1 Controllable Generation UCAP determination Eligibility WG September 12, 2017
2 Purpose and objective The objectives of this presentation include: Recap the installed capacity (ICAP) and unforced capacity (UCAP) definitions Understand the data requirements for UCAP Compare GADs and AESO data Request feedback from workgroup 1
3 Recall from July 4 th meeting UCAP Calculation for a Thermal Resource Example: Gas Combined Cycle with a nameplate capacity of 500 MW Seasonal Net Dependable (ICAP) accounts for the impact of ambient weather conditions (Summer) on unit performance Unforced Capacity (UCAP) is the ICAP value of the unit reduced by its recent actual forced outage rate during system demand periods (EFORd) Generator will able to offer 396 UCAP MW into the capacity auction Nameplate capacity rating = 500 MW Nameplate capacity modified for seasonal ambient limitations (ICAP). Example: If ambient temprature reduction is 10 % of the nameplate capacity. Ex. ICAP = 500 MW * 90% = 450 MW UCAP= ICAP * (1-EFORd) Forced outage rate = 12% UCAP = ICAP * (1- forced outage rate) Ex. If UCAP = 450 MW * (1-0.12) = 396 MW Public 2
4 UCAP calculation and data requirements UCAP= ICAP x (1- EFORd) where Equivalent Demand Forced Outage Rate (EFORd) is a measure of probability that a generating unit will not be available due to forced outages or forced derates when there is a demand on the unit to generate* The EFORd calculation relies on reliability data that comes from the Generation Availability Data System (GADS). GADs data are collected by NERC and provide information about the performance and outages / derates of generating units** The UCAP calculation may have different data requirements for uncontrollable and controllable generation AESO does not have GADS data *PJM Capacity Market/ PJM Manual 18/PJM Capacity Market Operations ** 3
5 UCAP Calculation: ETS data deficiencies Information needed for calculating UCAP based on EFORd Duration of Forced outages, Planned Outages, Forced Derates and Planned Derates Service Hours (The period of time that the unit was generating electricity) Reserve Shutdown ( the period that the unit was available, but not dispatched) Number of Actual Starts and Attempted Unit Starts Do we have this information? NO Yes Yes NO Comments ETS gives the option to the participants to leave out the event type in their submissions within a 7 day period before the event. In the case that they do not submit this field, it would be automatically populated using a logic that does not allow participants to clearly distinguish between forced and planned events. Therefore the event field would not be useful in determining the type of the outages and derates. This could be extracted from the metered volumes. When the unit is available (AC 0) but generation is zero. The data are not available. Based on the data currently available, calculation of UCAP based on EFORd methodology will be time consuming and complex. This methodology needs information similar to what GADs provide. However, this method could be used in the future if the GADS data become available. 4
6 Conceptual differences between AC and UCAP Maximum Capability = 200 MW PJM Ambient temp and humidity adjustment Alberta Ambient temp and humidity adjustment Maximum Capability = 200 MW ICAP = 170 MW 30 MW Forced outages/derates 30 MW 30 MW Forced outages/derates 30 MW PJM based UCAP for thermal generator = 140 MW Planned Outages/derates Planned Outages/derates ACf: is 140MWs UCAP is ICAP adjusted for performance through GADS data In other jurisdictions This example is for illustrative purposes only 40 MW + Available 100 MW 40 MW Available Capacity (AC in ETS) 100 MW AC = 100 MW AESO AC data does not separate between ambient, forced or planned outages. AC accounts for all lost generation UCAP: ICAP after capacity reduction due to forced outages and derates AESO ACf: ICAP after capacity reduction due to implied forced outages and implied derates AESO AC: ICAP after capacity reduction due to forced outages and derates and planned outages 5
7 Questions for the workgroup discussion Which option should be used for the interim UCAP calculation? A NERC mandate for 20MW and greater generators: do Alberta generators follow this requirement and have GADS data? Is the quality robust enough for use for UCAP Calculation? Are categorization practices comparable for all generation owners? Approach for generators less than 20MWs? If In the event ETS data is used, should AESO prioritize classifying outages earlier for the purpose of calculating more accurate UCAP on time for delivery during the transition period? Should the AESO investigate GADS further? Use GADS, AC or ACf for UCAP calculations? What demand hours should be used? 6
8 Thank you
