1 CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2 Requirements. Roof and ceiling construction shall be capable of accommodating all loads imposed according to Section R01 and of transmitting the resulting loads to the supporting structural elements. R801. Roof drainage. In areas where expansive or collapsible soils are known to exist, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge roof drainage to the ground surface at least feet (12 mm) from foundation walls or to an approved drainage system. R801. Drainage control. Where required by the building official, all dwellings shall have a controlled method of water disposal from roofs that will collect and discharge all roof drainage in accordance with the Plumbing Code. SECTION R802 WOOD ROOF FRAMING R802.1 Identification. Load-bearing dimension lumber for rafters, trusses and ceiling joists shall be identified by a grade mark of a lumber grading or inspection agency that has been approved by an accreditation body that complies with DOC PS 20. In lieu of a grade mark, a certificate of inspection issued by a lumber grading or inspection agency meeting the requirements of this section shall be accepted. R Blocking. Blocking shall be a minimum of utility grade lumber. R End-jointed lumber. Approved end-jointed lumber identified by a grade mark conforming to Section R802.1 may be used interchangeably with solid-sawn members of the same species and grade. R Fire-retardant-treated wood. Fire-retardanttreated wood (FRTW) is any wood product which, when impregnated with chemicals by a pressure process or other means during manufacture, shall have, when tested in accordance with ASTM E 8, a listed flame spread index of 2 or less and shows no evidence of significant progressive combustion when the test is continued for an additional 20-minute period. In addition, the flame front shall not progress more than 10. feet (200 mm) beyond the center line of the burners at any time during the test. R Labeling. Fire-retardant-treated lumber and wood structural panels shall be labeled. The label shall contain: 1. The identification mark of an approved agency in accordance with Section 170. of the Building Code. 2. Identification of the treating manufacturer.. The name of the fire-retardant treatment.. The species of wood treated.. Flame spread and smoke-developed rating. 6. Method of drying after treatment. 7. Conformance to appropriate standards in accordance with Sections R through R For FRTW exposed to weather, or a damp or wet location, the words No increase in the listed classification when subjected to the Standard Rain Test (ASTM D 2898). R Strength adjustments. Design values for untreated lumber and wood structural panels as specified in Section R802.1 shall be adjusted for fire-retardanttreated wood. Adjustments to design values shall be based upon an approved method of investigation which takes into consideration the effects of the anticipated temperature and humidity to which the fire-retardant-treated wood will be subjected, the type of treatment and redrying procedures. R Wood structural panels. The effect of treatment and the method of redrying after treatment, and exposure to high temperatures and high humidities on the flexure properties of fire-retardant-treated softwood plywood shall be determined in accordance with ASTM D 16. The test data developed by ASTM D 16 shall be used to develop adjustment factors, maximum loads and spans, or both for untreated plywood design values in accordance with ASTM D 60. Each manufacturer shall publish the allowable maximum loads and spans for service as floor and roof sheathing for their treatment. R Lumber. For each species of wood treated, the effect of the treatment and the method of redrying after treatment and exposure to high temperatures and high humidities on the allowable design properties of fire-retardant-treated lumber shall be determined in accordance with ASTM D 66. The test data developed by ASTM D 66 shall be used to develop modification factors for use at or near room temperature and at elevated temperatures and humidity in accordance with ASTM D 681. Each manufacturer shall publish the modification factors for service at temperatures of not less than 80 F (27 C) and for roof framing. The roof framing modification factors shall take into consideration the climatological location. > 2008 OREGON RESIDENTIAL SPECIALTY CODE

2 R Exposure to weather. Where fire-retardant-treated wood is exposed to weather or damp or wet locations, it shall be identified as Exterior to indicate there is no increase in the listed flame spread index as defined in Section R when subjected to ASTM D R Interior applications. Interior fire-retardant-treated wood shall have a moisture content of not over 28 percent when tested in accordance with ASTM D 201 procedures at 92 percent relative humidity. Interior fire-retardant-treated wood shall be tested in accordance with Section R or R Interior fire-retardant-treated wood designated as Type A shall be tested in accordance with the provisions of this section. R Moisture content. Fire-retardant-treated wood shall be dried to a moisture content of 19 percent or less for lumber and 1 percent or less for wood structural panels before use. For wood kiln dried after treatment (KDAT) the kiln temperatures shall not exceed those used in kiln drying the lumber and plywood submitted for the tests described in Section R for plywood and R for lumber. R Structural glued laminated timbers. Glued laminated timbers shall be manufactured and identified as required in AITC A190.1 and ASTM D 77. R Structural log members. Stress grading of structural log members of nonrectangular shape, as typically used in log buildings, shall be in accordance with ASTM D 97. Such structural log members shall be identified by the grade mark of an approved lumber grading or inspection agency. In lieu of a grade mark on the material, a certificate of inspection as to species and grade issued by a lumber-grading or inspection agency meeting the requirements of this section shall be permitted to be accepted. R802.2 Design and construction. The framing details required in Section R802 apply to roofs having a minimum slope of three units vertical in units horizontal (2-percent slope) or greater. Roof-ceilings shall be designed and constructed in accordance with the provisions of this chapter and Figures R606.11(1), R606.11(2) and R606.11() or in accordance with AFPA/NDS. Components of roof-ceilings shall be fastened in accordance with Table R602.(1). R802. Framing details. Rafters shall be framed to ridge board or to each other with a gusset plate as a tie. Ridge board shall be at least 1-inch (2 mm) nominal thickness and not less in depth than the cut end of the rafter. At all valleys and hips there shall be a valley or hip rafter not less than 2-inch (1 mm) nominal thickness and not less in depth than the cut end of the rafter. Hip and valley rafters shall be supported at the ridge by a brace to a bearing partition or be designed to carry and distribute the specific load at that point. Where the roof pitch is less than three units vertical in units horizontal (2-percent slope), structural members that support rafters and ceiling joists, such as ridge beams, hips and valleys, shall be designed as beams. R Ceiling joist and rafter connections. Ceiling joists and rafters shall be nailed to each other in accordance with Table R802..1(9), and the rafter shall be nailed to the top wall plate in accordance with Table R602.(1). Ceiling joists shall be continuous or securely joined in accordance with Table R802..1(9) where they meet over interior partitions and are nailed to adjacent rafters to provide a continuous tie across the building when such joists are parallel to the rafters. Where ceiling joists are not connected to the rafters at the top wall plate, joists connected higher in the attic shall be installed as rafter ties, or rafter ties shall be installed to provide a continuous tie. Where ceiling joists are not parallel to rafters, rafter ties shall be installed. Rafter ties shall be a minimum of 2-inch by -inch (1 mm by 102 mm) (nominal), installed in accordance with the connection requirements in Table R802..1(9), or connections of equivalent capacities shall be provided. Where ceiling joists or rafter ties are not provided, the ridge formed by these rafters shall be supported by a wall or girder designed in accordance with accepted engineering practice. Collar ties or ridge straps to resist wind uplift shall be connected in the upper third of the attic space in accordance with Table R602.(1). Collar ties shall be a minimum of 1-inch by -inch (2 mm by 102 mm) (nominal), spaced not more than feet (19 mm) on center. R Ceiling joists lapped. Ends of ceiling joists shall be lapped a minimum of inches (76 mm) or butted over bearing partitions or beams and toenailed to the bearing member. When ceiling joists are used to provide resistance to rafter thrust, lapped joists shall be nailed together in accordance with Table R602.(1) and butted joists shall be tied together in a manner to resist such thrust. R802. Allowable ceiling joist spans. Spans for ceiling joists shall be in accordance with Tables R802.(1) and R802.(2). For other grades and species and for other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters. R802. Allowable rafter spans. Spans for rafters shall be in accordance with Tables R802..1(1) through R802..1(8). For other grades and species and for other loading conditions, refer to the AF&PA Span Tables for Joists and Rafters. The span of each rafter shall be measured along the horizontal projection of the rafter. Exception: Spans for rafters in accordance with WWPA Western Lumber Span Tables. R Purlins. Installation of purlins to reduce the span of rafters is permitted as shown in Figure R Purlins shall be sized no less than the required size of the rafters that they support. Purlins shall be continuous and shall be supported by 2-inch by -inch (1 mm by 102 mm) braces installed to bearing walls at a slope not less than degrees from the horizontal. The braces shall be spaced not more than feet (19 mm) on center and the unbraced length of braces shall not exceed 8 feet (28 mm). R802.6 Bearing. The ends of each rafter or ceiling joist shall have not less than 1 1 / 2 inches (8 mm) of bearing on wood or OREGON RESIDENTIAL SPECIALTY CODE

