Chapter 7 Conclusion 7.1 General
|
|
- Nickolas Shaw
- 5 years ago
- Views:
Transcription
1 Chapter General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due to deformation. It is therefore necessary to detect deformation as early as possible before they lead to problems or failures. Mechanical deformations do not necessarily change the operational characteristics of the transformer. Minor deformation in the winding of a transformer indicates no significant change in the operational characteristics, but mechanical properties of the copper might be changed seriously risking rupture on next event. Less severe deformations involve insulation rupture and partial discharges which after some time normally are discovered through oil analysis or tripping the buchholz relay. Conventional condition monitoring techniques such as dissolved gas analysis (DGA), Capacitance & Power factor and leakage reactance test are unlikely to be able to detect such minor mechanical damage until it develops into a dielectric or thermal fault. So, a specialist technique is clearly required for the monitoring and assessment of mechanical condition of the transformer and to be able to detect the incipient fault in transformer. The SFRA is a powerful method for the detection and diagnosis of the defects in the active part of power transformers. It can deliver valuable information about the mechanical as well as electrical condition of core, windings, internal connections and contacts. No other single test method for the condition assessment of power transformers can deliver such a diversity of information. Therefore the SFRA is an increasingly popular test Sweep Frequency Response Analysis (SFRA) is a tool that can give an indication of core or winding movement in transformers. This is done by performing a measurement, a simple one, looking at how well a transformer winding transmits a low voltage signal that varies in frequency. Just how well a transformer does this is related to its impedance, the capacitive and inductive 176
2 elements of which are intimately related to the physical construction of the transformer. Changes in frequency response as measured by SFRA techniques may indicate a physical change inside the transformer, the cause of which then needs to be identified and investigated. SFRA has been a key tool in the decision to scrap or reenergize a transformer. To get value from an SFRA test it is necessary to make sure that the measurements are credible, which requires good test technique and simple procedures; proper training is thus essential to control the measurement process. However special care must be taken both in application of the test to acceptable standards and in interpretation of the tests results to gain value from the tests themselves. When interpreting a trace, it is important to make use of all the information present to look at the whole picture. Small variations or displacements across a large frequency range may be much more important than a large variation in one part of the frequency range. In analyzing traces, lower frequencies tend to relate to larger objects; higher frequencies relate to smaller objects. In terms of size there is a general rule of thumb that, while reviewing a trace from left to right, from 20 Hz to 2 MHz, this corresponds to the core, clamping structure and yoke, main windings, tap leads and connecting leads. The actual position of resonances in the trace depends on the size of the transformer; lower MVA transformers tend to have their resonance shifted more to the higher frequencies. However, there are always exceptions to this rule of thumb and individual traces should be inspected on their merits. 177
3 7.2 Summary of Important Findings The following conclusions have been made regarding the simulated fault conditions Winding Earth Fault Damages HV U Phase Earth Fault & LV W Phase Earth Fault We can conclude from the practically simulated earth fault damages that the nature of the SFRA traces related to an earth fault depends on the connection of the winding, i.e. winding is Delta connected or Star connected. When transformer has developed earth fault in one phase of the delta connected winding, then following points are analyzed. There is a huge difference in the starting db value of the three phase open circuit frequency responses. (In our case, it is -45 db, -62 db and -92 db respectively) There is also a huge difference in the starting db value of the three phase short-circuit frequency responses. (In our case, it is -25 db, -28 db and -75 db respectively) The open circuit and short-circuit frequency responses shows the disturbances at low frequency in the two phases even though the earth fault has been developed at one phase. When transformer has developed earth fault in one phase of star connected winding then following point is analyzed. The open circuit frequency response of that phase shows that the impedance value of it is lower in low frequency range and high in medium & high frequency range as compared to the other healthy phases. It is possible to identify Earth Fault by other conventional method like TanDelta, Exciting Currents, Insulation Resistance, TTR, etc. SFRA when used in conjunction with other diagnostic tools can provide a complete condition assessment of the transformer. 178
