Common Covered Task 408OP Inspect Cathodic Protection Rectifier

Size: px
Start display at page:

Download "Common Covered Task 408OP Inspect Cathodic Protection Rectifier"

Transcription

1 Common Covered Task 408OP Inspect Cathodic Protection Rectifier Directions This training guide is to be used by a Veriforce Authorized Evaluator/Trainer and Trainee during on-thejob training (OJT) or prior to an evaluation as a resource. (S) Indicates a demonstration or skill task; (K) indicates a knowledge task. OJT Reminder OJT is an active hands-on process. Practice should be as similar to the actual job task as possible. However, if the training is being provided on an actual job site while a covered task is actually being performed, the Evaluator either needs to be qualified on that covered task or be assisted by someone who is qualified on the covered task. The Evaluator should closely monitor the Trainee's practices to ensure safe and correct task performance. At no time should a non-qualified individual perform, or train for, a covered task unless directed and observed by a qualified individual. However, if the span of control for that particular covered task is 1:0 (requiring only qualified individuals to perform the covered task), the training must be simulated. Training is simulated by "walking through" the task and simulating all actual manipulations (valves, switches, tools, etc.) an individual would use during the performance of a covered task. Simulating includes the use of safety and administrative requirements as if the task were being performed live. Refer to the Veriforce Evaluator Training Program for more on how to conduct formal OJT. Disclaimer This training resource is offered in good faith. Anyone choosing to utilize or rely on this training resource is doing so at their own discretion, risk and choice. Although every attempt has been made by Veriforce, LLC (the Company ) to ensure the correctness and suitability of this document and to correct any errors brought to the attention of the Company, the Company makes no representation or warranty regarding correctness or suitability (either directly or indirectly) of information referenced or implied within this training resource. In no event shall the Company be liable for any damages (including, but not limited to, special, incidental or consequential damages) whatsoever (including, but not limited to, death, personal injury, damage to person or property, loss of use, and/or loss of revenues), whether in an action of contract, negligence, or other action, arising out of or in any way associated with the use or misuse of this document. All critical information should be independently verified by the user and the user shall not rely on the contents provided herein without such independent verification. The subject matter included in this training has been compiled from a variety of sources and is subject to change without notice. The Company reserves the right to add, remove and alter information contained in this document without notice. The Company may provide links to other sites for your convenience; however, the Company takes no responsibility and makes no representation or warranty regarding the accuracy or currency of information contained within such sites. The Company does not endorse any information, goods, or services referred to within such sites, and the provision of links by the Company shall not be interpreted to be an endorsement of such information, goods or services. The content of this training resource is provided for personal use only, and all other use, copying or reproduction of this training or website or any part of it is prohibited. Page 1 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

2 Common Covered Task 408OP Inspect Cathodic Protection Rectifier Recommended Student Training or Resources: (b) (c) Introduction Rectifiers are the most frequently used power source for impressed current cathodic protection systems. Impressed current cathodic protection systems use the following components: A reliable power source A rectifier An anode This is the sacrificial element of an electrochemical cell consumed in the corrosion process. A cathode This is a metal surface, such as the pipeline. A metallic path between the anode & the cathode An electrolytic path This could be soil or water in this example. Rectifiers change alternating current (AC) power to the proper direct current (DC) power level. Providing the correct amount of DC power is an important part of ensuring appropriate cathodic protection. A rectifier that is providing too much DC power could cause coating damage, while a rectifier that is providing too little DC power may not provide adequate cathodic protection for the system. Therefore, it is crucial to inspect rectifiers to ensure they are operating as intended. According to 49 CFR (b) and 49 CFR (c), Each cathodic protection rectifier or other impressed current power source must be inspected six times each calendar year, but with intervals not exceeding months, to ensure that it is operating. Knowledge: Explain what is required prior to performing this task. Prior to performing this task, you will need to have the pipeline operator-approved procedures as well as the appropriate equipment and materials. The procedures will outline requirements for performing this task that are specific to the pipeline operator. Operators may also have specific requirements regarding the type of equipment that can be used to perform this task. Therefore, it s important to follow the specific requirements of the procedures and only use operatorapproved equipment. Doing so can ensure the task is performed correctly and according to the pipeline operator s standards. Page 2 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

3 Skill: Perform visual inspection of rectifier. In this objective, we ll discuss performing a visual inspection of the rectifier to check if there are any potential issues. Visual inspection is often the first sign that something could be wrong or potentially hazardous. Remember to always follow your pipeline operator-approved procedures while performing this task. You should check that the rectifier is properly mounted and level. Ensure that all connecting bolts are tight and secure. Check to make sure there isn t a rectifier support failure or that the support pole is damaged. Look for evidence of tampering such as a broken lock or scrapes along the edges where someone may have tried to pry the case open. Check the external wiring connections to ensure they are proper and tight. Make sure the AC input wiring isn t loose and that a proper ground connection is in place. Look for burn marks on the rectifier that may indicate damage from lightning or fire. You may also notice melted or charred marks. Inspect for insects, pests, varmints, or other creatures that may have taken up home or shelter in the rectifier cabinet. These can block airflow and also pose a potential hazard to you. Check that proper security is in place. Rectifiers should be locked in accordance with the pipeline operator approved procedures to protect against tampering or shock. Ensure that high voltage signage and markings are visible due to the high voltage present in rectifiers. If you notice something that fails visual inspection, consult your pipeline operator-approved procedures for information on the proper corrective measures. Knowledge: Explain techniques that may be used to determine if the rectifier case is energized with AC and DC voltage. Due to the electrical hazards present in rectifiers, it s important to ensure that the case isn t energized prior to performing work or testing the rectifier. If the case is energized, this indicates there is a problem. In this objective, we ll look at techniques that may be used to determine if the rectifier case is energized with AC or DC voltage. Remember to always follow your pipeline operator-approved procedures while performing this task. When using electronic testing devices, it s important to verify calibration and ensure that your device is in good working order. Checking the case with a faulty or non-calibrated device could lead to a false reading and potential electrical shock. Always follow the manufacturer s instructions for the device you are using. To check that the case is not hot, you can take an AC voltage-to-ground measurement with a portable meter (e.g. voltmeter or multimeter). For example, with a multimeter set to millivolts, connect the black lead to the ground and the red lead to the rectifier case and take a reading. Refer to your procedures to determine what voltage is appropriate. Page 3 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

