1 Hilti, Inc. November Dallas Parkway, Suite 1000 Plano, Texas Toll Free Website Guide Specification Specifier Notes: This guide specification is written in Construction Specifications Institute (CSI) 3-Part Format in accordance with The CSI Construction Specifications Practice Guide, including MasterFormat, SectionFormat, and PageFormat. This Section must be carefully reviewed and edited by the Architect or Engineer to meet the requirements of the Project and applicable building code. Coordinate this Section with Division 01, other specification sections, and the Drawings. Delete all Specifier Notes after editing this Section. Section numbers and titles are based on MasterFormat 2014 Update. SECTION GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS Specifier Notes: This Section covers Hilti X-BT-ER threaded fasteners for use in grounding and bonding for electrical systems. Consult Hilti, Inc. for assistance in editing this Section for the specific application. PART 1 GENERAL 1.1 SECTION INCLUDES A. Threaded Fasteners for Use in for Electrical Systems: Specifier Notes: Edit the following list as required for the Project. 1. Electrical grounding of instrumentation. 2. Electrical bonding of pipe flanges. for Electrical Systems

2 1.2 RELATED REQUIREMENTS Specifier Notes: Edit the following list of related sections as required for the Project. Limit the list to sections with specific information that the reader might expect to find in this Section, but is specified elsewhere. A. Section Facility Lightning Protection: Grounding of lightning protection system. B. Section Site Grounding: Site-related grounding components for buildings and facilities. 1.3 REFERENCE STANDARDS Specifier Notes: List reference standards used elsewhere in this Section, complete with designations and titles. A. ANSI/NETA ATS Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems. B. EN Lightning Protection Components (LPC) - Part 1: Requirements for Connection Components. C. IEC Safety of Machinery Electrical Equipment of Machines - Part 1: General Requirements. D. IEC Low-Voltage Switchgear and Controlgear - Part 7-2: Ancillary Equipment - Protective Conductor Terminal Blocks for Copper Conductors. E. IEEE 142 Recommended Practice for Grounding of Industrial and Commercial Power Systems. F. IEEE 1100 Recommended Practice for Powering and Grounding Electronic Equipment. G. NFPA 70 National Electrical Code (NEC). H. UL 467 Equipment. 1.4 PRE-INSTALLATION MEETINGS Specifier Notes: Edit pre-installation meetings as required for the Project. Delete if not A. Convene pre-installation meeting [1 week] [2 weeks] before start of Work of this Section. B. Require attendance of parties directly affecting Work of this Section, including Contractor, Engineer, installer, and manufacturer s representative. for Electrical Systems

3 C. Review the Following: 1. Materials. 2. Installation. 3. Protection. 4. Coordination with other Work. 1.5 SUBMITTALS Specifier Notes: Edit submittal requirements as required for the Project. Delete submittals not A. Comply with Division 01. B. Product Data: Submit manufacturer s product data, including installation instructions. C. Warranty Documentation: Submit manufacturer s standard warranty. 1.6 QUALITY ASSURANCE A. Grounding Materials: 1. NFPA 70, Chapter 2, Articles 200 and IEEE UL labeled. B. Manufacturer s Qualifications: Manufacturer regularly engaged, for a minimum of 5 years, in the manufacturing of threaded fasteners used in grounding and bonding for electrical systems. C. Installer's Qualifications: 1. Installer regularly engaged, for a minimum of 5 years, in installation of products specified in this Section. 2. Employ persons trained by manufacturer for installation of products specified in this Section. 1.7 DELIVERY, STORAGE, AND HANDLING A. Delivery Requirements: Deliver materials to site in manufacturer s original, unopened containers and packaging, with labels clearly identifying product name and manufacturer. B. Storage and Handling Requirements: 1. Store and handle materials in accordance with manufacturer s instructions. 2. Keep materials in manufacturer s original, unopened containers and packaging until installation. 3. Store materials in clean, dry area indoors. 4. Protect materials during storage, handling, and installation to prevent damage. 1.8 AMBIENT CONDITIONS A. Do not install threaded fasteners under ambient conditions outside manufacturer s limits. for Electrical Systems