9 Appendix B AC and AC f Overview Option 1: Use Available Capability as UCAP For existing resources this option uses historically submitted AC Variable resource may use capacity factors New resources and technologies may use class averages either from historical available capabilities or from sources outside the AESO for units with no historical data Seasons and demand hours will need to be defined Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) For existing resources this option uses historical AC submissions AC f may be calculated using a derate factor that only takes into account hours with forced outages and derates Forced outages are any outages/derates submitted within 7 days. Any submissions before 7 days are assumed to be planned Variable resource may use capacity factors New resources and technologies may use class averages either from historical available capabilities or from sources outside the AESO for units with no historical data Seasons and demand hours will need to be defined 8
10 Appendix B AC and AC f Advantages Option 1: Use Available Capability as UCAP Simple to understand and implement Availability of historical data Provides a conservative estimate of a plant s true capability as it includes planned and forced outages. Historical performance can be measured Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) This approach is closer in nature to way UCAP is calculated in North American capacity markets using GADs data Transition to GADS may be smoother as the difference in UCAP and ACF volumes may be lower Rules and compliance procedures in place to evaluate quality of AC submissions 9
11 Appendix B AC and AC f Disadvantages Option 1: Use Available Capability as UCAP Determining true availability of a unit will require additional work as some units may show full AC but not be dispatchable i.e. Long lead time, Mothball, peaking units, etc. AC data and rules were designed to meet the needs of an energy-only market and were not intended to fulfill the requirements of the UCAP calculation Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) More complex to implement as it requires parsing the data into planned and forced outages, which requires assumptions AC F will still be based on AC submissions, which were designed to meet the needs of an energy-only market and were not intended to fulfill the requirements of the UCAP calculation Methodology requires defining an approach to account for the impact of ambient weather conditions Method is still under investigation. AESO needs to further examine AC submission data to assess feasibility 10
12 Appendix B AC and AC f Example This example is only for illustrative purpose It intends to show the expected differences in magnitude between AC and AC f It uses a dummy generator with a maximum capability equal to 452 MW The same data set was used to calculate the AC and AC f values For the purpose of this example, the summer season comprised months from May to October and the winter season covered the months from November to April The actual months and HEs to be used in the UCAP methodology are yet to be decided 11
13 Appendix B AC and AC f Terminology Forced Outage Hours - FOH Sum of all hours experienced during Forced Outages. Forced outages are any outages submitted within 7 days. Equivalent Forced Derated Hours EFDH Forced derates are any derates submitted within 7 days. Each individual Forced Derating is transformed into equivalent full outage hour(s). This is calculated by multiplying the actual duration of the derating (hours) by the size of the reduction (MW) and dividing by the Maximum Capacity (MC). These equivalent hour(s) are then summed. (Derating Hours x Size of Reduction*)/ MC NOTE: Includes Forced Deratings during Reserve Shutdowns (RS). Service Hours SH Sum of all Unit Service Hours Equivalent Forced Derated Hours During Reserve Shutdowns EFDHRS Each individual Forced Derating or the portion of any Forced derating which occurred during a Reserve Shutdown (RS) is transformed into equivalent full outage hour(s). This is calculated by multiplying the actual duration of the derating (hours) by the size of the reduction (MW) and dividing by the Maximum Capacity (MC). These equivalent hour(s) are then summed. (Derating Hours x Size of Reduction*)/ MC 12
14 Appendix B AC and AC f Example Option 1: Use Available Capability as UCAP Option 2: Use Available Capability that only includes forced outages/derates but excludes planned outages (AC F ) AB1 Avg AC Median AC Max AC Min AC Summer Winter AC f = MC (1 Derate Factor) Derate Factor = FOH + EFDH FOH + SH + EFDHRS 100% AB1 Derate Factor AC f Summer 2.67% 440 Winter 4.25%
Document C-29. Procedures for System Modeling: Data Requirements & Facility Ratings. January 5 th, 2016 TFSS Revisions Clean Open Process Posting
Document C-29 Procedures for System Modeling: January 5 th, 2016 TFSS Revisions Clean Open Process Posting Prepared by the SS-37 Working Group on Base Case Development for the Task Force on System Studies.
More informationProcedure for ERO Support of Frequency Response and Frequency Bias Setting Standard. Event Selection Process
This procedure outlines the Electric Reliability Organization (ERO) process for supporting the Frequency Response Standard (FRS). A Procedure revision request may be submitted to the ERO for consideration.
