OSHA & Arc Flash. Scott Ray Distribution Project Engineer POWER Engineers, Inc.
|
|
- Ann Lindsey
- 6 years ago
- Views:
Transcription
1 OSHA & Arc Flash Scott Ray Distribution Project Engineer POWER Engineers, Inc.
2 Outline Arc Flash Overview OSHA Overview Arc Flash Study Next Steps Why This Method? Questions Methodology Steps Analysis
3 Arc Flash Overview What is Arc Flash? The thermal (heat) energy given off by an uncontrolled electrical arc through open air. Referred to as the incident energy in cal/cm 2. Can be between conductors or between conductors and ground.
4 Arc Flash Overview Four types of energy released in an arc: 1. High Temperature Heat Energy Temperatures can soar well above that of the surface of the sun (~10,000 F) in just a fracmon of a second 2. Blast Percussion Sound Damage VaporizaMon of solids to gases Shrapnel 3. High Intensity Light Flash 4. Super Heated Ball of Gas Plasma
5 Arc Flash Overview Requirements and Standards NESC OSHA NFPA 70E IEEE 1584
6 OSHA Overview (d)(1) Employer shall assess the workplace for hazards which necessitate the use of PPE Select and have employees use appropriate PPE to protect employees from hazards idenmfied in the hazard assessment
7 OSHA Overview This secmon covers the operamon and maintenance of electric power generamon, control, transformamon, transmission, and distribumon lines and equipment.
8 OSHA Overview
9 Arc Flash Study Methodology Methodology Follows the IEEE 1584 nine steps: 1. Collect the system and installamon data 2. Determine the system modes of operamon 3. Determine the bolted fault currents 4. Determine the arc fault currents 5. Find the protecmve device characterismcs and duramon of arcs
10 Arc Flash Study Methodology Methodology Follows the IEEE 1584 nine steps (cont d): 6. Document the system voltages and classes of equipment 7. Select the working distances 8. Determine the incident energy for all equipment 9. Determine the flash- protecmon boundary for all equipment
11 Arc Flash Study Steps 1 and 2: Standard data collecmon UMlize substamon single- lines to determine stamon operamng modes UMlize WindMil model to determine feeder modes of operamon
12 Arc Flash Study Steps 3 and 4: UMlize WindMil model to calculate fault currents on the system from substamon to out on feeders Three- phase faults for use in IEEE 1584 arc- in- box calculamons Single- phase faults for use in overhead lines and ARCPRO calculamons
13 Arc Flash Study Step 5: UMlize LightTable database for system protecmve devices
14 Arc Flash Study Steps 6 and 7: Use system voltages and equipment to determine: Arc Gaps Working Distances Used to develop PPE calorie curves
15 Arc Flash Study Analysis PPE Calorie Curve Development Use voltage, equipment type, arc gap and working distance informamon to develop curves Develop curves for: 5.0 cal/cm 2 Threshold for arc rated faceshield 8.0 cal/cm 2 Minimum ramng worn by personnel 40.0 cal/cm 2 Maximum desired ramng to be worn by personnel
16 Arc Flash Study Analysis Curve Development Generate Mme current points Develop curves via two methods: 1. IEEE 1584 EquaMons 2. ARCPRO Import points into LightTable to develop Mme current curves
17 Arc Flash Study Analysis Using LightTable Compare: ProtecMve device curves Calorie curves Fault currents 2.0 second cutoff Mme For each locamon give a ramng/grade Pass CondiMonal Pass Fail
18 Arc Flash Study Analysis Pass The U2 relay curve fully protects the 5.0, 8.0 and 40.0 cal/cm 2 curves from range of potenmal fault currents
19 Arc Flash Study Analysis CondiMonal Pass The U3 relay curve doesn t fully protect the 5.0, 8.0 and 40.0 cal/cm 2 curves from range of potenmal fault currents However protects up to the 2.0 second evacuamon Mme
