A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards
|
|
- Janice Hodges
- 5 years ago
- Views:
Transcription
1 Indian Journal of Science and Technology, Vol 9(30), DOI: /ijst/2016/v9i30/99034, August 2016 ISSN (Print) : ISSN (Online) : A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Nikita Rajan and Anu G. Kumar Department of Electrical and Electronics Engineering, Amrita School of Engineering, Coimbatore Amrita Vishwa Vidyapeetham, Amrita University, Coimbatore , Tamil Nadu, India; nikitarajan100@gmail.com, gk_anu@cb.amrita.edu Abstract Objective: Electrical power delivered to a load must be of sufficient quality to allow the load to function properly. Source side voltages and currents must be distortion free and of the proper magnitudes and frequencies. Critical equipment may undergo failure if quality power is not provided. So, the electrical voltages and currents flowing through our distribution system has to be monitored and analyzed to ensure quality power and thus proper working of the machineries in a technical institute. This paper presents a Power Quality Survey in a technical institute as per Standards. Methods: A Power Quality Survey has been conducted and the measured parameters are compared against Standards. Simulation study of the complete system is conducted using ETAP software, so as to understand the existing load flow and harmonic profile. Findings: Current and voltage harmonics was found to be within the limits at PCC. Improvement: Harmonic profile of UPS-Academic block improved, when the old UPS was replaced with a modern numeric UPS. Keywords: Point of Common Coupling, Power Quality, Total Harmonic Current Distortion, Total Harmonic Voltage Distortion 1. Introduction There are a number of sensitive and advanced equipment in any Engineering/academic institute, that are quite sensitive to Power Quality (PQ) disturbances in the supply network. These equipments require distortion-less supply to ensure proper working conditions. A Power Quality Survey is essential in any institute to monitor the quality of the power being supplied, for efficient operating of laboratory equipment 1 and to design a compensation technique for the problems identified, if any. In this paper, a detailed Power Quality Survey of the campus (Amrita 22 kv Electrical Distribution System) has been conducted, with an objective of identifying the Power Quality issues and to select suitable compensation techniques for the major problems being identified. As a part of the Power Quality survey, harmonic analysis of the Amrita 22 kv Electrical distribution system has also been conducted, to verify whether the THD limits at the point of common coupling are within the IEEE Standards. The single line diagram of the Amrita 22 kv distribution system, consisting of two Power houses are simulated in ETAP and its load flow analysis and harmonic analysis were performed under different operating conditions, namely With supply from Electricity board. With supply from DG sets. *Author for correspondence
2 A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards 2. Power Quality Power Quality has become an inevitable term in electrical power industry. The reason for this increased concern about Power Quality is mainly due to the use of modern equipments like power electronic devices, office and IT equipments, motor drives etc. All Technical institutions use these equipments; these equipments require quality and distortion less supply to operate properly 2. The major Power Quality issues include voltage variations (under voltage/over-voltage), transients, harmonics, flickers, frequency unbalance etc 3. These problems have to be taken care of to ensure Power Quality. By definition, power is the rate of energy consumption in an electric circuit and is equal to the product of voltage and current 2. So, quantitatively, Power Quality is directly proportional to the quality of voltage, as it is possible only to control the quality of voltage and not the quality of current that will be drawn by specific loads. Power Quality has been an existing issue ever since the invention of electric power, but it has gained importance in the recent years, due to the usage of more sensitive and critical equipments in domestic, commercial and industrial fields. The major Power Quality problems are: Sags/swells: Under-voltages and over-voltages on the power system. It can be corrected using power sources such as UPSs, generators or similar voltage restoration technologies. Surges: Voltage spikes caused mainly due to switching off of heavy electrical equipment(s). Harmonics: Distortion of current and voltage waveforms from sinusoidal shape. It is caused due to non-linear loads connected to the power system, often corrected using filtering equipments 4. Continuous Power Quality monitoring detects the presence of Power Quality problems and hence leads to the prevention of the same Power Quality Standards The current distortion and voltage distortion are measured and verified against IEEE Standards. 