Specific Equipment and Area - EAC District Office Substation
|
|
- Charles Hampton
- 5 years ago
- Views:
Transcription
1 On the 13th of April 2007 at 10:00 am magnetic field measurements were performed for the District Office Substation. The substation of interest is located on Mykhnon Street in Nicosia. {mosmap width='500' height='400' lat=' ' lon=' ' zoom='18' zoomtype='large' zoomnew='0' maptype='satellite' showmaptype='1' overview='0' text='district Office EAC Substation' tooltip='dwo' marker='1' align='center' key='abqiaaaa03cwbwhnzyjizsn-wwdqmhqctkyp5l8hb2mjngvvfkvpdgzbixqkqitrafigip chx6gplphdidvzga'} Σελίδα 1 / 21
2 Figure 1: EAC District Office Figure 2: EAC District Office outside Limiting exposure values have been provided by the ICNIRP recommendations and are guidelines to many countries and organizations. The exposure limits at 50 Hz are tabulated in the following table according to the limits given by ICNIRP. Σελίδα 2 / 21
3 Reference levels for Occupational exposure ICNIRP Frequency Electric Field Strength, E (V/m) Magnetic Field Strength, H (A/m) Magnetic Flux Density, B (µt) 50 Hz Reference levels for General Public exposure ICNIRP Frequency Electric Field Strength, E (V/m) Magnetic Field Strength, H (A/m) Magnetic Flux Density, B (µt) 50 Hz Table 2: ICNIRP exposure limits for Occupational and General Public exposure The obtained results for the RMS fields inside and outside the substation are shown in tables 3 and 4 respectively in the case when the substation is on. A comparison is also made with the ICNIRP recommendations. Σελίδα 3 / 21
4 District Office Substation: Fields Inside Substation when building was on Distance from Side /m Maximum Magnetic Field / µt at Z Height /m - Percentage of ICNIRP Occupational Standard /% 0.3m 1 m 1.75 m Basement Field Measurements (Distance from Left Inside Wall) 2m from Left Side 2,82 0,56% 0,95 0,19% 0,53 0,11% 4m from Left Side 2,48 0,50% 1,37 0,27% Σελίδα 4 / 21
5 0,94 0,19% Transformer Room 1 Field Measurements (Distance from Right Inside Wall) 3m from Right Side 0,43 0,09% 0,29 0,06% 0,43 0,09% 5m from Right Side 0,44 0,09% 0,41 0,08% 0,43 0,09% 9m from Right Side 1,15 0,23% 0,41 0,08% 0,42 0,08% Σελίδα 5 / 21
6 Transformer Room 2 Field Measurements (Distance from Right Inside Wall) 3m from Right Side 0,40 0,08% 0,29 0,06% 0,43 0,09% 5m from Right Side 0,49 0,10% 0,61 0,12% 0,50 0,10% 9m from Right Side 0,60 0,12% 0,40 0,08% 0,32 0,06% Transformer Room 3 Field Measurements (Distance from Right Inside Wall) Σελίδα 6 / 21
7 3m from Right Side 0,22 % 0,24 0,05% 0,50 0,10% 5m from Right Side 0,47 0,09% 0,56 0,11% 0,76 0,15% 9m from Right Side 0,52 0,10% 0,72 0,14% 1,02 0,20% Floor 1 Room Field Measurements Behind of 22-11KV Switchgear A Σελίδα 7 / 21
8 0,07 0,01% 0,09 0,02% 0,13 % In Front of 22-11KV Switchgear A 0,01% 0,01% 0,01% Behind of 22-11KV Switchgear B 0,01% 0,01% 0,02 0,00% In Front of 22-11KV Switchgear B 0,06 0,01% Σελίδα 8 / 21
9 0,01% 0,01% Behind of Switchgear 132KV 0,41 0,08% 0,29 0,06% 0,19 % In Front Switchgear 132KV 0,21 % 0,15 % 0,16 % Control Room Field Measurements In Front of Control Systems 0,15 % 0,10 0,02% 0,08 Σελίδα 9 / 21
10 0,02% Point A 0,46 0,09% Point B 0,16 % Point C 0,12 0,02% Table 3: Maximum Field Measurements inside District Office Substation (substation on) Σελίδα 10 / 21
11 District Office Substation: Fields Outside Substation when building was on Distance from Side /m Maximum Magnetic Field / µt at Z Height /m - Percentage of ICNIRP General Public Standard /% 0.3m 1 m 1.75 m Substation Left Side Field Measurements Left Outside Wall 2,22 2,22% Back Outside Wall 0,08 0,08% Σελίδα 11 / 21