4 There are various voltage testers that will alert you with flashing, beeping, and/or a general reading in the presence of an energized or hot connection. Some models have leads that you will need to connect in the same way as a voltmeter. Some of the newer models are contactless and allow you to hold the tip of the detector up to the case and press a button. If the tester flashes, beeps, or otherwise indicates voltage, exercise caution as this would indicate the cabinet is hot. Caution: Placing the back of your hand up to the rectifier case to determine if it is energized is usually not recommended. Grabbing an energized case with your fingers could cause your hand to clench from the current and not let go. Skill: Describe and demonstrate steps for testing/inspecting rectifier for proper operation. The task of inspecting a cathodic protection rectifier can be broken into three main steps. Verify the calibration of the meter or data logger. Check the rectifier cabinet for electrical shorts. Verify and interpret output of DC voltage and DC current using an appropriate instrument. Verify calibration of meter/data logger. To maintain the proper operation of the cathodic protection, the system s current and voltage need to be checked regularly. There are many different types of equipment that are used to take the current and voltage readings from the rectifier. The two most commonly used are: Digital voltmeters Data loggers Digital voltmeters are the most commonly used meters in comparison to data loggers. Digital voltmeters can handle AC voltage, DC voltage, and resistance measurements as well as many other functions. Data loggers are also used to take voltage and current readings, but unlike digital voltmeters, data loggers can gather GPS coordinates and store the collected data. All precision equipment needs to be calibrated and certified. For optimum accuracy, only use meters that have been calibrated and certified by the manufacturer. Meters should be recalibrated annually if damage occurs or if the meter reliability is in question. All meters should have a calibration sticker attached to them or documentation available stating the calibration specifics. Check rectifier cabinet for electrical shorts. Note: Any task that involves electricity is extremely dangerous and has a unique set of hazards associated with it. Therefore, you will need to utilize recognized industry safety best practices, proper personal protective equipment (PPE), and pipeline operator s policies and procedures to help ensure your safety. Before opening the rectifier cabinet, it needs to be checked for electrical shorts. Page 4 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

5 When checking for voltage with a digital voltmeter, attach the black probe to the ground rod and connect the red probe to various locations on the enclosure that will be touched by hand. Read the meter for any voltage potentials. Some other ways to ensure there are no potential shorting issues with the rectifier include the following: Looking - Look for signs of hot spots on the rectifier and loose wires. Smelling - Stand downwind of the rectifier and try to detect any odors of burned insulation or other materials. Selenium and other semiconductors smell like rotten eggs when burned. Listening - Listen around the rectifier for sounds of arcing, static, or frying. If a short is suspected, determine the power source. If the power source is a distribution transformer bank, contact the appropriate personnel to shut off the power. Contractors not authorized and/or not qualified to work on distribution transformers should notify the pipeline operator representative immediately. Once you have verified that the rectifier does not have any electrical shorts, you can open the rectifier enclosure and inspect the inside for any abnormal conditions. Some of the items to look for include: Signs of overheating or arcing Damaged components and wires Blown transient devices Loose ground wires Verify/Interpret output DC voltage and DC output current. The DC output voltage should be evaluated to determine if the rectifier is running properly and efficiently. Utilize the following steps when measuring the DC output voltage of the rectifier: Measure the DC output voltage across each anode s positive terminal and the structure s negative terminal. Verify the measured voltage is approximately equal to the voltage indicated on the rectifier voltmeter. Just as the DC output voltage should be evaluated, so should the DC output current. To measure the DC output current, the meter is connected across a known precision resistor called a shunt. In order to verify the current reading indicated by the rectifier ammeter, a digital voltmeter is used to measure the millivolt potential across the shunt. The reading is then multiplied by the shunt factor to calculate the DC output current of the rectifier. The shunt factor is calculated by dividing the amp rating of the shunt by the millivolt rating of the shunt. To calculate the shunt factor, use the following formula: amp rating/millivolt rating = shunt factor. For example, if you have an amp rating of 50 and a millivolt rating of 50, your shunt factor will be 1. The DC output current is calculated by multiplying the shunt factor and the millivolt reading from the digital voltmeter. Calculate the DC output current by using this formula: shunt factor x digital voltmeter reading (millivolt reading) = DC output current (amps). For example, if you have a shunt factor rating of.5 and a digital voltmeter reading of 30 millivolt, your DC output current will be 15 amps. Page 5 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

6 Another common tool used to measure the DC output current is the clamp meter. The clamp meter is connected around a DC output current cable within the rectifier to gather accurate readings. The final step of the inspection is to compare the rectifier output readings with readings from previous inspections. If there are significant changes in the rectifier DC output current readings, contact a qualified specialist to report a possible change in the system and/or the system environment. Contractors should contact the pipeline operator representative to report a possible change in the system and/or system environment. Abnormal Operating Conditions (AOCs) Candidates are required to possess the ability to RECOGNIZE and REACT to the listed AOCs for each task. Be prepared to answer questions concerning additional AOCs that may be relevant. Evaluators may ask questions about AOCs throughout the evaluation. An AOC is defined in 49 CFR and as: A condition identified by the pipeline operator that may indicate a malfunction of a component or deviation from normal operations that may: Indicate a condition exceeding design limits; or Result in a hazard(s) to persons, property, or the environment. Recognize: Unintentional releases, vapors, or hazardous atmosphere could be signs that an abnormal operating condition has occurred. Examples could include, but are not limited to: Blowing gas Puddles Dead vegetation React/Respond: Proper reactions and/or responses to take in the event of an unintentional release, vapors, or hazardous atmosphere include the following: Eliminate potential ignition sources. Move to a safe location. Notify emergency response personnel, as appropriate. Limit access to the location, as necessary. Follow appropriate procedures for notification, documentation, and remedial action. Recognize: Material defects, anomalies, or physical damage of pipe or a component that have impaired or are likely to impair the serviceability of the pipeline are abnormal operating conditions. Examples include, but are not limited to: Shorted rectifier case Vandalism Page 6 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