4 PART 2 PRODUCTS 2.1 MANUFACTURERS A. Manufacturer: Hilti, Inc., 7250 Dallas Parkway, Suite 1000, Plano, Texas Toll Free Website Specifier Notes: Specify if substitutions will be permitted. B. Substitutions: [Not permitted] [Comply with Division 01]. Specifier Notes: The electrical engineer must select, design, and evaluate the electrical wire, threaded fasteners, hardware, and grounding connectors for the specific application. 2.2 FASTENING SYSTEM A. Fastening System: Hilti X-BT-ER. 1. Threaded Fasteners: [ X-BT-ER M10/3 SN 4 ] [ X-BT-ER W10/3 SN 4 ] [ X-BT-ER M8/7 SN 4 ] [ X-BT-ER M6/7 SN 4 ] [ X-BT-ER W6/7 SN 4 ]. a. UL Listed: Listing number E B. Materials: 1. Shank: CR 500 (CrNiMo alloy) S31803 (1.4462); equivalent to A4/AISI grade Threaded Sleeve: X5CrNiMo H, Washer SN : S (X2CrNiMo , ). 4. Sealing Washer: Elastomer; black; resistant to UV, salt water, water, ozone, oils. C. Dimensions: 1. Thread Diameter: a. Threaded Fastener X-BT-ER M10/3 SN 4 : M10. b. Threaded Fastener X-BT-ER W10/3 SN 4 : UNC 3/8 inch. c. Threaded Fastener X-BT-ER M8/7 SN 4 : M8. d. Threaded Fastener X-BT-ER M6/7 SN 4 : M6. e. Threaded Fastener X-BT-ER W6/7 SN 4 : UNC 1/4 inch. 2. Thread Length: a. Threaded Fastener X-BT-ER M10/3 SN 4 : inch (24 mm). b. Threaded Fastener X-BT-ER W10/3 SN 4 : inch (24 mm). c. Threaded Fastener X-BT-ER M8/7 SN 4 : inch (24 mm). d. Threaded Fastener X-BT-ER M6/7 SN 4 : inch (20 mm). e. Threaded Fastener X-BT-ER W6/7 SN 4 : inch (20 mm). 3. Shank Diameter: inch (4.5 mm). 4. Washer SN Diameter: inch (12 mm). for Electrical Systems

5 5. Overall Length: a. Threaded Fastener X-BT-ER M10/3 SN 4 : inches (31.3 mm). b. Threaded Fastener X-BT-ER W10/3 SN 4 : inches (31.3 mm). c. Threaded Fastener X-BT-ER M8/7 SN 4 : inch (31.3 mm). d. Threaded Fastener X-BT-ER M6/7 SN 4 : inches (31.3 mm). e. Threaded Fastener X-BT-ER W6/7 SN 4 : inches (31.3 mm). D. Functional Bonding and Terminal Connection in a Circuit: For low permanent current due to static charge built-up in pipes or for low permanent current when closing electrical circuit. 1. Single-Point Connection: a. Threaded Fasteners: [ X-BT-ER M10/3 SN 4 ] [ X-BT-ER W10/3 SN 4 ] [ X-BT-ER M8/7 SN 4 ] [ X-BT-ER M6/7 SN 4 ] [ X-BT-ER W6/7 SN 4 ]. b. Maximum Allowable Permanent Current: 40 A. c. Connected Cable Size (tested to 40 A), IEC : Less than or equal to 10 mm 2 copper (size smaller or equal to 8 AWG). 1) Fastening of cables of larger diameters than 10mm 2 is acceptable, provided maximum permanent current of 40 A is not exceeded and provisions on cable lug thickness are observed. E. Protective Bonding Circuit: For discharging short circuit current while protecting electrical equipment or earth/ground or bonded cable trays and ladders. 1. Single-Point Connection: a. Threaded Fasteners: [ X-BT-ER M10/3 SN 4 ] [ X-BT-ER W10/3 SN 4 ] [ X-BT-ER M8/7 SN 4 ] [ X-BT-ER M6/7 SN 4 ] [ X-BT-ER W6/7 SN 4 ]. b. Maximum Short Circuit Current for Period of 1 s: 1,250 A. c. Connected Cable Size (tested to 1,250 A for 1 s), IEC : Less than or equal to 10 mm 2 copper (less than or equal to 8 AWG). 1) Fastening of cables of larger diameter than 10 mm 2 is acceptable provided maximum current of 1,250 A for a period of 1 second is not exceeded and provisions on cable lug thickness are observed. d. Connected Cable Size (tested to 750 A for 4 s), UL 467: Less than or equal to 10 AWG. 2. Double-Point Connection: for Electrical Systems

6 a. Threaded Fasteners: [ X-BT-ER M8/7 SN 4 ] [ X-BT-ER M6/7 SN 4 ] [ X-BT-ER W6/7 SN 4 ]. b. Maximum Short Circuit Current for Period of 1 s: 1,800 A. c. Connected Cable Size (tested to 1,800 A for 1 s), IEC : Less than or equal to 16 mm 2 copper (less than or equal to 6 AWG). 1) Fastening of cables of larger diameter than 10 mm 2 is acceptable provided maximum current of 1,800 A for a period of 1 second is not exceeded and provisions on cable lug thickness are observed. F. Lightning Protection: For high temporary current due to lightning. 1. Single-Point Connection: a. Threaded Fasteners: [ X-BT-ER M10/3 SN 4 ] [ X-BT-ER W10/3 SN 4 ] [ X-BT-ER M8/7 SN 4 ] [ X-BT-ER M6/7 SN 4 ] [ X-BT-ER W6/7 SN 4 ]. b. Maximum Current, EN and EN /prA: 50 ka for 2 ms. 2. When 1 Nut is Used and Cable Lug is in Contact with Base Material: a. Cable Lug: Direct contact with non-coated base material. b. Extra M10/W10 Stainless Steel Washer: Install between lock washer and cable lug. c. Base Material: Do not contact X-BT-ER SN washer, lock washer, and nut. d. Cable Lug Thickness: 2 mm to 12 mm. e. Minimum Cable Lug Hole Diameter: 13 mm. f. Maximum Tightening Torque: 8 Nm. g. Threaded Fasteners: [ X-BT-ER M10/3 SN 4 ] [ X-BT-ER W10/3 SN 4 ] [ X-BT-ER M8/7 SN 4 ]. h. Maximum Tested Current: 100 ka for 2 ms. G. Application Requirements: 1. Base Material: a. Minimum Thickness: 5/16 inch (8 mm). b. No through penetration. c. Steel Strength: No limits. 2. Maximum Thickness of Cable Lugs: a. Threaded Fasteners X-BT-ER M10/3 SN 4 and X-BT-ER W10/3 SN 4 : 0.12 inch (3 mm), single cable lug. b. Threaded Fasteners X-BT-ER M8/7 SN 4, X-BT-ER M6/7 SN 4, and X-BT-ER W6/7 SN 4 : 0.28 inch (7 mm), total of 2 cable lugs. for Electrical Systems