4 7.2.2 Short Circuited Turns or Lost Turns or Turn to Turn Short Fault Damage HV Tapping Short in V Phase When transformer has developed short circuited turns in one phase of the either winding, i.e. HV winding or LV winding then following points are analyzed. The open circuit frequency response of one phase (In our case it is V phase) of HV winding is different than the other two phases, and the first resonance is absent in the low frequency range, The open circuit frequency response of similar phase ( V phase) (as HV winding has) of LV winding is different than the other two phases, and also the first resonance is absent in the low frequency range (as HV winding has). The difference in the db value of the open circuit frequency response of the fault indicating phase with respect to other two healthy phases in the low frequency range of which winding ( HV or LV) is more, the actual lost of turns fault exist in that phase of a winding. It is possible to identify lost turns fault by other conventional method like no load excitation current, turns ratio and magnetic balance test, but in which winding HV or LV winding is a question mark. SFRA is the only test which can identify the winding and phase both of the lost turns fault if analysis is done with proper knowledge and experience Multiple Winding Fault Damages HV V Phase Tap Short + LV V Phase Earth Fault HV Winding: When the first resonance in the low frequency range is absent in the open circuit frequency response of any phase of HV or LV winding and then it merges with the other open circuit frequency responses of two phases in the medium and high frequency range, than it indicates that the short circuited turns fault has been developed in that phase of that winding. It can be found from other conventional method like, No Load Excitation Current, Turns Ratio and Magnetic Balance test also. LV Winding: When the open circuit frequency response of any phase of star connected winding shows that the impedance value of it is lower in low frequency 179
5 range and high in medium & high frequency range as compared to the other healthy phases than it indicates that the earth fault has been developed in that phase of star connected winding. It is possible to identify Earth Fault by other conventional method like, Tan Delta, Exciting Currents, Insulation Resistance, and TTR also. Based on the above SFRA data analysis it is concluded that the transformer has developed multiple winding fault, i.e. short circuited turns fault (i.e. Tap short fault) in V phase of HV winding and earth fault in V phase of LV winding. SFRA is able to identify both the faults very clearly which is not possible to achieve by only single test by any other method. It is the experience and interpretation of SFRA results plays a major role in identifying such multiple faults in transformer HV & LV Winding Short Fault Damage - HV & LV V Phase Short Fault Based on the SFRA data analysis it is concluded that when the transformer has developed HV and LV V phase short fault then following points are analyzed related to HV & LV windings. HV winding: The measured open circuit frequency response and the measured short circuit frequency response of HV winding shows that, U and V phase have problem due to V phase of HV delta connected winding is getting shorted to the V phase of LV star connected winding. LV winding: The measured open circuit frequency response of LV winding shows that at low frequency, U & V phase have problems where as at higher frequency, only V phase has problem due to V phase of HV winding is getting shorted to the V phase of LV winding Neutral & Phase of LV Star winding Short Fault Damage LV N & U Short Fault Based on the SFRA data analysis, it is concluded that when the U phase of LV winding is getting shorted with the neutral, i.e. when the transformer has developed short-circuited winding fault in U phase of LV winding. (LV N & U Short) then following points are analyzed. 180
6 Due to star connected LV N & U Short fault, the open circuit frequency response of U phase of delta connected HV winding is looks as the short circuit frequency response of it. When the winding of one phase is short circuited with the neutral, then the impedance value of open circuit frequency of that winding (In our case it is U phase) is 0 db throughout the whole frequency range Phase to Phase Short Fault Damage in LV Star Winding LV U & V Short Fault When the transformer has developed two windings of U & V phase short circuited fault in LV winding. then following points are analyzed.. Due to two phases U & V of LV star winding are short circuited, its effect can be seen in the open circuit frequency responses of U & V phase of HV delta winding. It happens because of impedance of LV winding has been shifted into the HV winding. The open circuit frequency responses of U phase (2U 2N) and V phase (2V 2N) of LV winding have the same shape and similar, but are different than the open circuit frequency response of W phase (2W 2N) which appears to be normal. The impedance value of open circuit frequency response of U phase & V phase of LV winding is same and is lower than the impedance value of W phase throughout the whole frequency range. It can happen if the SFRA signal is getting two windings short circuited path Winding Open Circuit and Short Circuit Fault Damages HV W phase open fault and HV U and V short fault damages. We can conclude from the practically simulated HV W Phase open fault & HV U & V Short fault damages that when transformer has developed open circuited winding fault in HV delta connected winding and when transformer has developed short circuited winding fault in HV delta connected winding then its SFRA responses consist following characteristics. 181