7 React/Respond: Proper reactions/responses to take in the event of material defects, anomalies, or physical damage of pipe or a component that have impaired or are likely to impair the serviceability of the pipeline include the following: Determine the extent, cause, and potential hazard(s) of the defect, anomaly, and/or damage. Mark the location so it may be easily located, as appropriate. Follow appropriate procedures for notification, documentation, and remedial action. Recognize: Failure or malfunction of pipeline component(s) is an abnormal operating condition. Examples could include, but are not limited to: Rectifier shows signs of being hit by lightning Rectifier support failure or support pole damaged Damaged rectifier internals Engine generator down Solar panel damage React/Respond: Proper reactions/responses to take in the event of a failure or malfunction of pipeline component(s) include the following: Determine the extent, cause, and potential hazard(s) of the failure and/or malfunction. Follow appropriate procedures for notification, documentation, and remedial action. Page 7 of 7 Copyright 2019 Veriforce, LLC. All rights reserved. Rev. # 6 03/06/2019

Electrical TP-18 February 2017 ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING

Electrical TP-18 February 2017 ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING ELECTRICAL TECHNICAL PAPER 18 FREQUENTLY ASKED QUESTIONS ABOUT CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING CATHODIC PROTECTION SYSTEM EQUIPMENT TESTING Question No. 1 What should I (the contractor) check

More information

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A.

TAG5000 WIRELESS PHASER. Instruction Manual HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS U.S.A. TAG5000 WIRELESS PHASER Instruction Manual TM HD ELECTRIC COMPANY 1475 LAKESIDE DRIVE WAUKEGAN, ILLINOIS 60085 U.S.A. PHONE 847.473.4980 FAX 847.473.4981 website: www.hdelectriccompany.com DESCRIPTION

More information

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com # # AAC Clamp Meter. Instruction Manual 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com #61-732 #61-736 400 AAC Clamp Meter Instruction Manual AC HOLD APO DC KMΩ mva WARNING Read First: Safety Information Understand

More information

312, 316, 318. Clamp Meter. Users Manual

312, 316, 318. Clamp Meter. Users Manual 312, 316, 318 Clamp Meter Users Manual PN 1989445 July 2002 Rev.2, 2/06 2002, 2006 Fluke Corporation. All rights reserved. Printed in China. All product names are trademarks of their respective companies.

More information

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S

PHASE ROTATION METER. Operating and Instruction Manual. a n d A C C E S S O R I E S PHASE ROTATION METER a n d A C C E S S O R I E S Operating and Instruction Manual HD ELECTRIC COMPANY 1 4 7 5 L A K E S I D E D R I V E WA U K E G A N, I L L I N O I S 6 0 0 8 5 U. S. A. PHONE 847.473.4980

More information

VARIABLE TRANSFORMER TYPE CATHODIC PROTECTION RECTIFIER

VARIABLE TRANSFORMER TYPE CATHODIC PROTECTION RECTIFIER VARIABLE TRANSFORMER TYPE CATHODIC PROTECTION RECTIFIER INSTALLATION, OPERATION, & MAINTENANCE MANUAL 15360 116 Avenue, Edmonton, Alberta, Canada T5M 3Z6 Phone: (780) 447-1114 Fax: (780) 454-0004 Website:

More information

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009

34134A AC/DC DMM Current Probe. User s Guide. Publication number April 2009 User s Guide Publication number 34134-90001 April 2009 For Safety information, Warranties, Regulatory information, and publishing information, see the pages at the back of this book. Copyright Agilent

More information

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL Table of Contents TITLE PAGE 1. GENERAL INSTRUCTIONS 1 1.1 Precaution safety measures 1 1.1.1 Preliminary 1 1.1.2 During use 2 1.1.3 Symbols

More information

Operation Manual for CTL-3000

Operation Manual for CTL-3000 CATH-TECH CORROSION CONTROL EQUIPMENT Operation Manual for CTL-3000 DCVG Survey Instrument Cathodic Technology Ltd. 15-1 Marconi Court Bolton, Ontario Canada L7E 1E2 Ph: ++1-905-857-1050 ctl@cath-tech.com

More information

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version

Mini Receiver. Off Peak System Control. Operation & Installation Guide for Power Line Carrier WARRANTY. (Applicable to Software Version MR9 WARRANTY Steffes Corporation ( Steffes ) warrants that the Steffes Power Line Carrier Mini Receiver is free from defects in materials and workmanship under normal use and service. Steffes obligation

More information

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual.

The table below lists the symbols used on the Clamp and/or in this manual. Important Information. See manual. i310s AC/DC Current Clamp Instruction Sheet Introduction The i310s Current Clamp ( Clamp ) has been designed for use with oscilloscopes and digital multimeters for accurate nonintrusive measurement of

More information

Dynatel 2250E/2273E Advanced Cable and Fault Locator

Dynatel 2250E/2273E Advanced Cable and Fault Locator Dynatel 2250E/2273E Advanced Cable and Fault Locator Operators Manual September 1999 78-8097-6500-7-B TABLE OF CONTENTS Introduction... 2 Installing or Replacing the Batteries... 2 Initial Receiver Configuration...