More informationGeoff Brown & Associates Ltd
Geoff Brown & Associates Ltd REVIEW OF WESTERN POWER S APPLICATION FOR A TECHNICAL RULES EXEMPTION FOR NEWMONT MINING SERVICES Prepared for ECONOMIC REGULATION AUTHORITY Final 20 August 2015 Report prepared
More informationTransmission Facilities Rating Methodology for Florida
Document title Transmission Facilities Rating Methodology for Florida Document number EGR-TRMF-00001 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning Duke
More informationSystem Operating Limit Definition and Exceedance Clarification
System Operating Limit Definition and Exceedance Clarification The NERC-defined term System Operating Limit (SOL) is used extensively in the NERC Reliability Standards; however, there is much confusion
More informationgeneration greater than 75 MVA (gross aggregate nameplate rating) Generation in the ERCOT Interconnection with the following characteristics:
A. Introduction 1. Title: Verification of Models and Data for Turbine/Governor and Load Control or Active Power/Frequency Control Functions 2. Number: MOD-027-1 3. Purpose: To verify that the turbine/governor
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationAgricultural Data Verification Protocol for the Chesapeake Bay Program Partnership
Agricultural Data Verification Protocol for the Chesapeake Bay Program Partnership December 3, 2012 Summary In response to an independent program evaluation by the National Academy of Sciences, and the
More informationUnit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition
Unit Auxiliary Transformer Overcurrent Relay Loadability During a Transmission Depressed Voltage Condition NERC System Protection and Control Subcommittee March 2016 NERC Report Title Report Date I Table
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
PRC-025-1 Generator Relay Loadability A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities
More informationTransmission Facilities Rating Methodology
Document title Transmission Facilities Rating Methodology Document number EGR-TRMC-00009 Applies to: Transmission Engineering, Transmission System Operations, and Transmission Planning- Progress Energy
More informationStatistical Pulse Measurements using USB Power Sensors
Statistical Pulse Measurements using USB Power Sensors Today s modern USB Power Sensors are capable of many advanced power measurements. These Power Sensors are capable of demodulating the signal and processing
More informationDUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES. Transmission Planning
DUKE ENERGY CAROLINAS TRANSMISSION SYSTEM PLANNING GUIDELINES Transmission Planning TABLE OF CONTENTS I. SCOPE 1 II. TRANSMISSION PLANNING OBJECTIVES 2 III. PLANNING ASSUMPTIONS 3 A. Load Levels 3 B. Generation
More informationPJM Regulation Study Update
PJM Regulation Study Update July 19, 2016 Eric J. Endress Engineer, Performance Compliance Acronym Definitions RegD = Regulation D, Dynamic Regulation RegA = Regulation A, Traditional Regulation ACE =
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationComfort and Load Control: It s Getting Hot in Here But is the Utility to Blame?
Comfort and Load Control: It s Getting Hot in Here But is the Utility to Blame? Frank Stern, Navigant, Boulder, CO, USA Nicholas DeDominicis, PECO, Philadelphia, PA, USA Greg Ekrem, Navigant, Boulder,
More informationPOWER POTENTIAL: DISTRIBUTED ENERGY RESOURCES (DER) TECHNICAL SPECIFICATIONS GUIDANCE FOR PROVISION OF REACTIVE AND ACTIVE POWER SERVICES
POWER POTENTIAL: DISTRIBUTED ENERGY RESOURCES (DER) TECHNICAL SPECIFICATIONS GUIDANCE FOR PROVISION OF REACTIVE AND ACTIVE POWER SERVICES For use with the Power Potential DER Technical Characteristics
More informationNORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE)
COORDONNATEUR DE LA FIABILITÉ Direction Contrôle des mouvements d énergie Demande R-3944-2015 NORMES DE FIABILITÉ DE LA NERC (VERSION ANGLAISE) Original : 2016-10-14 HQCMÉ-10, Document 2 (En liasse) Standard
More informationWireless Transmissions:
Wireless Transmissions: An Examination of OpenWay Smart Meter Transmissions in a 24-Hour Duty Cycle Jeff French Applications Engineer Mike Belanger Product Line Manager 2011, Itron Inc. All rights reserved.
