TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM
|
|
- Blanche Todd
- 5 years ago
- Views:
Transcription
1 TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM J A Wium Institute of Structural Engineering 19 November 2007 ISI2007-3
2 TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM TABLE OF CONTENTS 1. Introduction 2. Description of the investigation 3. Theoretical calculations : 4. Test series 4.1 Compressive strength tests 4.2 Deformation under screw forces 4.3 Lateral endurance tests and pull out capacity Screws Nails 4.4 Lateral strength and stiffness tests 5. Theoretical analysis to investigate lateral connection stiffness. 5.1 An 8m long 50 x 225 SA Pine rafter 5.2 A 6m long 36 x 150 SA Pine truss top chord member 6 Evaluation and interpretation of results 6.1 Pull out capacity 6.2 Compressive bearing pressures 6.3 Lateral restraint to truss chords and rafters 6.4 Construction 7. Conclusions and recommendations 8. References ANNEXURE A : ANNEXURE B : ANNEXURE C : ANNEXURE D : ANNEXURE E : ANNEXURE F : COMPRESSIVE STRENGTH TEST DEFORMATION UNDER SCREW LOAD SCREW PULL OUT CAPACITY LATERAL STIFFNESS AND STRENGTH TESTS Theoretical evaluation of lateral restraint provided by battens when ISOBOARD is used in an over rafter application. BRACING SYTEMS 1
3 TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM 1. Introduction An investigation was carried out by the Institute of Structural Engineering at the University of Stellenbosch to evaluate the structural performance of the ISOBOARD system in an over rafter and over truss application. This document describes the investigation which includes a described of the tests performed, and a presentation and interpretation of results. Finally, recommendations are made for the use of ISOBOARD in an over rafter and over truss application. (Definitions : For purpose of this investigation, a rafter is defined as a simply supported single span timber beam with its ends prevented from lateral movement and its ends prevented from torsional rotation about its longitudinal axis. A truss is defined as a built up structural assembly consisting of top and bottom chords, as well as vertical and/or diagonal web elements.) 2. Description of the investigation The investigation consisted of the following parts : - A desk top study was performed to determine the expected loads on the system. The structural strength and stability criteria as defined by Agrément South Africa were used for the assessment of the system. Loads were calculated using SABS 0160 (1989) to determine wind loading on roofs. - In support of the desk top study, a series of tests were performed in the laboratory. The testing was performed to determine certain material and system behaviour characteristics. The following tests were performed : Measurement of deformation of ISOBOARD under screw loads (fixation loads) (refer to Section 4.2) Compressive stiffness tests on ISOBOARD cut-outs (refer to Section 4.1) Repetitive lateral tests on batten and rafter systems with ISOBOARD installed in an over rafter application to simulate the movement in roofs due to long term thermal behaviour (refer to Section 4.3) Pull out tests on fasteners after completion of the repetitive loads on the batten and rafter systems (refer to Section 4.3) Lateral strength-stiffness tests on battens fixed to rafters through ISOBOARD (refer to Section 4.4) - A further desk top study was performed to study the capability of batten connections to provide lateral resistance to top chord members and rafters in bending. The study uses the information obtained in the strength-stiffness tests (Section 4.4). This evaluation is described in Section 5. 2
4 SCREW/NAIL ISOBOARD BATTEN (PURLIN) Rafter FIGURE 1 : ISOBOARD over rafter system The extent of the investigation included : - The thickness of ISOBOARD panels considered in the test series were as follows : o 25mm, 30mm and 40 mm panels were tested. - The following fasteners were used in the tests : o Screws : 150mm long below the head, 4.4mm diameter on the shaft above the thread, 5.3mm diameter measured over the thread. o Nails : 135 mm long, 5mm diameter 3. Theoretical calculations : The theoretical evaluation was performed based on the Agrément South Africa wind specifications which are summarized as follows : - Terrain Category 3 : i.e. suburbs, towns, wooded areas, industrial areas. - Altitude approximately at sea level - 25 year return period - No remarkable geographical features - Less than 5m from the ground - Ultimate load factor for wind load is 1.3 and for opposing self weight 0.9. From the above assumptions, it follows that the ultimate design pressures on the roof is 0.77 kpa upwards (local effects on eaves overhangs 1.01 kpa upwards). Based on different spacing of battens and rafters, the wind uplift on a connector (screw or nail) at a batten-rafter junction is given in Table 1a below. The values in the table are based on an assumed own weight of the roof material of 6kg/m 2. Similar wind uplift force on a connector (screw or nail) are shown in Table 1b for an eaves overhang of 600mm. Table 1a : Ultimate wind uplift forces on connectors at batten-rafter interface System Rafter x battens Nominal Own weight Nominal Wind uplift Resultant force (ULS)* = 0.9 DL WL 600 x kn down kn up kn up 750 x kn down kn up kn up 600 x kn down kn up kn up 750 x kn down kn up kn up * ULS = Ultimate limit state; DL = dead load; WL = wind load 3