More information

30 Bending Brake. Model Assembly and Operating Instructions. Distributed exclusively by Harbor Freight Tools.

30 Bending Brake. Model Assembly and Operating Instructions. Distributed exclusively by Harbor Freight Tools. 30 Bending Brake Model 41311 Assembly and Operating Instructions Distributed exclusively by Harbor Freight Tools. 3491 Mission Oaks Blvd., Camarillo, CA 93011 Copyright 1999 by Harbor Freight Tools. All

More information

PRODUCT SAFETY SOLUTIONS MODEL HWI-01. Model HWI-01 Serial Number:

PRODUCT SAFETY SOLUTIONS MODEL HWI-01. Model HWI-01 Serial Number: USER S MANUAL HOT WIRE IGNITION TESTER MODEL HWI-01 Model HWI-01 Serial Number: 1 HWI-01 HOT WIRE IGNITION TESTER IMPORTANT INSTRUCTIONS - - SAVE THESE INSTRUCTIONS Introduction Thank you for choosing

More information

4. CONNECTIONS. Make sure all connections to and in your Universal Rectifier are tight.

4. CONNECTIONS. Make sure all connections to and in your Universal Rectifier are tight. OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS I. WARNING Operating personnel should observe the following before attempting to operate or adjust the

More information

Electrical Measurement Safety. Sponsored By:

Electrical Measurement Safety. Sponsored By: Electrical Measurement Safety Sponsored By: About the Viewer Panel Slides: Go to the Links tab at the top and click on the link to download the PDF of the slides If you re watching the archive version,

More information

600A Clamp Meters w/tightsight Display

600A Clamp Meters w/tightsight Display V 750V #61-764 #61-766 #61-768 600A Clamp Meters w/tightsight Display Instruction Manual 99 Washington Street Melrose, MA 02176 Fax 781-665-0780 TestEquipmentDepot.com CAT.IV 600V CAT.III 1000V 600A 61-766

More information

Leaf Wetness Smart Sensor (Part # S-LWA-M003)

Leaf Wetness Smart Sensor (Part # S-LWA-M003) (Part # S-LWA-M003) The Leaf Wetness smart sensor is designed to work with the HOBO Weather Station or Micro Station Loggers. The smart sensor has a plug-in modular connector that allows it to be added

More information

netzerotools.com 374/375/376 Users Manual Clamp Meter

netzerotools.com 374/375/376 Users Manual Clamp Meter 374/375/376 Clamp Meter Users Manual Fluke 376 True RMS AC DC Clamp Meter Fluke 374 True RMS AC / DC Clamp Meter Fluke 373 True RMS AC Clamp Meter Fluke 375 True RMS AC / DC Clamp Meter LIMITED WARRANTY

More information

Table of Contents Title Page

Table of Contents Title Page Table of Contents Title Page Overview Unpacking Inspection Safety Information Rules For Safe Operation International Electrical Symbols The Meter Structure Rotary Switch Functional Buttons Display Symbols

More information

TA MHz oscilloscope probe TA MHz oscilloscope probe

TA MHz oscilloscope probe TA MHz oscilloscope probe TA375 100 MHz oscilloscope probe TA386 200 MHz oscilloscope probe User's Guide X1 X10 TA386 X1/X10 Max. 600 Vp Introduction This passive high-impedance oscilloscope probe is suitable for most oscilloscopes

More information

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN

COOPER POWER SERIES. External application of a motor start capacitor on a single-phase voltage regulator. Voltage Regulators MN225063EN Voltage Regulators MN225063EN Effective March 2017 Supersedes January 2012 (S225-60-10) COOPER POWER External application of a motor start capacitor on a single-phase voltage regulator SERIES DISCLAIMER

More information

CATHODIC PROTECTION FIELD TESTING

CATHODIC PROTECTION FIELD TESTING AIR FORCE HANDBOOK 32-1290(I) MIL-HDBK-1136/1 (SUPERSEDES NAVFAC MO-306.1) 1 February 1999 CATHODIC PROTECTION FIELD TESTING DEPARTMENTS OF THE AIR FORCE AND NAVY AIR FORCE HANDBOOK 32-1290(I) MIL-HDBK-1136/1

More information

C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER

C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER INSTALLATION, OPERATION, & MAINTENANCE MANUAL SINGLE PHASE INPUT MODEL: CC CURRENT CONTROL CV VOLTAGE CONTROL 15360 116 Avenue, Edmonton, Alberta,

More information

Current Probe Fixture Instruction Manual

Current Probe Fixture Instruction Manual Current Probe Fixture Instruction Manual 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 TEST METHODS 5 SAFETY 7 FIGURES 8 FORMULAS 10 MAINTENANCE 11 WARRANTY 12 2 INTRODUCTION figure 1 Mechanical

More information

ARBE-III Instruction Manual

ARBE-III Instruction Manual ARBE-III Instruction Manual Introduction ARBE-III is a solid state, fully regulated, universal power supply designed specifically for use of pre 1930 s battery operated radios. Three electronically isolated

More information

Broadband Current Probe Series Operation Manual

Broadband Current Probe Series Operation Manual Broadband Current Probe Series Operation Manual 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 OPERATING INSTRUCTIONS 5 FORMULAS 6 MAINTENANCE 7 WARRANTY 8 2 INTRODUCTION CURRENT PROBE SPECIFICATIONS

More information

User Manual Digital Multimeter

User Manual Digital Multimeter User Manual Digital Multimeter model no.: MSR-R500 Questions or Concerns? support@etekcity.com visit etekcity.com for more products Safe and Proper Usage Thank you for purchasing the Etekcity MSR-R500

More information

2015 RIGOL TECHNOLOGIES, INC.

2015 RIGOL TECHNOLOGIES, INC. Service Guide DG000 Series Dual-channel Function/Arbitrary Waveform Generator Oct. 205 TECHNOLOGIES, INC. Guaranty and Declaration Copyright 203 TECHNOLOGIES, INC. All Rights Reserved. Trademark Information

More information

Soil Moisture Smart Sensors (S-SMx-M005)