3 metal and not less than inches (76 mm) on masonry or concrete. R Finished ceiling material. If the finished ceiling material is installed on the ceiling prior to the attachment of the ceiling to the walls, such as in construction at a factory, a compression strip of the same thickness as the finish ceiling material shall be installed directly above the top plate of bearing walls if the compressive strength of the finish ceiling material is less than the loads it will be required to withstand. The compression strip shall cover the entire length of such top plate and shall be at least one-half the width of the top plate. It shall be of material capable of transmitting the loads transferred through it. R802.7 Cutting and notching. Structural roof members shall not be cut, bored or notched in excess of the limitations specified in this section. R Sawn lumber. Notches in solid lumber joists, rafters and beams shall not exceed one-sixth of the depth of the member, shall not be longer than one-third of the depth of the member and shall not be located in the middle one-third of the span. Notches at the ends of the member shall not exceed one-fourth the depth of the member. The tension side of members inches (102 mm) or greater in nominal thickness shall not be notched except at the ends of the members. The diameter of the holes bored or cut into members shall not exceed one-third the depth of the member. Holes shall not be closer than 2 inches (1 mm) to the top or bottom of the member, or to any other hole located in the member. Where the member is also notched, the hole shall not be closer than 2 inches (1 mm) to the notch. Exception: Notches on cantilevered portions of rafters are permitted provided the dimension of the remaining portion of the rafter is not less than -inch nominal (102 mm) and the length of the cantilever does not exceed 2 inches (610 mm). R Engineered wood products. Cuts, notches and holes bored in trusses, structural composite lumber, structural glue-laminated members or I-joists are prohibited except where permitted by the manufacturer s recommendations or where the effects of such alterations are specifically considered in the design of the member by a registered design professional. R802.8 Lateral support. Rafters and ceiling joists having a depth-to-thickness ratio exceeding to 1 based on nominal dimensions shall be provided with lateral support at points of bearing to prevent rotation. R Bridging. Rafters and ceiling joists having a depthto-thickness ratio exceeding 6 to 1 based on nominal dimensions shall be supported laterally by solid blocking, diagonal bridging (wood or metal) or a continuous 1-inch by -inch (2mmby76mm)woodstripnailedacrosstheraftersor ceiling joists at intervals not exceeding 8 feet (28 mm). R802.9 Framing of openings. Openings in roof and ceiling framing shall be framed with header and trimmer joists. When the header joist span does not exceed feet (19 mm), the header joist may be a single member the same size as the ceiling joist or rafter. Single trimmer joists may be used to carry a single header joist that is located within feet (91 mm) of the trimmer joist bearing. When the header joist span exceeds feet (19 mm), the trimmer joists and the header joist shall be doubled and of sufficient cross section to support the ceiling joists or rafter framing into the header. Approved hangers shall be used for the header joist to trimmer joist connections when the header joist span exceeds 6 feet (1829 mm). Tail joists over feet (68 mm) long shall be supported at the header by framing anchors or on ledger strips not less than 2 inches by 2 inches (1 mm by 1 mm). R Wood trusses. R Truss design drawings. Truss design drawings, prepared in conformance to Section R , shall be provided to the building official and approved prior to installation. Truss design drawings shall include, at a minimum, the information specified below. Truss design drawing shall be provided with the shipment of trusses delivered to the jobsite. 1. Slope or depth, span and spacing. 2. Location of all joints.. Required bearing widths.. Design loads as applicable..1. Top chord live load (as determined from Section R01.6)..2. Top chord dead load... Bottom chord live load... Bottom chord dead load... Concentrated loads and their points of application..6. Controlling wind and earthquake loads.. Adjustments to lumber and joint connector design values for conditions of use. 6. Each reaction force and direction. 7. Joint connector type and description (e.g., size, thickness or gage) and the dimensioned location of each joint connector except where symmetrically located relative to the joint interface. 8. Lumber size, species and grade for each member. 9. Connection requirements for: 9.1. Truss to girder-truss Truss ply to ply. 9.. Field splices. 10. Calculated deflection ratio and/or maximum description for live and total load. 11. Maximum axial compression forces in the truss members to enable the building designer to design the size, connections and anchorage of the permanent continuous lateral bracing. Forces shall be shown on the truss design drawing or on supplemental documents.. Required permanent truss member bracing location OREGON RESIDENTIAL SPECIALTY CODE

4 TABLE R802.(1) CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics without storage, live load = 10 psf, L/Δ = 20) CEILING JOIST SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # Southern -pine # # DEAD LOAD = psf Maximum ceiling joist spans (continued) OREGON RESIDENTIAL SPECIALTY CODE

5 CEILING JOIST SPACING ( 2 TABLE R802.(1) continued CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics without storage, live load = 10 psf, L/Δ = 20) SPECIES AND GRADE # #1 #2 # # # DEAD LOAD = psf Maximum ceiling joist spans Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE

6 TABLE R802.(2) CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics with limited storage, live load = 20 psf, L/Δ = 20) CEILING JOIST SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # DEAD LOAD = 10 psf Maximum ceiling joist spans (continued) OREGON RESIDENTIAL SPECIALTY CODE

7 CEILING JOIST SPACING ( 2 TABLE R802.(2) continued CEILING JOIST SPANS FOR COMMON LUMBER SPECIES (Uninhabitable attics with limited storage, live load = 20 psf, L/Δ = 20) SPECIES AND GRADE # #1 #2 # # # DEAD LOAD = 10 psf Maximum Ceiling Joist Spans Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE

8 TABLE R802..1(1) RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling not attached to rafters, L/Δ = 180) RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

9 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1(1) continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls. b. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE

10 TABLE R802..1(2) RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling attached to rafters, L/Δ = 20) RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

11 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1(2) continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Roof live load=20 psf, ceiling attached to rafters, L/Δ = 20) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls. b. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE 1

12 RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # TABLE R802..1() RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

13 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1() continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls. b. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE

14 RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # TABLE R802..1() RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

15 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1() continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls. b. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE

16 RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # TABLE R802..1() RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling attached to rafters, L/Δ = 20) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

17 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1() continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling attached to rafters, L/Δ = 20) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (feet (feet (feet (feet (feet (feet (feet (feet (feet (feet Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls. b. Span exceeds 26 feet in length OREGON RESIDENTIAL SPECIALTY CODE 7

18 TABLE R802..1(6) RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling attached to rafters, L/Δ = 20) RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) (feet (feet (feet (feet (feet (feet (feet (feet (feet (feet OREGON RESIDENTIAL SPECIALTY CODE

19 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1(6) continued RAFTER SPANS FOR COMMON LUMBER SPECIES (Ground snow load=0 psf, ceiling attached to rafters, L/Δ = 20) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (feet (feet (feet (feet (feet (feet (feet (feet (feet (feet Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls OREGON RESIDENTIAL SPECIALTY CODE 9