12 Right Outside Wall 0,15 0,15% Front Outside Wall 0,48 0,48% Table 4: Maximum Field Measurements outside District Office Substation (substation on) Accordingly the obtained results for the RMS fields inside and outside the substation in the case when District office Substation was powered off, are shown in tables 5 and 6 respectively. A comparison is again made with the ICNIRP recommendations. District Office Substation: Fields Inside Substation when building was off Distance from Side /m Maximum Magnetic Field / μT at Z Height /m - Percentage of ICNIRP Occupational Standard /% Σελίδα 12 / 21
13 0.3m 1 m 1.75 m Basement Field Measurements (Distance from Left Inside Wall) 2m from Left Side 0,006% 0,005% 0,008% 4m from Left Side 0,008% 0,007% 0,05 0,011% Transformer Room 1 Field Measurements (Distance from Right Inside Wall) 3m from Right Side Σελίδα 13 / 21
14 0,05 0,009% 0,007% 0,10 0,020% 5m from Right Side 0,006% 0,006% 0,06 0,011% 9m from Right Side 0,09 0,018% 0,007% 0,02 0,005% Transformer Room 2 Field Measurements (Distance from Right Inside Wall) 3m from Right Side 0,02 0,004% Σελίδα 14 / 21
15 0,005% 0,05 0,009% 5m from Right Side 0,008% 0,05 0,009% 0,10 0,019% 9m from Right Side 0,008% 0,006% 0,006% Transformer Room 3 Field Measurements (Distance from Right Inside Wall) 3m from Right Side 0,009% 0,008% Σελίδα 15 / 21
16 0,06 0,013% 5m from Right Side 0,05 0,009% 0,008% 0,14 0,028% 9m from Right Side 0,06 0,012% 0,05 0,010% 0,06 0,011% Floor 1 Room Field Measurements Behind of 22-11KV Switchgear A 0,007% 0,10 0,020% 0,14 0,028% Σελίδα 16 / 21
17 In Front of 22-11KV Switchgear A 0,01 0,002% 0,01 0,001% 0,01 0,002% Behind of 22-11KV Switchgear B 0,02 0,004% 0,02 0,005% 0,06 0,012% In Front of 22-11KV Switchgear B 0,006% 0,005% 0,006% Behind of Switchgear 132KV 0,01 Σελίδα 17 / 21
18 0,002% 0,02 0,004% 0,02 0,004% In Front Switchgear 132KV 0,02 0,005% 0,005% 0,006% Control Room Field Measurements In Front of Control Systems 0,11 0,02% 0,093 0,019% 0,07 0,01% Point A 0,69 Σελίδα 18 / 21
19 0,138% Point B 0,13 0,026% Point C 0,13 0,026% Table 5: Maximum Field Measurements inside District Office Substation (substation off) District Office Substation: Fields Outside Substation when building was off Distance from Side /m Maximum Magnetic Field / μT at Z Height /m - Percentage of ICNIRP General Public Standard /% 0.3m Σελίδα 19 / 21
20 1 m 1.75 m Substation Left Side Field Measurements Left Outside Wall 1,77 1,77% Back Outside Wall % Right Outside Wall 0,10 Σελίδα 20 / 21
21 0,10% Front Outside Wall 0,41 0,41% Table 6: Maximum Field Measurements outside District Office Substation (substation off) Σελίδα 21 / 21
High Voltage Overhead Power Lines, 21 Georgiou Eikosari, Dali
On the 22nd of July 2009 at 17:30 pm, electric and magnetic field measurements were performed for 21 Georgiou Eikosari, Dali overhead power lines. The EMF measurements were performed inside and outside
More informationOverhead Power Lines: Argaki area in Moni, Limassol
The measurements were performed on the 21st of September 2011 at 11:50 am during clear weather conditions. The EMF measurements were performed inside the plot area in direct proximity to the overhead power
More informationLOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS
LOW-FREQUENCY MAGNETIC FIELDS IN SECONDARY SUBSTATIONS Peter Leipold, Klaus-Peter Panzlaff Bewag Aktiengesellschaft, Puschkinallee 52, D-12435 Berlin Tel.: +49 30 267 10 350 - Fax: +49 30 267 10 352 -
More informationMAGNETIC FIELD METER Operator s Manual
Edition 4.4 September 2011 MAGNETIC FIELD METER 3000 Operator s Manual The MFM 3000 is a professional magnetic field instrument To make the best use of the instrument we recommend that you read this manual
More informationCode of Practice for Proposed Mobile Phone Base Station Installations on University Premises.