20 Arc Flash Study Analysis Fail The U4 relay cover fails to protect the 5.0 and 8.0 cal/cm 2 curves from range of potenmal fault currents (40.0 cal/cm 2 curve is a condimonal pass)
21 Next Steps Use the results as part of overall arc flash safety program LocaMons with Pass condimons no addimonal analysis needed CondiMonal pass condimons determine whether results are acceptable for situamon and work to be performed Fail condimons Use WindMil and LightTable to adjust protecmve device sekngs
22 Why This Method? Doesn t require a detailed model Can be used independent of fault analyses Arc flash analysis models use IEEE empirically derived models only applicable for certain scenarios
23 QuesMons? Scom Ray POWER Engineers, Inc. (503)
A Guide to Establish an Arc Flash Safety Program for Electric Utilities
A Guide to Establish an Arc Flash Safety Program for Electric Utilities by Craig Clarke, P.E. Eaton Corporation 50 Soccer Park Rd. Fenton, MO 63026 (636) 717-3406 CraigClarke@Eaton.com Ilanchezhian Balasubramanian,
More informationArc Flash Study Principles & Procedures for below 15 kv AC Systems. Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur
Arc Flash Study Principles & Procedures for below 15 kv AC Systems Xuan Wu, Dennis Hoffman, Ronald Wellman, and Manish Thakur Agenda Arc Flash Study Purposes Introduction of Arc Flash Arc Flash Risk Locations
More informationARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR
More informationElectrical Arc Hazards
Arc Flash Analysis 1996-2009 ETAP Workshop Operation Notes Technology, 1996-2009 Inc. Operation Workshop Technology, Notes: Arc Inc. Flash Analysis Slide 1 Electrical Arc Hazards Electrical Arcs can occur
More informationFirst Draft Language
110.16 First Draft Language (B) Service Equipment. In addition to the requirements in (A), service equipment shall contain the following information: (1) Nominal system voltage (2) Arc flash boundary (3)
More informationArc Flash Analysis Training
Arc Flash Analysis Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq An arc flash analysis study is
More informationSelection of PPE Practical experience of different arc assessment methods and their comparison
Selection of PPE Practical experience of different arc assessment methods and their comparison Dr.-Ing. Thomas Jordan Markus Kauschke Slide 1 ICOLIM 2017 Selection of Arc Flash PPE BSD Electrical Safety
More informationSteve Kovach District Sales Engineer
Steve Kovach District Sales Engineer 630-740-7463 Steveekovach@Eaton.com Institute of Electrical and Electronics Engineers American Society of Safety Engineers 1 Electrical Hazards Electrical Hazards Shock
More informationArc Flash Mitigation An Overview. Gus Nasrallah, P.E. Electroswitch May 30, 2013
Arc Flash Mitigation An Overview Gus Nasrallah, P.E. Electroswitch May 30, 2013 Agenda Origin of Modern Arc Flash studies Why Now more than before NFPA 70E Standards Protection Zone IEEE 1584 2002 IEEE
More informationARC FLASH & PPE UPDATE. Michael Olivo, P.E. Aaron Ramirez, E.I.T.
ARC FLASH & PPE UPDATE Michael Olivo, P.E. Aaron Ramirez, E.I.T. What is Arc Flash? Arc Flash is the release of heat and light produced when electrical current flows through an air gap between two conductors
More informationCause, Effect & Mitigation Strategies
WSU HANDS ON RELAY SCHOOL 2019 Arc Flash Fault Cause, Effect & Mitigation Strategies Joe Xavier, Technical Manager West Region Arc Flash Fault - Agenda What is an Arc Flash? Why and when does Arc Flash
More informationArc Flash Analysis and Documentation SOP
Arc Flash Analysis and Documentation SOP I. Purpose.... 2 II. Roles & Responsibilities.... 2 A. Facilities Maintenance (FM).... 2 B. Zone Supervisors/ Shop Foremen... 2 C. PMCS & CPC... 2 III. Procedures...