20 RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # TABLE R802..1(7) RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD (Ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum Rafter Spans a (continued) (feet (feet (feet (feet (feet (feet (feet (feet (feet (feet OREGON RESIDENTIAL SPECIALTY CODE

21 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1(7) continued RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD (Ceiling not attached to rafters, L/Δ = 180) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (feet Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls OREGON RESIDENTIAL SPECIALTY CODE 8-21

22 TABLE R802..1(8) RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD (Ceiling attached to rafters, L/Δ = 20) RAFTER SPACING ( SPECIES AND GRADE # #1 #2 # # # # #1 #2 # # # # #1 #2 # # # DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a (continued) OREGON RESIDENTIAL SPECIALTY CODE

23 RAFTER SPACING ( 2 SPECIES AND GRADE # #1 #2 # # # TABLE R802..1(8) continued RAFTER SPANS FOR 70 PSF GROUND SNOW LOAD a (Ceiling attached to rafters, L/Δ = 20) DEAD LOAD = 10 psf DEAD LOAD = 20 psf Maximum rafter spans a Check sources for availability of lumber in lengths greater than 20 feet. For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. The tabulated rafter spans assume that ceiling joists are located at the bottom of the attic space or that some other method of resisting the outward push of the rafters on the bearing walls, such as rafter ties, is provided at that location. When ceiling joists or rafter ties are located higher in the attic space, the rafter spans shall be multiplied by the factors given below: H C /H R Rafter Span Adjustment Factor 1/ / / 0.8 1/ /7. or less 1.00 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls OREGON RESIDENTIAL SPECIALTY CODE 8-2

24 RAFTER SLOPE : : : 7: 9: : RAFTER SPACING ( TABLE R802..1(9) a, b, c, d, e, f, g RAFTER/CEILING JOIST HEEL JOINT CONNECTIONS GROUND SNOW LOAD (psf) Roof span (feet) Required number of 16d common nails a,b per heel joint splices c,d,e,f For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.079kP a. a. 0d box nails shall be permitted to be substituted for 16d common nails. b. Nailing requirements shall be permitted to be reduced 2 percent if nails are clinched. c. Heel joint connections are not required when the ridge is supported by a load-bearing wall, header or ridge beam. d. When intermediate support of the rafter is provided by vertical struts or purlins to a loadbearing wall, the tabulated heel joint connection requirements shall be permitted to be reduced proportionally to the reduction in span. e. Equivalent nailing patterns are required for ceiling joist to ceiling joist lap splices. f. When rafter ties are substituted for ceiling joists, the heel joint connection requirement shall be taken as the tabulated heel joint connection requirement for two-thirds of the actual rafter-slope. g. Tabulated heel joint connection requirements assume that ceiling joists or rafter ties are located at the bottom of the attic space. When ceiling joists or rafter ties are located higher in the attic, heel joint connection requirements shall be increased by the following factors: H C /H R Heel Joint Connection Adjustment Factor 1/ 1. 1/ 1. 1/ 1.2 1/ /10 or less 1.11 where: H C = Height of ceiling joists or rafter ties measured vertically above the top of the rafter support walls. H R = Height of roof ridge measured vertically above the top of the rafter support walls OREGON RESIDENTIAL SPECIALTY CODE

25 For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 degree = rad. NOTE: Where ceiling joints run perpendicular to the rafters, rafter ties shall be nailed to each rafter near the top of the ceiling joist. FIGURE R BRACED RAFTER CONSTRUCTION R Design. Wood trusses shall be designed in accordance with accepted engineering practice. The design and manufacture of metal-plate-connected wood trusses shall comply with ANSI/TPI 1. The truss design drawings shall be prepared by a registered professional where required by the statutes of the jurisdiction in which the project is to be constructed in accordance with Section R R Applicability limits. The provisions of this section shall control the design of truss roof framing when snow controls for buildings not greater than 60 feet ( mm) in length perpendicular to the joist, rafter or truss span, not greater than 6 feet (10 97 mm) in width parallel to the joist span or truss, not greater than two stories in height with each story not greater than 10 feet (08 mm) high, and roof slopes not smaller than : (2-percent slope) or greater than : (100-percent slope). Truss roof framing constructed in accordance with the provisions of this section shall be limited to sites subjected to a maximum design wind speed of 110 miles per hour (9 m/s), Exposure A, B or C, and a maximum ground snow load of 70 psf (2 P a). Roof snow load is to be computed as: 0.7 p g. R Bracing. Trusses shall be braced to prevent rotation and provide lateral stability in accordance with the requirements specified in the construction documents for the building and on the individual truss design drawings. In the absence of specific bracing requirements, trusses shall be braced in accordance with the Building Component Safety Information (BCSI 1-0) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses. R Alterations to trusses. Truss members shall not be cut, notched, drilled, spliced or otherwise altered in any way without the approval of a registered design professional. Alterations resulting in the addition of load (e.g., HVAC equipment, water heater) that exceeds the design load for the truss shall not be permitted without verification that the truss is capable of supporting such additional loading. R Truss to wall connection. Trusses shall be connected to wall plates by the use of approved connectors having a resistance to uplift of not less than 17 pounds (779 N) and shall be installed in accordance with the manufacturer s specifications. For roof assemblies subject to wind uplift pressures of 20 pounds per square foot (960 P a) or greater, as established in Table R01.2(2), see section R R Roof tie-down. R Uplift resistance. Roof assemblies which are subject to wind uplift pressures of 20 pounds per square foot (960 P a) or greater as established in Table R01.2(2) shall have rafters or truss ties provided at bearing locations in accordance with Table R > > > 2008 OREGON RESIDENTIAL SPECIALTY CODE 8-2

26 TABLE R a, b, c, d REQUIRED STRENGTH OF TRU OR RAFTER TIE-DOWN CONNECTIONS TO RESIST WIND UPLIFT FORCES DESIGN WIND LOAD (psf) A continuous load path shall be designed to transmit the uplift forces from the rafter or truss ties to the foundation. SECTION R80 ROOF SHEATHING R80.1 Lumber sheathing. Allowable spans for lumber used as roof sheathing shall conform to Table R80.1. Spaced lumber sheathing for wood shingle and shake roofing shall conform to the requirements of Sections R90.7 and R90.8. Spaced lumber sheathing is not allowed in Seismic Design Category D 2. TABLE R80.1 MINIMUM THICKNE OF LUMBER ROOF SHEATHING RAFTER OR BEAM SPACING ( TOTAL ROOF WIDTH INCLUDING OVERHANG (feet) ,008 1, ,06 1,216 1,68 1, ,12 1, 1,6 1,728 1,920 For SI: 1 inch = 2. mm, 1 foot = 0.8 mm, 1 pound per square foot = 0.79kP a, 1 pound = 0. kg. a. Wind uplift forces are based on 2-inch spacing of roof trusses or rafters. For spacing other than 2 inches, forces shall be adjusted accordingly. b. Interpolation is permitted for intermediate values of wind uplift pressures and roof widths. c. The rated capacity of approved tie-down devices is permitted to include up to a 60-percent increase for wind effects where allowed by material specifications. d. Figure R01.2() and Table R01.2(2) shall be used in determining the design wind load. MINIMUM NET THICKNE ( R80.2 Wood structural panel sheathing. R Identification and grade. Wood structural panels shall conform to DOC PS 1, DOC PS 2 or, when manufactured in Canada, CSA 07, and shall be identified by a grade mark or certificate of inspection issued by an approved agency. Wood structural panels shall comply with the grades specified in Table R (1). R Exposure durability. All wood structural panels, when designed to be permanently exposed in outdoor applications, shall be of an exterior exposure durability. Wood structural panel roof sheathing exposed to the underside may be of interior type bonded with exterior glue, identified as Exposure 1. R Fire-retardant-treated plywood. The allowable unit stresses for fire-retardant-treated plywood, including fastener values, shall be developed from an approved method of investigation that considers the effects of anticipated temperature and humidity to which the fire-retardant-treated plywood will be subjected, the type of treatment and redrying process. The fire-retardant-treated plywood shall be graded by an approved agency. R Allowable spans. The maximum allowable spans for wood structural panel roof sheathing shall not exceed the values set forth in Table R (1), or APA E0. R80.2. Installation. Wood structural panel used as roof sheathing shall be installed with joints staggered or not staggered in accordance with Table R602.(1), or APA E0 for wood roof framing or with Table R80. for steel roof framing. > 2 / 8 8 a 1 1 / 2 T & G 60 b 72 c For SI: 1 inch = 2. mm. a. Minimum 270 F b, 0,000 E. b. Minimum 20 F b, 660,000 E. c. Minimum 600 F b, 1,10,000 E. SECTION R80 STEEL ROOF FRAMING R80.1 General. Elements shall be straight and free of any defects that would significantly affect their structural performance. Cold-formed steel roof framing members shall comply with the requirements of this section. R Applicability limits. The provisions of this section shall control the construction of steel roof framing for buildings not greater than 60 feet ( mm) perpendicular to the joist, rafter or truss span, not greater than 0 feet ( 192 mm) in width parallel to the joist span or truss, not greater than two stories in height and roof slopes not smaller than : (2-percent slope) or greater than : (100 percent slope). Steel roof framing constructed in accordance with the provisions of this section shall be limited to sites subjected to a maximum design wind speed of 110 miles per hour (9 m/s), Exposure A, B, or C, and a maximum ground snow load of 70 pounds per square foot (0 P a). R In-line framing. Steel roof framing constructed in accordance with Section R80 shall be located directly in line with load-bearing studs below with a maximum tolerance of / inch (19 mm) between the centerline of the stud and the roof joist/rafter OREGON RESIDENTIAL SPECIALTY CODE