7 When any phase of delta connected HV winding is open circuited then following points are analyzed. The open circuit frequency responses of three phase of HV winding are similar and having general shape as delta connected winding has. The short circuit frequency response of faulty phase (open circuited phase) has higher starting db value than the starting db value of other two healthy phases and then short circuit frequency responses of all the three phases of HV windings have similar shape from medium frequency to higher frequency (in our case it is from 30 KHz to 2 MHz frequency) The open circuit frequency response of similar (faulty phase of HV winding) phase of LV star connected winding is different than the open circuit frequency responses of other two phases in only low frequency ranges (in our case it is from 1 KHZ to 10 KHZ frequency). When any phase of delta connected HV winding is short circuited then following points are analyzed. The starting db value of faulty phase (short circuited phase) of open circuit frequency response of HV delta connected winding is 0 db and it remains 0 db up to high frequency (in our case it is 200 KHZ frequency) and then increases up to few db (in our case it is -7 db) at 2 MHz frequency. The short circuit frequency response of faulty phase (short circuited phase) is similar as its open circuit frequency response. The starting db value of open circuit frequency response of similar (faulty phase of HV winding) phase of LV star connected winding is 0 db and it remains 0 db up to low frequency (in our case it is 2 KHz frequency) and then it is merged with the open circuit frequency responses of other two phases at medium lower frequency (in our case it is 25 KHZ frequency). 182
8 7.2.8 Multiple Short Circuit Winding Fault Damages HV U & V and LV V & W Short Fault When the transformer has developed multiple short circuited winding fault, i.e. in HV winding U & V phase short and in LV winding V and W phase short, then following points are analyzed. HV Winding: The open circuit frequency response and short circuit frequency response of HV U phase is same and having 0 db value up to 200 khz frequency. It indicates that the winding of HV U phase (1U 1V) is getting short circuited. The open circuit frequency responses and short circuit frequency responses of HV V & W phase are same and they have starting db value of -22 db in both the cases. It indicates that the two windings of V & W phases of LV winding are short circuited. LV Winding: The starting db values of the open circuit frequency responses of all the three phases of LV winding are 0 db and it remains 0 up to 2 khz frequency for U phase response and remains 0 up to 4 khz frequency for V and W phase responses. The impedance value of V & W phases is lower than the impedance value of U phase from 2 khz to 2 MHz frequency. Above can happen if the V & W phases of LV winding are short circuited and U phase of HV winding is short circuited Winding & Core Short Fault Damages LV V & Core Short and HV V & Core Short fault damages We can conclude from the above practically simulated core & LV V phase winding short fault and core & HV V phase winding short fault damages that the nature of the SFRA traces related to core & winding short fault is different for the Star connected winding and Delta connected winding. When transformer has developed core & winding short fault at one phase of star connected winding then following point is analyzed. 183
9 The open circuit frequency response of the phase which is shorted with the core and the open circuit frequency responses of the other two healthy phases are similar and having general shape up to high frequency (in our case it is 100 KHz frequency) and then after that frequency, the open circuit frequency response of that shorted phase has different magnitudes of inductive and capacitive resonances than the open circuit frequency responses of the other two phases. When transformer has developed core & winding short fault at one phase of delta connected winding then following points are analyzed. The open circuit and short circuit frequency responses of the two phases have the same and lesser impedance value with respect to open circuit and short circuit frequency response of the third phase between medium frequency to high frequency range. (in our case it is from 30 KHz to 2 MHz frequency) Due to delta connection, the short circuit occurs at one phase of the winding and the core; its effect can be seen in the other phase also Core and Frame Short Fault Damage Practically simulated core and frame short fault on the transformer could not be identified by when the data analysis is performed on three phase comparison basis. When SFRA data analysis of