More informationPRC Generator Relay Loadability. A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1
A. Introduction 1. Title: Generator Relay Loadability 2. Number: PRC-025-1 Purpose: To set load-responsive protective relays associated with generation Facilities at a level to prevent unnecessary tripping
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules. 45-day Formal Comment Period with Initial Ballot June July 2014
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0
ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES 2014-03-31 - Revision 0 EUB Decision 2007-071 Board Direction 52 For questions or comments regarding
More informationVoltage and Reactive Procedures CMP-VAR-01
Voltage and Reactive Procedures CMP-VAR-01 NERC Standards: VAR-001-2 VAR-002-1.1b Effective Date: 07/31/2012 Document Information Current Revision 2.0 Review Cycle Annual Subject to External Audit? Yes
More informationSYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011
SYNCHROPHASOR TECHNOLOGY GLOSSARY Revision Date: April 24, 2011 Baselining using large quantities of historical phasor data to identify and understand patterns in interconnection-wide grid behavior, to
More informationEngineering Recommendation M30 Issue Standard Electricity Network Operator Electricity Smart Meter Configurations
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Engineering Recommendation M30 Standard Electricity Network Operator Electricity Smart Meter s www.energynetworks.org PUBLISHING AND
More informationTransmission Availability Data System Phase II Final Report
Transmission Availability Data System Phase II Final Report Prepared by the Transmission Availability Data System Task Force for the NERC Planning Committee Approved by the Planning Committee on: Table
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationStandard VAR-002-2b(X) Generator Operation for Maintaining Network Voltage Schedules
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationCentral Hudson Gas & Electric Corporation. Transmission Planning Guidelines
Central Hudson Gas & Electric Corporation Transmission Planning Guidelines Version 4.0 March 16, 2016 Version 3.0 March 16, 2009 Version 2.0 August 01, 1988 Version 1.0 June 26, 1967 Table of Contents
More informationGridLiance Reliability Criteria
GridLiance Reliability Criteria Planning Department March 1, 2018 FOREWORD The GridLiance system is planned, designed, constructed, and operated to assure continuity of service during system disturbances
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document Version 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying the definition.
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationUtility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:
Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n
More informationTRANSMISSION FACILITIES...7
Table of Contents 1. INTRODUCTION...4 1.1. Objective... 4 1.2. NERC FAC-008 Compliance... 4 1.3. Seminole s Normal Rating... 5 1.4. Seminole s Four-Hour Rating... 5 1.5. Seminole s Emergency Rating...
More informationPlanning Criteria. Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group
Planning Criteria Revision 1.4 MAINTAINED BY: Transmission Working Group System Protection and Control Working Group Supply Adequacy Working Group PUBLISHED: 10/9/2017 LATEST REVISION: Effective 7/25/2017
More informationTTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line
TTC Study for: the PEGS-Ambrosia Lake 230 kv Line and the PEGS-Bluewater 115 kv Line Vince Leung March 27, 2017 Reviewed by Johnny Nguyen Table of Contents Background 2 Objective 3 Base Case Assumptions
More informationCapacity Market Prequalification
Capacity Market Prequalification T-4 Auction December 2016 Early Auction January 2017 Transitional Arrangement Auction March 2017 Guidance document for Capacity Market participants Capacity Market Prequalification
More informationFinal ballot January BOT adoption February 2015
Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationMidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above
MidAmerican Energy Company Reliability Planning Criteria for 100 kv and Above March 13, 2018 Issued by: Dehn Stevens, Director System Planning and Services 1.0 SCOPE This document defines the criteria
More informationTable 1 - Assignment of BA Obligations... 8
Dynamic Transfer Reference Guidelines Version 2 June 2010 Table of Contents Table of Contents Chapter 1 Overview... 3 Purpose... 3 Terms... 3 Chapter 2 Dynamic Schedule Versus Pseudo-tie Fundamentals...
More informationModule 7-4 N-Area Reliability Program (NARP)
Module 7-4 N-Area Reliability Program (NARP) Chanan Singh Associated Power Analysts College Station, Texas N-Area Reliability Program A Monte Carlo Simulation Program, originally developed for studying
More informationLoad-Frequency Control Service in a Deregulated Environment
Load-Frequency Control Service in a Deregulated Environment A. P. Sakis Meliopoulos Fellow School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, GA 30332-0250 George J.