4. System Overview The 22 kv electrical distribution system of Amrita campus consists of two power houses, viz. Power House-1 (PH-1) and Power House-2 (PH-2), as shown in Figure 1. Figure 1. Overview of the system under consideration. Power House-1 consists of 2 transformers of 500 kva each and three diesel generators of different ratings. The system parameters of Power House-1 are shown in Table 1. Table 1. System parameters of Power House-1 Sl. No. EQUIPMENT RATING 1 Power Grid 22 kv 2 Generator (G1) 0.2 MW 3 Generator (G2) 0.2 MW 4 Generator (G3) MW 5 Transformer (T1) 500 kva 6 Transformer (T2) 500 kva 7 Loads 57.4 MVA 2 Indian Journal of Science and Technology
3 Nikita Rajan and Anu G. Kumar Figure 2. Single line diagram of Power House-1. The single line diagram of Power House-1 is shown in Figure 2. Power House-2 consists of 2 transformers of 500 kva each and two diesel generators. The system parameters of Power House-1 are shown in Table 2. The single line diagram of Power House-1 is shown in Figure 3. Table 2. System parameters of Power House-2 Sl. No. EQUIPMENT RATING 1 Power Grid 22 kv 2 Generator (G1) 500 kva 3 Generator (G2) 500 kva 4 Transformer (T6) 500 kva 5 Transformer (T8) 500 kva 6 Loads 49.8 MVA Figure 3. Single line diagram of Power House Power Quality Survey The survey was done with an objective to understand the load flow of the entire distribution system and also to measure the harmonics and to verify whether it is within the limits as per the IEEE Standards. The on-site readings were taken with Power Quality Indian Journal of Science and Technology 3
4 A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards analyzer (Fluke 435). Data samples were recorded at critical points. 5.1 Power Quality at PCC Power House-1 The readings obtained at PH-1 are shown in Table Performance Evaluation of UPS IT Block Figure 4 shows the data samples of the neutral current of the UPS in IT block measured in Fluke 435. The data was recorded for duration of 24 hours. Table 3. PCC readings of Power House-1 Voltage V rms ph-ph (V) RMS Current (A) Real power (kw) Apparent power (kva) Reactive power (kvar) PF V 249 A Power House-2 The readings obtained at PH-2 are shown in Table 4. Table 4. PCC readings of Power House-2 Voltage V rms ph-ph (V) RMS Current (A) Real power (kw) Apparent power (kva) Reactive power (kvar) PF V 420 A From the data collected from Power Quality analyzer (Fluke 435), a comparison has been done with the IEEE limits and it is shown in Table 5. Table 5. Comparison with IEEE limits location I sc /I L Current THD (limit) Current THD (actual) PH % 5-7 % PH % % 4 Indian Journal of Science and Technology
5 Nikita Rajan and Anu G. Kumar Figure 4. Neutral current of old UPS-IT block. Figure 6. Current THD of electrical machines laboratory. From the recorded data, it could be observed that the neutral varies between 18 A to 36 A, which is a large variation and it is not a permissible condition. Figure 5 shows the fluke data of the current THD of the UPS in IT block. The data was recorded for a duration of 24 hours. From the recorded data, the current THD is found to be 64%, which is high. Hence, compensation was required with immediate effect. Due to the these abnormalities, the old UPS in IT block is now replaced with a new numeric modular UPS. 5.4 Power Systems Laboratory Figure 7 shows the data samples of the current THD at the incoming of the machines lab, while the lab was working on power systems laboratory experiments. From the recorded data, it could be observed that the third and fifth Harmonics are more dominant. Figure 7. Current THD of machines lab (AC machines lab). Figure 5. Current THD of UPS-IT block. 5.3 Electrical Machines Laboratory Figure 6 shows the data samples of the current THD at the incoming of the machines lab, while the lab was working on AC machines laboratory experiments. The data was recorded continuously for 2 hours. From the recorded data, it could be observed that the third and fifth Harmonics are more dominant. 6. ETAP Simulation Study The single line diagram of PH-1 and PH-2 are simulated in ETAP Power House-1 (PH-1): Load Flow Analysis (with supply from EB) The ETAP simulation result of load flow analysis of PH-1 under EB supply is shown in Figure 8. Indian Journal of Science and Technology 5