Code of Practice for Proposed Mobile Phone Base Station Installations on University Premises. Introduction. Mobile phone base stations are low power (typically a few tens of watts) radio transmitters with
More informationDeveloping and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany
Developing and Implementing Protective Measures for ELF EMF - Sources and exposures- Rüdiger Matthes Federal Office for Radiation Protection Germany 1 Non-ionising Radiation Ionising Radiation >0 to 300
More informationHuman Exposure Requirements for R&TTE and FCC Approval
Human Exposure Requirements for R&TTE and FCC Approval Derek Y. W. LEUNG Founding and Committee Member of EMC Chapter- IEEE-HK Requirements of Non-Specific Short Range Device (SRD) for CE Marking Radio
More information6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report
The Millbrook Power (Gas Fired Power Station) Order 6.2 Environmental Statement Appendices Volume N Appendix 15.1 EMF Report Planning Act 2008 The Infrastructure Planning (Applications: Prescribed Forms
More informationDESIGN OF A 45 CIRCUIT DUCT BANK
DESIGN OF A 45 CIRCUIT DUCT BANK Mark COATES, ERA Technology Ltd, (UK), mark.coates@era.co.uk Liam G O SULLIVAN, EDF Energy Networks, (UK), liam.o sullivan@edfenergy.com ABSTRACT Bankside power station
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Electric and Magnetic Field Measurement For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field
More informationReport On. RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna. FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW
Report On RF Exposure Assessment of the Sepura plc SRG3900 with AQHB Antenna FCC ID: XX6SRG3900UW Industry Canada ID: 8739A-SRG3900UW Document 75908189 Report 04 Issue 2 March 2010 TUV Product Service
More informationAnalytical Design Optimization of 765 kv Transmission Line Based on Electric and Magnetic Fields for Different Line Configurations
Available onlinewww.ejaet.com European Journal of Advances in Engineering and Technology, 2018, 5(2): 91-98 Research Article ISSN: 2394-658X Analytical Design Optimization of 765 kv Transmission Line Based
More informationElectromagnetic environment in Electrical Hypersensitives homes and workplaces. Kjell Hansson Mild. National Institute for Working Life, Umeå, Sweden
Electromagnetic environment in Electrical Hypersensitives homes and workplaces National Institute for Working Life, Umeå, Sweden External sources: High voltage power lines, distribution lines magnetic
More informationEXPOSURE to electromagnetic fields (EMFs) is not a
1800 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 3, JULY 2005 Measurements of Electric and Magnetic Fields Due to the Operation of Indoor Power Distribution Substations Anastasia S. Safigianni, Member,
More informationFor Isotropic Measurement of Magnetic and Electric Fields
Field Analyzers EFA-300 For Isotropic Measurement of Magnetic and Electric Fields Evaluation of Field Exposure compared to Major Standards and Guidance (selectable) Shaped Time Domain (STD) an innovative
More informationELF Magnetic Field Security Zones around High Voltage Power Lines
ELF Magnetic Field Security Zones around High Voltage Power Lines Carlos Lemos Antunes 1,2,3 (1) Lab. CAD/CAE, Electrical Engineering Dept, University of Coimbra Pólo II, 3030 290 Coimbra (Portugal) (2)
More informationAnalysis of magnetic and electromagnetic field emissions produced by a MRI device
Sept. 8-1, 21, Kosice, Slovakia Analysis of magnetic and electromagnetic field emissions produced by a MRI device D. Giordano, M. Borsero, G. Crotti, M. ucca INRIM Istituto Nazionale di Ricerca Metrologica,
More informationYARRANLEA SOLAR PROJECT. Electromagnetic Radiation Assessment. Zenviron Document: 8013-EL-R
YARRANLEA SOLAR PROJECT Electromagnetic Radiation Assessment Zenviron Document: 8013-EL-R-160819-1 DOCUMENT DETAILS Revision History REV. DESCRIPTION PREPARED CHECKED APPROVED DATE A Initial Issue ABC
More informationLow Frequency. Precision test equipment for safety in electric and magnetic fields
Low Frequency Precision test equipment for safety in electric and magnetic fields Your One-Stop Shop for Safety in Electromagnetic Fields Narda Safety Test Solutions device technologies highly simplify
More informationTechnical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure
Technical Committee106 Methods for the assessment of electric, magnetic and electromagnetic fields associated with human exposure International Electrotechnical Commission Michel Bourdages Secretary International
More informationWorkplace safety for demagnetizer operators
Content Basics International recommendations according to ICNIRP Accident prevention regulation BGV B11 (Germany) Electromagnetic exposure of classic demagnetizers Safety concept of Maurer Magnetic AG
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationELECTROMAGNETIC 0 Hz 300 GHz
ELECTROMAGNETIC 0 Hz 300 GHz Field characterization & occupational exposure sources Laura FILOSA 1. Organization of the NIR Module 2. European frame introduction 3. Electromagnetic field characterization
More informationMagnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements SEYED REZA ATEFI
Magnetic Field Measurement in Residential Areas Göteborg, Borås and Mark Residential Area Measurements Master of Science Thesis in Biomedical Engineering SEYED REZA ATEFI Department of Signals and Systems
More informationAppendix 6-F: Electric and Magnetic Field Study Report
Draft Environmental Impact Statement Cricket Valley Energy Project Dover, NY Appendix 6-F: Electric and Magnetic Field Study Report ELECTRIC & MAGNETIC FIELDS (EMFs) STUDY REPORT For the CRICKET VALLEY
More informationELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION
Rev. Roum. Sci. Techn. Électrotechn. et Énerg. Vol. 61, 1, pp. 178 182, Bucarest, 2016 ELECTROMAGNETIC POLLUTION INSIDE HIGH VOLTAGE SUBSTATION BILLEL ALI RACHEDI 1, ABDESSELAM BABOURI 1, ZHANG XUN 2 Key
More informationTechnical Note 2. Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment
Technical Note 2 Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment Technical Note: Standards-compliant test of non-ionizing electromagnetic radiation on radar equipment
More informationEnvironmental Exposures to ELF Georg Neubauer
Environmental Exposures to ELF Georg Neubauer 1 Table of Content Environmental exposures to ELF sources Measurement methods Requirements on measurements Conclusions 2 Environmental exposure to ELF sources
More informationElectric and magnetic field levels around Christchurch
Electric and magnetic field levels around Christchurch M D Gledhill 1992/1 NRL Report Report NRL 1992/1 ISSN O111-753x ELECTRIC AND MAGNETIC FIELD LEVELS AROUND CHRISTCHURCH M D Gledhill National Radiation
More informationPROBLEMS on Transformers
PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary
More informationSafety Evaluation Within a Magnetic Field Environment
EXPOSURE LEVEL TESTER ELT-400 Safety Evaluation Within a Magnetic Field Environment Direct evaluation of field exposure in comparison with major standards and regulations such as Directive 2013/35/EU for
More informationEvaluation on the Potential Risk Hazards of Magnetic Field Radiated from Cast Resin Transformer Electric Substation
Australian Journal of Basic and Applied Sciences, 5(9): 150-159, 2011 ISSN 1991-8178 Evaluation on the Potential Risk Hazards of Magnetic Field Radiated from Cast Resin Transformer Electric Substation
More informationResearch Activities Plan. Appendix K Magnetic Fields from Submarine Cables
VOWTAP Research Activities Plan Appendix K Magnetic Fields from Submarine Cables December 2013 Electrical Engineering and Computer Science Practice Virginia Offshore Wind Technology Advancement Project
More informationExperimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines
American J. of Engineering and Applied Sciences 4 (2): 209-213, 2011 ISSN 1941-7020 2011 Science Publications Experimental Study of Electromagnetic Environment in the Vicinity of High Voltage Lines 1 Wafa
More informationAnalysis of static and time-variable magnetic fields
Magnetometer HP-01 Analysis of static and time-variable magnetic fields Field exposure evaluation according to current standards and regulations such as Directive 2013/35/EU for workplaces Frequency-selective
More informationRF-EXPOSURE ASSESSMENT REPORT
RF-EXPOSURE ASSESSMENT REPORT EN 62311 RF-Exposure evaluation of electronic equipment Report Reference No.... : G0M-1206-2043-TEU311E-V01 Testing Laboratory... : Address... : Storkower Str. 38c 15526 Reichenwalde
More informationELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE
ELF ELECTRIC AND MAGNETIC FIELDS MEASUREMENTS IN GREECE E. Karabetsos, G. Filippopoulos, D. Koutounidis CH. Govari, N. Skamnakis Non ionizing radiation office, Greek atomic energy commission, P. O. BOX
More informationComparison of international policies on electromagnetic fields. (power frequency and radiofrequency fields)
Comparison of international policies on electromagnetic fields (power frequency and radiofrequency fields) Comparison of international policies on electromagnetic fields (power frequency and radiofrequency
More informationEN EMF REPORT For. Two way radio Model No.: RT-5R
Report No.: B-E16049599 Page 1 of 9 EN 62311 EMF REPORT For Zhengzhou Eshow Import and Export Trade Co., Ltd. Two way radio Model No.: RT-5R Model No. Trade Name Prepared for Address : RT-5R : N/A : Zhengzhou
More informationSelective and broadband high frequency field analysis
ELECTRIC AND MAGNETIC FIELD ANALYZER EHP-200A Selective and broadband high frequency field analysis New solution for isotropic measurements in the 9 khz 30 MHz range Electric Fields from 0.02 to 1000 V/m
More informationFirst South East European Regional CIGRÉ Conference. Portoroz, Slovenia, 7 8 June 2016
First South East European Regional CIGRÉ Conference Portoroz, Slovenia, 7 8 June 2016 Assessment of new OHL of Slovak Republic Transmission System with regard to the recommendation of the Directive No.