More informationMicro-synchrophasors for distribution systems: implications for grid reliability and resilience
Micro-synchrophasors for distribution systems: implications for grid reliability and resilience i-pcgrid March 31, 2017 Dr. Alexandra (Sascha) von Meier Director, Electric Grid Research, California Institute
More informationADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030
ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: December 17, 2018 The following changes, additions, revisions, and/or deletions
More informationArc Hazard Assessment for DC Applications in the Transit Industry
Arc Hazard Assessment for DC Applications in the Transit Industry Kenneth S.Y. Cheng Kinectrics Inc. Toronto, Canada Stephen L. Cress Kinectrics Inc. Toronto, Canada Donald J. Minini Excalibur Associates,
More informationArc Flash and NFPA 70E
Arc Flash and NFPA 70E Presented by: J.D. Kyle Safe Work Practices Wearing Proper PPE? OSHA 1910.333 (a) (1) not to work hot or live except : 1. De energizing introduces additional or increased hazards
More information2015 NFPA 70E. SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation
2015 NFPA 70E SESHA 2015 ARIZONA MINI CONFERENCE December 10, 2015 Intel Corporation Introduction Jeffrey A. Pugh, P.E. Pugh Engineering LLC Bachelor of Science Degrees in Electrical Engineering and Computer
More informationNATIONAL ELECTRIC SAFETY CODE 2012 EDITION
NATIONAL ELECTRIC SAFETY CODE (ANSI C2 / NESC) 2012 EDITION Jim Tomaseski IBEW Director of Safety and Health EEI Safety and Health Committee Conference NESC 2012 IMPORTANT DATES SEPTEMBER 1, 2009 - Preprint
More informationPaul Dobrowsky Innovative Technology Services
Significant Changes to NFPA 70E -2009 Edition Paul Dobrowsky Innovative Technology Services 2008 IEEE PCIC 1 Repeat Presentation This has been previously presented 2008 IEEE Electrical Safety Workshop
More informationSECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 73 OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY SPEC WRITER NOTE: Delete between // -- // if not applicable to project. Also, delete any other item or
More informationArc Flash Hazard Standards:
Arc Flash Hazard Standards: The Burning Question Presented by Sesha Prasad Specialist Power System Engineer Welcon Technologies At IDC Electrical Arc Flash Forum Melbourne April 14th & 15th 2010. Session
More informationREDUCING ARC FLASH HAZARD BY REMOTE SWITCHING
The Electrical Power Engineers Qual-Tech Engineers, Inc. 21 Johnson Road Building #1 Suite 23 Houston, PA 15342-13 Phone 724-873-9275 Fax 724-873-891 www.qualtecheng.com REDUCING ARC FLASH HAZARD BY REMOTE
More informationNFPA-70E. Electrical Safety in the Workplace. Standard for Edition
NFPA-70E Standard for Electrical Safety in the Workplace 2015 Edition NFPA-70E 90.1 Purpose. The purpose of this standard is to provide a practical safe working area for employees relative to the hazards
More informationSECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY
SECTION 16075 - SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide a short-circuit, component protection, flash
More informationSTANDARDIZING ARC FLASH PPE LABELS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 01 Johnson Road Building #1 Suite 03 Houston, PA 1534-1300 Phone 74-873-975 Fax 74-873-8910 www.qualtecheng.com STANDARDIZING ARC FLASH PPE LABELS
More informationDC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE
DC ARC FLASH. THE IMPLICATIONS OF NFPA 70E 2012 ON BATTERY MAINTENANCE William Cantor, P.E. TPI Exton, PA 19341 Phil Zakielarz TPI Exton, PA 19341 Mario Spina Verizon Wireless Uniontown, OH 44685 Abstract
More informationArc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010
Arc Flash Hazard and Mitigation 2 nd Workshop on Power Converters for Particle Accelerators June 14 16, 2010 Paul Bellomo June 14-16, 2010 2nd Workshop on Power Converters for Particle Accelerators - Arc
More informationCOMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS
COMMON SOURCES OF ARC FLASH HAZARD IN INDUSTRIAL POWER SYSTEMS Joost Vrielink Hans Picard Wilbert Witteman Eaton Eaton SABIC-IP Europalaan 202 7559 SC Hengelo Europalaan 202 7559 SC Hengelo Plasticslaan