Core & Frame Short Fault has been done (for the Dyn11 transformer) on the basis of the comparisons can be made against the baselines and previous data then following points are analyzed. The open circuit frequency response of U phase, V phase and W phase of HV winding for the core & frame short fault condition is having lesser impedance value (In our case it is of 2.5 db, 5.0 db and 7.5 db respectively) than the open circuit frequency response of U phase, V phase and W phase of HV winding for the healthy condition of transformer at lower frequency (In our case it is 10 khz frequency). The measured short circuit frequency response of U phase and V phase of HV winding for the core & frame short fault condition is having higher impedance value (In our case it is of 9 db and 4 db respectively) than the measured short circuit frequency response of U phase and V phase of HV winding for the 184
10 healthy condition of transformer where as the measured short circuit frequency response of W phase of HV winding for the core & frame short fault condition is having lesser impedance value (in our case it is 5 db). than the measured short circuit frequency response of W phase of HV winding for the healthy condition of transformer at medium frequency (In our case it is 28 khz frequency) The measured open circuit frequency response of U phase, V phase and W phase of LV winding for the core & frame short fault condition is different than the measured open circuit frequency response of U phase, V phase and W phase of LV winding for the healthy condition of the transformer at higher frequency (In our case it is after 300 khz frequency) Coil and Core Assembly Displacement (CCA displaced by 30 mm approx.) Practically simulated Coil and Core Assembly displacement (CCA displacement) for 30 mm (approx.) displacement fault on the transformer could not be identified by when the data analysis is performed on three phase comparison basis and when the data analysis is performed on the basis of the comparisons can be made against the baselines and previous data also. 7.3 Future Scope of Research Work Consequent to investigations carried out in this thesis, the following aspects are being suggested as future research work to be carried out. The first important step towards improving FRA interpretation is to ensure that the measurement is of good quality, as presented in chapter 4 of this thesis.. When the quality of the measurement is confirmed and the frequency range for interpretation assessed, the visual inspection of the variations between the test and the reference results is the actual approach for FRA interpretation. The experimental work provided in this thesis shows how various faults can be detected by FRA. 185
11 The following aspects are being suggested to improve FRA interpretation as future research work. Compare the sensitivity of the different FRA test types i.e. end-to-end (open and short circuit), capacitive inter-winding, and inductive inter-winding to detect different transformer failure modes. Assess the possibility of detecting faults by comparing the results obtained using both directions of end-to-end tests when no reference result is available. Transformer modeling based on geometrical parameters as a means to support the interpretation and derive a fundamental understanding of the FRA resonances, possibly also to generate a kind of database collecting the effects of different winding damage on the FRA spectra. 186
Vallabh Vidyanagar, Anand, INDIA
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis
More informationBenefits of SFRA - Case Studies
6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO
More informationINTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER
Volume: 03 Issue: 07 July16 www.irjet.net p-issn: 2395-0072 INTERPRETATION METHODOLOGY TO IDENTIFY FAULT LOCATION IN A POWER TRANSFORMER Sameer S. Patel 1, 1 Student, Electrical Dept, Rajasthan Institute
More informationMatz Ohlen Director Transformer Test Systems. Megger Sweden
Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser - OMICRON Transformers Diagnostic Testing - OVERALL DGA Oil Screen Power Factor / Capacitance Exciting Current Transformer
More informationVariation in SFRA plot due to design and external parameter
Chapter 6 Variation in SFRA plot due to design and external parameter 6.1 Introduction As the experience grows with Sweep Frequency Response Analysis in world, it is useful to discuss the measurements
More informationInvestigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)
Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA) Priti G 1*, Sindekar AS 2 P.G. Scholar, Department of Electrical Engineering, Government College of
More informationFault Detection in Transformer Using Frequency (Sweep) Response Analysis
Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Miss. Kajal R. Pachbhai PG Student at Ballarpur Institute of Technology, Ballarpur-442701 India kajalpachbhai86@gmail.com Mr. Sagar
More informationTesTIng of Power. Transformers are the largest, most. feature. By brandon dupuis
feature By brandon dupuis An Introduction to Electrical diagnostic TesTIng of Power Transformers 38 Transformers are the largest, most expensive, and highly critical components of most utility substations.
More informationUnderstanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA
Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser, OMICRON electronics Corp. USA Understanding the Value of Electrical Testing for Power Transformers Charles Sweetser,
More informationRESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS
RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)
More informationField Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis
Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Ambuj Kumar, Sunil Kumar Singh, Shrikant Singh Abstract Sweep frequency response analysis has been turning out a
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More informationAdvanced Diagnostic Testing Services. Provides detailed and reliable results
Advanced Diagnostic Testing Services Provides detailed and reliable results Advanced Diagnostic Testing Services from the world s leading manufacturer of power transformers ABB leadership begins with our
More informationIJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):
IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online): 2321-0613 Conditioning Monitoring of Transformer Using Sweep Frequency Response for Winding Deformation
More informationInnovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Dr. Michael Krüger, Alexander Kraetge, OMICRON electronics GmbH, Austria Alexander
More informationCASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION. - S K Mishra & S K Das NHPC Ltd O&M Division
CASE STUDY- FAULT IN POWER TRANSFORMER AT LOKTAK POWER STATION - S K Mishra & S K Das NHPC Ltd O&M Division 1 PRESENTATION COVERS Introduction DESCRIPTION OF EVENTS INITIAL RESPONSE DETAILED INSPECTION
More informationOMICRON Seminar on Substation Testing and Diagnosis. October 23, 2017 Dubai, United Arab Emirates. October 24, 2017 Abu Dhabi, United Arab Emirates
OMICRON Seminar on Substation Testing and Diagnosis October 23, 2017 Dubai, United Arab Emirates October 24, 2017 Abu Dhabi, United Arab Emirates Time Optimized Substation Asset Testing and Diagnosis Agenda
More informationEffective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers
Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers Alexander Dierks, Herman Viljoen, Alectrix (Pty) Ltd, South Africa
More informationREPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD.
REPORT ON INVESTIGATION OF FAILURE OF 100 MVA, 220/66-33/11 KV POWER TRANSFORMER AT 220KV GEETA COLONY SUBSTATION OF DELHI TRANSCO LTD. (DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/2015-16/Mgr(T)O&M-E-2/22
More informationImportance of Transformer Demagnetization
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance
More informationSAMPLE. Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs.
