1 Martin Stoessl R&D Manager Siemens Transformers Austria - Weiz
2 Transformer reliability Ability to perform its required functions under stated conditions for a specified period of time Failure termination of the ability It is often reported as a probability 2
3 Transformer Reliability - based on ANSI C (1986) Definitions: Population: Transformers that have given common specific characteristics Failure: Termination of a transformer to perform its specific functions Failure with forced outage: Failure of a transformer that requires its immediate removal from the system for more than 1 day in conjunction with internal measures Failure Rate FR [%] = (nf / SY) 100 The ration of the number of failures with forced outage of a given population over a given period of time to the number of accumulated service years for all transformers in that period of time Mean Time Between Failures MTBF [years] = 1 / FR Mean Time between failures (MTBF) = 1 / FR (years) N: Number of units in service within evaluation period (floating 10 years) SY: Number of service years accumulated with [N] units in service nf: Number of failures with forced outage of a population within the evolution period 3
4 Transformer Reliability - based on ANSI C (1986) FRe and MTBF as a degree of Reliability: Failure rate and reliability are related in the following way: R = e -λt t... time in year λ failure rate in failures per transformer-years of service (λ=nf/sy) e MTBF is considered to be the reciprocal of failure rate for purpose of estimating reliability: MTB = 1 / λ MTBF and reliability are related in the following way: R = e -t/mtbf Example: Given a constant MTBF of 500 years The reliability R of a transformer surviving t years of service without a failure would be shown as below: λ = t R For a given MTBF of 500 years the probability of a transformer surviving 20 years of service without failure is 96.08% 4
5 CIGRE activities related to Transformer Reliability SC A2 Reliability Advisory Group 2006 Bathtub curve Reliability databases WG A2.37: Reliability Surveys difficult to get reliable data WG A2.43: TR Bushing reliability (Um 72,5 kv) Started in June 2010 Plans to work on topics like post mortem and end of life decision. 5
6 Reliability of main accessories A2 session papers in Paris 2010 showed that accessories cause a significant proportion of the power transformer major failures. new bushing and tap-changer technologies were introduced recently these technologies and their impact on maintenance have to be reviewed Future task of CIGRE Study Committee A2 6
7 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 7
8 Electrical insulation system transformer insulation life [1] total time between initial state (new) and the final state when due to normal service thermal ageing dielectric short-circuit mechanical movement could result in a high risk of electrical failure [1] IEC Loading guide for oil-immersed power transformers 8
9 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 9
10 Thermal es and ageing Caused by the heating due to no-load and load losses Chemical Polymerization Depolymerization Physical Diffusion Expansion/contraction 10
11 Thermal ageing retardation Control possibilities Reduce temp. rises by new cooling stage control (overall loss of life optimization) Hot spot factor determination and control Proper material selection Initial moisture content Air sealing Forced cooling Design know how [1] [1] IEC Loading guide for oil-immersed power transformers 11
12 Manufacturer activities Continue verification cooling calculations Interfaces for dynamic calculation Cooling calculation for alternative insulation fluids Repair experience Post mortem analysis Material tests Supplier control 12
13 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 13
14 Electrical es and ageing Caused by the electrical field and the interaction within the insulation system Increased local temperatures Partial Discharge X-Wax Leakage current Creeping distance Electrical treeing Static electrification could appear 14
15 Electrical ageing retardation Control possibilities Proper material selection Supplier quality control PD free transformers Design and processing know how Calculation possibilities 15
16 Manufacturer activities Continuous adaptation of the transients package to needs of design departments, and to customer Testing and evaluation of new insulation components and materials Basic reproducible test and comparative investigations Optimize technology to ease production and deliver PD-free products 16
17 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 17
18 Ambient Caused by different ambient es the inner & outer systems of a Transformer could be damaged Humidity High/extreme low ambient temperature Altitude Pollution Wind Earthquake 18
19 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical 19