More informationCREATING A COMPARATIVE MAP OF RELATIVE POWER FOR DC ARC FLASH METHODOLOGIES. A Thesis. presented to
CREATING A COMPARATIVE MAP OF RELATIVE POWER FOR DC ARC FLASH METHODOLOGIES A Thesis presented to the Faculty of California Polytechnic State University, San Luis Obispo In Partial Fulfillment of the Requirements
More information{40C54206-A3BA D8-8D8CF }
Informative Annex D Incident Energy and Arc Flash Boundary Calculation Methods This informative annex is not a part of the requirements of this NFPA document but is included for informational purposes
More informationWebinar: An Effective Arc Flash Safety Program
Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of
More information2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis
1 Summary 1.1 Provide a complete Arc Flash Hazard Analysis for the project indicated in the accompanying RFP. The Analysis may be performed: independent of the construction project in concert with the
More informationFt Worth IEEE-PES. Presented by: Doug Harris Specifications Engineer Dallas, TX. Arc-Flash Hazard Mitigation & Selectivity
Ft Worth IEEE-PES Presented by: Doug Harris Specifications Engineer Dallas, TX Arc-Flash Hazard Mitigation & Selectivity Electrical hazards Energized circuit/conductor Today s power system engineer must
More informationAN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC
More informationTHREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA
THREE PHASE PAD MOUNTED DISTRIBUTION TRANSFORMER ARC FLASH TESTING JUNE 23, 2009 FERRAZ SHAWMUT HIGH POWER LABORATORY NEWBURYPORT, MA Witnessed by: Jim Phillips, PE, Consultant Craig DeRouen, ERMCO Director
More informationArc Flash Calculation Methods
Arc Flash Calculation Methods Course No: E04-033 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F:
More informationAN EXAMPLE OF A STANDARD ARC FLASH PPE LABELING STRATEGY
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com AN EXAMPLE OF A STANDARD ARC
More informationDESIGN STANDARD DS 29
Assets Delivery Group Engineering DESIGN STANDARD DS 29 VERSION 1 REVISION 2 MAY 2018 FOREWORD The intent of Design Standards is to specify requirements that assure effective design and delivery of fit
More information2017 ELECTRICAL SAFETY SERVICES. Arc Flash Electrical Maintenance Lockout/Tagout And More
2017 ELECTRICAL SAFETY SERVICES Arc Flash Electrical Maintenance Lockout/Tagout And More ABOUT LEWELLYN TECHNOLOGY Improving workplace safety since 1993 Daryn Lewellyn founded Lewellyn Technology more
More informationDesign Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost
Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost Adam T. Powell, PE President Emerald Engineering, Inc. Jeffrey L. Small, Sr. Senior
More informationElectrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1
Electrical Safety Policy Health and Safety FCX-HS03 Release 07/2018 Version 1 POTENTIAL FATAL RISKS Exposure to Electrical Hazards CRITICAL CONTROLS Access Control Barriers and Segregation Electrical PPE
More informationSECTION POWER SYSTEMS STUDIES
PART 1 - GENERAL 1.1 RELATED SECTIONS: Refer to Division 15 for Mechanical requirements. Refer to Division 16 for Electrical requirements. 1.2 OBJECTIVE: A. The short-circuit study is to calculate the
More informationElectrical Severity Measurement Tool Revision 4
Electrical Severity Measurement Tool Revision 4 November 2017 Electrical Severity Measurement Tool 1.0 Purpose: This tool is intended to measure the severity of exposure to an electrical safety event based
More informationElectrical Overcurrent Studies
Electrical Overcurrent Studies 11-01-2011 Deliverables associated with electrical overcurrent studies are as follow : a. Draft Reports i. Construction Related Projects have the following draft reports
More informationThe advantages of transformers. EMC-ESD in de praktijk Jan-Kees van der Ven
The advantages of transformers EMC-ESD in de praktijk 09-11-2016 Jan-Kees van der Ven Introduction RH Marine Additional benefits Common mode reduction LF Harmonic reduction Common mode reduction HF Fault
More informationElectric Arc and associated Hazards in the Rail Transit Industry Are we up to date with current developments?