Soil Moisture Smart Sensors (S-SMx-M005) s (S-SMx-M005) The Soil Moisture smart sensor is used for measuring soil water content and is designed to work with smart sensor-compatible HOBO data loggers. It combines the innovative ECH 2 O Dielectric

More information

Model : OPERATING MANUAL Table of Contents (1)

Model : OPERATING MANUAL Table of Contents (1) Table of Contents (1) Title Overview Unpacking Inspection Safety Information Rules For Safe Operation International Electrical Symbols The Meter Structure Functional Buttons Measurement Operation A. DC

More information

80i-600A AC Current Probe

80i-600A AC Current Probe x Instruction Sheet 80i-600A AC Current Probe INTRODUCTION The Model 80i-600A is a clamp-on ac current probe designed to extend the current measuring capability of an ac current meter to 600 amperes. A

More information

DIGITAL MULTIMETER 405

DIGITAL MULTIMETER 405 DIGITAL MULTIMETER 405 TAKE MEASUREMENT CAREFULLY AND YOU LL SPARE YOUR METER AND YOURSELF, SOME PAIN Nearly every electrical engineer has a hand held digital multimeter (DMM). We sometimes take them for

More information

MS2030 CAT III 600 V A V AUTO RS232

MS2030 CAT III 600 V A V AUTO RS232 MS2030 AC Digital Clamp Meter User s Manual CAT III 600 V AUTO RS232 A V CONTENTS 1.Introduction...1 2.Safety Information...1 2.1 Precautions...1 2.2 Safety Symbols...3 3. Description...4 3.1 Front Panel...4

More information

P5100A & P5150 High Voltage Probes Performance Verification and Adjustments

P5100A & P5150 High Voltage Probes Performance Verification and Adjustments x P5100A & P5150 High Voltage Probes Performance Verification and Adjustments ZZZ Technical Reference *P077053001* 077-0530-01 xx P5100A & P5150 High Voltage Probes Performance Verification and Adjustments

More information

UT207A/208A/209A Operating Manual. Table of Contents

UT207A/208A/209A Operating Manual. Table of Contents Table of Contents Title Overview Unpacking Inspection Safety Information Rules for Safe Operation International Electrical Symbols The Meter Structure Display Symbols Functional Buttons The Effectiveness

More information

80i-110s. AC/DC Current Probe Instructions. Introduction

80i-110s. AC/DC Current Probe Instructions. Introduction 80i-110s.book Page 1 Monday, December 5, 2016 12:12 PM 80i-110s AC/DC Current Probe Instructions Introduction The Fluke 80i-110s (the Probe or Product) is a clamp-on AC/DC Current Probe that reproduces

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Digital Voltage Detector 0-999kV Operating Instructions VD1000PTM

Digital Voltage Detector 0-999kV Operating Instructions VD1000PTM Digital Voltage Detector 0-999kV Operating Instructions VD1000PTM CONTENTS Limitation of Warranty and Liability 2 Product Safety Information 3 Design and Function Battery Replacement 4 Voltage Detection

More information

INSTRUCTION MANUAL INF Fax: (503)

INSTRUCTION MANUAL INF Fax: (503) INSTRUCTION MANUAL INF151 1-800-547-5740 Fax: (503) 643-6322 www.ueiautomotive.com email: info@ueitest.com Introduction Congratulations on your purchase of the INF151 infrared thermometer. Like all UEi

More information

374/375/376 Clamp Meter

374/375/376 Clamp Meter 374/375/376 Clamp Meter Users Manual PN 3608883 July 2010 2010 Fluke Corporation. All rights reserved. Printed in China. Specifications are subject to change without notice. All product names are trademarks

More information

80i-110s AC/DC CURRENT PROBE

80i-110s AC/DC CURRENT PROBE Table of Contents 3 80i-110s AC/DC CURRENT PROBE Users Manual November 1996 1994, 1996 Fluke Corporation. All rights reserved. All product names are trademarks of their respective companies. Printed in

More information

DIGITAL CLAMPMETER MODEL

DIGITAL CLAMPMETER MODEL DIGITAL CLAMPMETER MODEL - 2718 TAKE MEASUREMENT CAREFULLY AND YOU LL SPARE YOUR METER AND YOURSELF, SOME PAIN Nearly every electrical engineer has a hand held digital clamp meter (Tongtester). We sometimes

More information

Electrical Multimeter

Electrical Multimeter 113 Electrical Multimeter Instruction Sheet Safety Information A Warning statement identifies hazardous conditions and actions that could cause bodily harm or death. A Caution statement identifies conditions

More information

Meters and Test Equipment

Meters and Test Equipment Installation Knowledge and Techniques Meters and Test Equipment OBJECTIVES Meters and Test Equipment DMM s and VOM s Describe the difference between a DMM and a VOM. Describe the methods for measuring

More information

Model UT20B: OPERATING MANUAL Table of Contents (1)

Model UT20B: OPERATING MANUAL Table of Contents (1) Table of Contents (1) Title Overview Unpacking Inspection Safety Information Rules For Safe Operation International Electrical Symbols Rotary Switch Display Symbols Measurement Operation A. AC Voltage

More information

VT1586A Rack Mount Terminal Panel Installation and User s Manual

VT1586A Rack Mount Terminal Panel Installation and User s Manual VT1586A Rack Mount Terminal Panel Installation and User s Manual Manual Part Number: 82-0095-000 Rev. June 16, 2003 Printed in U.S.A. Certification VXI Technology, Inc. certifies that this product met

More information

UM TEA1721 universal mains white goods flyback SMPS demo board. Document information

UM TEA1721 universal mains white goods flyback SMPS demo board. Document information TEA1721 universal mains white goods flyback SMPS demo board Rev. 1 27 January 2012 User manual Document information Info Keywords Abstract Content TEA1721XT, flyback, non-isolated, dual output, white goods,

More information

C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER

C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER C.P. SENTINEL AUTOMATIC TYPE CATHODIC PROTECTION RECTIFIER INSTALLATION, OPERATION, & MAINTENANCE MANUAL REV. 3.0 NOVEMBER,2004 SINGLE PHASE INPUT MODEL: CP ON POTENTIAL CONTROL CI IR FREE POTENTIAL CONTROL

More information

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit. 1. This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse

More information

AC68C. Users Manual. True RMS AC/DC Clamp Multimeter. PN July Amprobe Test Tools. All rights reserved.