7 3. Detailing: a. Spacing: Minimum inch (15 mm) center-to-center. b. Edge Distance: Minimum inch (6 mm) center-to-edge. 4. Corrosion Resistance of Hilti CR500 and S31803 Stainless Steel Material: Equivalent to AISI 316 (A4) steel grade. PART 3 EXECUTION 3.1 EXAMINATION A. Examine areas to receive grounding and bonding for electrical systems. B. Notify Architect of conditions that would adversely affect installation or subsequent use. C. Do not begin installation until unacceptable conditions are corrected. 3.2 INSTALLATION A. Install grounding and bonding for electrical systems in accordance with IEEE 142, IEEE 1100, and NFPA 70. B. Install threaded fasteners for use in grounding and bonding for electrical systems in accordance with manufacturer s Instructions for Use supplied with fasteners at locations indicated on the Drawings. C. Pre-drill holes in base steel to proper depth using manufacturer s step-shank drill bit. 1. Ensure holes are perpendicular to surface. D. Ensure drilled holes and areas around drilled holes are free of liquids and debris before installation of threaded fasteners. E. Drive threaded fasteners into drilled holes in base steel using manufacturer s powder-actuated tool and cartridges. 1. Fastener Stand-Off: inches to inches (25.7 mm to 26.8 mm) for proper compression of sealing washers. F. Permanently attach equipment and grounding conductors before energizing equipment. G. Connect to site grounding system as specified in Section H. Bond to lightning protection system as specified in Section for Electrical Systems

8 3.3 FIELD QUALITY CONTROL ANSI/NETA ATS refers to specific ANSI standards and includes procedures and acceptable values for acceptance testing electrical equipment in accordance with those standards. Section 4 of ANSI/NETA ATS stipulates division of responsibility, possibly conflicting with conditions of the contract or general requirements. A. Inspect and test in accordance with ANSI/NETA ATS, except Section 4. B. : Perform inspections and tests listed in NETA ATS, Section C. Perform ground resistance testing in accordance with IEEE 142. D. Perform continuity testing in accordance with IEEE 142. E. When improper grounding is found on receptacles, check receptacles in entire project and correct. Perform retest. 3.4 PROTECTION A. Protect Work of this Section from damage during construction. END OF SECTION for Electrical Systems

The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15.

The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15. The following excerpt are pages from the North American Product Technical Guide, Volume 1: Direct Fastening, Edition 15. Please refer to the publication in its entirety for complete details on this product

More information

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Hilti, Inc South 122 nd East Avenue Tulsa, OK Attached are page(s) from the 2013 Hilti North American Product Technical Guide Volume 1 Direct Fastening. For complete details on this product, including data development, product specifications, general

More information

Product Guide Specification

Product Guide Specification Halfen USA, Inc. July 2014 8521 FM 1976 PO Box 547 Converse, Texas 78109 Toll Free 800-423-9140 Fax 877-683-4910 Website www.halfenusa.com Email info@halfenusa.com Product Guide Specification Specifier

More information

Product Guide Specification

Product Guide Specification HALFEN USA Inc. March 2012 8521 FM 1976 P.O. Box 547 Converse, TX 78109 Toll Free 800-423-9140 Fax 888-277-1695 Website www.halfenusa.com E-mail info@halfenusa.com Product Guide Specification Specifier

More information

Product Guide Specification

Product Guide Specification Extrutech Plastics, Inc. September 2012 5902 West Custer Street Manitowoc, Wisconsin 54220 Toll Free 888-818-0118 Phone 920-684-9650 Fax 920-684-4344 Website www.epiplastics.com E-mail info@epiplastics.com

More information

Product Guide Specification

Product Guide Specification Product Guide Specification Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat,

More information

Trusted ICC ES. Issued 06/2018 HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES. Issued 06/2018 HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 4185 Issued 06/2018 This report is subject to renewal 06/2019. SECTION: 05 05 23

