a power interruption would create life safety or health hazards. Must automatically transfer in 10 seconds Shall be listed for emergency use (UL 1008 only). Shall supply only emergency loads. Application examples include any system where a power interruption would create hazards or hamper rescue or fire fighting operations. Must automatically transfer in 60 seconds Shall be listed for emergency use (UL 1008 only). Application examples include any system where a power interruption would cause discomfort or disrupt a process. Automatic/manual transfer. No transfer time requirement. Allows for option as such as: Go to neutral position Auto/Manual Selector switch Application examples include emergency call centers ATS labeled for use on emergency systems. No requirement for transfer time. Transfer equipment separate from other emergency, legally required, or optional loads. Must include provisions for roll-up generator if using one generator.

13 Transfer Switch Transition Types 2007 Eaton Corporation. All rights reserved.

14 Open Transition Also called a break-before-make switch. One set of contacts opens before the other set closes There is a definite break in power as the load is taken off one source and connected to another. This is the most common and least expensive Normal Loads TS N TS E Emergency

15 Delayed Transition Break Both Sides Delayed Transition One set of contacts opens before the other The other set of contacts delays in closing Load is disconnected from power during all transfers Normal Loads TS N TS E Emergency

16 Delayed Transition Time delay neutral Requires a 3 position mechanism Timed delay in the neutral position, typically 0-120sec 3 sec is typically a good starting point Load Voltage Decay Senses back emf voltage Will pause in neutral position until regenerative voltages are at 10-30% On Eaton transfer switches option 32 cannot be reprogrammed in the field. A new controller must be purchased. 32a 32b

17 Closed Transition Normal Loads TS N TS E Emergency 100 m/secs overlap-time

18 Closed Transition Closed Transition is also called a make-before-break switch. There is no interruption in power to a critical load when using this type of switch. Both power sources are connected to the load before the break occurs. Parallels the loads for < 100ms The two power sources have to have the same voltage and frequency and be synchronized for the switch to transfer. Permits the periodic testing of an emergency source, such as a generator, without interrupting power to the loads

19 Consideration for selecting Transition Types When transferring two live sources, abnormal motor inrush current can occur leading to possible damage of motor windings, insulation, couplings and in some cases, the load itself. Inrush currents are caused by the motor s residual voltage being out of phase with the voltage source to which it s being transferred. Methods of control are: Open Inphase transfer Motor load disconnect control circuit Delayed transition - Time Delay Neutral, Load Voltage Decay Closed transition less than 100 ms paralleling of sources

20 Open In-phase Transfer 32f Feature that allows a live transfer between two sources only when the phase difference between the two is near to zero. This feature prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred How it works: Monitor samples the relative phase angle between the two sources being transferred When the two sources are within the desired phase angle different and are approaching zero phase angle difference, the inphase monitor signals the transfer switch to operate. The operating time of the transfer switch is key in utilizing an inphase monitor (must transfer in less than ten cycles) In-phase monitor and VFD s do not work well together, use TDN. In-phase doesn t give the VFD s time to reset.

21 Motor Load Disconnect Control Circuit 45 Selected motor loads are de-energized during transfer operation Controller signals contact to open approx. 3 seconds prior to transfer, thus de-energizing selected loads. Loads are turned onto the generator after a designated time delay. Loads can be turned on at one time or sequentially so as to not block load the generator. Motor load disconnect works well when the generator is sized at the min.

22 Automatic Transfer Switches - Main Components 2007 Eaton Corporation. All rights reserved.

23 Transfer Switch Main Components An automatic transfer switch (ATS) is made up of several main components Controller Continually monitors the condition of the power sources Initiates start command to backup generator, Initiates transfer and retransfer to good power source Power switching device Power device rated to transfer the load to/from the power sources Control Power Transformer panel Supplies operational power to the switching device/controller

24 Main Components - Controller In an ATS, the controller is basically the brains of the ATS, that contains all the logic/intelligence to initiate the switching. The controller performs following functions: Senses the source voltage and frequency Sends a start command to the back up power if the main source is lost. Commercial ATC-300+ Controller

25 Main Components Switching Device The switching device is the main power device that transfers the load from one power source to another. The switching device includes the main power device and the transfer mechanism. The ATS controller tells the switching device when to make the transfer/retransfer to a good source Two basic types of switching devices: Contactor Specifically designed contactors to perform load transfer between to AC sources. Transfer switches do not use motor starting/lighting type contactors. Molded Case/Power Case Switch A molded case or power case circuit breaker without and /or with a trip unit. Used when a circuit requires a compact, high capacity disconnect device.