27 R80.1. Roof trusses. The design, quality assurance, installation and testing of cold-formed steel trusses shall be in accordance with the AISI Standard for Cold-formed Steel Framing-Truss Design (COFS/Truss). Truss members shall not be notched, cut or altered in any manner without an approved design. R80.2 Structural framing. Load-bearing steel roof framing members shall comply with Figure R80.2(1) and with the dimensional and minimum thickness requirements specified in Tables R80.2(1) and R80.2(2). Tracks shall comply with Figure R80.2(2) and shall have a minimum flange width of 1 1 / inches (2 mm). The maximum inside bend radius for load-bearing members shall be the greater of / 2 inch (2. mm) or twice the uncoated steel thickness. Holes in roof framing members shall comply with all of the following conditions: 1. Holes shall conform to Figure R80.2(); 2. Holes shall be permitted only along the centerline of the web of the framing member;. Holes shall have a center-to-center spacing of not less than 2 inches (610 mm);. Holes shall have a width not greater than 0. times the member depth, or 2 1 / 2 inches (6 mm);. Holes shall have a length not exceeding 1 / 2 inches (11 mm); and 6. Holes shall have a minimum distance between the edge of the bearing surface and the edge of the hole of not less than 10 inches (2 mm). Framing members with web holes not conforming to these requirements shall be patched in accordance with Section R80..6 or designed in accordance with accepted engineering practices. R Material. Load-bearing steel framing members shall be cold-formed to shape from structural quality sheet steel complying with the requirements of one of the following: 1. ASTM A 6: Grades, 7, 0 and 0 (Class 1 and ). 2. ASTM A 792: Grades, 7, 0 and 0A.. ASTM A 87: Grades, 7, 0 and 0 (Class 1 and ).. ASTM A 100: Grades, 7, 0 and 0. R Identification. Load-bearing steel framing members shall have a legible label, stencil, stamp or embossment with the following information as a minimum: 1. Manufacturer s identification. 2. Minimum uncoated steel thickness in inches (mm).. Minimum coating designation.. Minimum yield strength, in kips per square inch (ksi). R80.2. Corrosion protection. Load-bearing steel framing shall have a metallic coating complying with one of the following: 1. A minimum of G 60 in accordance with ASTM A A minimum of AZ 0 in accordance with ASTM A A minimum of GF 60 in accordance with ASTM A 87. R80.2. Fastening requirements. Screws for steel-tosteel connections shall be installed with a minimum edge distance and center-to-center spacing of 1 / 2 inch (1 mm), shall be self-drilling tapping, and shall conform to SAE J78. Structural sheathing shall be attached to roof rafters with NOMINAL MEMBER SIZE MEMBER DESIGNATION a TABLE R80.2(1) LOAD-BEARING COLD-FORMED STEEL MEMBER SIZES WEB DEPTH ( MINIMUM FLANGE WIDTH ( MAXIMUM FLANGE WIDTH ( MINIMUM LIP SIZE ( 0S162-t S162-t S162-t S162-t S162-t For SI: 1 inch = 2. mm. a. The member designation is defined by the first number representing the member depth in hundredths of an inch, the letter s representing a stud or joist member, the second number representing the flange width in hundredths of an inch, and the letter t shall be a number representing the minimum base metal thickness in mils [see Table R80.2(2)]. TABLE R80.2(2) MINIMUM THICKNE OF COLD-FORMED STEEL ROOF FRAMING MEMBERS For SI: DESIGNATION (mils) MINIMUM UNCOATED THICKNE ( REFERENCED GAGE NUMBER inch = 2. mm, 1 mil = 0.02 mm OREGON RESIDENTIAL SPECIALTY CODE 8-27

28 FIGURE R80.2(1) C-SECTION FIGURE R80.2(2) TRACK SECTION For SI: 1 inch = 2. mm. FIGURE R80.2() WEB HOLES minimum No. 8 self-drilling tapping screws that conform to SAE J78. Screws for attaching structural sheathing to steel roof framing shall have a minimum head diameter of inch (7. mm) with countersunk heads and shall be installed with a minimum edge distance of / 8 inch (10 mm). Gypsum board ceilings shall be attached to steel joists with minimum No. 6 screws conforming to ASTM C 9 and shall be installed in accordance with Section R80. For all connections, screws shall extend through the steel a minimum of three exposed threads. All self-drilling tapping screws conforming to SAE J78 shall have a minimum Type II coating in accordance with ASTM B 6. Where No. 8 screws are specified in a steel-to-steel connection, reduction of the required number of screws in the connection is permitted in accordance with the reduction factors in Table R80.2. when larger screws are used or when one of the sheets of steel being connected is thicker that mils (0.8 mm). When applying the reduction factor, the resulting number of screws shall be rounded up. TABLE R80.2. SCREW SUBSTITUTION FACTOR THINNEST CONNECTED STEEL SHEET (mils) SCREW SIZE # # # For SI: 1 mil = 0.02 mm. R80. Roof construction. Steel roof systems constructed in accordance with the provisions of this section shall consist of both ceiling joists and rafters in accordance with Figure R80. and fastened in accordance with Table R OREGON RESIDENTIAL SPECIALTY CODE

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2

More information

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2

More information

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2

More information

ROOF-CEILING CONSTRUCTION

ROOF-CEILING CONSTRUCTION CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings (see Section

More information

3.1 General Provisions

3.1 General Provisions WOOD FRAME CONSTRUCTION MANUAL 107 3.1 General Provisions 3.1.1 Prescriptive Requirements The provisions of this Chapter establish a specific set of resistance requirements for buildings meeting the scope

More information

A. Rough carpentry includes but is not limited to the following:

A. Rough carpentry includes but is not limited to the following: SECTION 06100 ROUGH CARPENTRY PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification Sections,

More information

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION SECTION R507 DECKS R507.1 Application. The provisions of this section shall provide prescriptive requirements for the design and construction of all uncovered, wood-framed, single-span exterior decks.