Keep Powering On SAMPLE Determining the health of your power transformer begins with Transformer Clinic s SAMPLE testing programs. Overheating, arcing, partial discharge, and other active or slow-evolving
More informationEffective maintenance test techniques for power transformers
Effective maintenance test techniques for power transformers by Alexander Dierks, Herman Viljoen, Alectrix, South Africa, and Dr. Michael Krüger, Omicron Electronics, Austria Due to ever-increasing pressure
More informationTRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING
Training Title TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING Training Duration 5 days Training Date Transformer Operational Principles, Selection & Troubleshooting 5 15 19 Nov $4,250
More informationTransformers handling and transport
Special tests (Credit: http://www.breakbulk.com/wp-content/uploads/2015/02/20141117160247x.jpg) Transformers handling and transport Damages that may arise and how to find them Table of contents summary
More informationDiscipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1
Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector
More informationEPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY
EPS AUSTRALIA SERVICES HV TESTING & COMMISSIONING CAPABILITY EPS AUSTRALIA SERVICES COMPANY OVERVIEW EPS is a recognised company specialising in Electrical, Instrumentation, Structural, Mechanical and
More informationA Literature Survey on Frequency Response Analysis for Detection of Transformer Winding Fault
IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 07, 2015 ISSN (online): 2321-0613 A Literature Survey on Frequency Response Analysis for Detection of Transformer Winding
More informationEFFECETIVE TRANSFORMER CONDITION ASSESSMENT
EFFECETIVE TRANSFORMER CONDITION ASSESSMENT Luwendran Moodley, Doble Engineering Africa Abstract. This paper details a novel approach to transformer condition assessment. This method has proven itself
More informationSERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT
SERVICE OFFERINGS FOR POWER SYSTEM STUDY & CONDITION MONITORING FOR STATIC EQUIPMENT Page TABLE OF CONTENTS POWER SYSTEM STUDY: 5 DATA COLLECTION AND NETWORK MODELLING 5 LOAD FLOW STUDY 5 SHORT CIRCUIT
More informationFRAX Series Sweep Frequency Response Analyzers
FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built
More informationFAULT IDENTIFICATION IN TRANSFORMER WINDING
FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract
More informationTraining Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.
Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training
More informationOperational Management of Grid Transformers An Experience of POWERGRID
Operational Management of Grid Transformers An Experience of POWERGRID 1.0 Introduction P.N. Dixit, GM; S. Victor, AGM; V.K. Bhaskar, CM; Gunjan Agrawal, Manager Operation Services Department Power Grid
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationAutomatic Transformer Winding Analyser
2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance
More informationHIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24
LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should
More informationAnalysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation
ARCHIVES OF ELECTRICAL ENGINEERING VOL. 67(1), pp. 51 64 (2018) DOI 10.24425/118991 Analysis of Frequency Response measurement results with end-to-end/interwinding test setup correlation SZYMON BANASZAK,
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationFRANEO 800. The next generation for a reliable core and winding diagnosis of power transformers
FRANEO 800 The next generation for a reliable core and winding diagnosis of power transformers The next generation of power transfor Mechanical or electrical problems in power transformer windings, contacts
More informationAfrica Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound
Africa Utility Week Focus Day 2014 Substation Condition Monitoring Benefits of Ultrasound Agenda Review - Substation Condition Monitoring Electrical discharge Types and origin In switchgear Results/consequences
More informationFRAX Series Sweep Frequency Response Analyzers
FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software Imports data from other
More informationEXPERIENCE WITH DETECTION AND IDENTIFICATION OF WINDING BUCKLING IN POWER TRANSFORMERS. Victor V. Sokolov and Boris V. Vanin ZTZ-Service Company
EXPERENCE WTH DETECTON AND DENTFCATON OF WNDNG BUCKLNG N POWER TRANSFORMERS Victor V. Sokolov and Boris V. Vanin ZTZ-Service Company ABSTRACT The paper summarizes experience with identification of buckling
More informationApplication of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation
CIGRE SC A1 & D1 JOINT COLLOQUIUM October 24, 2007 Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation S. A. BHUMIWAT Independent Consultant
More informationCHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES
CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationAssessment of Winding Deformation in Power Transformer using SFRA and Numerical Techniques Ashwini Bhujangrao Gaikwad