26 Main Components Contactor Switching Device Contactor based The contactor switching device includes the main power assembly and the operating mechanism. The power assembly is composed of the individual power poles. The operating mechanism includes the solenoid and the mechanical interlock. Power Assembly 3 Pole Contactor Source 2 Bus Moving Contact Source 1 Bus Load Bus Operating Mechanism Single Power Pole

27 Main Components Molded Case or Power Case Circuit Breaker Switching Device Molded Case or Power Case Circuit Breaker Based The molded case/power case circuit breaker switching device is a circuit breaker without and/or with the overcurrent trip. The switching device is composed of two separate power devices. One device is for closing on source 1 and the other for closing on source 2. The operating mechanism includes the motor operator. 3 Pole Molded Case Switch Power Assembly 3 Pole Power Case Switch Power Assembly Motor Operating Mechanism Source 1 Device Source 2 Device Motor Operator in Power Case Switch

28 Main Components Transformer Panel Control Power Provided by small Control Power Transformers CPT- connected to the normal and the emergency source. The good source then provides the control power needed for the ATS to properly operate. Provided with a multi tap primary allowing the CPT to be used on different voltage applications permitting a simple field change from one voltage to another.

29 Basic Information for ATS Selection When selecting a Transfer Switch, review the following: Types of load to be transferred Transition type Open In phase, Delayed, Closed Transition Application Type Life Safety, Emergency, Optional Switch Ratings Voltage rating, Phase, # poles Continuous Current rating/amps Overload and fault current withstand ratings Configuration Type Service Entrance Bypass Isolation

30 UPS and ATS Basics Questions?

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

The Connecticut Light and Power Company

The Connecticut Light and Power Company The Connecticut Light and Power Company and The United Illuminating Company Exhibit B - Generator Interconnection Technical Requirements May 12, 2010 Page 1 of 26 Table of Contents 1. SCOPE... 3 2. GENERAL

More information

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions April 25, 2017 Mike Carter Power Quality Symptoms What Is Normal? Power Quality Approach Find and fix Ride-through Solutions Protection/Compensation Schemes Other Power Quality Solutions What Can Go Wrong?

More information

Table 6.1 Fault Code List Code indication (Note 3)

Table 6.1 Fault Code List Code indication (Note 3) 62 Table 6.1 Fault List UA801 UA802 UA803 UA804 UA805 UA806 UA807 UA808 UA810 UA812 UA813 UA814 UA815 UA817 UA821 AC VOLTAGE OUT OF RANGE AC FREQUENCY OUT OF RANGE AC PHASE ROTATION ERROR OPE. OVER OVER

More information

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS Copyright Mitsubishi Electric Power Products TABLE OF CONTENTS 1. SCOPE... 1 1.1 The System... 1 2. SYSTEM DESCRIPTION... 1 2.1 Components... 1 2.2 Modes

More information

Generation Interconnection Requirements at Voltages 34.5 kv and Below

Generation Interconnection Requirements at Voltages 34.5 kv and Below Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM SECTION 263353 - THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM PART 1 GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL 1.1 SUMMARY Liebert NX UPS GUIDE SPECIFICATIONS 40-80kVA, 80-120kVA and 160-200kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL This specification defines the electrical and mechanical

More information

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE PAGE 262400-1 SECTION 262400 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

Power-Sure 700. Technical Data TD158001EN. Contents

Power-Sure 700. Technical Data TD158001EN. Contents Technical Data TD158001EN Power-Sure 700 Supersedes August 2015 Contents Description Page General description... 2 Power-Sure 700 benefits.... 2 Specifications... 3 Industry standards and certifications...