More information

Fastener Schedule. a, b, c. FASTENER Roof 3-8d (2 1 / ) / ) 3-10d. 3-10d ( ) 3-16d box nails. (3 1 2 toe nails on one side

Fastener Schedule. a, b, c. FASTENER Roof 3-8d (2 1 / ) / ) 3-10d. 3-10d ( ) 3-16d box nails. (3 1 2 toe nails on one side ITEM 1 DESCRIPTION OF BUILDING ELEMENTS Blocking between joists or rafters to top plate, toe 2 Ceiling joists to plate, toe 3 4 5 6 Ceiling joists not attached to parallel rafter, laps over partitions,

More information

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK:

SECTION ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: SECTION 061000 - ROUGH CARPENTRY 1.1 DESCRIPTION OF WORK: A. Definition: Rough carpentry includes carpent~y work not specified as part of other sections and which is generally not exposed, except as otherwise

More information

Trusted ICC ES PASLODE, Evaluation. report, or as to any. ICC-ES Evaluation

Trusted ICC ES PASLODE, Evaluation. report, or as to any. ICC-ES Evaluation 0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3072 Reissued 09/2018 Revised 10/2018 This report is subject to renewal 09/2020.

More information

LP SolidStart LSL. LP SolidStart LSL Prescriptive Roof Framing Technical Guide 2500F b-1.75e, 2360F b -1.55E and 1730F b -1.

LP SolidStart LSL. LP SolidStart LSL Prescriptive Roof Framing Technical Guide 2500F b-1.75e, 2360F b -1.55E and 1730F b -1. LP SolidStart LSL LP SolidStart LSL Prescriptive Roof Framing Technical Guide 2500F b-1.75e, 2360F b -1.55E and 1730F b -1.35E LSL Please verify availability with the LP SolidStart Engineered Wood Products

More information

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year.

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-403 Reissued October, 009 This report is subject to re-examination in one year. www.icc-es.org (800) 43-6587 (56) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06 10 00- ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including Contracting Requirements and Division 1 Specification Sections, apply

More information

Exterior Wall Fastener Schedule

Exterior Wall Fastener Schedule City of Republic Community Development Department Exterior Wall Fastener Schedule REVISION DATE: JANUARY 2017 Design and construction (2012 IRC Section R602.3): Exterior walls of wood frame construction

More information

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY

Collins Engineers Palmetto Islands County Park Boardwalk Repairs 03/28/2014 SECTION ROUGH CARPENTRY PART 1 GENERAL 1.1 RELATED SECTIONS SECTION 061000 ROUGH CARPENTRY A. Drawings and general provisions of the Construction Contract, including General Conditions and Division 1 Specification Sections, apply

More information

2x6. 2x8. 2x10. Size. 2-2x10 8'-5" w/ 2 NJ 7'-3" w/ 2 NJ

2x6. 2x8. 2x10. Size. 2-2x10 8'-5 w/ 2 NJ 7'-3 w/ 2 NJ 1 Rafter Size Spacing Allowable span 24" 11'-9" 24" 2x6 14'-1" 2x4 12" 15'-6" 12" 24" 14'-10" 24" 2x8 18'-2" 2x6 12" 20'-5" 12" 24" 18'-2" 24" 2x10 22'-3" 2x8 12" 25'-8" 12" 24" 21'-0" 24" 2x12 25'-9"

More information

Introducing AJSTM INSTALLATION GUIDE USA. 8 th Edition USA

Introducing AJSTM INSTALLATION GUIDE USA. 8 th Edition USA The SIMPLE FRAMING SYSTEMSM INSTALLATION GUIDE USA for Floors This Installation Guide is intended to provide general information for the designer and end-user. For further information, please refer to

More information

Wood Connections. Concepts of Well Designed Connections

Wood Connections. Concepts of Well Designed Connections Wood Connections Sam Hensen, P.E. Branch Engineering Manager Concepts of Well Designed Connections Must provide sufficient capacity to transfer loads to supporting members Utilize fastener spacing which

More information

ICC-ES Evaluation Report

ICC-ES Evaluation Report ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2608 Reissued January 2016 This report is subject to renewal January 2017. A Subsidiary of the International Code Council DIVISION:

More information

Wood Roof Framing Common Design and Construction Defects Concurrent Session #5.3, Friday April 28, 2017, 9:45 AM-10:30 AM

Wood Roof Framing Common Design and Construction Defects Concurrent Session #5.3, Friday April 28, 2017, 9:45 AM-10:30 AM Wood Roof Framing Common Design and Construction Defects Concurrent Session #5.3, Friday April 28, 2017, 9:45 AM-10:30 AM William J. Dery, PE Sr. Structural Engineer Outline 1. Wood Roof Framing 101 the

More information

ESR-1254 * DELETED BY CITY OF LOS ANGELES. Reissued April 1, 2006 This report is subject to re-examination in one year.

ESR-1254 * DELETED BY CITY OF LOS ANGELES.   Reissued April 1, 2006 This report is subject to re-examination in one year. ESR-1254 Reissued April 1, 2006 This report is subject to re-examination in one year. www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional

More information

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years. ICC-ES Evaluation Report www.icc-es.org (800) -6587 (56) 699-05 ESR-0 Reissued March, 0 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION: 06 00 00

More information

DIVISION 6 WOOD AND PLASTICS

DIVISION 6 WOOD AND PLASTICS DIVISION 6 WOOD AND PLASTICS PART 1 - GENERAL 1.01 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. ICC-ES Evaluation Report ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:

More information

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-2648 Reissued June 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

MAT105: Floor Framing

MAT105: Floor Framing MAT105: Copyright 2007 American Forest & Paper Association, Inc. Because the common applications for wood framing are in residential construction, the details of this program will be based on the IRC which

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 PART I - GENERAL 1.01 DESCRIPTION A. Scope: Work of this Section shall include all materials and installation necessary to provide Rough Carpentry as shown and detailed on the Drawings and

More information

Sections & Details VOCABULARY

Sections & Details VOCABULARY 1 Sections & Details VOCABULARY 1 ROOF FRAMING DETAIL RIDGE BOARD SHEATHING SHINGLES WEB FASCIA RAFTER (chord) SOFFIT SHEATHING STUD INSULATION DOUBLE TOP PLATE CEILING JOIST 2 FOUNDATION DETAIL STUD SHEATHING

More information

SECTION ROUGH CARPENTRY

SECTION ROUGH CARPENTRY SECTION 06100 ROUGH CARPENTRY PART 1 GENERAL 1.1 DESCRIPTION OF WORK A. The work includes furnishing all labor, materials and equipment required to complete the Rough Carpentry work as shown on the Drawings

More information

Nailed Structural-Use Panel and Lumber Beams

Nailed Structural-Use Panel and Lumber Beams D A T A F I L E Nailed Structural-Use Panel and Lumber Beams When roof load or span requirements are too great to allow use of commonly available dimension lumber or timbers, a box beam constructed of

More information

3. Are component and cladding design pressures consistent with ASCE 7 for the wind speed and exposure category (ASCE 7 Fig. 6-3)?