AC68C. Users Manual. True RMS AC/DC Clamp Multimeter. PN July Amprobe Test Tools. All rights reserved. AC68C True RMS AC/DC Clamp Multimeter Users Manual PN 2729051 July 2006 2006 Amprobe Test Tools. All rights reserved. Printed in Taiwan For detailed specifications and ordering info go to www.testequipmentdepot.com

More information

Grid Radar Installation Manual

Grid Radar Installation Manual Grid Radar Installation Manual MODELS GN-RD-001 120V Single Phase / Wye, 240V Single Phase, with Neutral GN-RD-002 277V 3-Phase Wye, with Neutral GN-RD-003 480V 3-Phase Delta, no Neutral GN-RD-004 208V

More information

14 Piece Slide Hammer and Puller Set

14 Piece Slide Hammer and Puller Set Owner s Manual & Safety Instructions Save This This Manual Keep Keep this this manual manual for for the the safety safety warnings warnings and and precautions, assembly, assembly, operating, inspection,

More information

Oberebenestrasse Bremgarten Switzerland Tel Fax

Oberebenestrasse Bremgarten Switzerland Tel Fax Oberebenestrasse 11 5620 Bremgarten Switzerland Tel. +41 56 640 06 70 Fax. +41 56 640 06 74 Single Phase - Battery Operated Automatic Transformer Turns Ratiometer Test System Model: TR-1 Model: TR-1P Instruction

More information

Nashville Etagere/Bookcase

Nashville Etagere/Bookcase UNIT WEIGHT: 0 LB -WIS WEIGHT CAPACITY PER SHELF/TIER: FLOATING SHELVES: 5 lb STANDARD SHELVES: 5 lb Nashville Etagere/Bookcase .00 4.00 0.50 0.50.00 8.00.00.00.00.00 7.00.00.00 4.50.00 7.00.00.00 DISCLAIMER:

More information

A1800 ALPHA meter special installation instructions DANGER

A1800 ALPHA meter special installation instructions DANGER March 010 I4-405A General A1800 APHA meter special installation instructions 3-element meters used for 3-wire delta service applications This leaflet contains special installation instructions for 3-wire

More information

Model 228 Current Leakage Tester INSTRUCTION MANUAL

Model 228 Current Leakage Tester INSTRUCTION MANUAL Model 228 Current Leakage Tester INSTRUCTION MANUAL 1 About this Manual To the best of our knowledge and at the time written, the information contained in this document is technically correct and the procedures

More information

374/375/376 Clamp Meter

374/375/376 Clamp Meter 374/375/376 Clamp Meter Users Manual PN 3608883 July 2010 2010 Fluke Corporation. All rights reserved. Printed in China. Specifications are subject to change without notice. All product names are trademarks

More information

Wilcom MODEL T136BGMZW CIRCUIT TEST SET. Operating Instructions

Wilcom MODEL T136BGMZW CIRCUIT TEST SET. Operating Instructions Wilcom MODEL T136BGMZW CIRCUIT TEST SET Operating Instructions T136BGM Current Test Set Operating Instructions 811-233-010 February 2007 Copyright (c) 2007 Wilcom All Rights reserved Wilcom reserves the

More information

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL GENERAL INSTRUCTIONS This instrument complies with IEC 1010-1 (61010-1@IEC: 2001), CAT. II 1000V and CAT. III 600V overvoltage standards. See Specifications.

More information

Test Procedure for the CCR120PS3AGEVB Evaluation Board CAUTION: VERY HIGH VOLTAGE MAY CAUSE SEVERE INJURY OR DEATH

Test Procedure for the CCR120PS3AGEVB Evaluation Board CAUTION: VERY HIGH VOLTAGE MAY CAUSE SEVERE INJURY OR DEATH Test Procedure for the CCR120PS3AGEVB Evaluation Board CAUTION: VERY HIGH VOLTAGE MAY CAUSE SEVERE INJURY OR DEATH 1 Devices under test - Driver board CCR120PS3AGEVB - LED board CCR120PS3BGEVB 1/29/2014

More information

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL- KM 2782 / 2782-T

DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL- KM 2782 / 2782-T DIGITAL DUAL DISPLAY AC/DC CLAMP METER MODEL- KM 2782 / 2782-T KM 2782 V 400A POWER G 17,Bharat Industrial Estate, T. J. Road, Sewree (W), Mumbai - 400 015. INDIA. Sales Direct : (022) 24156638 Tel. :

More information

POWER TRACE TM TASCO, INC.

POWER TRACE TM TASCO, INC. POWER TRACE TM Instruction Manual PTL610 TASCO, INC. HOW YOUR POWER TRACE TM OPERATES The Power Trace TM is composed of two primary components: the Receiver and the Transmitter. When the Transmitter is

More information

Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM. Patent No. 6,275,022

Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM. Patent No. 6,275,022 Analog Voltage Detector 1-450kV Operating Instructions VDAO450TM Patent No. 6,275,022 CONTENTS Limitation of Warranty and Liability 2 Product Safety Information 3 Design and Function 4 Operating Procedure

More information

Independent Technology Service Inc Independence Ave. Chatsworth, California Toll Free:

Independent Technology Service Inc Independence Ave. Chatsworth, California Toll Free: Independent Technology Service Inc. 9182 Independence Ave. Chatsworth, California 91311 www.itscnc.com Toll Free: 1.800.342.3475 NEW Brush Amplifiers For Fadal Machines AMP-0006N-ITS AMP-0021N-ITS NEW

More information

WARNING: Do not work around outlets while the power is on. Do not stick fingers or tools into an electrical box while the power is on.