More information

Product Guide Specification

Product Guide Specification VT Industries, Inc. April 2014 890 Central Court New Albany, Indiana 47150 Toll Free (800) 626-6271 Fax (712) 368-4111 Website www.vtindustries.com E-mail door_info@vtindustries.com Product Guide Specification

More information

Product Guide Specification

Product Guide Specification Shield Casework February 2014 3421 Merriam Lane Overland Park, Kansas 66203 Phone 913-744-2183 Fax 913-384-3477 Website www.shieldcasework.com E-mail info@shieldcasework.com Product Guide Specification

More information

S-BT screw-in stainless steel and carbon steel threaded studs

S-BT screw-in stainless steel and carbon steel threaded studs S-BT screw-in stainless steel and carbon steel threaded studs Product data Dimensions S-BT-MR M10/15 SN 6 S-BT-MR M10/15 SN 6 AL**) S-BT-MR W10/15 SN 6 S-BT-MR W10/15 SN 6 AL**) S-BT-MR M10/15 SN 5 ***)

More information

ETCHED PLAQUES by Matthews International

ETCHED PLAQUES by Matthews International ETCHED PLAQUES by Matthews International Note: These specifications were current at the time of publication but are subject to change without notice. Please confirm the accuracy of these specifications

More information

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS SECTION 270536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCESA / NASA UFGS-27 05 28.36 40 (August 2011) ----------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (November 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

Product Guide Specification For Nonrated & 20-Minute Rated Doors

Product Guide Specification For Nonrated & 20-Minute Rated Doors Woodtech Trading Company 455 Fourth Avenue E.N. P.O. Box 2609 Columbia Falls, MT 59912 800-775-1352 (phone) 800-775-1353 (fax) www.woodtechdoor.com Product Guide Specification For Nonrated & 20-Minute

More information

SECTION ROOF ACCESSORIES. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION ROOF ACCESSORIES. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 07720 ROOF ACCESSORIES PART 1 GENERAL 1.1 SECTION INCLUDES Display hidden notes to specifier. (Don't know how? Click Here) A. Attachment clamp system for standing seam metal roofs. B. Attachment

More information

SECTION STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS SECTION 05 12 00 - STRUCTURAL STEEL FRAMING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

A. Deviation from this standard must be approved by the Project Architect.

A. Deviation from this standard must be approved by the Project Architect. September 2012, rev. 00 26 5600 Exterior Lighting PART 1. GENERAL 1.01 Related Documents A. Deviation from this standard must be approved by the Project Architect. B. Drawings and general provisions of

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-27 05 28.36 40 (May 2017) --------------------------------- Preparing Activity: NASA Superseding UFGS-27 05 28.36 40 (August 2014) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: ELCO CONSTRUCTION PRODUCTS 1032 KERR DRIVE DECORAH, IOWA 52101

DIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: ELCO CONSTRUCTION PRODUCTS 1032 KERR DRIVE DECORAH, IOWA 52101 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-87 (2) 99-043 www.icc-es.org ESR-3332 Reissued 09/207 This report is subject to renewal 09/208. DIVISION: 0 00 00 METALS

More information

Hilti X-BT Threaded Fastener Specification. Supplement 02/2012. X-BT threaded fasteners for use in nuclear power plants

Hilti X-BT Threaded Fastener Specification. Supplement 02/2012. X-BT threaded fasteners for use in nuclear power plants Hilti X-BT Threaded Fastener Specification Operating instructions: DX 450-SCT Supplement 02/2012 X-BT threaded fasteners for use in nuclear power plants February 2012, revised August 2012 Early strength

More information

Product Guide Specification

Product Guide Specification VT Industries, Inc. 1000 Industrial Park PO Box 490 Holstein, Iowa 51025 Toll Free (800) 827-1615 Phone (712) 368-4381 Fax (712) 368-4111 Website www.vtindustries.com E-mail info@vtindustries.com Product

More information

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18

StormTrap Guide Specification. StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18 StormTrap Guide Specification StormTrap SingleTrap on Pad Foundation Groundwater BELOW Invert Revised 11/21/18 This product guide specification is written according to the Construction Specifications Institute

More information

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17

StormTrap Guide Specification. StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17 StormTrap Guide Specification StormTrap 2 SingleTrap on Aggregate Foundation Groundwater BELOW Invert Revised 11/30/17 This product guide specification is written according to the Construction Specifications

More information

Special Provision No. 904S14 October OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows:

Special Provision No. 904S14 October OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows: DOWELS INTO CONCRETE Item No. Special Provision No. 904S14 October 2005 OPSS 904, January 1995, Construction Specification for Concrete Structures, is amended as follows: 904.02 REFERENCES Section 904.02

More information

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY SECTION 26 05 36 CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY PART 1 -GENERAL 1.1 SUMMARY A. Section includes cable tray. 1.2 REFERENCES A. ASTM A 123 Standard Specification for Zinc (Hot-Dip Galvanized)

More information

Letter of Transmittal/Submittal

Letter of Transmittal/Submittal Letter of Transmittal/Submittal FROM: TO: Baker Concrete Construction 1904 Jasper Street DATE JOB NUMBER 09/23/10 Aurora, CO 80011 9921 303.367.8111 ATTENTION Nick Dewald 937.536.9000 RE: Bruce Herman

More information

Product Guide Specification

Product Guide Specification Zurn Industries, LLC November 2014 1801 Pittsburgh Avenue Erie, PA 16502 Toll Free (855) 663-9876 Phone (814) 455-0921 Fax (814) 871-6141 Website www.zurn.com Product Guide Specification Specifier Notes:

More information

SECTION SITE FURNISHINGS FOR CFCRT. 1. American Society for Testing and Materials (ASTM).