More informationTransmission Availability Data System 2008 Automatic Outage Metrics and Data Report Region: RFC
Transmission Availability Data System 2008 Automatic Outage Metrics and Data Report Region: RFC Table of Contents 1 Introduction...1 1.1 Contributors and Acknowledgements... 1 1.2 TADS History... 1 1.3
More informationEvaluation of Algorithm Performance /06 Gas Year Scaling Factor and Weather Correction Factor
Evaluation of Algorithm Performance - 2005/06 Gas Year Scaling Factor and Weather Correction Factor The annual gas year algorithm performance evaluation normally considers three sources of information
More informationReliability Guideline Integrating Reporting ACE with the NERC Reliability Standards
Reliability Guideline Integrating Reporting ACE with the NERC Reliability Standards Applicability: Balancing Authorities (BAs) Introduction and Purpose: It is in the public interest for NERC to develop
More informationVI.D AIR DISCONNECT SWITCHES
VI.D AIR DISCONNECT SWITCHES DMS #84474 Page 1 of 20 Revised: AIR DISCONNECT SWITCH RATINGS PENNSYLVANIA - NEW JERSEY - MARYLAND INTERCONNECTION PLANNING AND ENGINEERING COMMITTEE TRANSMISSION AND SUBSTATION
More informationSystem Ratings, Limits and Real-Time Monitoring. Presented to: Operating Committee April 21, 2016
System Ratings, Limits and Real-Time Monitoring Presented to: Operating Committee April 21, 2016 Thermal Facility Ratings In New England Summer ratings (April 1 to October 31) Winter ratings (November
More informationStandard MOD Area Interchange Methodology
A. Introduction 1. Title: Area Interchange Methodology 2. Number: MOD-028-2 3. Purpose: To increase consistency and reliability in the development and documentation of Transfer Capability calculations
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements
Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area
More informationAir Monitoring Directive Chapter 9: Reporting
Air Monitoring Directive Chapter 9: Reporting Version Dec 16, 2016 Amends the original Air Monitoring Directive published June, 1989 Title: Air Monitoring Directive Chapter 9: Reporting Number: Program
More informationGeneral Specifications
General Specifications GS 77J0A070E Model VJA7 Distributor (Multifunction) (Isolated Singleoutput and Isolated Dualoutput Types) Overview This plugin type distributor is used in combination with wire type
More informationRecently, the SS38 Working Group on Inter-Area Dynamic Analysis completed two study reports on behalf of the UFLS Regional Standard Drafting Team.
December 7 th, 2010 NPCC Full Member Committee; Please find attached a draft revised NPCC Regional Reliability Directory #12 Underfrequency Load Shedding Program Requirements and a draft revised NPCC UFLS
More informationCymbaluk Noise Complaints
Decision 20259-D01-2015 Cymbaluk Noise Complaints December 22, 2015 Alberta Utilities Commission Decision 20259-D01-2015 Cymbaluk Noise Complaints Proceeding 20259 Application 20259-A001 December 22, 2015
More informationWATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:
WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced
More informationAHRI Standard Standard for Performance Rating of Modulating Positive Displacement Refrigerant Compressors
AHRI Standard 545 2017 Standard for Performance Rating of Modulating Positive Displacement Refrigerant Compressors IMPORTANT SAFETY RECOMMENDATIONS AHRI does not set safety standards and does not certify
More information60V, 50mA, Ultra-Low Quiescent Current, Linear Regulator
General Description The MAX17651 ultra-low quiescent current, high-voltage linear regulator is ideal for use in industrial and batteryoperated systems. The device operates from a 4V to 60V input voltage,
More informationCalculating and Using Reporting ACE in a Tie Line Bias Control Program
Calculating and Using Reporting ACE in a Tie Line Bias Control Program Introduction: Tie Line Bias 1 (TLB) control has been used as the preferred control method in North America for 75 years. In the early
More informationROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT
ROCHESTER PUBLIC UTILITIES FACILITY RATINGS METHODOLOGY FOR TRANSMISSION, SUBSTATION, & GENERATION EQUIPMENT Page 1 of 8 The document describes the current methodology used for developing facility ratings