More informationPHYSICS VCE UNITS 3&4 DIAGNOSTIC TOPIC TESTS 2017
PHYSICS VCE UNITS 3&4 DIAGNOSTIC TOPIC TESTS 2017 TEST 3: TOTAL 45 MARKS (45 MINUTES) Student s Name: Teacher s Name: Directions to students Write your name and your teacher s name in the spaces provided
More informationFrench children exposure to 50 Hz magnetic field
French children exposure to 50 Hz magnetic field Isabelle Magne 1, Martine Souques 2, Jacques Lambrozo 2, Mfoihaya Bedja 3, Gilles Fleury 3, Laurent Le Brusquet 3, Alexandre Carlsberg 4, François Deschamps
More informationNIR MEASUREMENTS. Principles and practices of EMF characterization and measurements
IRPA 1 1th International Congress of the International Radiation Protection Association 19th-4th October 008, Buenos Aires, Argentina RC-11 NIR MEASUREMENTS. Principles and practices of EMF characterization
More informationGE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class
GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial
More informationEvaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400
EXPOSURE LEVEL TESTER ELT-400 Application Note 1108 Evaluation of exposure to pulsed magnetic fields by examining the variations in the spectrum and over time with ELT-400 Introduction The ELT-400 is a
More informationAPPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS
109 APPENDIX 4 TYPICAL LAYOUT, VALUES AND CONSTANTS TYPICAL LAYOUT The purpose of a transformer is to transfer energy from the input to the output through the magnetic field. The layout of a partial typical
More informationE) all of the above E) 1.9 T
1. The figure shows a uniform magnetic field that is normal to the plane of a conducting loop, which has a resistance R. Which one of the following changes will cause an induced current to flow through
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationElectromagnetic Fields, Mobile Telephones and Health
Electromagnetic Fields, Mobile Telephones and Health Dr. Matti Rajala European Commission Directorate General for Health and Consumer Protection - Luxembourg Council Recommendation 12th July (1999/519/EC)
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationELECTROMAGNETIC SHIELDING PRODUCTS
ELECTROMAGNETIC SHIELDING PRODUCTS WWW.SATISHIELDING.COM SATI SHIELDING Sati Shielding S.r.l. was set up on 23 December 2015, thanks to the merger of different professional skills: marketing and organisational
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationESO 210 Introduction to Electrical Engineering
ESO 210 Introduction to Electrical Engineering Lecture-19 Magnetic Circuits and Introduction to Transformers 2 SERIES CONNECTION OF MUTUALLY COUPLED COILS A mutual term will alter the total inductance
More informationv1.0.1 March AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual
v1.0.1 March 2018 2018 AlphaLab, Inc. All rights reserved. TriField EMF Meter Owner s Manual TABLE OF CONTENTS Overview... 1 Introduction... 1 Features... 1 Applications... 1 Using the TriField EMF Meter...
More informationAbbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel Fax Web
An Coimisiún um Rialáil Cumarsáide Abbey Court Irish Life Centre Lower Abbey Street Dublin 1 Tel +353 1 804 9600 Fax +353 1 804 9680 Email info@comreg.ie Web www.comreg.ie Programme of Measurement of Non-Ionising
More informationIOSH Webinar. Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH
IOSH Webinar Control of Electromagnetic Fields at work regulations 2016 Part 2 EMF exposure assessment 4 th May 2017 Julia Clark FSRP CMIOSH www.linkmicrotek.com Previously Webinar part one covered: Definition
More informationSubject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater
EMF Measurements, Surveys & Risk Assessment EMF Mitigation Shielding & Cancellation E-Mail: dvitale@vitatech.net www.vitatech.net VitaTech Electromagnetics, LLC 115 Juliad Ct., Suite 105 Fredericksburg,
More informationExposure Level Tester ELT-400
Safety Evaluation within a Magnetic Field Environment Exposure Level Tester ELT-400 Direct Evaluation of Field Exposure Compared to Major Standards (IEEE C95.6) Automatic Exposure Evaluation for Various
More informationRF EME ANALYSIS REPORT TELSTRA CORPORATION LIMITED WIFI BASE CUBE
RF EME ANALYSIS REPORT TELSTRA CORPORATION LIMITED WIFI BASE CUBE October2014 Prepared by PO Box 680 CLAREMONT WA 6910 08 9381 7199 (telephone) 08 9381 7166 (facsimile) www.t-r-s.com.au James Ward RF EME
More informationMeasurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013
Measurements of Exposures Around Vodafone New Zealand Limited Cellsites from June 2012 to May 2013 This report was prepared for: Vodafone New Zealand Limited Private Bag 92161 AUCKLAND By M Dirksen Reviewed
More information1 Dockland Central, Guild St, Dublin 1 1 Lárcheantar na ndugaí, Sráid na ngildeanna, BÁC 1 Tel Teil
An Coimisiún um Rialáil Cumarsáide 1 Dockland Central, Guild St, Dublin 1 1 Lárcheantar na ndugaí, Sráid na ngildeanna, BÁC 1 Tel Teil +353 1 804 9600 www.comreg.ie Programme of Measurement of Non-Ionising
More information1 Dockland Central, Guild St, Dublin 1 1 Lárcheantar na ndugaí, Sráid na ngildeanna, BÁC 1 Tel Teil
An Coimisiún um Rialáil Cumarsáide 1 Dockland Central, Guild St, Dublin 1 1 Lárcheantar na ndugaí, Sráid na ngildeanna, BÁC 1 Tel Teil +353 1 804 9600 www.comreg.ie Programme of Measurement of Non-Ionising
More informationIntertek Testing Services ETL SEMKO
Page 1 of 6 Maximum Permissible Exposure (MPE) Evaluation Report Report No. : EME-030276 Model No. : ME101 Issued Date : Mar. 5, 2003 Applicant Test By : NETGEAR, Inc. 4500 Great America Parkway, Santa
More informationSelective and broadband low frequency field analysis
ELECTRIC AND MAGNETIC FIELD ANALYZER EHP-50C Selective and broadband low frequency field analysis Electric and magnetic low frequency field analysis up to 100 khz Isotropic measurement with a dynamic range
More information1. Introduction. Keywords Non-ionizing radiation, Electric field, Magnetic field, Power line, Kaduna metropolis, ICNIRP 2010 guideline
American Journal of Condensed Matter Physics, (): - DOI:.9/j.ajcmp.. Measurement and Analysis of Health Effects Due to Exposure to Non-Ionizing Radiation from High Tension Cables around Kaduna Metropolis,
More informationELECTROMAGNETIC FIELD APPLICATION TO UNDERGROUND POWER CABLE DETECTION
ELECTROMAGNETIC FIELD APPLICATION TO UNDERGROUND POWER CABLE DETECTION P Wang *, K Goddard, P Lewin and S Swingler University of Southampton, Southampton, SO7 BJ, UK *Email: pw@ecs.soton.ac.uk Abstract:
More informationI1A Magnetic Field Transducers
DESCRIPTION: The I1A denotes a range of SENIS Magnetic Fieldto-Voltage Transducers with integrated 1-axis Hall Probe. It measures magnetic fields perpendicular to the probe plane (By). The Hall Probe contains
More informationReport On. Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System