6 A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Figure 8. from EB). ETAP simulation result-load flow analysis result of power house-1 (with supply From the load flow analysis of PH-1 with supply from EB, it is observed that transformer (T2) is underutilized (0.114 MVA, i.e. 22.7%). Hence, it is recommended that the load can be supplied from transformer (T1) alone, except at the time of peak load demand. 6.2 Power House-1 (PH-1): Harmonic Analysis (with supply from EB) The ETAP simulation result of harmonic analysis of PH-1 under EB supply is shown in Figure 9. From the harmonic analysis of PH-1 with supply from EB, it could be observed that the harmonic distortion (THD and IHD) exceeds the limits. 6.3 Power House-1 (PH-1): Load Flow Analysis (with supply from DG) The ETAP simulation result of load flow analysis of PH-1 under DG supply is shown in Figure 10. From the load flow analysis of PH-1, it is observed that a major portion of the demand is shared by the losses; total demand MW, total losses MW). Figure 9. ETAP simulation result-harmonic analysis result of Power House-1 (with supply from EB). 6 Indian Journal of Science and Technology
7 Nikita Rajan and Anu G. Kumar Figure 10. from DG). ETAP simulation result-load flow analysis result of Power House-1 (with supply 6.4 Power House-1 (PH-1): Harmonic Analysis (with supply from DG) The ETAP simulation result of harmonic analysis of PH-1 under DG supply is shown in Figure 11. From the harmonic analysis of PH-1 with supply from DG sets, it could be observed that the harmonic distortion (THD and IHD) exceeds the limits. 6.5 Power House-2 (PH-2): Load Flow Analysis (with supply from EB) The ETAP simulation result of load flow analysis of PH-2 under EB supply is shown in Figure 12. From the load flow analysis of PH-2, it is observed that both transformers are slightly overloaded (by MVA). Figure 11. from DG). ETAP simulation result-load flow analysis result of Power House-1 (with supply Indian Journal of Science and Technology 7
8 A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards Figure 12. from EB). ETAP simulation result-load flow analysis result of Power House-2 (with supply 6.6 Power House-2 (PH-2): Harmonic Analysis (with supply from EB) The ETAP simulation result of the harmonic analysis of PH-2 under EB supply is shown in Figure Power House-2 (PH-2): Load Flow Analysis (with supply from DG sets) The ETAP simulation result of load flow analysis of PH-2 under DG supply is shown in Figure 14. Figure 13. ETAP simulation result-harmonic analysis result of Power House-2 (with supply from EB). 8 Indian Journal of Science and Technology
9 Nikita Rajan and Anu G. Kumar Figure 14. ETAP simulation result-load flow analysis result of Power House-2 (with supply from DG sets). 6.8 Power House-2 (PH-2): Harmonic Analysis (with supply from DG sets) The ETAP simulation result of harmonic analysis of PH-2 under DG supply is shown in Figure 15. From the harmonic analysis of Power House-2, it could be observed that THD is within the limit (as per IEEE Std.). Figure 15. ETAP simulation result-harmonic analysis result of Power House-2 (with supply from DG sets). Indian Journal of Science and Technology 9
10 A Power Quality Survey on a 22 kv Electrical Distribution System of a Technical Institution as per Standards 3. Recommendations and Improvements PCC: The transformer (T2) is found to be underutilized. The power can be supplied from transformer (T1) alone, except at the time of peak loads. UPS IT block: Due to the the abnormalities of the UPS in IT block and being an old UPS, the old UPS in IT block can be replaced with a modern numeric modular UPS. Electrical Machines Laboratory: The current THD was found to be approximately 25%, which violates the limit. Hence, small scale compensation is required, which can be achieved by implementing a suitable filter at the rectifier input of the laboratory. Power systems laboratory: The THD was found to be approximately 28%, which violates the limit. Hence, small scale compensation is required, which can be achieved by implementing a suitable filter at the rectifier input of the laboratory. Figure 16. Neutral current of new UPS-IT block. Figure 17. Current THD of new UPS-IT block. 10 Indian Journal of Science and Technology
11 Nikita Rajan and Anu G. Kumar Figure 16 shows the data samples of the neutral current of the new UPS in IT block recorded in Power Quality analyzer (Fluke 435) From the Fluke 435 recorded data, the neutral current was found to be less than 1A - Permissible. Figure 16 the fluke data of the current THD of the new UPS in IT block. The data was recorded for duration of 24 hours. From the Fluke 435 recorded data, the neutral current was found to be less than 1A - Permissible. Figure 17 the fluke data of the current THD of the new UPS in IT block. The data was recorded for duration of 24 hours. From the Fluke 435 recorded data, the current THD is found to be reduced from 64% to 6%. The harmonic profile was found to be improved to a large extent. 