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationNPCC Regional Reliability Reference Directory # 12. Underfrequency Load Shedding Program Requirements
NPCC Regional Reliability Reference Directory # 12 Under frequency Load Shedding Program Requirements Task Force on System Studies Revision Review Record: June 26 th, 2009 March 3 rd, 2010 Adopted by the
More informationAlberta Reliability Standard Frequency Response and Frequency Bias Setting BAL-003-AB-1.1
1. Purpose The purpose of this reliability standard is to: (a) require sufficient frequency response from the ISO to maintain Interconnection frequency within predefined bounds by arresting frequency deviations
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document JanuaryVersion 2 April 2014 This technical reference was created by the Definition of Bulk Electric System drafting team to assist entities in applying
More informationOPTIONS [MATH FUNCTION] [TOTALIZER] [FLOW CORRECTION]
INST. INE-288C OPTIONS [MATH FUNCTION] [TOTALIZER] [FLOW CORRECTION] FOR AL/AH3000 SERIES HYBRID RECORDER Retain this manual apart from the instrument and in an easily accessible. Please make sure that
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationCOURSE NOTES Testing Compliance to Energy Efficiency Standards
COURSE NOTES Testing Compliance to Energy Efficiency Standards Introduction These course notes are to be read in association with the PI University video course, Testing Compliance to Energy Efficiency
More informationFrequency Response Characteristic Survey Training Document
Frequency Response Characteristic Survey Training Document Training Document Subsections Frequency Response Characteristic Response to Internal and External Generation/Load Imbalances Frequency Bias versus
More informationLab/Project Error Control Coding using LDPC Codes and HARQ
Linköping University Campus Norrköping Department of Science and Technology Erik Bergfeldt TNE066 Telecommunications Lab/Project Error Control Coding using LDPC Codes and HARQ Error control coding is an
More informationLine Impedance Estimation Using SCADA Data
Line Impedance Estimation Using SCADA Data Presenter: Ramiro Da Corte - Power System Engineer Prepared by: James Shen - Principal Engineer, AESO Nov. 5, 214 Background AESO is responsible for grid reliability
More informationAvailable Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University
Available Transfer Capability (ATC) EE 521 Analysis of Power Systems Chen-Ching Liu Washington State University i Available Transfer Capability (ATC) ATC measures the residual transfer capability in the
More informationA New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol
A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to
More informationDIGITAL THERMOMETER VIEW RECORDERS Digital Thermometer FEATURES
Digital Thermometer High-Accuracy Reference Junction Compensation: Compensation accuracy (±0.2 C) Input terminals are provided on both front and rear panels, and an input site is switch selectable. The
More informationCategory: ELECTRICITY Requirement: EL-ENG Page: 1 of 13. Document(s): S-E-01, S-E-04 Issue Date: Effective Date:
Requirements for Certification Category: ELECTRICITY Requirement: EL-ENG-11-02 Page: 1 of 13 Requirements for Certification and Use of Portable Measuring Apparatus for Reverification and Dispute Meter
More informationElectricity Ten Year Statement November Electricity Ten Year Statement November Appendix D
Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationST662AB ST662AC. DC-DC converter from 5 V to 12 V, 0.03 A for Flash memory programming supply. Features. Description
ST662AB ST662AC DC-DC converter from 5 V to 12 V, 0.03 A for Flash memory programming supply Features Output voltage: 12 V ± 5 % Supply voltage range: 4.5 V to 5.5 V Guaranteed output current up to 30
More informationAppendix D Fault Levels
Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses
More informationGeneral report format, ref. Article 12 of the Birds Directive, for the report
Annex 1: General report format, ref. Article 12 of the Birds Directive, for the 2008-2012 report 0. Member State Select the 2 digit code for your country, according to list to be found in the reference
More informationProposed Language in BAL-003-1/Comments New Standard or Other Action R1. Each Balancing Authority shall This. Attachment A.