3. Are component and cladding design pressures consistent with ASCE 7 for the wind speed and exposure category (ASCE 7 Fig. 6-3)? Mobile County Public Works Residential Plan Reviewers Checklist For Structural Requirements of Wood Framed Residences Recommendation: Permit as Noted Revise Plans and Resubmit MCPW Ref. No. Design Criteria:

More information

Multi-Institutional Academic Health Science & Research Center Evansville, IN

Multi-Institutional Academic Health Science & Research Center Evansville, IN SECTION 06 1053 - MISCELLANEOUS ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions Division 01 Specification

More information

Section Downloads. Terminology Outline. Industry Standards/ Publications. American Softwood Lumber Standard ANSI/TPI 1. Section 02: Terminology

Section Downloads. Terminology Outline. Industry Standards/ Publications. American Softwood Lumber Standard ANSI/TPI 1. Section 02: Terminology Section Downloads Download & Print TTT I Sec 02 Slides TTT I Sec 02 Handouts Version 2.1 Section 02: Terminology 1 2 Terminology Outline Industry Standards/Publications Truss Terms Bracing Terms Design

More information

Joint Evaluation Report

Joint Evaluation Report 0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-2909 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:

More information

APA Performance Rated Rim Boards

APA Performance Rated Rim Boards D a t a F i l e APA Performance Rated Rim Boards A Rim Board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: LAMINATED VENEER LUMBER SECTION: LAMINATED STRAND LUMBER REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: LAMINATED VENEER LUMBER SECTION: LAMINATED STRAND LUMBER REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 03 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 06 00 00 WOOD, PLASTICS

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 87 () 99 0 www.icc es.org ESR 9 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 WOOD, PLASTICS AND COMPOSITES

More information

LVL8 H1.2 GENERAL FRAMING. Eco Friendly Revolutionary H1.2 Treatment Azotek by Zelam

LVL8 H1.2 GENERAL FRAMING. Eco Friendly Revolutionary H1.2 Treatment Azotek by Zelam LVL8 H1.2 GENERAL FRAMING Eco Friendly Revolutionary H1.2 Treatment Azotek by Zelam NPIL/MARCH2015 Introduction to NelsonPine LVL8 H1.2 NelsonPine LVL is an engineered wood composite made from rotary peeled

More information

Garage Design Guide. October 2018

Garage Design Guide. October 2018 Garage Design Guide October 2018 The Corporation of the Township of Hamilton 8235 Majestic Hills Drive, P.O. Box 1060, Cobourg Ontario K9A 4W5 Tel: 905-342-2810 Fax: 905-342-2818 Email: Tim Jeronimus (Chief

More information

VERSA-LAM BCI INSTALLATION GUIDE LIMIT STATES DESIGN CANADA

VERSA-LAM BCI INSTALLATION GUIDE LIMIT STATES DESIGN CANADA INSTALLATION GUIDE VERSA-LAM BCI LIMIT STATES DESIGN CANADA The information in this document pertains use in the CANADA ONLY, Limit States Design. Refer the appropriate Specifier Guide US for use in the

More information

602.4, TABLE 602.4, , , , , , , , , TABLE

602.4, TABLE 602.4, , , , , , , , , TABLE 602.4, TABLE 602.4, 602.4.1, 602.4.2, 602.4.3, 602.4.4, 602.4.5, 602.4.9, 2304.11, 2304.11.1, TABLE 2304.11.1.1, 2304.11.2, 2304.11.3, 602.4.8, 602.4.8.2, 602.4.8.1, 602.4.6, 602.4.6.2, 602.4.6.1, 2304.11.4,

More information

VERSA-LAM. An Introduction to VERSA-LAM Products

VERSA-LAM. An Introduction to VERSA-LAM Products 44 VERSA-LAM An Introduction to VERSA-LAM Products VERSA-LAM is one of the strongest and stiffest engineered wood products approved in the UK. 241 302 356 406 VERSA-LAM products are excellent as floor

More information

PROJECT INSTRUCTIONS Roofing

PROJECT INSTRUCTIONS Roofing PROJECT INSTRUCTIONS Roofing This handout outlines some basic regulations contained within the 2015 Minnesota State Building Code, as well as other good building practices. However, this handout is not

More information

B. Related Sections: The following Sections contain requirements that relate to this Section:

B. Related Sections: The following Sections contain requirements that relate to this Section: SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

IRC 2015 Code Compliant Wood Framed Residential Details. Incorrect Installations of Connectors with code references and remedies, discussion.

IRC 2015 Code Compliant Wood Framed Residential Details. Incorrect Installations of Connectors with code references and remedies, discussion. IRC 2015 Code Compliant Wood Framed Residential Details Incorrect Installations of Connectors with code references and remedies, discussion. You can help to avoid this, by being diligent with inspections.

More information

Use the Design Properties (100% Load Duration) Table from Page 3 for questions 1-7

Use the Design Properties (100% Load Duration) Table from Page 3 for questions 1-7 www.garyklinka.com page 1 of 16 Truss Joist I-Joist Quiz Instructions: www.garyklinka.com 1. Print these pages. 2. Print referencing manual from my site at http://garyklinka.com/manuals/tj-4000.pdf or

More information

Featuring TJ Rim Board and TimberStrand LSL

Featuring TJ Rim Board and TimberStrand LSL #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and TimberStrand LSL Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load

More information

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California / 16

ICBO Evaluation Service, Inc Workman Mill Road, Whittier, California / 16 ER-5736 Reissued September 1, 2002 ICBO Evaluation Service, Inc. 5360 Workman Mill Road, Whittier, California 90601 www.icboes.org Filing Category: FASTENERS Wood Hangers and Framing Anchors USP LUMBER

More information

Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later

Lateral Support. Decks over 24 above grade require lateral support* *Exceptions to be discussed later Lateral Support Decks over 24 above grade require lateral support* *Exceptions to be discussed later Decking Types of Decking: -2x4s & 2x6s -five quarter span rated decking boards -Wood plastic composite

More information

IRC 2012 Code Compliant Wood Framed Residential details. Miss Installed Connectors with code references and remedies, discussion.

IRC 2012 Code Compliant Wood Framed Residential details. Miss Installed Connectors with code references and remedies, discussion. IRC 2012 Code Compliant Wood Framed Residential details Miss Installed Connectors with code references and remedies, discussion. You can help avoid this, by being diligent with inspections. Notes to Attendees

More information

CUTTING, NOTCHING, AND BORING OF WOOD FRAMING MEMBERS (Unless an alternate design is provided by a licensed Engineer or Architect)

CUTTING, NOTCHING, AND BORING OF WOOD FRAMING MEMBERS (Unless an alternate design is provided by a licensed Engineer or Architect) INFORMATION BULLETIN / PUBLIC - BUILDING CODE REFERENCE NO.: 91.2320 Effective: 5-23-00 DOCUMENT NO. P/BC 2002-007 Revised: 2-01-01 Previously Issued As: IB ST-14 CUTTING, NOTCHING, AND BORING OF WOOD

More information

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II SECTION 061000 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The General Conditions, any Supplementary General Conditions and Division 1, General Requirements, are hereby made a part of

More information

City of Virginia Beach, Virginia Typical Deck Details

City of Virginia Beach, Virginia Typical Deck Details City of Virginia Beach, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential, single-level decks only. Construction cannot

More information

JOIST DETAILS Plate nail, 16d (0.15" x 1 ") at 1 on-center Blocking panel: 1 1 8" TJ Rim Board, 1 1 TimberStrand SL or TJI joist Toe nail, 10d (0.11" x ") at on-center A1 CS BEAM DETAILS L1 eb stiffener

More information

REPORT HOLDER: JAACO CORPORATION NORTHEAST 68 TH STREET, SUITE C-130 REDMOND, WASHINGTON EVALUATION SUBJECT:

REPORT HOLDER: JAACO CORPORATION NORTHEAST 68 TH STREET, SUITE C-130 REDMOND, WASHINGTON EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2961 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 05 00

More information

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc.

2. Wood grounds, nailers, blocking, miscellaneous framing, sleepers, etc. 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"

More information

ROOFING City of Grand Rapids Building Safety Division

ROOFING City of Grand Rapids Building Safety Division ROOFING City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Grand

More information

A. Product Data: For each type of process and factory-fabricated product indicated.

A. Product Data: For each type of process and factory-fabricated product indicated. SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Wood framing. 2. Wood supports. 3. Wood blocking. 4. Wood cants. 5. Wood nailers. 6. Wood furring.