5 Table 1b : Ultimate wind uplift forces on connectors at batten-rafter interface at eaves overhang System Rafter x battens Nominal Own weight Nominal Wind uplift Resultant force (ULS)* = 0.9 DL WL 600 x kn down kn up kn up 750 x kn down kn up kn up 600 x kn down kn up kn up 750 x kn down kn up kn up * ULS = Ultimate limit state; DL = dead load; WL = wind load 4. Test series 4.1 Compressive strength tests A series of tests was performed to determine the compressive strength of the ISOBOARD panels. Tests were performed on ten 50mm x 50mm samples of ISOBOARD panels, each with a thickness of 25mm, 30mm and 50mm. This test focused primarily on obtaining the panel compressive strength and force-deformation characteristics. The tests were performed according to SANS The Zwig testing machine in the structural laboratory with a capacity of 250 kn was used. Loading rate is shown in Table A1 for each of the tests. The results of the tests are summarized in Annexure A. Results are presented in Tables A1 and A2. A graphical presentation of the test results are presented in Figures A1 to A4. An image of a typical test specimen in the Zwig testing machine is shown in Figure A5. The method to determine yield stress can be seen in Figures A2 to A4. From the results in table A1 and A2 it can be seen that yield was reached for all specimens before a deformation of 10% of the specimen. 4.2 Deformation under screw forces The specimens prepared for the lateral endurance tests (see Section 4.3) were used to measure deformations (indent) of the ISOBOARD panel under screw forces (refer to Figure B1). Panels of 25mm, 30mm and 40 mm were measured. Four fixings were measured for each ISOBOARD panel thickness. The purpose of the measurements was to determine the extracting force which the ISOBOARD exerts on the screw. The maximum values are shown in bold in the table for each ISOBOARD thickness. 4.3 Lateral endurance tests and pull out capacity Screws The lateral displacement of the screw and panel arrangement was tested to investigate the behaviour under repetitive loads. The thickness of ISOBOARDs panels to be tested was 25mm, 30mm and 40mm. Tests were performed with and without ISOBOARD in place. Frames were made up consisting of four connections each, screw fixing two purlins to two rafters. The assembly was then placed in a testing frame where an imposed deformation was acting on the purlins. 4
6 The imposed deformation was 3mm in each direction, which represents a 20 change in temperature for a 10m long steel sheet (temperature coefficient of expansion taken to be 12 x10-6 m/m/ C.): o = 10 x 20 x 12 x10-6 = 2.4 mm, say 3mm. o Number of repetitions : 350 days x 30 years = o Period of application : 24 hours. The test pieces were placed in the testing assembly with a 0.5 mm clearance of movement in each direction. The number of repetitions was applied over a period of 24 hours. The test frame, test set-up and pull out tests are shown in Figures C1 to C5. Upon completion of the repetitive load testing, the pull out capacity of the screws was obtained through pull out tests performed in the Zwig testing machine (capacity 250 kn). A pull-out rate of 3mm/min. was applied as per ASTM D (Figure C6). Pull-out capacities for screws with and without repetition loads are summarized in Table C1. It can be seen that the repetition loads had negligible influence of the pull-out capacity Nails Tests were performed on similar assemblies as for connections with screws. Nail lengths of 150mm and 120mm were used together with ISOBOARD thickness of 30mm. The tests were performed for comparison with the screw connection tests. Frames were made up consisting of four connections each, nailing two battens to two rafters. The assembly was then placed in a testing frame where an imposed deformation was acting on the purlins. The imposed deformation was 3mm in each direction, which represents a 20 change in temperature for a 10m long steel sheet (temperature coefficient of expansion taken to be 12 x10-6 m/m/ C.): o = 10 x 20 x 12 x10-6 = 2.4 mm, say 3mm. o Number of repetitions : 350 days x 30 years = o Period of application : 24 hours. The test pieces were placed in the testing assembly with a 0.5 mm clearance of movement in each direction. The number of repetitions was applied over a period of 24 hours. An additional arrangement was prepared and similarly tested without ISOBOARD, using four connection points for 125 mm nails. Upon completion of the repetition loads, pull out tests were performed at a rate of 3mm/min as per ASTM D , using the Zwig testing machine. The pull out capacities for different nail lengths in battens with and without ISOBOARD, are presented in Table C2. The nail pull out capacities are significantly less than those of the screws. The influence of nail length can also be seen from the table. 4.4 Lateral strength and stiffness tests A series of tests was performed to determine the lateral strength and stiffness of screw connections through ISOBOARD panels. The purpose of the tests was to determine the capacity of the connections to provide effective lateral restraint. This is of importance in roof members where the battens or purlins provide lateral restraint for sections under compression or bending. The lateral load capacity of the following connections was evaluated : o Four connection points using 145 mm screws (4.5 mm diameter) connecting a batten with a rafter through 40 mm ISOBOARD 5