Assessment of Winding Deformation in Power Transformer using SFRA and Numerical Techniques Ashwini Bhujangrao Gaikwad Department of Electrical Engineering National Institute of Technology Rourkela Assessment
More informationTECHNIQUES AND STANDARD
TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies
More informationTechnical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope
Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site
More informationTest description for dry-type transformers chapter for special tests
Test description for dry-type transformers chapter for special tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 4. SOUND LEVEL MEASUREMENT 7 4.1. STANDARD 7 4.2. AIM 7 4.3. THEORETICAL PRINCIPAL
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER
ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK 1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department of Measurement and Applied Electrical Engineering, Faculty of Electrical
More informationTransformer condition assessment with an integrated test van
Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)
More informationCircuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method
Circuit design for reproducible on-site measurements of transfer function on large power transformers using the SFRA method C. Homagk 1*, T. Leibfried 1, K. Mössner 1 and R. Fischer 1 Institute of Electric
More informationPower systems 2: Transformation
Power systems 2: Transformation Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. s you will recall from our Introduction to
More informationTransformer Factory Testing
Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationPower Transformer Condition Assessment Based on Standard Diagnosis
Power Transformer Condition Assessment Based on Standard Cattareeya Suwanasri Abstract The diagnostic techniques of electrical and insulating oil testing are proposed to assess the internal condition of
More informationResearch Article Transformer Winding Deformation Profile using Modified Electrical Equivalent Circuit
Research Journal of Applied Sciences, Engineering and Technology 9(4): 288-295, 215 DOI:1.1926/rjaset.9.147 ISSN: 24-7459; e-issn: 24-7467 215 Maxwell Scientific Publication Corp. Submitted: August 13,
More informationTransformer Shunt Fault Detection using Two Techniques
Transformer Shunt Fault Detection using Two Techniques Swathy Sasikumar 1, Dr. V. A. Kulkarni 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationShunt Capacitance Influences on Single-Phase Transformer FRA Spectrum
213 Electrical Insulation Conference, #25 Ottawa, Ontario, Canada, 2 to 5 June 213 Shunt Capacitance Influences on Single-Phase Transformer FRA Spectrum Mehdi Bagheri *, B.T. Phung *, Trevor Blackburn
More informationWe can classify test failure modes in power transformers according to transformer components
ON-SITE TESTS We can classify test failure modes in power transformers according to transformer components ABSTRACT To prevent unexpected outages it is necessary to implement a field test programme. It
More informationANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER
POWER ENGINEERING AND ELECTRICAL ENGINEERING, VOL. 9, NO. 2, JUNE 2011 65 ANALYSIS OF TRANSIENT ACTIONS INFLUENCE IN POWER TRANSFORMER Jozef JURCIK.1, Miroslav GUTTEN 1, Daniel KORENCIAK 1 1 Department
More informationDemagnetization of Power Transformers Following a DC Resistance Testing
Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.
More informationCHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS
38 CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 3.1 INTRODUCTION Addition of more generating capacity and interconnections to meet the ever increasing power demand are resulted in
More informationCondition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology
Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of
More informationIVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1
Hour 3 slide Three Phase Transformer (sect. 2.6) A set of three similar single phase transformers may be connected to form a three-phase transformer (three-phase transformer bank). The primary and secondary
More informationDiagnostic testing of cast resin transformers
Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com
More informationPower Measurements and Basic Electrical Diagnostic Tests
Power Measurements and Basic Electrical Diagnostic Tests Instrument Basics Burden VA Sources V and I Meters V and I KVL and KCL Kelvin Connection KVL and KCL Kelvin Connection 4-Wire Technique Exclude
More informationPomona, CA May 24 & 25, LTC Applications - Location, Series & Preventative Auto Transformers
Pomona, CA May 24 & 25, 2016 LTC Applications - Location, Series & Preventative Auto s siemens.com/answers Introduction Tap changer at active part Example of 3-phase tapchanger Page 2 Winding Configurations
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationHands-On Transformer Testing and Maintenance
Hands-On Course Description This Hands-On course will teach you how to prioritize your transformer maintenance strategy, stretch your maintenance budget and at the same time maximize the life and condition
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationFIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC.