More information

THE ENGINEERED WOOD ASSOCIATION

THE ENGINEERED WOOD ASSOCIATION D A T A F I L E APA Performance Rated Rim Boards A rim board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top

More information

Beam & Header Technical Guide. LP SolidStart LVL. 2900F b -2.0E. U.S. Technical Guide U.S. TECHNICAL GUIDE

Beam & Header Technical Guide. LP SolidStart LVL. 2900F b -2.0E. U.S. Technical Guide U.S. TECHNICAL GUIDE U.S. Technical Guide U.S. TECHNICAL GUIDE LP SolidStart LVL & Header Technical Guide 2900F b -2.0E Please verify availability with the LP SolidStart Engineered Wood Products distributor in your area prior

More information

Sections & Details. WOOD SILL and FLOOR CONSTRUCTION NOTES

Sections & Details. WOOD SILL and FLOOR CONSTRUCTION NOTES 2 Sections & Details WOOD SILL and FLOOR CONSTRUCTION NOTES 1 Commonly Used Lumber Common LENGTHS include: 8, 10, 12, 14, 16 NOMINAL SIZES 2 x 4 2 x 6 2 x 8 2 x 10 2 x 12 ACTUAL SIZES 1 ½ x 3 ½ 1 ½ x 5

More information

DECKS. Stairway illumination Positive attachment of ledger Lateral load connection required board (R507.2) required (R ) (R311.7.

DECKS. Stairway illumination Positive attachment of ledger Lateral load connection required board (R507.2) required (R ) (R311.7. DECKS Max. riser height-7 ¾ Min. tread depth-10 Landings required at (R311.7.5.1) (R311.7.5.2) top and bottom of stairs (R311.7.6) Notched guardrail post NOT allowed Graspable handrail required Spacing

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3096 Reissued 01/2017 This report is subject to renewal 01/2018. DIVISION: 06 00 00 WOOD, PLASTICS

More information

(800) (562) A Subsidiary of the International Code Council

(800) (562) A Subsidiary of the International Code Council ICC-ES Evaluation Report ESR-65 Issued October, 009 This report is subject to re-examination in two years. www.icc-es.org (800) -6587 (56) 699-05 A Subsidiary of the International Code Council DIVISION:

More information

PART II ENGINEERED BASIS OF RIDGE AND EAVE VENT DETAILS

PART II ENGINEERED BASIS OF RIDGE AND EAVE VENT DETAILS PART II ENGINEERED BASIS OF RIDGE AND EAVE VENT DETAILS A - INTRODUCTION This report addresses engineered design for unblocked wood structural panel (plywood or OSB) roof diaphragms with either continuous

More information

Typical Deck Details Based on the City of Nixa Residential Deck Ordinance

Typical Deck Details Based on the City of Nixa Residential Deck Ordinance Typical Deck Details Based on the City of Nixa Residential Deck Ordinance The use of this package in lieu of submitted drawings applies to Single Span, Single Level, Residential Decks ONLY. Decks must

More information

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A SECTION 061050 - MISCELLANEOUS CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification

More information

Pulaski County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code

Pulaski County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code Pulaski County, Virginia Typical Deck Details Based on the 2012 Virginia Residential Code The design details in this document apply to residential, single-level decks only. Construction cannot deviate

More information

Structural Criteria for Residential Flush-Mounted Solar Arrays

Structural Criteria for Residential Flush-Mounted Solar Arrays Structural Criteria for Residential Flush-Mounted Solar Arrays Planning and Development Building & Safety Division 1. ROOF CHECKS A. Visual Review/Contractor s Site Audit of Existing Conditions: 1) Is

More information

Structural Criteria for Residential Rooftop Solar Energy Installations

Structural Criteria for Residential Rooftop Solar Energy Installations DOCUMENT #5 Structural Criteria for Residential Rooftop Solar Energy Installations STRUCTURAL CRITERIA FOR RESIDENTIAL FLUSH-MOUNTED SOLAR ARRAYS 1. ROOF CHECKS A. Visual Review/Contractor s Site Audit

More information

Building for High Wind Resistance in Light-Frame Wood Construction

Building for High Wind Resistance in Light-Frame Wood Construction Building for High Wind Resistance in Light-Frame Wood Construction DESIGN GUIDE Meeting the Challenge of High Wind Design Designing a structure to withstand the devastating forces of tornados is one of

More information

SECTION: 15 ZONING RULE LOT AREA 6134 S.F S.F. BUILDING AREA (FOOTPRINT) LOT COVERAGE 20.2% 24.86' FRONT YARD SIDE YARD 8.

SECTION: 15 ZONING RULE LOT AREA 6134 S.F S.F. BUILDING AREA (FOOTPRINT) LOT COVERAGE 20.2% 24.86' FRONT YARD SIDE YARD 8. PROPOSED 1ST FLOOR PROPOSED 2ND FLOOR Anthony Hatziioannou Architect, P.C. EXISTING 1ST FLOOR ZONING CALCULATION JURISDICTION: TOWN OF OYSTER BAY SECTION: 15 BLOCK: 71 LOT: ZONE: RESIDENCE R1-7 PERMITTED

More information

TYPICAL PATIO COVERS. OWNER: ADDRESS: PHONE:

TYPICAL PATIO COVERS.  OWNER: ADDRESS: PHONE: City of Aliso Viejo Building Division 12 Journey, Suite 100 Aliso Viejo, CA 92656 (949)425-2540 Fax (949)425-3899 www.cityofalisoviejo.com TYPICAL PATIO COVERS 111 I. GENERAL Patio covers are one-story,

More information

Structural Criteria for Residential Rooftop Solar Energy Installations

Structural Criteria for Residential Rooftop Solar Energy Installations TOOLKIT DOCUMENT #5 Structural Criteria for Residential Rooftop Solar Energy Installations CRITERIA FOR RESIDENTIAL FLUSH-MOUNTED SOLAR ARRAYS STRUCTURAL 1. ROOF CHECKS A. Visual Review/Contractor s Site

More information

Maryland Building Officials Association Typical Deck Details

Maryland Building Officials Association Typical Deck Details Maryland Building Officials Association Typical Deck Details Based on the International Residential Code The design details in this document apply to residential decks only. Framing requirements are limited

More information

Ash Brook Golf Course Scotch Plains, New Jersey

Ash Brook Golf Course Scotch Plains, New Jersey SECTION 062013 - EXTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Load Tables, Technical Data and Installation Instructions

Load Tables, Technical Data and Installation Instructions W22. W22. W22. W22. W22 W22.. Simpson Strong-Tie Fastening Systems Structural Wood-to-Wood Connections Including Ledgers Designed to provide an easy-to-install, high-strength alternative to through-bolting

More information

T-BRACE / I-BRACE DETAIL WITH 2X BRACE ONLY

T-BRACE / I-BRACE DETAIL WITH 2X BRACE ONLY August 10, 2010 T-BRACE / I-BRACE DETAIL WITH 2X BRACE ONLY ST - T-BRACE 2 R MiTek Industries, Chesterfield, MO Page 1 of 1 Note: T-Bracing / I-Bracing to be used when continuous lateral bracing is impractical.