8. Conclusion A Power Quality Survey in a 22 kv electrical distribution system of a technical institute was conducted with an objective to understand the existing harmonic profile and the load flow. Various inferences were drawn from the load flow analysis and harmonic analysis done in ETAP software. It is observed that significant distortion in the current waveforms exist due to the use of electronic switching equipments. The UPS in the IT block was identified as a major harmonic causing load. Increasing use of these equipments can result in serious problems in the near future. As a result of the survey conducted, the old UPS was replaced with a modern UPS, which led to a noticeable improvement in the harmonic profile. The issues related to Power Quality are mainly contributed by voltage fluctuations in the supply. Voltage quality issues are the prime cause of other Power Quality issues. So, a control of the voltage fluctuations will greatly reduce the impact of other related issues 6. Hence, similar Power Quality surveys are essential in any technical or commercial institute prior to any new electrical installations, so as to understand the existing electrical profile and thereby to adjust the new installations accordingly. This will lead to the availability of quality power and consequently result in less damage of the sensitive equipments. 9. Acknowledgment Authors would like to thank Amrita Vishwa Vidyapeetham University and Department of Science and Technology for the financial support for carrying out this work. 10. References 1. Jain S, Agarwal P, Gupta HO. A survey of harmonics: Indian scenario. Proceedings of the IEEE INDICON; 2004 Dec. p Prabaakaran K, Chitra N, Senthil Kumar A. Power Quality enhancement in microgrid - A survey. IEEE International Conference on Circuits, Power and Computing Technologies (ICCPCT); 2013 Mar. p Ignatova V, Villard D, Hypolite JM. Simple indicators for an effective Power Quality monitoring and analysis. IEEE 15th International Conference on Environment and Electrical Engineering (EEEIC)); 2015 Jun. p Mack GW, Santoso S. Understanding power system harmonics. IEEE Power Engineering Review Dec; 21(11): Gosbell VJ, Perera S, Barr R, Baitch A. Primary and secondary indices for Power Quality (PQ) survey reporting. IEEE 11th International Conference on Harmonics and Quality of Power; 2004 Sep. p Ribeiro PF. Common misapplications of the IEEE 519 harmonic standard: Voltage or current limits. Power and Energy Society General Meeting-Conversion and Delivery of Electrical Energy in the 21st Century; Jul. p Indian Journal of Science and Technology 11
Power Quality Analysis: A Study on Off-Line UPS Based System
Power Quality Analysis: A Study on Off-Line UPS Based System P.K.DHAL Department of Electrical and Electronics Engineering VelTech Dr.RR&Dr.SR Technical University # 42 Avadi- VelTech Road, Chennai-62
More informationAvailable online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015
Available online at www.sciencedirect.com ScienceDirect Procedia Technology 21 (2015 ) 310 316 SMART GRID Technologies, August 6-8, 2015 A Zig-Zag Transformer and Three-leg VSC based DSTATCOM for a Diesel
More informationInternational Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD
Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND
More informationPOWER QUALITY REPORT
Power Quality Research Lab., I-7, Wyb. Wyspiaoskiego 27, 50-370 Wrocław, Poland phone +48713202626, fax +48713202006, email: zbigniew.leonowicz@pwr.wroc.pl Facility: XXX POWER QUALITY REPORT Start Monitoring:
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationA PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits
CS 36 HOSP 14 36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationVoltage Support and Reactive Power Control in Micro-grid using DG
International OPEN ACCESS Journal Of Modern Engineering Research (IJMER) Voltage Support and Reactive Power Control in Micro-grid using DG Nagashree. J. R 1, Vasantha Kumara. T. M 2, Narasimhegowda 3 1
More informationHarmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry
I J C T A, 9(37) 2016, pp. 769-781 International Science Press Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry D. Ravichandran * and Er. R. Panneerselvam ** Abstract:
More informationPower Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss
Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationPOWER FACTOR CORRECTION AND ITS PITFALLS
Technical Note No. May 1999 POWER FACTOR CORRECTION AND ITS PITFALLS This Technical Note considers power factor correction as applied by large customers and the possible consequences when power factor
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationPower Quality Study of Electrical Installation in Academic Institute Case Study
Power Quality Study of Electrical Installation in Academic Institute Case Study Mr. Mukteshwar N. Patil 1, Prof. Rajesh M. Holmukhe 1#, Mr. Sadashiv Munde 2 1 Department of Electrical Engineering, Bharati
More informationModeling of Statcom. P.M. Sarma and Dr. S.V. Jaya Ram Kumar. Department of Electrical & Electronics Engineering GRIET, Hyderabad, India
International Journal of Electrical Engineering. ISSN 974-2158 Volume 6, Number 1 (213), pp. 69-76 International Research Publication House http://www.irphouse.com Modeling of Statcom P.M. Sarma and Dr.