Electric Arc and associated Hazards in the Rail Transit Industry Are we up to date with current developments? Dev Paul, P.E. AECOM Oakland, CA Abstract: Electrical arcing faults are inherent characteristics
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More informationCHANGEABILITY OF ARC FLASH PARAMETERS AND ITS IMPACT ON HAZARD MITIGATION IN LOW VOLTAGE POWER SYSTEMS
CHANGEABILITY OF ARC FLASH PARAMETERS AND ITS IMPACT ON HAZARD MITIGATION IN LOW VOLTAGE POWER SYSTEMS by Abdeslem Kadri Bachelor of Engineering, Boumerdes University INELEC, 1996 A thesis presented to
More informationNOTICE ER Roland Flood Pumping Station Arc Flash Study
NOTICE This document contains the expression of the professional opinion of SNC-Lavalin Inc. (SLI) as to the matters set out herein, using its professional judgment and reasonable care. It is to be read
More informationKey factors to maintaining arc flash safety
APPLICATI TE Key factors to maintaining arc flash safety Arc flash and blast When an arc fault occurs, the result is a massive electrical explosion. The light and heat emitted by the explosion is known
More informationSELFRIDGE AIR TRAFFIC CONTROL Mark Winsor, Air Traffic Manager, Steven Oliver, RAPCON Chief Controller,
SELFRIDGE AIR TRAFFIC CONTROL Mark Winsor, Air Traffic Manager, 239-5190 Steven Oliver, RAPCON Chief Controller, 239-4517 APPROACH CONTROL AIRSPACE Click Click Click MTC NOT TO SCALE MTC
More informationPRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE
PRODUCTIVELY SAFER LOCK-OUT TAG-OUT PROCEDURE with PESDs WRITTEN BY: Philip B. Allen, Owner and CEO 1515 W. Kimberly Road Davenport, Iowa 52807, USA 1.800.280.9517 www.graceport.com PRODUCTIVELY SAFER
More informationIndustrial Electrician Level 3
Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide
More informationAPPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY
APPLYING LOW-VOLTAGE CIRCUIT BREAKERS TO LIMIT ARC FLASH ENERGY Copyright Material IEEE Paper No. PCIC-2006-2 George Gregory Kevin J. Lippert Fellow Member, IEEE Senior Member, IEEE Schneider Electric
More informationA controlled arc-flash, produced in a flashtube. Even though the energy level used is fairly low (85 joules), the low-impedance, low-inductance
An arc flash (also called a flashover), which is distinctly different from the arc blast, is part of an arc fault, a type of electrical explosion or discharge that results from a low-impedance connection
More informationSWITCHING SAFETY & RELIABILITY CONFERENCE
SWITCHING SAFETY & RELIABILITY CONFERENCE JARGON WORKSHEET Energize (v) Energize is the process of applying rated voltage to circuit or equipment. Modified IEEE or OSHA from Adj. to verb. To make a piece
More informationThomas Wilkins Wilkins Consulting Henderson Nevada U.S.A.
Medium Voltage Vacuum Circuit Breaker with Mechanically Interlocked Grounding Switch (VDH/GSMI) Provides Better Safety and Reliability for Wind and Solar Power Plants and Their Personnel than Remote Transfer
More informationElectrical Measurement Safety. Sponsored By:
Electrical Measurement Safety Sponsored By: About the Viewer Panel Slides: Go to the Links tab at the top and click on the link to download the PDF of the slides If you re watching the archive version,
More informationElectrical PIP ELEGL03 Guidelines for Power Systems Analysis
July 2016 Electrical PIP ELEGL03 PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements
More informationThis section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.
Basis of Design This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Background Information A Short Circuit and Coordination
More informationCopper Core & Coil Transformer
Copper Core & Coil Transformer Transformer Stomach Pain Normal Operation: Transformer internal structures and windings are subjected to mechanical forces due to the magnetic forces. Through fault current
More information101 PTW Software Standard 3-Day Training
101 PTW Software Standard 3-Day Training DAPPER, CAPTOR, A_FAULT, and TMS SKM Power*Tools For Windows Software Training Course Objectives To develop a working knowledge of the Power*Tools for Windows DAPPER,
More informationUpgrading Your Electrical Distribution System To Resistance Grounding
Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding
More informationStandards for MV switchgear rated for arc flash protection
Standards for MV switchgear rated for arc flash protection by Bryan Johnson, ABB Switchgear standards historically considered the electrical capability of switchgear with little regard to the effects of
More informationPREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!
PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling
More informationHoneywell Salisbury PrismShield Colors within Sight, Safety on Site
Honeywell Salisbury PrismShield Colors within Sight, Safety on Site The Right Way to Distinguish Every Color Right Away The Honeywell Salisbury PrismShield improves color recognition and general visibility
More informationPower System Study for the Pebble #2 Lift Station Las Vegas, Nevada
PQTSi Power System Study for the Pebble #2 Lift Station Las Vegas, Nevada Coordination Study and Arc Flash Analysis Power Quality Technical Services, Inc. 683 Scenic Tierra Ln. Henderson, NV 89015 Prepared
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DEPARTMENT OFFICE
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DEPARTMENT OFFICE SPECIFICATION EO 2018 REVISION 1 October, 2009 EFFECTIVE DATE NOVEMBER 1, 2009
More information[ENE02] Artificial neural network based arcing fault detection algorithm for underground distribution cable
[ENE02] Artificial neural network based arcing fault detection algorithm for underground distribution cable Chan Wei Kian 1, Abdullah Asuhaimi Mohd. Zin 1, Md. Shah Majid 1, Hussein Ahmad 1, Zaniah Muda
More informationCyberspace Governance:
Cyberspace Governance: security, surveillance and privacy: metadata Virgilio Almeida Harvard University Cambridge, October 2016 References YA De Montjoye, CA Hidalgo, M Verleysen, VD Blondel, Unique in
More informationA DUMMIES GUIDE TO GROUND FAULT PROTECTION
A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding
More informationARC FLASH HAZARD ANALYSIS AND MITIGATION
ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword
More informationMethods to Reduce Arc-Flash Hazards
Methods to Reduce Arc-Flash Hazards Exercise: Implemetig Istataeous Settigs for a Maiteace Mode Scheme Below is a oe-lie diagram of a substatio with a mai ad two feeders. Because there is virtually o differece
More informationArc Flash Hazard. Can HRG Technology play a role in prevention?
Arc Flash Hazard Can HRG Technology play a role in prevention? Although arc hazards have existed since man began using electricity, increasing deaths, injuries and property loss from arcing faults have
More informationBest Practice Reducing The Risk of Arc Flash Cross Over
Best Practice Reducing The Risk of Arc Flash Cross Over 1 2 Electrical Systems Are Critical 3 Why Do We Complete Electrical Maintenance Energized?? 4 Which Bulb Is Not Working?? 5 Functioning Correctly
More informationElectrical CSA Z462. oberonsafety oberonsafety (USA & Canada) (55) (Mexico)
User Guide Oberon ArcShieldTM NFPA 70E CSA Z462 Use This product should be used in accordance with all labeling and the NFPA 70E (USA) and CSA Z462 (Canada) standards Important Warning!! This product does
More information1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:
ENGINEERING SERVICES 1960 Research Drive, Suite 100, Troy, Michigan 48083 ARC FLASH REDUCTION with SEPAM RELAY ZONE SELECTIVE INTERLOCKING REVISION: December 10, 2007 (Supersedes previous versions) Prepared
More informationEnclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System
Technical Data TD008010EN Supersedes February 2016 Enclosed circuit breaker (ECB) with Arcflash Reduction Maintenance System The information below is taken directly from the National Electrical CodeT (NEC)
More informationNeed for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design
IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas
More informationEmployment for All! Spectrum AGM Conrad Tyrkin October 2014
Employment for All! Spectrum AGM Conrad Tyrkin October 2014 Thanks for having me! Today I want to talk about: - Who I am - Why we are talking about jobs - What we are doing about ge:ng jobs for everyone
More informationHow does an Arc occur?
How does an Arc occur? Arc Flash Suits are designed to provide protection from arc flash heat exposures. Arc flash suits are designed to protect the electrical technician from heat and to reduce or minimize
More informationLOCKOUT / TAGOUT PROGRAM
Page 1 of 7 1. SCOPE LOCKOUT / TAGOUT PROGRAM This Program outlines the purpose, rules, responsibilities and techniques to be followed by all University of Pittsburgh employees to guard against the unexpected
More informationSingle Earthed Neutral and Multi Earthed Neutral. Single Earthed Neutral and Multi Earthed Neutral: Multi Grounded Neutral System (MEN):
Single Earthed Neutral and Multi Earthed Neutral. SEPTEMBER 6, 2011 5 COMMENTS Single Earthed Neutral and Multi Earthed Neutral: In Distribution System Three Phase load is unbalance and non linear so The
More informationHow does an Arc occur?