in Approved Standard Translation to R1. Each Balancing Authority shall review its Frequency Bias Each Balancing Authority shall report its previous year s Settings by January 1 of each Frequency Response
More informationThe LIPAedge program has established the following rules for its operation:
LIPAedge Impact Methodology The LIPAedge program is a residential and small commercial direct load control program. The program has the following components: 1. Customer receives a programmable thermostat
More informationTampa Electric Company Facility Rating Methodology Approved 11/20/2018
Tampa Electric Company Facility Rating Methodology Approved 11/20/2018 Effective Date: 12/01/2018 Responsible Department: System Planning Review Cycle: 3 Years Last Date Reviewed: 11/16/2018 Next Planned
More information15.2 Rate Schedule 2 - Payments for Supplying Voltage Support Service
15.2 Rate pport Service This Rate Schedule applies to payments to Suppliers who provide Voltage Support Service to the ISO. Transmission Customers and Customers will purchase Voltage Support Service from
More informationArea Control Error (ACE) Equation Special Cases
Area Control Error (ACE) Equation Special Cases Purpose: It is the obligation of each Balancing Authority to manage its Area Control Error in accordance with NERC reliability standards. This Standard provides
More informationATTACHMENT Y STUDY REPORT
Dynegy Marketing and Trade, LLC Wood River Units 4 & 5: 473 MW Retirement: June 1, 2016 ATTACHMENT Y STUDY REPORT March 23, 2016 PUBLIC / REDACTED PUBLIC VERSION EXECUTIVE SUMMARY An Attachment Y notification
More informationStandard Development Timeline
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard is adopted by the Board of Trustees. Description
More informationOffice for Nuclear Regulation
Office for Nuclear Regulation ASSESSMENT REPORT Civil Nuclear Reactors Programme NNB Genco: Hinkley Point C Pre-Construction Safety Report 2012 Assessment Report for Work Stream B14, Radiation Protection
More informationNARUC. Summer Committee Meetings. Staff Subcommittees on Electricity & Electric Reliability
NARUC Summer Committee Meetings Staff Subcommittees on Electricity & Electric Reliability NARUC Summer Committee Meetings Agenda 10:00-11:00 am Tour of the Newtown Creek Biodigester Plant 1:00 2:00 pm
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More information8th Floor, 125 London Wall, London EC2Y 5AS Tel: +44 (0) Fax: +44 (0)
Ms Kristy Robinson Technical Principal IFRS Foundation 30 Cannon Street London EC4M 6XH 27 January 2016 Dear Kristy This letter sets out the comments of the UK Financial Reporting Council (FRC) on the
More informationLoss of Solar Resources during Transmission Disturbances due to Inverter Settings II
Loss of Solar Resources during Transmission Disturbances due to Inverter Settings II Informational Webinar on Level 2 NERC Alert Ryan Quint, Senior Manager, Advanced Analytics and Modeling Rich Bauer,
More informationMSI Design Examples. Designing a circuit that adds three 4-bit numbers
MSI Design Examples In this lesson, you will see some design examples using MSI devices. These examples are: Designing a circuit that adds three 4-bit numbers. Design of a 4-to-16 Decoder using five 2-to-4
More informationTransmission Availability Data System Automatic Outage Metrics and Data. Region: RFC 2009 Report
Transmission Availability Data System Automatic Outage Metrics and Data Region: RFC 2009 Report Table of Contents 1 Introduction... 1 1.1 Contributors and Acknowledgements...1 1.2 TADS History...1 1.3
More informationParasitically Powered Digital Input
EVALUATION KIT AVAILABLE Click here for production status of specific part numbers. General Description The is an IEC 61131-2 compliant, industrial digital input (DI) device that translates a 24V digital
More informationBulk Electric System Definition Reference Document
Bulk Electric System Definition Reference Document January, 2014 This draft reference document is posted for stakeholder comments prior to being finalized to support implementation of the Phase 2 Bulk
More informationThe Engineering Problem. Calculating GIC Flow through the EHV System
The Engineering Problem Calculating GIC Flow through the EHV System 1 Creating the GIC System Model Since the EHV system is a three-phase balanced network, it is only necessary to model a single-phase
More informationConsultation on Proposed National Rollout of Electricity and Gas Smart Metering
Consultation on Proposed National Rollout of Electricity and Gas Smart Metering RESPONSE FROM: Elster Metering Ltd RESPONSE SUBMISSION DATE: 12 th December 2011 DOCUMENT TYPE: Consultation Paper REFERENCE:
More informationDistributed generation on 11kV voltage constrained feeders
Distributed generation on 11kV voltage constrained feeders Report produced by University of Strathclyde for the Accelerating Renewables Connection Project Authors: Simon Gill: simon.gill@strath.ac.uk Milana
More informationG1 Capacity Market Metering
G1 Capacity Market Metering EMRS Guidance Public Version: 3.0 Date: 20 April 2018 Table of Contents Change Amendment Record 3 1. Introduction 4 2. Purpose 4 3. What are the allowed types of metering configuration?
More informationPRC Disturbance Monitoring and Reporting Requirements
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More information