More informationInfluence of Switching Elements on Harmonics and Power Factor Improvement
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 7, Issue 12 (July 2013), PP. 18-24 Influence of Switching Elements on Harmonics
More informationSTATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads
STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of
More informationPower Quality Compensation by using UPFC
ISSN: 2454-132X Impact factor: 4.295 (Volume 4, Issue 2) Available online at: www.ijariit.com Power Quality Compensation by using UPFC P. Madhumathi madhumathi9196@gmail.com Vivekanada College of Engineering
More informationII. RESEARCH METHODOLOGY
Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationA Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller
IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 09 (September. 2014), V3 PP 11-20 www.iosrjen.org A Versatile Control Scheme for UPQC for Power Quality Improvement
More informationImprovement of Power Quality using Unified Power Quality Conditioner with Distributed Generation
Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation Prof. S. S. Khalse Faculty, Electrical Engineering Department, Csmss Chh Shahu College of Engineering, Aurangabad,
More informationEmicon Engineering Consultants L.L.C.
Emicon Engineering Consultants L.L.C. Power Quality Consulting & Solutions Presentation / Pre-Qualification Emicon, Specialised in Power Quality Consulting and Pollution Control on Electrical Network www.emiconconsultants.com
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationEnhancement of Power Quality Using Advanced Series Active Power Filters
Enhancement of Power Quality Using Advanced Series Active Power Filters Manoj siva kumar 1, P.Rayalakshmi 2 Associate Professor, Dept. of EEE, PBRVITS, Kavali, SPSR Nellore, A.P, India 1 M.Tech Student,
More informationHarmonics Reduction using 4-Leg Shunt Active Power Filters
Harmonics Reduction using 4-Leg Shunt Active Power Filters K Srinivas Assistant Professor & Department of EEE & JNTUH CEJ Telangana, India. Abstract Harmonics in power system are caused by highly non-linear
More informationUNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY
International Journal of Electrical Engineering & Technology (IJEET) Volume 7, Issue 6, Nov Dec, 2016, pp.55 63, Article ID: IJEET_07_06_005 Available online at http://www.iaeme.com/ijeet/issues.asp?jtype=ijeet&vtype=7&itype=6
More informationSimulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side
Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side 1 Jaykant Vishwakarma, 2 Dr. Arvind Kumar Sharma 1 PG Student, High voltage and Power system, Jabalpur
More informationPower quality measurements in a singlehouse
24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 2: Power quality and electromagnetic compatibility Power quality measurements in a singlehouse microgrid
More informationImprovement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.
, 2011;4(12) Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces H.A. Khalik, M. A. Aziz, and E. Farouk. Electrical power and Machines Engineering
More informationVoltage Quality Enhancement in an Isolated Power System through Series Compensator
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 12, Issue 6 (June 2016), PP.20-26 Voltage Quality Enhancement in an Isolated Power
More informationISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer
ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering
More informationDESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK
DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK 1 Hitesh Kumar Yadav, 2 Mr.S.M.Deshmukh 1 M.Tech Research Scholar, EEE Department, DIMAT Raipur (Chhattisgarh), India 2 Asst. Professor, EEE Department,
More informationPerformance of DVR under various Fault conditions in Electrical Distribution System
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 1 (Nov. - Dec. 2013), PP 06-12 Performance of DVR under various Fault conditions
More informationWorld Academy of Science, Engineering and Technology International Journal of Electrical and Computer Engineering Vol:7, No:6, 2013
Investigating the Effect of Using Capacitorsin the Pumping Station on the Harmonic Contents (Case Study: Kafr El-Shikh Governorate, Egypt) Khaled M. Fetyan Abstract Power Factor (PF) is one of the most
More informationCHAPTER 4 HARMONICS AND POWER FACTOR
4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried
More informationHarmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits
WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*
More informationA Voltage Controlled D-STATCOM for Power Quality Improvement with DVR
A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR Rongali. Shiva Kumar P.G Student Scholar, Department of Electrical & Electronics Engineering, Gokul Group Of Institutions Abstract:
More informationHarmonics Elimination Using Shunt Active Filter
Harmonics Elimination Using Shunt Active Filter Satyendra Gupta Assistant Professor, Department of Electrical Engineering, Shri Ramswaroop Memorial College of Engineering and Management, Lucknow, India.