20 Mechanical Caused by acceleration during Transport Installation Operation inner & outer systems of a Transformer might be damaged 20
21 Operation conditions Transformer operating of the electrical insulation system Thermal Electrical Ambient Mechanical Real case studies shows a combination of es as well as interactions 21
22 Real case study #1 Sealed GSU Transformer Manufactured in 1952 Power: 8 MVA Rating: 115,5 / 5,25 kv Measurement of Degree of Polymerization (DP-value) in 1982 (after 30 years!!!) Phase 1: HV-winding, shielding ring: DP = 884 Phase 2: HV-winding, leads: DP = 902 Phase 3: HV-winding, winding insulation: DP =
23 #1: Actual Investigations 2011 (after around 60 years of operation) HV leads ~ 300 LV leads ~ 100 DP-distribution over winding height DP average =
24 Real case study #2 Sealed GSU Transformer Manufactured in 1966 Power:103 //51,5 / 51,5 MVA Rating:403// 16 / 16 kv Measurement of T1Q: 642 T1R: 449 T1S: 449 T1T: 704 Samples were taken from LV flexible connector Tests were performed according ISO 14453:
25 #2: Refurbishment Result in 2006 Measurement of De-polymerization (DP value) We expect a transformer rest life time of >13 years under the used load conditions for all 4 transformers. This assessment is based on the results of the performed measurements, the fact that the transformers are new sealed and that the insulation oil is purified. 25
26 In order to create a save energy supply worldwide we as power transformer manufacturers design, build and deliver reliable transformers as a fundamental responsibility Thank you for your attention! 26
Transformer Technology Seminar What to consider at Design Reviews
Pomona CA, May 24-25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Why to perform Design Review Meetings? To ensure both parties having the same understanding of the
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More informationTechnical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope
Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site
More informationPresentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 "Transformers"
CONSEIL INTERNATIONAL DES GRANDS RESEAUX ELECTRIQUES INTERNATIONAL COUNCIL ON LARGE ELECTRIC SYSTEMS STUDY COMMITTEE A2 TRANSFORMERS Presentation of CIGRE activities on Power Transformers C. Rajotte (CA)
More informationPresentation of CIGRE activities on Power Transformers. C. Rajotte (CA) Chairman SC A2 "Transformers"
CONSEIL INTERNATIONAL DES GRANDS RESEAUX ELECTRIQUES INTERNATIONAL COUNCIL ON LARGE ELECTRIC SYSTEMS STUDY COMMITTEE A2 TRANSFORMERS Presentation of CIGRE activities on Power Transformers C. Rajotte (CA)
More informationSiemens Transformer Technology Seminar Insulation & Thermal Design
Customer Technical Meeting Pomona, CA May 24 25, 2016 Siemens Transformer Technology Seminar Insulation & Thermal Design Siemens AG Transformers siemens.com/answers Winding Selection Windings: Page 2 Winding
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationSiemens Transformer Technology Seminar Low Partial Discharge Transformers
West Coast Technical Meeting Pomona CA, May 24-25, 2016 Siemens Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Low Partial Discharge Page 2 Why highlight Low Partial Discharge
More informationTransformer condition assessment with an integrated test van
Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)
More informationHVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N
S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV
More informationPES & IAS NY Chapter And NY LMAG June 23 rd, 2015
PES & IAS NY Chapter And NY LMAG June 23 rd, 2015 High Temperature Insulation Systems and their use in Mobile Transformers Myron B. Bell, PE mbell@deltastar.com Delta Star, Inc. June 23 rd 2015 Introduction
More informationOptimization of power transformers based on operative service conditions for improved performance
21, rue d Artois, F-75008 PARIS A2-207 CIGRE 2012 http : //www.cigre.org SUMMARY Optimization of power transformers based on operative service conditions for improved performance A.Prieto, M.Cuesto, P.Pacheco,
More informationABB Power Products Service
Raben Naidoo, Technology days, May 21-22th, 2014, Cape Town, South Africa, Enhanced availability of transformers via transformer remote monitoring - TEC ABB Power Products Service Why a session on availability?
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationCOMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3
CONTENTS COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3 CONSTRUCTION... 4 ~ 5 A. CORE AND FRAME... 4 B. COIL... 5 C. TEMPERATURE INDICATOR... 5 CHARACTERISTICS... 6 MANUFACTURING FACILITIES...
More informationTransformer Design: Economics & Reliability
Transformer Design: Economics & Reliability Weidmann-ACTI Inc. Technical Conference New Diagnostic Concepts for Better Asset Management November 8 10, 2004 Holiday Inn Capitol Plaza, Sacramento, CA H.
More informationDEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER
DEFERRING REPLACEMENT OF A 600 MVA, 345GRD Y/138GRD Y/ 13.8 kv SHELL TYPE WESTINGHOUSE AUTOTRANSFORMER JESSE M LOPEZ CPS ENERGY USA EMILIO MORALES CRUZ QUALITROL USA SUMMARY Power transformers are essential
More informationTransformer Technology Seminar Winding Selection
Pomona, CA May 24 25, 2016 Transformer Technology Seminar Siemens AG Transformers siemens.com/answers Windings: Page 2 Example GSU 274/464MVA H0 H1 H2 H3 U U I I H L H L N = N N = N L H H L HV: 405kV ±8x1.25%
More informationCASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division
CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More informationRESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)
More informationPower Transformers Basics
Power Transformers Basics Transformer Basic Objective Introduce Basic Transformer Theory as it Relates to Diagnostics Provide a Better Understanding of the Diagnostic Test Environment Identify Important
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationPerforming reliable and reproducible frequency response measurements on power transformers
Topic Performing reliable and reproducible frequency response measurements on power transformers Prof. Dr. Stephanie Uhrig, Munich University of Applied Sciences Michael Rädler, OMICRON electronics GmbH
More informationArild Furnes,ATPA OGP/Petrobras workshop, Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems
Arild Furnes,ATPA OGP/Petrobras workshop, 22.09.09 Dry type transformers-ideal for FPSO - Transformers for electrical and drive systems September 24, 2009 Slide 1 Transformers for Ships and Offshore -
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationPAPER. Dry-type transformer innovation: HiDry 72 for subtransmission lines
PAPER Title Dry-type transformer innovation: HiDry 72 for subtransmission lines Registration Nº: (Abstract) Authors of the paper Name Country e-mail Martin Carlen Switzerland martin.carlen@ch.abb.com Mariano
More informationEfacec work every day to anticipate solutions for a sustainable world in the new energy era.
Transformers Efacec is the largest industrial portuguese company of the electric and electromechanical sector developing high technology products, solutions and systems used every day by millions of people
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationPOWER TRANSFORMERS CATALOGUE
COMPANY INFORMATION ARTRANS S.A. started off as a small factory in April 2, 1982 located in Mendoza, Argentina. Now, three decades later it is a globally recognized manufacturer of distribution, transmission,
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationWorking Group Members
POWER TRANSFORMER - STANDARDISATION MANUAL 6 Chapter - 7 Design Review Working Group Members Mr. M. Vijayakumaran ALSTOM Ltd Mr. S. K. Negi Mr. Y. V. Joshi GETCO GETCO 6 POWER TRANSFORMER - STANDARDISATION
More information3. COMBINED TRANSFORMERS Oil-paper insulation
3. COMBINED TRANSFORMERS Oil-paper insulation 123 kv Combined transformers. 26 Instrument transformers High voltage INTRODUCTION Combined instrument transformers contain a current transformer and an inductive
More informationDispersing the clouds gain clear insight into your bushings using advanced diagnostic methods
Topic Dispersing the clouds gain clear insight into your bushings using advanced diagnostic methods Abstract: Bushing diagnosis can include various methods, from a simple visual inspection or a conventional
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60076-7 First edition 2005-12 Power transformers Part 7: Loading guide for oil-immersed power transformers IEC 2005 Copyright - all rights reserved No part of this publication
More informationEnergy Division. Bowthorpe LV/MV Surge Arresters
Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early
More informationInsulation Level and Test Technology of. 1000kV Power Transformer
Insulation Level and Test Technology of 1000kV Power Transformer Li Guangfan, Wang Xiaoning, Li Peng et al HIMALAYAL - SHANGHAI - CHINA Abstract: The insulation coordination for the first 1000kV UHVAC
More information2. Group Discussion Meeting in Paris Session 2014
CIGRE 2014 A2-00 SPECIAL REPORT FOR GROUP A2 (Transformer) Pawel WARCZYNSKI Energopomiar Elektryka - Poland - PS1 Gerhard GREVE - ABB AG Germany - PS2 Raj AHUJA SPX Corporation United States of America
More informationTransformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications
The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of
More informationWinding Temperature Measurement in a 154 kv Transformer Filled with Natural Ester Fluid
J Electr Eng Technol Vol. 8, No. 1: 156-162, 2013 http://dx.doi.org/10.5370/jeet.2013.8.1.156 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Winding Temperature Measurement in a 154 kv Transformer Filled
More informationUnderground System Design TADP 547
Underground System Design TADP 547 Industry Standards, Specifications and Guides Presentation 6.4 Instructor: Frank Frentzas Industry Organizations Several professional organizations develop standards
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationMots clés Power Transformer, Condition Assessment, On-line Monitoring Internet. Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM T&D, Germany
Benefit of sensors for on-line monitoring systems for power transformers Mots clés Power Transformer, Condition Assessment, On-line Monitoring Internet Par S. Tenbohlen *, T. Stirl, M. Rösner * * ALSTOM
More informationHOW TO SAFE GUARD THE TRANSFORMER..???