America Report On Radio Frequency Exposure Testing of the Winland Electronics, Inc. EnviroAlert Electronic Multi-Zone Environmental Alarm System EN62311 January 2008 AS/NZS 2772.2:2011 October 2017 REPORT
More informationSummerland Planning Advisory Committee
Summerland Planning Advisory Committee SunPAC Meeting #32 May 10, 2011 1 SunPAC Meeting Agenda Call to Order Agenda Item: 1 Item 1: Pledge of allegiance and roll call Item 2: Public comment period Item
More informationSRM When Safety Counts SRM SRM-3006 Selective Radiation Meter for electromagnetic fields up to 6 GHz
SRM When Safety Counts SRM-3006 SRM-3006 Selective Radiation Meter for electromagnetic fields up to 6 GHz Make Safety obvious by measurement Radio, television, cellular telephony, wireless... Electromagnetic
More informationINTERNATIONAL COMMISSION ON NON IONIZING RADIATION PROTECTION ICNIRP STATEMENT
INTERNATIONAL COMMISSION ON NON IONIZING RADIATION PROTECTION ICNIRP STATEMENT GUIDANCE ON DETERMINING COMPLIANCE OF EXPOSURE TO PULSED FIELDS AND COMPLEX NON SINUSOIDAL WAVEFORMS BELOW 100 khz WITH ICNIRP
More informationHeRO duet
HeRO duet CUSTOMER SERVICE TABLE OF CONTENTS TABLE OF CONTENTS OVERVIEW OVERVIEW OVERVIEW OVERVIEW USING HeRO duet USING HeRO duet USING HeRO duet Current HeRO Score HeRO USING HeRO duet USING HeRO duet
More informationDistributed Series Reactor An overview of the conductor impacts of the DSR
1 Distributed Series Reactor An overview of the conductor impacts of the DSR Joseph Goldenburg, P.E. Mechanical Section Lead and Hardware Manager at NEETRAC 2 DSR Technology Overview History Table of Contents
More informationSafety Code 6 Analysis Freedom Mobile 3G & LTE Network. Radio frequency exposure for uncontrolled and controlled environment.
Safety Code 6 Analysis Freedom Mobile 3G & LTE Network Radio frequency exposure for uncontrolled and controlled environment Freedom Mobile 207 Queen's Quay West, Suite 710 Toronto, ON M5J 1A7 3655 Wesbrook
More informationDesign of magnetic field alarm powered by magnetic energy harvesting
Design of magnetic field alarm powered by magnetic energy harvesting Kunihisa Tashiro 1, Azusa Ikegami 1, Syoichiro Shimada 1, Hiroaki Kojima 1, Hiroyuki wakiwaka 1 1 Spin Device Technology Center Shinshu
More informationElectricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies
Electricity Supply to Africa and Developing Economies. Challenges and opportunities. Technology solutions and innovations for developing economies Magnetic induced currents and voltages on earthed lines
More informationBy Gill ( ) PDF created with FinePrint pdffactory trial version
By Gill (www.angelfire.com/al4/gill ) 1 Introduction One of the main reasons of adopting a.c. system instead of d.c. for generation, transmission and distribution of electrical power is that alternatin
More informationF1A Magnetic Field Transducers
DESCRIPTION: The F1A denotes a range of SENIS Magnetic Fieldto- Voltage Transducers with fully integrated 1-axis Hall Probe. It measures magnetic fields perpendicular to the probe plane (By). The Hall
More informationVoltage Detectors. Voltage Detectors Voltage Detectors
Voltage Detectors Voltage Detectors One of the most important operations when working on electrical switchgear is to check that voltage is absent, and this requires voltage detectors that meet the highest
More informationRF Exposure Evaluation Declaration
RF Exposure Evaluation Declaration Product Name : 300Mbps Wi-Fi Range Extender Model No. : TL-WA855RE Applicant : TP-Link Technologies Co., Ltd. Address : Building 24(floors1,3,4,5) and 28(floors1-4) Central
More informationPage 2 A 42% B 50% C 84% D 100% (Total 1 mark)
Q1.A transformer has 1150 turns on the primary coil and 500 turns on the secondary coil. The primary coil draws a current of 0.26 A from a 230 V ac supply. The current in the secondary coil is 0.50 A.