More informationImprovement of Power Quality Using a Hybrid UPQC with Distributed Generator
Improvement of Power Quality Using a Hybrid with Distributed Generator M. K. Elango, T. Tamilarasi, Professor PG student Department of Electrical and Electronics Engineering Department of Electrical and
More informationImprovement of Power Quality Using a Hybrid Interline UPQC
Improvement of Power Quality Using a Hybrid Interline UPQC M.K.Elango 1, C.Vengatesh Department of Electrical and Electronics Engineering K.S.Rangasamy College of Technology Tiruchengode, Tamilnadu, India
More informationStudy of Power Factor Correction in Single Phase AC-DC Converter
Avneet Kaur, Prof. S.K Tripathi, Prof. P. Tiwari 89 Study of Power Factor Correction in Single Phase AC-DC Converter Avneet Kaur, Prof. S.K Tripathi, Prof. P. Tiwari Abstract: This paper is regarding power
More informationCASE STUDY. Implementation of Active Harmonic Filters at Ford Motor Company SA Silverton Plant
CASE STUDY Implementation of Ford Motor Company SA Silverton Plant 1 SCENARIO Ford Motor Company is a global automotive and mobility company based in Dearborn, Michigan. Ford Motor Company of Southern
More informationThe Influence of Voltage Flicker for the Wind Generator upon Distribution System
The Influence of Voltage Flicker for the Wind Generator upon Distribution System Jin-Lung Guan, Jyh-Cherng Gu, Ming-Ta Yang, Hsin-Hung Chang, Chun-Wei Huang, and Shao-Yu Huang Digital Open Science Index,
More informationMinimization of Harmonic Distortion of Industrial Motor Drives with Active Power Filter in Paper Mill - a Case Study
Minimization of Harmonic Distortion of Industrial Motor Drives with Active Power Filter in Paper Mill - a Case Study Y.Kusumalatha, Ch.Saibabu, and Y.P.Obulesu Abstract With the increasing of non-linear
More informationModelling and Simulation of PQ Disturbance Based on Matlab
International Journal of Smart Grid and Clean Energy Modelling and Simulation of PQ Disturbance Based on Matlab Wu Zhu, Wei-Ya Ma*, Yuan Gui, Hua-Fu Zhang Shanghai University of Electric Power, 2103 pingliang
More informationINTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION
International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA
More informationWorld Journal of Engineering Research and Technology WJERT
wjert, 2017, Vol. 3, Issue 4, 120-128 Original Article ISSN 2454-695X Vimalakeerthy. WJERT www.wjert.org SJIF Impact Factor: 4.326 HARMONICS ELIMINATION IN ISOLATED POWER SYSTEM USING COMPENSATORS Dr.
More informationSOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson
SOURCES OF ERROR IN UNBALANCE MEASUREMENTS V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson Integral Energy Power Quality Centre School of Electrical, Computer and Telecommunications Engineering
More informationPerformance of Indirectly Controlled STATCOM with IEEE 30-bus System
Performance of Indirectly Controlled STATCOM with IEEE 30- System Jagdish Kumar Department of Electrical Engineering, PEC University of Technology, Chandigarh, India E-mail : jk_bishnoi@yahoo.com Abstract
More informationGrid Converters for Photovoltaic
Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements
More informationComparative Study of Sag & Swell Mitigation by a Novel Multi Level DVR with Wavelets
Comparative Study of Sag & Swell Mitigation by a Novel Multi Level DVR with Wavelets G. Devadasu Department of EEE, CMR College of Engineering and Technology Dr. M. Sushama Department of EEE, JNTUH University
More informationHarmonic Analysis and Its Mitigation Using Different Passive Filters
Harmonic Analysis and Its Mitigation Using Different Passive Filters Ashlin Gloria Reginald 1, K J Thomas 2 1 PG Scholar, Amal Jyothi College of Engineering, Kanjirapally Kottayam, India ashlingloriar@gmail.com
More informationCase Study 38 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at Usha Martin Wire Rope Plant.
CS 38 ENRG 14 Reduction in Break Down and Specific Energy Consumption by Reducing Harmonics at a Steel Wire Rope Plant APQI (C) Copyright (2013) All Rights Reserved 1 target of reducing energy consumption
More informationHarmonic distortion Blackouts Under or over voltage Dips (or sags) and surges, Transients.