Contact us = sales@liveline.co.za How does an Arc occur? Arc Flash Suits are designed to provide protection from arc flash heat exposures. Arc flash suits are designed to protect the electrical technician
More informationPre-Engineering/Engineering Technology
Job Ready Assessment Blueprint Pre-Engineering/Engineering Technology Test Code: 2475 / Version: 01 Copyright 2007. All Rights Reserved. General Assessment Information Pre-Engineering/Engineering Technology
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationContact Voltage Detection
Contact Voltage Detection Midwest Rural Energy Conference 48th Annual Rural Energy Conference March 11-12 La Crosse, Wisconsin Chad Hadley, Senior Engineer Overview Contact Voltage Definition History Equipment
More informationREVIEWED HES MANAGER
Page 1 of 7 APPROVAL ORIGINATED SAFETY & SECURITY SPECIALIST REVIEWED HES MANAGER AUTHORIZED AMERICAS REGION MANAGER R. J. MEERMAN J.E. LANDRY T. A. POTTER DISTRIBUTION HARD COPY Copy 1 COMPLIANCE DEPARTMENT
More informationNORTHWEST FLORIDA STATE COLLEGE MONUMENT SIGNS WITH LED DISPLAYS
PREPARED FOR: FOUNDATION PLAN & STRUCTURAL NOTES DESIGNED BY: NJB DRAWN BY: NJB REVIEWED BY: BLSE S1 PREPARED FOR: FRAMING PLANS DESIGNED BY: NJB DRAWN BY: NJB REVIEWED BY: BLSE S2 PREPARED FOR: SECTION
More informationIntroduction to Bowtie Methodology for a Laboratory Setting
Introduction to Bowtie Methodology for a Laboratory Setting ACS 251st National Meeting Division of Chemical Health and Safety Developing, Implementing & Teaching Hazard Assessment Tools Mary Beth Mulcahy,
More informationSpray Painting Policy
Spray Painting Policy Form: Revision: MFG-20 C Revision Date: 1-8-2018 Spray Painting Policy Granite Falls, MN New Ulm, MN Watertown, SD Prentice, WI a.) Configuring, testing and maintaining the paint
More informationEE223D: Distribution Power Transformer
EE223D: Distribution Power Transformer Aug 07-09, 2018 / Dubai EE223 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive course is designed to provide participants with the skills
More informationEffective System Grounding
Effective System Grounding By Andrew Cochran of I-Gard and John DeDad of DeDad Consulting The costs associated with losses stemming from ground faults are staggering. For example, over a seven year period,
More informationElectrical Hazards, Safety, Ladders, Fall Protection, and Code
Youth Explore Trades Skills Electrical Hazards, Safety, Ladders, Fall Protection, and Code Description s work in many dangerous environments. Electric shock, burns, and falls are among the most common
More informationMITIGATING ELECTRIC SHOCK AND ARC FLASH ENERGY A TOTAL SYSTEM APPROACH FOR PERSONNEL AND EQUIPMENT PROTECTION
MITIGATING ELECTRIC SHOCK AND ARC FLASH ENERGY A TOTAL SYSTEM APPROACH FOR PERSONNEL AND EQUIPMENT PROTECTION Copyright Material IEEE Paper No. PCIC-2010-41 Daleep C. Mohla, P.E. Tim Driscoll. P.E. Paul
More informationRoadmaps to Ocean Worlds
Roadmaps to Ocean Worlds OPAG September 2017 La Jolla Amanda Hendrix (PSI), Terry Hurford (GSFC) co-chairs Congressional DirecMon From the Commerce, JusMce, Science, and Related Agencies AppropriaMons
More informationLevel 3 Certificate in Occupational Safety and Health. Unit 2: Controlling Hazards in the Workplace. Specimen Examination Question Paper
Level 3 Certificate in Occupational Safety and Health Unit 2: Controlling Hazards in the Workplace Specimen Examination Question Paper DO NOT OPEN THIS BOOKLET UNTIL YOU ARE INSTRUCTED TO DO SO PLEASE
More informationPPE: Why Fabric Matters
PPE: Why Fabric Matters Chris Corner Vice President of International Business Development January 12, 2016 Agenda TenCate Overview Inherently Flame Resistant Fibers How Inherently Flame Resistant Fabrics
More informationUnderstanding the Charger's Contribution to a DC Arc Flash
Understanding the Charger's Contribution to a DC Arc Flash April 2016 Richard Hutchins R&D Specialist La Marche Mfg. Co. Des Plaines, IL 60018 Introduction In a typical DC system with batteries and chargers,
More informationCentral Hudson Gas & Electric Corporation. Transmission Planning Guidelines
Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents
More information