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

Connection of Embedded Generating Plant up to 5MW

Connection of Embedded Generating Plant up to 5MW Engineering Recommendation No.3 of the Electricity Distribution Code Connection of Embedded Generating Plant up to 5MW Version 1.0 30th November 2005 Prepared by: Al Ain Distribution Company, Abu Dhabi

More information

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2 Guide and Requirements for Service at 69,000 to 287,000 Volts R 0.2 September - 2011 Disclaimer This document is not intended as a design specification or as an instruction manual for the Load Customer

More information

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION POWER QUALITY A N D Y O U R B U S I N E S S A SUMMARY OF THE POWER QUALITY REPORT PUBLISHED BY THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION H YDRO ONE NETWORKS INC SEPTEMBER 2014

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards Change History Date Description of Change Pages / Sections Modified 8/23/17 Updated sections on System Design and Performance Requirements; Submittals; Equipment; Accessories or Special Features; Quality

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Short Circuit Current Calculations

Short Circuit Current Calculations Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that

More information

1C.6.1 Voltage Disturbances

1C.6.1 Voltage Disturbances 2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope The purpose of this document is to state typical levels of voltage disturbances, which may be encountered by customers

More information

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption

More information

TN, TT & IT Earthing Arrangements

TN, TT & IT Earthing Arrangements TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal)

Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal) Modbus Map: InfraStruXure Symmetra 3-Phase 990-3249 // Status Word 0 40000 0 8 Reserved R = UPS ready to provide power to the load upon return of normal line voltage or upon user command = State == Enable

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner conditioning products Electronic voltage regulator -Sure 700 & 800 -Suppress T7 & 100 Harmonic correction unit Sag ride-through power conditioner The power to work Basics of power quality The partner you

More information

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: December 17, 2018 The following changes, additions, revisions, and/or deletions

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240 Industrial Environment AC-DC Converters >100 Watt W Series 120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240 Rugged 35 mm DIN-rail snap-fit design 3000 V AC input to

More information

Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing

Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing Select the right transfer switch to avoid transient problems By John Stark, Marketing Communications

More information

Contents. 1 Introduction Assessment criteria Assessment Recommendations References... 8

Contents. 1 Introduction Assessment criteria Assessment Recommendations References... 8 Note: This is a translation of the RSK recommendation entitled Ein- oder zweiphasiger Ausfall des Haupt-, Reserve- oder Notstromnetzanschlusses. In case of discrepancies between the English translation

More information

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- /

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- / Z7 2. Type designation Z 7- / Transfer mode without code: Users can set the matter : self-throwing and self-reset (power network to power network) S: self-throwing and not self-reset (power network to

More information

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems Presented for the IEEE Central TN Section / Music City Power Quality Group August 1, 2006 By Ed Larsen and Bill

More information

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks 2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution

More information

SECTION POWER SYSTEMS STUDIES

SECTION POWER SYSTEMS STUDIES PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Division 15 for Mechanical requirements. Refer to Division 16 for Electrical requirements. 1.2 OBJECTIVE: A. The short-circuit study is to calculate the

More information

UNDERSTANDING POWER QUALITY

UNDERSTANDING POWER QUALITY Technical Note No. 1 June 1998 UNDERSTANDING POWER QUALITY This Technical Note describes the range of problems, what causes them, what they affect and what could be done to manage them. Integral Energy,

More information

ATC Controllers. High efficiency Comprehensive function The new generation VFD

ATC Controllers. High efficiency Comprehensive function The new generation VFD High efficiency Comprehensive function The new generation VFD The power of fusion. 1833 1874 1886 1893 1897 1899 1906 1908 1911 1914 1934 1961 1962 1963 1967 1977 1983 1984 1989 There s a certain energy

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

NAME OF (VENDOR/MANUFACTURER) Clause No. Clause Description Comments, if any Remarks, if any

NAME OF (VENDOR/MANUFACTURER) Clause No. Clause Description Comments, if any Remarks, if any BSNL seeks comments on Draft GR for UPS from UPS/Invertors vendors BSNL INVITES COMMENTS FROM UPS / INVERTOR VENDORS ON DRAFT GR FOR UPS PREPARED BY BSNL. COMMENTS MAY BE GIVEN TO BSNL CORPORATE OFFICE,

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56 1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked

More information

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis 1 Summary 1.1 Provide a complete Arc Flash Hazard Analysis for the project indicated in the accompanying RFP. The Analysis may be performed: independent of the construction project in concert with the

More information

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Purpose This section specifies the requirements for protective relays and control devices for Generation Entities interconnecting

More information

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (11) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008990 1.0 Organisation Valid from Valid until Regionnätsaffärer