SECTION SITE FURNISHINGS FOR CFCRT. 1. American Society for Testing and Materials (ASTM). PART 1 - GENERAL 1.1 SECTION INCLUDES A. Benches. B. Trash receptacles. C. Bike storage. 1.2 REFERENCE STANDARDS A. Including but not limited to: 1. American Society for Testing and Materials (ASTM). 1.3

More information

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL

EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING MASTER SPECIFICATION SECTION 05720 METAL FENCING, GATES & RAILING SYSTEM PART 1 GENERAL EMMEGI ARCHITECTURAL FENCING is a high quality steel fencing system comprised of a hybrid

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

B. Manufacturers: Square-D, G.E. or Westinghosue.

B. Manufacturers: Square-D, G.E. or Westinghosue. SECTION 16470 - PANELBOARDS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410 DOCUMENT 009104 - ADDENDUM NO. 4 Issued to all Bidders: Date: October 14, 2015 Contract Name: Electrical Installation Contract Number: C8410 This addendum forms a part of the Bid described above. The original

More information

Material Specifications Technical Data

Material Specifications Technical Data 3.4.3.1 Product 3.4.3.2 Material Speciications 3.4.3.3 Technical Data 3.4.3.4 Installation Instructions 3.4.3.5 Ordering Information 3.4.3.1 Product Hilti provides a wide range of solutions for the attachment

More information

SolarMount (E)volution

SolarMount (E)volution SolarMount (E)volution SOLARMOUNT (E)VOLUTION: THE BEST JUST GOT BETTER. Engineering, Excellence, and Ease. Performance Engineered for versatility and reduced installation time, SolarMount (E)volution

More information

SECTION MASONRY ANCHORAGE AND REINFORCEMENT. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION MASONRY ANCHORAGE AND REINFORCEMENT. Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 04080 MASONRY ANCHORAGE AND REINFORCEMENT Display hidden notes to specifier. (Don't know how? Click Here) A. Post installed masonry anchors. B. Miscellaneous

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART I - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT SECTION 21 05 53 IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT Display hidden notes to specifier. (Don't know how? Click Here) Copyright 2015-2015 ARCAT, Inc. - All rights reserved PART 1 GENERAL

More information

SECTION BULLET- RESISTANT DOORS

SECTION BULLET- RESISTANT DOORS 1 SECTION 08 3950 BULLET- RESISTANT DOORS PART 1- GENERAL 1.01 SUMMARY A. This Section Includes: 1. Bullet- resistant steel door and frame systems. 2. Door hardware for bullet- resistant steel door and

More information

Communications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site

Communications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site Communications Integrators, Inc. June 2008 2625 S. Wilson Street, Suite 105 Tempe, Arizona 85282 Toll Free (800) 679-9711 Web Site www.ciinet.com Product Guide Specification Specifier Notes: This product

More information

Wood Deck Anchor. Instructions READ CAREFULLY Garrymore Ln Missoula, MT

Wood Deck Anchor. Instructions READ CAREFULLY Garrymore Ln Missoula, MT Wood Deck Anchor 9889 Garrymore Ln Missoula, MT 59808 888-687-3552 +1-406-549-0769 www.aquacreek.com Instructions PART #: F-40220-AT1 Pro Pool Lift - Weight Capacity (450 LBS) / Max Setback (19 ) Pro Pool

More information

A. This Section includes plumbing fixtures and related components.

A. This Section includes plumbing fixtures and related components. SECTION 224200 PLUMBING FIXTURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

1.04 QUALITY ASSURANCE

1.04 QUALITY ASSURANCE SECTION 07312 ARCHITECTURAL ASPHALT SHINGLES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI SELF-DRILLING AND SELF-PIERCING SCREWS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI SELF-DRILLING AND SELF-PIERCING SCREWS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2196 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 05 00

More information

TYPE APPROVAL CERTIFICATE

TYPE APPROVAL CERTIFICATE Page 1 / 5 File number: ACM 139/1905/2 Product code: 0226H This certificate is not valid when presented without the full attached schedule composed of 7 sections www.veristar.com TYPE APPROVAL CERTIFICATE

More information

Product Guide Specification

Product Guide Specification JELD-WEN, inc. November 2014 825 Shiner Road, PO Box 311 Towanda, Pennsylvania 18848 Toll Free 800-255-0785 Website www.miratectrim.com E-mail miratec@jeld-wen.com Product Guide Specification Specifier

More information

Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later

Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later Lateral Support Decks over 24 above grade require lateral support* *Exceptions to be discussed later Decking Types of Decking: -2x4s & 2x6s -five quarter span rated decking boards -Wood plastic composite

More information

FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS

FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS DIVISION 23 FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS Part I General 1.1 Related Documents A. All terms and general provisions of contract, General and Supplementary Conditions, and Specification

More information

MTS-ZB. RENOGY Photovoltaic Module Z-Bracket Mounting System E Philadelphia St, Ontario, CA Version: 1.