7 o o Four connection points using 165 mm nails connecting a batten with a rafter through 40 mm ISOBOARD Four connection points using 125 mm nails connecting a batten with a rafter (without ISOBOARD). All battens used were 50 x 76 mm. The connections were tested by application of a lateral load to a batten on a rafter. An arrangement was used where the rotation of the batten could be limited under lateral load, in order to simulate a continuous batten supported on more than one rafter. The test arrangement can be seen in Figure D1 and D2. Short sections of batten were tested by applying a lateral load from the Zwig machine. The results of the tests are presented in Annexure D. Table D1 shows the range of tests performed which includes the following basic variables : o connections with screws and ISOBOARD, o connections with nails and ISOBOARD, o connections with nails without ISOBOARD (standard construction). The choice of variable enables a comparison between standard construction and the effect of ISOBOARD on the connection. The results of the tests are presented in graphical format in Figure D3. The figure shows that connections with nails and no ISOBOARD have a significantly higher lateral capacity and stiffness than those using ISOBOARD. An approximate lateral stiffness of 500 kn/m was obtained for the specimen without ISOBOARD. An approximate stiffness of 50 kn/m was obtained for specimens with ISOBOARD. 5. Theoretical analysis to investigate lateral connection stiffness. One of the roles of battens in roof systems is to provide lateral restraint to compression members in trusses, and to provide lateral restraint to compression edges of rafters in bending. Since a much lower lateral stiffness was obtained during the test series for systems with ISOBOARD, an analysis was performed to investigate the effects of the lower connection stiffness on the ability of the connection to provide lateral restraint. This evaluation is described in this Section. Analyses were performed using the PROKON commercial software package. For the purpose of evaluation the following two structural configurations were considered : - An 8m long 50 x 225 SA Pine Grade 6 timber beam, considered to be acting as a rafter supporting battens. - A 6m long 36 x 150 Pine Grade 4 timber section, considered to act as a top chord truss member Second order analyses were performed on all the structural configurations. The purpose was to determine if lateral buckling occurs under axial compression (truss chord) or compression in bending (rafter). The analyses for these configurations are described in the following sections. 5.1 An 8m long 50 x 225 SA Pine rafter The following values were first calculated by hand for the 50 x 225 rafter : 6
8 - The maximum bending resistance for a 8m long beam was determined without lateral top flange restraint. A value of M r = 0.93 knm was calculated (SABS :1994) - The maximum bending resistance was determined for a beam with lateral support of the top flange. A value of 3.42 knm was calculated (SABS :1994). If the resistance factor (Ф) and the multiplication of the γ i factors are both taken as unity, then this value is 5.61 knm. The rafter was then modeled in the PROKON analysis by using shell elements. 4 elements were used in the depth of the rafter, and 52 along the length of the rafter. The top of the rafter was given an initial central lateral displacement of 10mm perpendicular to the rafter longitudinal axis. The top of the rafter followed a parabolic shape with zero lateral displacement at the supports, and 10mm in the centre. The bottom of the rafter had no initial lateral displacement. This initial lateral displacement initiated a lateral buckling behaviour in the second order analyses. The following cases were considered : - Case 1 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 0.93 knm in the rafter. No lateral restraint was provided at the top of the rafter. This was the maximum load that could be applied. With an increase of 5% of the forces which generated this bending moment value, the analysis was terminated by the program to due instability. - Case 2 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 0.93 knm in the rafter. Lateral restraint was provided at the top of the rafter using spring elements at a spacing of 307mm and each