Power Quality Standards in India Power Quality is a measure of an ideal power supply system. It can be defined as any power problem manifested in voltage, current and frequency deviations that result in
More informationISSN: ISO 9001:2008 Certified International Journal of Engineering and Innovative Technology (IJEIT) Volume 5, Issue 11, May 2016
Power Loss Minimization In Distribution System Using Static VAR Compansator Mohamed Hussien Zahran, Hamdy A. M. Shatla, Salama Abo_Zead Dept. of Electrical Engineering, Al-Azhar University, Cairo, Egypt
More informationA Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW
A Novel Ultra High Fidelity Power Quality and Energy Management Software Using NI LabVIEW Shishir Sarkar 1, Dr. S. Chatterji 2, Shimi S.L 3, Sonia Rawat 4 1 M.E Student, Electrical Engineering Department,
More informationCOMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER FILTER
International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 3 ǁ March. 2013 ǁ PP.25-30 COMPENSATION OF POWER QUALITY PROBLEMS USING ACTIVE POWER
More informationApplication Guidance Notes: Technical Information from Cummins Generator Technologies
Application Guidance Notes: Technical Information from Cummins Generator Technologies AGN 087 Power Factor DEFINITIONS What is Power Factor? Power factor is a way of identifying the electrical relationship
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationEmergency Generator Sizing and Motor Starting Analysis
Emergency Generator Sizing and Motor Starting Analysis Mukesh Kumar Kirar, Ganga Agnihotri Abstract This paper investigates the preliminary sizing of generator set to design electrical system at the early
More informationStatic Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1
Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of
More informationIMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs
IMPROVING POWER QUALITY AND ENHANCING THE LIFE OF POWER EQUIPMENT, IN RAILWAY TSSs Mr. P. Biswas, ABB ABSTRACT The Indian Railways employ single phase 25 kv Traction sub-station (TSS) for supplying power
More informationPOWER QUALITY MONITORING - PLANT INVESTIGATIONS
Technical Note No. 5 January 2002 POWER QUALITY MONITORING - PLANT INVESTIGATIONS This Technical Note discusses power quality monitoring, what features are required in a power quality monitor and how it
More informationPQ Audit - The right choice to ensure power system performance. Mr Lalit Kumar Wasan Tata Power- DDL
PQ Audit - The right choice to ensure power system performance Mr Lalit Kumar Wasan Tata Power- DDL Outline vpower Quality v Present Challenges v Harmonics & Its Impact on DISCOM v Future Challenges Roof-Top
More informationINVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER
IOSR Journal of Electronics & Communication Engineering (IOSR-JECE) ISSN(e) : 2278-1684 ISSN(p) : 2320-334X, PP 68-73 www.iosrjournals.org INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE
More informationFFT Analysis of THD in Distribution System with Grid Connected RES
FFT Analysis of THD in Distribution System with Grid Connected RES Avinash Kumar Tiwari 1, A.K.Jhala 2 PG Scholar, Department of EE, RKDF College of Engg, Bhopal, M.P., India 1 Head, Department of EE,
More informationSizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks
Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks André Braga Instituto Superior Técnico Av. Rovisco Pais, 1049-001 Lisbon, Portugal
More informationMotors and drives. Module B- Introduction to input measurements
Motors and drives Module B- Introduction to input measurements Introduction to input measurements There are a number of locations where input measurements may be made Which is the most important location
More informationSHUNT ACTIVE POWER FILTER
75 CHAPTER 4 SHUNT ACTIVE POWER FILTER Abstract A synchronous logic based Phase angle control method pulse width modulation (PWM) algorithm is proposed for three phase Shunt Active Power Filter (SAPF)
More informationAcknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.