MTS-ZB. RENOGY Photovoltaic Module Z-Bracket Mounting System E Philadelphia St, Ontario, CA Version: 1. MTS-ZB RENOGY Photovoltaic Module Z-Bracket Mounting System 2775 E Philadelphia St, Ontario, CA 91761 1-800-330-8678 1 Version: 1.0 Important Safety Instructions Please save these instructions. This manual

More information

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions

Outline. Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions www.we-llc.com Outline Grounding Washer, Electrical Equipment Bond (WEEB) Acme Cable Clips Acme Conduit Entry (ACE) Questions Bonding & Grounding Grounding Terms Equipment Grounding: The National Electrical

More information

USER MANUAL Nord-Lock X-series washers

USER MANUAL Nord-Lock X-series washers USER MANUAL Nord-Lock X-series washers JOINT GUIDE 3 ASSEMBLY INSTRUCTIONS 4 TECHNICAL DATA 5 TORQUE GUIDE 5 THE EXCEPTIONAL SYSTEM THAT PREVENTS BOLT LOOSENING AND SLACKENING Nord-Lock X-series washers

More information

A. Extent of structural precast concrete work is shown on drawings and in schedules.

A. Extent of structural precast concrete work is shown on drawings and in schedules. SECTION 03 41 00 - STRUCTURAL PRECAST CONCRETE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 specification

More information

A. Product Data: For each electrical identification product indicated.

A. Product Data: For each electrical identification product indicated. SECTION 16075 - ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Fastener Basics. Common Fastener Types. Fastener Materials. Grade / Class and Fastener Strength

Fastener Basics. Common Fastener Types. Fastener Materials. Grade / Class and Fastener Strength Fastener Basics Common Fastener Types Fastener Grade (US) or Class (metric) refers to the mechanical properties of the fastener material. Generally, a higher number indicates a stronger, more hardened

More information

SECTION SIGNAGE

SECTION SIGNAGE SECTION 10 14 00 SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1 specification section, apply

More information

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY SECTION 280553-IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY PART 1 - GENERAL 1.1 DESCRIPTION A. This specification section covers the furnishing and installation of nameplates, labels, wire markers,

More information

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section 02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,

More information

SECTION CONCRETE ANCHORING. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION CONCRETE ANCHORING. Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES SECTION 03 15 00 CONCRETE ANCHORING Display hidden notes to specifier. (Don't know how? Click Here) A. General purpose mechanical anchors for horizontal and vertical

More information

Ground Clamps Cable Tray

Ground Clamps Cable Tray commercial and industrial fittings: ing Fittings and Solderless Connectors Clamps Cable Tray Terminates ground wire to cable tray. For aluminum or copper conductors. 1 4 hex wrench tightens both tray and

More information

GROUNDING EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA

GROUNDING EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA EA PAGE 86 5000 500 5040 5060 5080 500 50 540 560 580 500 540 560 580 5300 5340 5360 5380 5400 5440 5460 5480 5500 5540 5560 700 705 75 70 75 730 740 745 750 755 765 770 775 780 790 7300 7305 730 C 00 C 0

More information

SECTION TRANSFORMERS

SECTION TRANSFORMERS SECTION 16460 - TRANSFORMERS PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Section

More information

Elco Construction Products 1301 Kerr Drive Decorah, IA fax:

Elco Construction Products 1301 Kerr Drive Decorah, IA fax: Technical Manual 2010 HangerMate anchors were designed to speed installation of fire sprinkler, HVAC, refrigeration, general piping, and electrical systems. They can also be used to install strut channels,

More information

SECTION TRACER WIRE FOR NONMETALLIC PIPE

SECTION TRACER WIRE FOR NONMETALLIC PIPE PART 1 GENERAL 1.1 DESCRIPTION A. The CONTRACTOR shall furnish and install a conductive tracer wire with all buried plastic water mains, services and appurtenances in accordance with the Water Utilities

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS PART 1 GENERAL 1.01 Scope of Work A. Provide material, accessories, tools, equipment and labor as required for the complete fabrication

More information

MTS-ACB. RENOGY Photovoltaic Module Adjustable Curved Bracket E Philadelphia St, Ontario, CA Version: 1.