More information

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality

More information

Switching power supplies CP range, Linear power supplies CP-L range. Content

Switching power supplies CP range, Linear power supplies CP-L range. Content CP range, Linear power supplies CP-L range Content Switching power supplies, primary switch mode, CP range Benefits and advantages... 136 Approvals... 137 Ordering details... 138 Technical data... 11 Dimensional

More information

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems SECTION 26 33 53 - STATIC UNINTERRUPTIBLE POWER SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

Grounding Recommendations for On Site Power Systems

Grounding Recommendations for On Site Power Systems Grounding Recommendations for On Site Power Systems Revised: February 23, 2017 2017 Cummins All Rights Reserved Course Objectives Participants will be able to: Explain grounding best practices and code

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information

SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL TYPE RTS03ATB AUTOMATIC TRANSFER SWITCH RPTCS CONTROL EFFECTIVE 1/19/2011 SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL PART 1 - GENERAL

More information

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements... Requirements for Interconnection Facilities Teck Metals Ltd. Transmission Assets: 1. Facility Connection Requirements 2. Technical Performance Requirements References: (Most recent version in each instance)

More information

Power Protection and Conditioning

Power Protection and Conditioning 2/50 Voltage Wave Attenuation CBEMA Constant Voltage Power Supply Voltage surge with a virtual front time of 1.2 ms and a time to half-value of 50 ms delivered across an open circuit. 8/20 Current Wave

More information

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.1 SUMMARY DISCONTINUED PRODUCT GUIDE SPECIFICATIONS 15-75 kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL These specifications describe requirements for a complete power conditioning and

More information

First Draft Language

First Draft Language 110.16 First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1) Nominal system voltage (2) Arc flash boundary (3)

More information

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL 1.1 SUMMARY GUIDE SPECIFICATIONS 100-200 kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL These specifications describe requirements for a complete power conditioning and distribution system,

More information

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE PART 1 GENERAL 1.01 SCOPE A. Furnish and install the low voltage automatic transfer switches having the ratings, features/accessories and enclosures

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI OVERVIEW In the present business climate, companies are under constant pressure to increase profitability by increasing productivity, maximizing

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

Roadmap For Power Quality Standards Development

Roadmap For Power Quality Standards Development Roadmap For Power Quality Standards Development IEEE Power Quality Standards Coordinating Committee Authors: David B. Vannoy, P.E., Chair Mark F. McGranghan, Vice Chair S. Mark Halpin, Vice Chair D. Daniel

More information

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Please use the Q & A utility to ask us any questions concerning the material being presented.

Please use the Q & A utility to ask us any questions concerning the material being presented. Meet Our Team Webinar Notes Please use the Q & A utility to ask us any questions concerning the material being presented. You can find a recording of this webinar and presentation on our Video Library

More information

PART 1 OWNER/APPLICANT INFORMATION

PART 1 OWNER/APPLICANT INFORMATION CALHOUN COUNTY ELECTRIC COOP. ASSN. Application for Operation of Customer-Owned Generation This application should be completed as soon as possible and returned to the Cooperative in order to begin processing

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY -- D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,...

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,... - District Standard - FAC Facility Design, Connections 950.001 and Maintenance CHELAN COUNTY ~ PUBLIC UTILITY DISTRICT Owned By The People~ Serve Facility Connection Requirements Page 1 of 101 EFFECTIVE

More information

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control. Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)

More information

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE UNINTERRUPTIBLE POWER SUPPLY MODEL 9800AE SINGLE MODULE SYSTEM SPECIFICATIONS In no event shall MEPPI be liable for the accuracy, completeness or usefulness of the following specifications or for any modification(s)

More information

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947 Motor--protective circuit--breaker system J7M -AM System Rated operational current 25 A. Switching capacity up to 10 A, 100 ka/415 V. Switching capacity 16 A, 20 A, 25 A, 16 ka/415 V. Fixed short--circuit

More information

3Ø Short-Circuit Calculations

3Ø Short-Circuit Calculations 3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective

More information

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

T-68 Protecting Your Equipment through Power Quality Solutions

T-68 Protecting Your Equipment through Power Quality Solutions T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What

More information

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Power Quality and Circuit Imbalances 2015 Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron Summary of IEEE 1159 Terms Category Types Typical Duration

More information