CPRI HOW TO SAFE GUARD THE TRANSFORMER..??? CPRI Efficient and Effective network planning, Design and Forecasting Highly Reliable and Stable Protection system and co-ordination Measures to mitigate various
More informationTransformer Shunt Fault Detection using Two Techniques
Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,
More informationLiquid-Filled Transformers
Liquid-Filled Transformers Custom Transformers at Standard Prices NIAGARA TRANSFORMER CORP. Induction Furnace Transformer Cycloconverter Rectifier Duty Transformer Arc Furnace Transformer Full Range of
More informationFederal Power Transformers LLC based in Abu Dhabi, UAE
www.fpt.ae Federal Power Transformers LLC based in Abu Dhabi, UAE CONTENTS The Company...03 Design Process...05 Manufacturing...07 Testing...11 Quality...13 After Sales Support & Other Services...15 Satisfied
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationCIGRE Liaison Report
Agenda October 22nd, 2012 CIGRE Liaison Report Overview of CIGRE 44 th Session U.S. Representation in CIGRÉ Study Committees Details on A2 Study Committee Details on B3 Study Committee Details on D1 Study
More informationTransformer Technology Seminar GIC Capability of Power Transformers
Pomona CA, May 24-25, 2016 Transformer Technology Seminar GIC Capability of Power Transformers Siemens AG Transformers siemens.com/answers Geo-magnetic Induced Current GIC resistant Transformers page 2
More informationAcoustic Emission in power transformers. Ajusco 15, Colonia Portales, Delegación Benito Juárez, C.P , México, D.F.
Acoustic Emission in power transformers 1 More expensive equipment in the substation Many years of operation First indication of a problem: Dissolved Gases Begin investigation to determine the origin of
More informationThe measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation
DIAGNOSIS The measurement and normalisation of dielectric dissipation factor for diagnostics of transformer insulation Introduction The Dielectric Dissipation Factor (DDF) is known as the loss factor or
More informationRevision of C Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components. Mike Spurlock Chairman
Revision of C57.143-2012 Guide for Application of Monitoring Equipment to Liquid Immersed Transformers and Components Mike Spurlock Chairman All participants in this meeting have certain obligations under
More informationCAST RESIN DRY TRANSFORMER
CAST RESIN DRY TRANSFORMER Majority owned subsidiary company of ELETTROMECCANICA COLOMBO s.a.s., Italy Elettromeccanica India Elettromeccanica India Pvt Ltd (EIPL) is a joint-venture company with Elettromeccanica,
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationArc Suppression Coils
Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More informationDielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction
DIAGNOSIS ABSTRACT Dielectric tests have been used for decades for diagnosis of power transformers and bushings. In addition to the traditional tests at line frequency, modern types of dielectric tests
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION IEC TS 60076-14 First edition 2004-11 Power transformers Part 14: Design and application of liquid-immersed power transformers using high-temperature insulation materials This English-language
More informationAustralian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS
AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement
More informationConvincing technology creates compact performance
siemens.com/energy Convincing technology creates compact performance The GEAFOL Basic: the optimum foundation for power distribution Answers for energy. Contents The GEAFOL Basic: A true GEAFOL and more
More informationRegional Technical Seminar
Regional Technical Seminar TRANSFORMER 101 Transformer 101 Dharam Vir Vice President of Engineering Dharam.Vir@spx.com Agenda 1.Review transformers: How they work (textbook vs reality) 2.How do we build
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationSGMF(T) series. Onsite Mobile AC High Voltage Test System. Applications:
SGMF(T) series Onsite Mobile AC High Voltage Test System On-site AC high voltage test systems are used for voltage withstanding test, partial discharge measurement, tan delta measurement on those instrument
More informationOnsite Mobile AC High Voltage Test System
TSGMF(T) series Onsite Mobile AC High Voltage Test System Onsite mobile AC high voltage test systems are used for withstand voltage testing, partial discharge measurement, tan delta measurement to instrument
More informationRegional Technical Seminar SHORT CIRCUIT FORCES
Regional Technical Seminar SHORT CIRCUIT FORCES Short Circuit Forces Wallace Exum Electrical Design Engineer wallace.exum@spx.com Agenda 1. What is Short Circuit 2. Types of Faults 3. How to Calculate
More informationMaintenance & Diagnosis Strategies. for. High Voltage Substations
Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils
More information- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.
QTMS The transformer monitor shall provide data integration platform, cooling supervision & monitoring. User configurable without need of a technician, a 100% configurable to specific customer requirement.
More informationCholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service
Cholla T809 Condition Assessment Report Provided by students of Northern Arizona University with the support of Arizona Public Service Andrew Morin, Richard Barnes, Kyle Wiedeman, Scott Lederhos, Kenneth
More informationLife Prediction of Mold Transformer for Urban Rail
, pp.13-18 http://dx.doi.org/10.14257/astl.2014.48.03 Life Prediction of Mold Transformer for Urban Rail Hyun-il Kang and Won-seok Choi Department of Electrical Engineering, Hanbat National University,
More informationAC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER
AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual
More informationAutomatic Transformer Winding Analyser
2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance
More informationHOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS
HOT SPOT STUDIES FOR SHEET WOUND TRANSFORMER WINDINGS Sheldon P. Kennedy, Thomas Gordner Niagara Transformer Jean-Noel Bérubé Qualitrol / Neoptix Robert Ringlee, Jacques Aubin Consultant ABSTRACT Application
More informationApplication of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation
CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant
More informationVariation in SFRA plot due to design and external parameter
Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements
More informationAS/NZS :2013 (IEC , , MOD)
AS/NZS 60076.7:2013 (IEC 60076-7, Ed. 1.0 2005, MOD) Australian/New Zealand Standard Power transformers Part 7: Loading guide for oil-immersed power transformers AS/NZS 60076.7:2013 AS/NZS 60076.7:2013
More informationAutotransformer Condition Monitoring Systems
Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following
More informationWe can classify test failure modes in power transformers according to transformer components
ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It
More informationPD Diagnostic Applications and TechImp solutions
PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006
More informationN S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon
N S Sodha, Former Executive Director, POWERGRID Corpn, Gurgaon POWER TRANSFORMERS Factory condition POWER TRANSFORMERS Site condition POWER TRANSFORMER FAULTS Faults in a Transformer 1. Internal Faults
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationTECHIMP Power Transformer Monitoring
TECHIMP Power Transformer Monitoring Kontakt: Martin Hesse Techimp Germany GmbH i.g. E-Mail: mhesse@techimp.com Tel.: +49 5724 391 007 Mobil: +49 170 2364 735 PD Monitoring of Power Transformers Power
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationDesign Improvement by Diagnostics of Transformers still in Operation and of Apparatuses taken out of Service
Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque, 13-15 Nov 2006 "New Diagnostic Concepts for Better Asset Management" Weidmann-ACTI Inc. Fifth Annual Technical Conference, Albuquerque,
More informationMatz Ohlen Director Transformer Test Systems. Megger Sweden
Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance
More informationINCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR
INCREASE TRANSFORMER RELIABILITY AND AVAILBILITY: FROM CONDITION ASSESSMENT TO SITE REPAIR Pierre Lorin Pravin Khanna Peter Werle Lars Eklund pravin.t.khanna@us.abb.com peter.werle@de.abb.com ABB Transformers
More informationPower Factor Insulation Diagnosis: Demystifying Standard Practices
Power Factor Insulation Diagnosis: Demystifying Standard Practices Dinesh Chhajer, PE 4271 Bronze Way, Dallas Tx Phone: (214) 330 3238 Email: dinesh.chhajer@megger.com ABSTRACT Power Factor (PF) testing
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationFault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 1. Introduction Fault location on communication and power cables
More informationMV Power Cable Testing Training
MV Power Cable Testing Training Contact us Today for a FREE quotation to deliver this course at your company?s location. https://www.electricityforum.com/onsite-training-rfq Since power cables are used
More informationIN ELECTRICAL ENGINEERING - I C M E T CRAIOVA
Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes
More informationB3-102 THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV SUBSTATIONS
21, rue d'artois, F-75008 Paris http://www.cigre.org B3-102 Session 2004 CIGRÉ THE ROMANIAN EXPERIENCE REGARDING THE RISK OF MANAGEMENT IN THE OPERATION AND MAINTENANCE OF LARGE POWER TRANSFORMERS IN HV
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationTechnical recommendation for the purchase of Real Time Thermal Rating for transformers
Version: 1.0 Date of Issue: December 2014 1 Technical recommendation for the purchase of Real Time Thermal Rating for transformers 1 Purpose The purpose of this document is to set out and describe the
More informationEE223D: Distribution Power Transformer
EE223D: Distribution Power Transformer Aug 07-09, 2018 / Dubai EE223 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive course is designed to provide participants with the skills
More informationPower transformers for Network, Rectifiers, Furnace
E N G L I S H OTN, OTR, OTF Transformers Power transformers for Network, Rectifiers, Furnace TTR TTO OTN, OTR, OTF reactors TTH OTN, OTR, OTF Transformers Technology Design Our designers experience combined
More informationPrimary Test Manager (PTM) Testing and management software for primary assets
Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear
More information