MTS-ACB. RENOGY Photovoltaic Module Adjustable Curved Bracket E Philadelphia St, Ontario, CA Version: 1. MTS-ACB RENOGY Photovoltaic Module Adjustable Curved Bracket 2775 E Philadelphia St, Ontario, CA 91761 1-800-330-8678 1 Version: 1.0 Important Safety Instructions Please save these instructions. This manual

More information

THE SCOUT WOOD-DECK ANCHOR

THE SCOUT WOOD-DECK ANCHOR THE SCOUT WOOD-DECK ANCHOR 1.95" SCOUT POOL LIFT (SOLD SEPARATELY) 6" 6" [356mm] 14" [152mm] 6" [406mm] 16" OC [368mm] 14 1/8" WOODEN OR SYNTHETIC DECKING BOLT COPPER BONDING-LUG (ANY OF FOUR CORNERS)

More information

Section COUPLINGS AND COUPLING ADAPTERS. This Section covers couplings and coupling adapters for ductile iron and steel pipe.

Section COUPLINGS AND COUPLING ADAPTERS. This Section covers couplings and coupling adapters for ductile iron and steel pipe. PART 1 GENERAL 1.01 SUMMARY Section 15155 This Section covers couplings and coupling adapters for ductile iron and steel pipe. 1.02 MEASUREMENT AND PAYMENT A. No separate payment for Work performed under

More information

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series

1. ANSI/ASME Standard B , Square and Hex Bolts and Screws, Inch Series SECTION 31 66 13 HELICAL PILES AND HELICAL ANCHORS PART 1 - GENERAL 1.1 DESCRIPTION A. This work pertains to furnishing and installing Helical Piles and Bracket Assemblies shown in the Contract in accordance

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 07311 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-08 33 13 (May 2009) Change 2-11/12 --------------------------- Preparing Activity: USACE Nontechnical Title Revision (August 2015) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

I-VICFLEX.VS1. Victaulic VicFlex Style VS1 Dry Sprinkler WARNING WARNING TECHNICAL DATA BEND CHARACTERISTICS INSTALLATION INSTRUCTIONS SIDEWALL

I-VICFLEX.VS1. Victaulic VicFlex Style VS1 Dry Sprinkler WARNING WARNING TECHNICAL DATA BEND CHARACTERISTICS INSTALLATION INSTRUCTIONS SIDEWALL INSTALLATION INSTRUCTIONS I-VICFLEX.VS1 Victaulic VicFlex Style VS1 Dry Sprinkler SIDEWALL Y Read and understand all instructions before attempting to install any Victaulic VicFlex Style VS1 Dry Sprinklers.

More information

1.1 RELATED DOCUMENTS

1.1 RELATED DOCUMENTS SECTION 050505 -BEVEL RAIL ENDS PART 1- GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the contract, including General and Supplementary Conditions and Division 01 Specification Sections

More information

St. Monica Food Pantry Low Voltage (600V and less) Conductors and Cables sys-tek No

St. Monica Food Pantry Low Voltage (600V and less) Conductors and Cables sys-tek No St. Monica Food Pantry 26 0519-1 ELECTRICAL WORK DIVISION 26 SECTION 260519 LOW VOLTAGE (600V AND LESS) PART 1. GENERAL 1.1 WIRES (SINGLE CONDUCTOR) AND CABLES (MULTI-CONDUCTOR ASSEMBLIES) USED FOR THE

More information

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY

SECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related

More information

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric

More information

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM 2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System

More information

Swerve Rack CUSTOM RACKS AVAILABLE

Swerve Rack CUSTOM RACKS AVAILABLE CUSTOM RACKS AVAILABLE Swerve Rack The design of the Swerve mirrors the bike frame, thus providing superior bike support while making it easy to secure both the bike frame and wheel with a standard u-lock.

More information

1. ASME A Scheme for the Identification of Piping Systems.

1. ASME A Scheme for the Identification of Piping Systems. SECTION 40 05 53 - IDENTIFICATION FOR PROCESS PIPING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Nameplates. 2. Tags. 3. Stencils. 4. Pipe markers. 5. Labels. 6. Lockout devices. B. Related Requirements:

More information

RADIO AND TELEVISION SATELLITE EQUIPMENT

RADIO AND TELEVISION SATELLITE EQUIPMENT ARTICLE 810 RADIO AND TELEVISION SATELLITE EQUIPMENT Introduction to Article 810 Radio and Television Satellite Equipment This article covers transmitter and receiver (antenna) equipment and the wiring

More information

The School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS

The School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 10441 (10 14 00) SIGNAGE A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division-1 specification section,

More information

Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder. Installation Instructions Revised 9/2/2016

Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder. Installation Instructions Revised 9/2/2016 Attachment of Residential Deck Ledger to Side of Metal Plate Connected Wood Truss Floor Ladder Installation Instructions Revised 9/2/2016 SBCA has been the voice of the structural building components industry

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

Page 1 of 6 Systems Inc.