Preface p. xv Acknowledgements p. xix Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p. 6 Power Quality Monitoring p. 7 Power
More informationElectric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development
Electric Power Quality Monitoring and Analysis at a Tri-generation Plant under Development IOANA PISICĂ, LAURENŢIU CONSTANTIN LIPAN, PETRU POSTOLACHE, CORNEL TOADER Department of Power Systems University
More informationIMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES
IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES P. K. Mani 1 and K. Siddappa Naidu 2 1 Department of Electrical and Electronics Engineering, Vel Tech Multitech Dr. Rangarajan Dr. Sakunthala Engineering
More informationDesign Strategy for Optimum Rating Selection of Interline D-STATCOM
International Journal of Engineering Science Invention ISSN (Online): 2319 6734, ISSN (Print): 2319 6726 Volume 2 Issue 3 ǁ March. 2013 ǁ PP.12-17 Design Strategy for Optimum Rating Selection of Interline
More informationMitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India
Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Abstract: The objective of this research is to develop a novel voltage control scheme that
More informationReduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc
International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 10, Issue 7 (July 2014), PP.01-15 Reduction of Voltage Imbalance in a Two Feeder
More informationPerformance Evaluation for Different Levels Multilevel Inverters Application for Renewable Energy Resources
Performance Evaluation for Different Levels Multilevel Inverters Application for Renewable Energy Resources M.Charai 1, A.Raihani 1, O.Bouattan 1, H.Naanani 2 1 Laboratoire des Signaux, Systèmes Distribués
More informationImprove Power Factor and Reduce the Harmonics Distortion of the System
Research Journal of Engineering Sciences ISSN 2278 9472 Improve Power Factor and Reduce the Harmonics Distortion of the System Abstract Jain Sandesh, Thakur Shivendra Singh and Phulambrikar S.P. Electrical
More information29 Level H- Bridge VSC for HVDC Application
29 Level H- Bridge VSC for HVDC Application Syamdev.C.S 1, Asha Anu Kurian 2 PG Scholar, SAINTGITS College of Engineering, Kottayam, Kerala, India 1 Assistant Professor, SAINTGITS College of Engineering,
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationImproving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics
Indonesian Journal of Electrical Engineering and Computer Science Vol. 3, No. 2, August 2016, pp. 282 ~ 295 DOI: 10.11591/ijeecs.v3.i2.pp282-295 282 Improving the Power Factor Correction in the Presence
More informationLow Pass Harmonic Filters
Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power
More informationFUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION IN GRID CONNECTED WIND ENERGY CONVERSION SYSTEM
International Journal of Electrical and Electronics Engineering Research (IJEEER) ISSN 2250-155X Vol. 3, Issue 4, Oct 2013, 129-138 TJPRC Pvt. Ltd. FUZZY LOGIC CONTROLLER BASED UPQC FOR POWER QUALITY MITIGATION
More informationThe Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller
The Impact of Connecting Distributed Generation to the Distribution System E. V. Mgaya, Z. Müller This paper deals with the general problem of utilizing of renewable energy sources to generate electric
More informationISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013
A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of
More informationPower Quality improvement of a three phase four wire system using UPQC
International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Volume: 2 Issue: 4 July-215 www.irjet.net p-issn: 2395-72 Power Quality improvement of a three phase four wire system
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationTransient Detection in Industrial Grids and Compensation Using FCL DVR
Available Online at www.ijcsmc.com International Journal of Computer Science and Mobile Computing A Monthly Journal of Computer Science and Information Technology IJCSMC, Vol. 4, Issue. 3, March 2015,
More informationMitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)
Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering
More informationMitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)
Vol. 3, Issue. 4, Jul. - Aug. 2013 pp-2367-2373 ISSN: 2249-6645 Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM) B. Giri Prasad Reddy 1, V. Obul
More informationMitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction System
ISSN (Print) : 2347-671 (An ISO 3297: 27 Certified Organization) Vol. 4, Special Issue 6, May 215 Mitigation of Negative Sequence Currents and Effect of Magnetic Inrush Currents in Indian Railway Traction
More informationJewell DPM Power / Power Factor Size 96/96 BEST IN CLASS
Application: The Jewell DPM Power 96x96 series measures system active Power (Import/Export), Reactive Power (Import/Export), Apparent Power & Power Factor of Three Phase and Single Phase Network. It has
More informationNew Time Domain Electric Arc Furnace Model for Power Quality Study
New Time Domain Electric Arc Furnace Model for Power Quality Study Deepak C. Bhonsle Electrical Engineering Department Maharaja Sayajirao University of Baroda Vadodara, INDIA dcbhonsle@gmail.com Dr. Ramesh
More informationIMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)
IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR) Hadi Suyono 1, Lauhil Mahfudz Hayusman 2 and Moch. Dhofir 1 1 Department of Electrical Engineering, Brawijaya University, Malang,
More informationT-68 Protecting Your Equipment through Power Quality Solutions
T-68 Protecting Your Equipment through Power Quality Solutions Dr. Bill Brumsickle Vice President, Engineering Nov. 7-8, 2012 Copyright 2012 Rockwell Automation, Inc. All rights reserved. 2 Agenda What
More informationActive Harmonic Filter (AF3)
Active Harmonic Filter (AF3) Active Harmonic Filter Improving the Efficiency and Life of System by use of Digital Active Power Conditioner HARMONICS 50 Hz, fundamental 100 Hz, 2nd Harmonic 150 Hz, 3rd
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More information