More information

Originally Issued: 09/26/2012 Revised: 10/15/2018 Valid Through: 09/30/2019

Originally Issued: 09/26/2012 Revised: 10/15/2018 Valid Through: 09/30/2019 SUNMODO CORPORATION 14800 NE 65 th Street Vancouver, WA 98682 SUNMODO EZ ROOF MOUNT L-FOOT KITS FOR SHINGLE ROOFS CSI Section: 06 25 23 Wood, Plastic, and Composite Fastenings 07 71 00-Roof Specialties

More information

FASTENERS BUILDING DEPARTMENT

FASTENERS BUILDING DEPARTMENT FASTENERS BUILDING DEPARTMENT 952-446-1660 WWW.CITYOFMINNETRISTA.COM This handout is intended only as a guide and is based in part on the 2015 Minnesota Residential Code, Minnetrista City ordinances, and

More information

2002 ADDENDUM to the 1997 NDS and PRIOR EDITIONS

2002 ADDENDUM to the 1997 NDS and PRIOR EDITIONS AMERICAN FOREST & PAPER ASSOCIATION American Wood Council Engineered and Traditional Wood Products March 2002 2002 ADDENDUM to the 1997 NDS and PRIOR EDITIONS The 2001 Edition of the National Design Specification

More information

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 9 Ventilation Overview Revised

ESCONDIDO FIRE DEPT TRAINING MANUAL Section Truck Module Page 1 of 9 Ventilation Overview Revised Truck Module Page 1 of 9 INTRODUCTION Each firefighter must have a thorough knowledge of the proper methods used to ventilate a structure. Ventilation itself does not put out fires! However, effective

More information

WOODEN BUILDINGS 6.1 INTRODUCTION 6.2 TYPICAL DAMAGE AND FAILURE OF WOODEN BUILDINGS. Chapter 6

WOODEN BUILDINGS 6.1 INTRODUCTION 6.2 TYPICAL DAMAGE AND FAILURE OF WOODEN BUILDINGS. Chapter 6 Chapter 6 WOODEN BUILDINGS 6.1 INTRODUCTION Wood has higher strength per unit weight and is, therefore, very suitable for earthquake resistant construction. But heavy cladding walls could impose high lateral

More information

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems Overview Revised 9/2/2016

Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems Overview Revised 9/2/2016 Attachment of Residential Deck Ledger to Metal Plate Connected Wood Truss Floor Systems Overview Revised 9/2/2016 SBCA has been the voice of the structural building components industry since 1983, providing

More information

APPLICATION FOR A BUILDING PERMIT

APPLICATION FOR A BUILDING PERMIT APPLICATION FOR A BUILDING PERMIT City of San Jacinto 595 S. San Jacinto Ave San Jacinto CA 92583 95.487.7330 fax 95.654.9896 Must print legibly, submit (3) sets of building and plot plans. Fill out all

More information

TRUS JOIST RIM BOARD. Featuring TJ Rim Board and TimberStrand LSL. Multiple thicknesses, grades, and products to cover all your rim board needs

TRUS JOIST RIM BOARD. Featuring TJ Rim Board and TimberStrand LSL. Multiple thicknesses, grades, and products to cover all your rim board needs #TJ-8000 SPECIFIER S GUIDE TRUS JOIST RIM BOARD Featuring TJ Rim Board and Multiple thicknesses, grades, and products to cover all your rim board needs 1¼" Thickness matches lateral load capacity of 2x

More information

REINFORCEMENT DESIGN FOR METAL BUILDING SYSTEMS

REINFORCEMENT DESIGN FOR METAL BUILDING SYSTEMS REINFORCEMENT DESIGN FOR METAL BUILDING SYSTEMS By Donald L. Johnson, P.E. RETROFIT PROJECTS CAN BE NECESSARY FOR ANY NUMBER OF REASONS, though change in use is one of the most common. Change of use can

More information

City of Long Beach Department of Development Services Building and Safety Bureau. Wood Frame Prescriptive Provisions For Residential Construction

City of Long Beach Department of Development Services Building and Safety Bureau. Wood Frame Prescriptive Provisions For Residential Construction City of Long Beach Department of Development Services Building and Safety Bureau Wood Frame Prescriptive Provisions For Residential Construction Information Bulletin BU-010 Eff: 01-01-2011 Rev: 07-05-2017

More information

BRACING BRACING SECTION 7 SECTION 7

BRACING BRACING SECTION 7 SECTION 7 If we are to learn from the past, it is clear that there is generally a lack of understanding of the purpose of roof bracing and who should be responsible for it. This has led to disputes, claims and,

More information

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY

DIVISION 6 WOODS AND PLASTICS SECTION ROUGH CARPENTRY DIVISION 6 WOODS AND PLASTICS SECTION 06 10 00 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01

More information

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013.

ICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1790 Reissued September 1, 2012 This report is subject to renewal September 1, 2013. A Subsidiary of the International Code Council

More information

PV System Structural Criteria

PV System Structural Criteria PV System Structural Criteria Town of Atherton Building Department 91 Ashfield Road Atherton, California 94027 Phone: (650) 752-0560 STRUCTURAL CRITERIA FOR RESIDENTIAL ROOFTOP FLUSH-MOUNTED SOLAR ARRAYS

More information

Glulam Connection Details

Glulam Connection Details T E C H N I C A L N O T E Glulam Connection Details Note: This version is superseded by a more current edition. Check the current edition for updated design and application recommendations. ENGINEERED

More information

LP SolidStart Laminated Strand Lumber (LSL) and Laminated Veneer Lumber (LVL) Louisiana-Pacific Corporation Revised July 21, 2017

LP SolidStart Laminated Strand Lumber (LSL) and Laminated Veneer Lumber (LVL) Louisiana-Pacific Corporation Revised July 21, 2017 LP SolidStart Laminated Strand Lumber (LSL) and Laminated Veneer Lumber (LVL) PR-L280(C) Louisiana-Pacific Corporation Revised July 21, 2017 Products: LP SolidStart 1.35E, 1.55E, and 1.75E LSL LP SolidStart

More information

Pryda Timber Connectors

Pryda Timber Connectors Pryda Timber Connectors Pryda Lintel Guide Engineered Steel Wall Lintels March 2014 ESSENTIAL NOTES PRYDA PRODUCT GUIDES INTRODUCTION The information in this Product Guide is provided for use in Australia

More information

GLOSSARY OF TERMS SECTION 8

GLOSSARY OF TERMS SECTION 8 GLOSSARY OF TERMS SECTION 8 Anchor Bolt Angle Base Plate Bay Blocking CCB Centerline Chord Cladding Clip Closure Strip An A-307 steel bolt embedded in the concrete footing to anchor the base plate of the

More information

ONE AND TWO FAMILY DWELLINGS Uncovered Decks July, 2007

ONE AND TWO FAMILY DWELLINGS Uncovered Decks July, 2007 ONE AND TWO FAMILY DWELLINGS Uncovered Decks July, 2007 In the City of Lee s Summit, the construction of uncovered decks with a floor surface more than 30 inches above the adjacent grade level requires

More information

FREDERICK COUNTY USBC/IRC 2015

FREDERICK COUNTY USBC/IRC 2015 8/1/2018 FREDERICK COUNTY USBC/IRC 2015 IS DECK SUPPORTED AT HOUSE WALL W/LEDGER BOARD WITH REQUIRED LATERAL BRACING? YES NO OR IS DECK FREE STANDING WITH TWO GIRDERS (Free Standing)? YES NO EXTERIOR GROUND

More information

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers.

1.03 QUALITY ASSURANCE A. Inspection Agencies: 1. SPIB: Southern Pine Inspection Bureau; for all structural framing of roof joists and headers. DIVISION 6 - WOOD AND PLASTICS SECTION 06100 - ROUGH CARPENTRY PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Rough carpentry for: a. Wood framing and sheathing for the new Rest Area building additions.

More information

ROOF SYSTEM DESIGN GUIDE

ROOF SYSTEM DESIGN GUIDE #TJ-9005 SPECIFIE S GUIDE OOF SYSTEM DESIGN GUIDE Featuring Trus Joist, Microllam LVL, and Parallam PSL Long-Length afters with Consistent Strength and Stability Engineered Solutions for Complex oof Systems

More information