Page 1 of 6 Systems Inc. Page 1 of 6 This symbol indicates that dangerous voltage constituting a risk of electric shock is present within this unit. This symbol indicates that there are important operating and maintenance instructions

More information

Rayport G Eco Dealer Kit

Rayport G Eco Dealer Kit Rayport G Eco Dealer Kit Installation Guide www.aetenergy.com Supporting a Cleaner, Greener Tomorrow 1. Table of Contents 1. Table of Contents P2 2. Installer Notes P3 3. Parts List P4-7 4. Tool List P8

More information

Assmann Corporation of America TANK INSTALLATION AND USE GUIDELINES FOR BULK STORAGE TANKS

Assmann Corporation of America TANK INSTALLATION AND USE GUIDELINES FOR BULK STORAGE TANKS Assmann Corporation of America TANK INSTALLATION AND USE GUIDELINES FOR BULK STORAGE TANKS General Information Assmann polyethylene storage tanks are manufactured to give you the toughest, most reliable

More information

Installation Instructions/Operation and Maintenance Manual. PS DOORS Contact Information. Website psdoors.com

Installation Instructions/Operation and Maintenance Manual. PS DOORS Contact Information. Website psdoors.com Ladder Safety Gate Installation Instructions/Operation and Maintenance Manual Models All Models: LSG-5 to LSG-48 Table of Contents Product Information...2 Inspection & Mainteance...2 Warranty Information...2

More information

Wisconsin Contractors Institute Continuing Education

Wisconsin Contractors Institute Continuing Education IMPORTANT NOTE: You should have received an email from us with a link and password to take your final exam online. Please check your email for this link. Be sure to check your spam folder as well. If you

More information

Cisco Aironet 2.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT2588P3M-N)

Cisco Aironet 2.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT2588P3M-N) Cisco Aironet.4-GHz/5-GHz 8-dBi Directional Antenna (AIR-ANT588P3M-N) This document outlines the specifications for the Cisco Aironet AIR-ANT588P3M-N.4/5-GHz 8-dBi 3-Port Directional Antenna with N-connectors

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING SECTION 230516 - EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION SLATE SHINGLES. 1.1 SUMMARY A. Section Includes: 1. Slate shingles over underlayment nailed to roof sheathing.

SECTION SLATE SHINGLES. 1.1 SUMMARY A. Section Includes: 1. Slate shingles over underlayment nailed to roof sheathing. SECTION 07 31 26 SLATE SHINGLES SPEC WRITER NOTES: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Slate shingles

More information

FLOOR ANCHOR SYSTEM APPLICATIONS L TRACK APPLICATIONS

FLOOR ANCHOR SYSTEM APPLICATIONS L TRACK APPLICATIONS FLOOR ANCHOR SYSTEM APPLICATIONS Sure-Lok recommends the following for floor anchor system layout and installation. These recommendations are not all-inclusive and may not be applicable to every system

More information

SIG-032-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY III LUMINAIRE ARM (SEE CONTRACT) 6'-0", 8'-0", 10'-0" NOMINAL SPREAD

SIG-032-B TRAFFIC SIGNAL MAST ARM POLE AND MAST ARM DETAILS - CATEGORY III LUMINAIRE ARM (SEE CONTRACT) 6'-0, 8'-0, 10'-0 NOMINAL SPREAD Michigan Department of Transportation 6'-0", 8'-0", 10'-0" NOMINAL SPREAD (SEE CONTRACT) LUMINAIRE ARM (SEE CONTRACT) POLE CAP 1'-6" (6'-0" ARM) 1'-10" (8'-0" ARM) 2'-0" (10'-0" ARM) NOMINAL RISE 2.38"

More information

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33 Part VIII Electrical CHAPTER 33 GENERAL REQUIREMENTS < SECTION E3301 GENERAL E3301.1 Scope. The installation of electrical systems, equipment and components indoors and outdoors that are within the scope

More information

Slate Shingle Specifications

Slate Shingle Specifications Slate Shingle Specifications California Slate is a proud member of the Slate Roofing Contractors Association of North America, Inc. (SRCA) which publishes Section 07310 Slate Shingles setting forth architectural

More information

INSTALLATION GUIDE SM SOLAR MOUNT PUB15JAN01

INSTALLATION GUIDE SM SOLAR MOUNT PUB15JAN01 MOUNT INSTALLATION GUIDE PUB5JAN0 SM SOLAR Wrenches and Torque Wrench Size Recommended Torque (ft-lbs) /4 Hardware 7/6 *0 3/8 Hardware 9/6 *30 # Hardware 5/6 0 Torques are not designed for use with wood

More information

SCREW FASTENER SELECTION FOR COLD-FORMED STEEL FRAME CONSTRUCTION

SCREW FASTENER SELECTION FOR COLD-FORMED STEEL FRAME CONSTRUCTION test TECHNICAL NOTE On Cold-Formed Steel Construction $5.00 Cold-Formed Steel Engineers Institute Washington, DC www.cfsei.org 866-465-4732 SCREW FASTENER SELECTION FOR COLD-FORMED STEEL FRAME CONSTRUCTION

More information

DIRECT FASTENING SYSTEMS. Hilti. Outperform. Outlast.

DIRECT FASTENING SYSTEMS. Hilti. Outperform. Outlast. DIRECT FASTENING SYSTEMS. Hilti. Outperform. Outlast. Powder-Actuated Tools and Fasteners DX - Light Tools DX 460-F8 Page 140 DX 460 MX Page 141 Consumables X-U, X-C, X-FS, X-HS U, X-M, X-EM Page 142 Insulation

More information