More informationRegulatory Framework for RF Safety in Mauritius
Regulatory Framework for RF Safety in Mauritius Jerome LOUIS Director Engineering ICTA This Session PART I Background Base Station Site Selection Base Station authorisation process Exposure Limits adopted
More informationRF Field Strength Meter TDM-200. Instruction Booklet. Laplace Instruments Ltd. Supplied by:
Supplied by: Laplace Instruments Ltd 3B, Middlebrook Way CROMER, Norfolk NR27 9JR UK Tel: 01263 51 51 60 Fax: 01263 51 25 32 E-mail: tech@laplace.co.uk RF Field Strength Meter TDM-200 Instruction Booklet
More informationSRM-3000 Selective Radiation Meter
SRM-3000 Selective Radiation Meter Complete Solution for Selective Measurement of RF and Microwave Electromagnetic Fields Isotropic and Single-Axis Measurements from 100 khz to 3 GHz Excellent Immunity
More informationITU-T Study Group 5. EMF Environmental Characterization
International Telecommunication Union EMF Environmental Characterization Jeffrey Boksiner Senior Consultant, Telcordia Technologies, Inc Workshop on: EMC, safety and EMF effects in telecommunications o
More informationContinuously monitors and stores the levels of Electromagnetic fields Up to four simultaneous bands: GSM 900 / 1800 MHz / UMTS / Broadband 100 khz 3
Continuously monitors and stores the levels of Electromagnetic fields Up to four simultaneous bands: GSM 900 / 1800 MHz / UMTS / Broadband 100 khz 3 GHz Magnetic fields monitoring from 10 Hz to 5 khz Automatic
More informationATA s Nanoradian-Class Rotational Sensors. 10 November 2009
ATA s Nanoradian-Class Rotational Sensors 10 November 2009 ATA Overview Founded 1975 A-TECH Corporation, d.b.a. Applied Technology Associates Customers Include USAF, Sandia NL, US Army, MDA, NASA, US Navy,
More informationMr. Aaron Zack Tel: Subject: AC ELF EMF EMC Magnetic Field Testing for a Sauna Heater
115 Juliad Court, Suite 105 Fredericksburg VA, 22406 Phone 540 286 1984 Fax 540 268 1865 www.vitatech.net November 14th, 2012 Mr. Aaron Zack Tel: 877.292.0020 President/CEO Email: azack@sunlighten.com
More informationCode No: R Set No. 1
Code No: R05310204 Set No. 1 III B.Tech I Semester Regular Examinations, November 2007 ELECTRICAL MACHINES-III (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions
More informationSafety Evaluation Within a Magnetic Field Environment
EXPOSURE LEVEL TESTER ELT-400 Safety Evaluation Within a Magnetic Field Environment Direct evaluation of field exposure in comparison with major standards Automatic exposure evaluation for various waveforms
More informationPRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.
TRANSMISSION LINES PRELIMINARIES Generators and loads are connected together through transmission lines transporting electric power from one place to another. Transmission line must, therefore, take power
More informationThe Nature of Electric and Magnetic Fields 2017
The Nature of Electric and Magnetic Fields 2017 FACT SHEET 1 3 4 5 What are Electric and Magnetic Fields (EMF)? How are electricity and EMF related? Many people will have seen the attraction or repulsion
More informationBiljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010
Biljana Tanatarec Doron Net d.o.o. ISO/HZN National Workshop on Social Responsibility Zagreb, 9 10 September 2010 Introduction Working in Doron Net d.o.o. Head of DN Laboratory Doron Net is a member of
More informationMulti Voltage Multi Circuit Transmission Tower Design to Reduce Right of Way
Indian Journal of Science and Technology, Vol 9(33), DOI: 10.17485/ijst/2016/v9i33/95239, September 2016 ISSN (Print) : 0974-6846 ISSN (Online) : 0974-5645 Multi Voltage Multi Circuit Transmission Tower
More informationH3A Magnetic Field Transducer
DESCRIPTION: The H3A denotes a range of Low Noise SENIS Magnetic Field-to-Voltage Transducers with hybrid 3- axis Hall Probe. The Hybrid Hall Probe integrates three highresolution with good angular accuracy
More informationSRM: WHEN SAFETY COUNTS. SRM-3006: SELECTIVE RADIATION METER FOR ELECTROMAGNETIC FIELDS UP TO 6 GHz
SRM: WHEN SAFETY COUNTS SRM-3006: SELECTIVE RADIATION METER FOR ELECTROMAGNETIC FIELDS UP TO 6 GHz SAFETY? Radio, TV, mobile phones, wireless services: Electromagnetic fields are the medium wherever such
More informationAUTOMOTIVE CURRENT TRANSDUCER HC6F600-S
AUTOMOTIVE CURRENT TRANSDUCER HC6F600-S 18198102215 Page 1/5 Introduction Principle of HC6F Family The HC6F Family is for use on the electronic measurement of DC, AC or pulsed currents in high power and
More informationCOMPLIANT Common Mode Chokes - UU9.8 & UU10.5 Series
Document FR00 COMPLIANT Common Mode Chokes - UU9.8 & UU0.5 Series Order Code MCU 000 MCU 0002 Core Mounting Inductance mh (Min) UU9.8 Series Current Rating ma (steady state) 350 350 Leakage DC Inductance
More information