WARNING: Do not work around outlets while the power is on. Do not stick fingers or tools into an electrical box while the power is on. Instructions for SnapRays Guidelights WARNING Failure to turn OFF electrical power prior to installation of the Guidelight can result in electrical shock, fires, and/or death. www.snappower.com CAUTION:

More information

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER

OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL M-2625 AUTO RANGING DIGITAL MULTIMETER with Temperature Probe Copyright 2007 Elenco Electronics, Inc. Contents 1. Safety Information 3,4 2. Safety Symbols 5 3. Front Plate

More information

EM420A/420B DIGITAL MULTIMETER OWNERS MANUAL Read this owners manual thoroughly before use

EM420A/420B DIGITAL MULTIMETER OWNERS MANUAL Read this owners manual thoroughly before use http://www.all-sun.com EM420A/420B DIGITAL MULTIMETER OWNERS MANUAL V Read this owners manual thoroughly before use WARRANTY This instrument is warranted to be free from defects in material and workmanship

More information

Operator s Manual. PP016 Passive Probe

Operator s Manual. PP016 Passive Probe Operator s Manual PP016 Passive Probe 2017 Teledyne LeCroy, Inc. All rights reserved. Unauthorized duplication of Teledyne LeCroy documentation materials is strictly prohibited. Customers are permitted

More information

T-L 810-T TRANSMITTER GUIDE

T-L 810-T TRANSMITTER GUIDE T-L 810-T TRANSMITTER GUIDE Pg. 2 HOW IT WORKS 2 TEST BEAC 3 MOUNTING 3 CODE SWITCH SETTINGS 3 BATTERY BACKUP 3 TRANSMITTER FUNCTI SWITCH SETTINGS 3 INDICATOR LEDS 4 T-L ELECTRIC PANEL 5 T-L PPC III ENGINE

More information

Broadband Current Probe Series Operation Manual

Broadband Current Probe Series Operation Manual Broadband Current Probe Series Operation Manual 1 TABLE OF CONTENTS WARRANTY 3 INTRODUCTION 4 GENERAL INFORMATION 5 OPERATING INSTRUCTIONS 6 FORMULAS 7 MAINTENANCE 8 2 WARRANTY INFORMATION A.H. Systems

More information

323/324/325 Clamp Meter

323/324/325 Clamp Meter 323/324/325 Clamp Meter Users Manual May 2012 Rev.1, 06/15 2012-2015 Fluke Corporation. All rights reserved. Specifications are subject to change without notice. All product names are trademarks of their

More information

Dawson DDM190. Digital Multimeter User s Manual

Dawson DDM190. Digital Multimeter User s Manual Dawson DDM190 Digital Multimeter User s Manual TABLE OF CONTENTS LIMITED WARRANTY AND LIMITATION OF LIABILITY... 3 Out of the Box... 3 Accessories.. Error! Bookmark not defined. Safety Information... 7

More information

10 Ton Pull Back Ram

10 Ton Pull Back Ram 10 Ton Pull Back Ram Model 97207 Set up And Operating Instructions Diagrams within this manual may not be drawn proportionally. Due to continuing improvements, actual product may differ slightly from the

More information

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual

NEO CAR AUDIO. Neo AUXiN AUX INPUT INTERFACE. Instruction Manual NEO CAR AUDIO Neo AUXiN AUX INPUT INTERFACE Instruction Manual IMPORTANT NOTE Neo AUXiN Dip switch positions MUST be set BEFORE any other step is taken. Otherwise, the kit will not operate properly. See

More information

P5100A & P5150 High Voltage Probes Performance Verification and Adjustments

P5100A & P5150 High Voltage Probes Performance Verification and Adjustments x P5100A & P5150 High Voltage Probes Performance Verification and Adjustments ZZZ Technical Reference *P077053002* 077-0530-02 xx P5100A & P5150 High Voltage Probes Performance Verification and Adjustments

More information

Installation Instructions

Installation Instructions Articulating Hex Monitor Mount Stand Installation Instructions UNPACKING Carefully open the carton, remove contents, and place them on a protected surface to avoid damage. Check the parts and the Supplied

More information

50 Ω Dummy Load for Transmitter testing and experiments

50 Ω Dummy Load for Transmitter testing and experiments 50 Ω Dummy Load for Transmitter testing and experiments Many thanks for purchasing this dummy load, it has been designed to provide constant 50 Ω impedance to a radio transmitter to allow off air tests

More information

User Manual Digital Multimeter. model no.: MSR-U1000

User Manual Digital Multimeter. model no.: MSR-U1000 User Manual Digital Multimeter model no.: MSR-U1000 This Operating Manual covers information on safety and cautions. Please read the relevant information carefully and observe all the Warnings and Notes

More information

MS6231 DIGITAL ENGINE ANALYZER OPERATOR S MANUAL CONTENTS CONTENTS

MS6231 DIGITAL ENGINE ANALYZER OPERATOR S MANUAL CONTENTS CONTENTS CONTENTS MS6231 DIGITAL ENGINE ANALYZER OPERATOR S MANUAL CONTENTS 1. SAFETY INFORMATION 1 1.1 PRELIMINARY 2 1.2 DURING USE 3 1.3 SYMBOLS 5 1.4 MAINTENANCE 6 2. DESCRIPTION 8 2.1 NAMES OF COMPONENTS 9

More information

OWNER'S MANUAL LS4000W, LS4000B, LS4000S LS4001W, LS4001B, LS4001S. AM/FM Stereo Receiver and Compact Disc Player

OWNER'S MANUAL LS4000W, LS4000B, LS4000S LS4001W, LS4001B, LS4001S. AM/FM Stereo Receiver and Compact Disc Player OWNER'S MANUAL LS4000W, LS4000B, LS4000S LS4001W, LS4001B, LS4001S AM/FM Stereo Receiver and Compact Disc Player Designed for In-Wall Installation of All Recreational Vehicles, Motor Homes and Mobile Housings