Regional Technical Seminar FIELD ELECTRICAL TESTING SPX TRANSFORMER SOLUTIONS, INC. Field Electrical Testing Applications Key Purposes of Field Electrical Testing: Receiving inspection Acceptance testing/commissioning
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationPerforming reliable and reproducible frequency response measurements on power transformers
Topic Performing reliable and reproducible frequency response measurements on power transformers Prof. Dr. Stephanie Uhrig, Munich University of Applied Sciences Michael Rädler, OMICRON electronics GmbH
More informationCONTENTS. 1. Introduction Generating Stations 9 40
CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific
More informationPDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics
PDS100 Application Note: The use of High Frequency Current Transformer as sensor for Transformer diagnostics CASE STUDY 1 (Doble Client Conference 2011, ACCA committee meeting) Dissolved Gas Analysis (DGA)
More informationTransformer Engineering
Transformer Engineering Design, Technology, and Diagnostics Second Edition S.V. Kulkarni S.A. Khaparde / 0 \ CRC Press \Cf*' J Taylor & Francis Group ^ч_^^ Boca Raton London NewYork CRC Press is an imprint
More informationMaintenance & Diagnosis Strategies. for. High Voltage Substations
Maintenance & Diagnosis Strategies for High Voltage Substations 1/ 52 Robin Fischer, 28 April 2004 Diagnosis of Substation Equipment Power Transformers Instrument Transformers Switch-Gears Breakers Coils
More informationCHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION
18 CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 2.1 INTRODUCTION Transformers are subjected to a variety of electrical, mechanical and thermal stresses during normal life time and they fail when these
More informationON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS
ON-LINE PARTIAL DISCHARGE DETECTION ON TRANSFORMERS Pantelis D. AGORIS 1, Sander MEIJER 1, Edward GULSKI 1, Johan J. SMIT 1, A. Jos L.M. KANTERS 2 1 Delft University of Technology - The Netherlands 2 TenneT
More informationIN ELECTRICAL ENGINEERING - I C M E T CRAIOVA
Taking into account that power transformer is the major item of equipment in power systems, its correct operation is vital to system operation. It is well known that transformer failures are sometimes
More informationTransient Recovery Voltage at Transformer Limited Fault Clearing
Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.
More informationThe importance of partial discharge testing throughout the development and operation of power transformers
The importance of partial discharge testing throughout the development and operation of power transformers Ulrike Broniecki OMICRON Energy Solutions GmbH, Berlin Power transformers are exposed to intense
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationTransformer Winding Deformation Analysis using SFRA Technique
Journal for Research Volume 01 Issue 11 January 2016 ISSN: 2395-7549 Transformer Winding Deformation Analysis using SFRA Technique Mr. Patil Ritesh Anil PG Student Prof. G.K.Mahajan Associate Professor
More informationEE059: Transformer Operation, Maintenance, Diagnosis & Testing
EE059: Transformer Operation, Maintenance, Diagnosis & Testing EE059 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: Power and distribution transformers are essential devices in electricity
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationDielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor
Dielectric response and partial discharge measurements on stator insulation at varied low frequency Nathaniel Taylor Rotating Electrical Machines : The Stator and its Windings turbo-generator motor hydro-generator
More information12 Transformers and other Equipment for Switchgear Installations
12 Transformers and other Equipment for Switchgear Installations 12.1 Transformers 12.1.1 Design, types and dimensions The purpose of transformers is to transfer electrical energy from systems of one voltage
More informationReport on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)
Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated
More informationTertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.
Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing
More information, ,54 A
AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate
More informationCase Studies of Electric Power Equipment Diagnostics Using Acoustic Emission
17th World Conference on Nondestructive Testing, 25-28 Oct 2008, Shanghai, China Case Studies of Electric Power Equipment Diagnostics Using Acoustic Emission Oswaldo G. SANTOS FILHO 1, Sergio L. ZAGHETTO
More informationRarely used, problems with unbalanced loads.
THREE-PHASE TRANSFORMERS Transformers used in three-phase systems may consist of a bank of three single-phase transformers or a single three-phase transformer which is wound on a common magnetic core.
More informationRESONANT TRANSFORMER
RESONANT TRANSFORMER Whenever the requirement of the test voltage is too much high, a single unit transformer can not produce such high voltage very economically, because for high voltage measurement,
More information