More information

AM-510 Commercial / Residential Multimeter. AM-510-EUR Digital Multimeter. Users Manual

AM-510 Commercial / Residential Multimeter. AM-510-EUR Digital Multimeter. Users Manual AM-510 Commercial / Residential Multimeter AM-510-EUR Digital Multimeter Users Manual AM-510 Commercial / Residential Multimeter AM-510-EUR Digital Multimeter English Users Manual Limited Warranty and

More information

AT Advanced Wire Tracer. Users Manual

AT Advanced Wire Tracer. Users Manual AT-1000 Advanced Wire Tracer Users Manual AT-1000 Advanced Wire Tracer English Users Manual AT1000_Rev001 2008 Amprobe Test Tools. All rights reserved. Limited Warranty and Limitation of Liability Your

More information

Wilcom MODEL T136BSBZW CIRCUIT TEST SET. Operating Instructions

Wilcom MODEL T136BSBZW CIRCUIT TEST SET. Operating Instructions Wilcom MODEL T136BSBZW CIRCUIT TEST SET Operating Instructions T136BSB Current Test Set Operating Instructions 811-230-007 February 2007 Copyright (c) 2007 Wilcom All Rights reserved Wilcom reserves the

More information

AN Extended Range Proximity with SMSC RightTouch Capacitive Sensors

AN Extended Range Proximity with SMSC RightTouch Capacitive Sensors AN 24.19 Extended Range Proximity with SMSC RightTouch Capacitive Sensors 1 Overview 2 Audience 3 References SMSC s RightTouch 1 capacitive sensor family provides exceptional touch interfaces, and now

More information

DCM730. Digital Clamp Meter User s Manual

DCM730. Digital Clamp Meter User s Manual DCM730 Digital Clamp Meter User s Manual Table of Contents LIMITED WARRANTY AND LIMITATION OF LIABILITY...1 Out of the Box...1 Safety Information...2 INTRODUCTION...4 Components and Buttons...6 Names of

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

Planar PIN diode in a SOD523 ultra small plastic SMD package.

Planar PIN diode in a SOD523 ultra small plastic SMD package. Rev. 10 12 May 2015 Product data sheet 1. Product profile 1.1 General description Planar PIN diode in a SOD523 ultra small plastic SMD package. 1.2 Features and benefits High voltage, current controlled

More information

OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS

OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS I. WARNING Operating personnel should observe the following before attempting to operate or adjust the

More information

BB Product profile. 2. Pinning information. 3. Ordering information. FM variable capacitance double diode. 1.1 General description

BB Product profile. 2. Pinning information. 3. Ordering information. FM variable capacitance double diode. 1.1 General description SOT23 Rev. 3 7 September 2011 Product data sheet 1. Product profile 1.1 General description The is a variable capacitance double diode with a common cathode, fabricated in silicon planar technology, and

More information

Planishing hammer stand For use with SKU Planishing hammer

Planishing hammer stand For use with SKU Planishing hammer Planishing hammer stand For use with SKU 94847 Planishing hammer Model 96300 Assembly And Operation Instructions Please Note: Planishing Hammer not included with Stand. Due to continuing improvements,

More information

STAFF User Manual. Manual Part #

STAFF User Manual. Manual Part # STAFF User Manual Manual Part # 030-00085-00 Introduction Congratulations on the purchase of your new STAFF Secondary Fault Locator. The STAFF is specially designed to detect conductor to earth/ground

More information

Bulk Current Injection Probe Test Procedure

Bulk Current Injection Probe Test Procedure Bulk Current Injection Probe Test Procedure 1 TABLE OF CONTENTS INTRODUCTION 3 GENERAL INFORMATION 4 TEST METHODS 6 SAFETY 8 FIGURES 9 FORMULAS 12 MAINTENANCE 13 WARRANTY 14 2 INTRODUCTION CURRENT PROBE

More information

Heavy Duty Soldering Gun Kit

Heavy Duty Soldering Gun Kit Heavy Duty Soldering Gun Kit Stock Number W2019A OWNER'S MANUAL FOR YOUR SAFETY, please read these instructions carefully and retain them for future use. SPECIFICATIONS Electrical:... 120 V AC, 60 Hz,.07A

More information

Table of Contents GDM-356. Page

Table of Contents GDM-356. Page Table of Contents Title Overview Unpacking Inspection Safety Information Rules For Safe Operation International Electrical Symbols The multimeter Structure Functional Buttons Display Symbols Measurement

More information

BC145 SIGNAL ISOLATOR BOARD

BC145 SIGNAL ISOLATOR BOARD BC145 SIGNAL ISOLATOR BOARD 4/17 Installation & Operating Manual MN1373 Any trademarks used in this manual are the property of their respective owners. Important: Be sure to check www.baldor.com to download

More information

LOCKOUT / TAGOUT PROGRAM

LOCKOUT / TAGOUT PROGRAM Page 1 of 7 1. SCOPE LOCKOUT / TAGOUT PROGRAM This Program outlines the purpose, rules, responsibilities and techniques to be followed by all University of Pittsburgh employees to guard against the unexpected

More information

Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM

Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM Analog Voltage Detector 0-40kV Operating Instructions VDA040CTM CONTENTS Limitation of Warranty and Liability 2 Product Safety Information 3 Design and Function 4 Voltage Detection in the C Position 5-6

More information

Owner s Manual & Safety Instructions

Owner s Manual & Safety Instructions Owner s Manual & Safety Instructions Save This Manual Keep this manual for the safety warnings and precautions, assembly, operating, inspection, maintenance and cleaning procedures. Write the product s

More information

15B & 17B. Users Manual. Multimeters

15B & 17B. Users Manual. Multimeters 15B & 17B Multimeters Users Manual PN 1991246 October 2002 Rev. 3, 3/04 2002-2004 Fluke Corporation. All rights reserved. Printed in China. All product names are trademarks of their respective companies.

More information