with a stiffness of 50 kn/m (screw connection with ISOBOARD). The lateral displacement was 0.07mm. - Case 3 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 5.61 knm in the rafter. Lateral restraint was provided at the top of the rafter using spring elements at a spacing of 614 mm with a stiffness of 500 kn/m (nail connection without ISOBOARD). The system was stable and it shows that nails and battens provide adequate restraint to the rafter. - Case 4 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 5.61 knm. Lateral restraint was provided at the top of the rafter using spring elements at a spacing of 614 mm with a stiffness of 50 kn/m (screw connection with ISOBOARD). The system was stable and it shows that screws through ISOBOARD and and battens provide adequate restraint to the rafter. - Case 5 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 5.61 knm in the rafter. Lateral restraint was provided at the top of the rafter using spring elements at a spacing of 307mm with a stiffness of 500 kn/m (nail connection without ISOBOARD). The system was stable and it shows that nails and battens provide adequate restraint to the rafter. - Case 6 : An application of equal vertical point loads at 307mm spacing on the top of the rafter to develop a bending moment of 5.61 knm in the rafter. Lateral restraint was provided at the top of the rafter using spring elements at a spacing of 307mm with a stiffness of 50 kn/m (screw connection with ISOBOARD). The system was stable and it shows that screws through ISOBOARD and and battens provide adequate restraint to the rafter. For each case the stability of the rafter was calculated applying a second order analysis. All rafter configurations were stable, i.e. no lateral torsional buckling occurred. The only case where no additional load could be applied is Case 1 (no top of rafter restraint).. An increase of 5% of the applied load resulted in an instability. This is similar to the result from the hand calculation based on the design code (SABS :1994) The lateral displacement of the rafter was calculated for each case and is summarized in Table E1. The unrestrained rafter has by far the largest lateral displacement. Although the connections with 7
9 screws have a much lower stiffness than that of the nails, the lateral displacement is still very small. A print out of the final displaced rafter is presented for each case in Figures E1 to E A 6m long 36 x 150 SA Pine truss top chord member The following values were used for the analysis of the top chord truss member : - An axial compression load of 50 kn (9.3 MPa < Ф x f cp = 10.8 MPa) - Vertical batten loads of 0.28 kn spaced at approximately 800 mm. The top chord was modeled in the PROKON analysis to be made up of beam elements. 64 elements were used along the length of the chord. The chord was given an initial central lateral displacement of 5mm perpendicular to the chord longitudinal axis. This initial lateral displacement initiated a lateral buckling behaviour in a second order analyses. The following cases were considered : - Case 1 : Two intermediate vertical supports at 2.25m spacing. Lateral restraint at 0.75m with a stiffness of 500 kn/m (nails) : o Maximum lateral displacement = 14.5mm (too high) - Case 2 : Two intermediate vertical supports at 2.25m spacing. Lateral restraint at 0.375m with a stiffness of 50 kn/m (screws). o UNSTABLE Although the condition of combined axial compression and bending is not considered in the evaluation above, it is clear that a truss with a top chord member restrained by battens, fixed with screws through ISOBOARD, is not sufficiently restrained to prevent instability. 6 Evaluation and interpretation of results The test series and theoretical analyses allow an evaluation of the following three basic aspects of the system where ISOBOARD is used in an over rafter application : - pull out capacity of the connection : this is, the ability of the connection to resist uplift forces from wind - bearing capacity : this is the ability of the ISOBOARD panels to resist compressive bearing pressures at batten-rafter connections - lateral restraint provided to rafter and truss members in compression (or bending). These three aspects plus construction aspects are evaluated in the following sections. 6.1 Pull out capacity The maximum wind uplift force at a connection between batten and rafter (or truss chord) is shown in Table 1a to be kn (750 x 1500mm spacings) on the roof, and kn (750 x 1500 spacing) for a 600mm eaves overhang. The maximum uplift force due to the resistance of the ISOBOARD after tightening a screw at a connection between batten and rafter (or truss chord), is given as 0.56 kn (Table B1). The smallest pull out capacity achieved for a connection with screws is kn (Tabel C1). The smallest pull out capacity achieved for a nail is 0.44 kn (Table C2) (ignoring the smallest results of kn) Thus the ratio between pull out capacity and uplift force is as follows : 8
10 3.477/( ) = 2.54 (Screw) : Roof 3.477/( ) = 1.93 (Screw) : Overhang 0.44/( ) = 0.32 (nail) : Roof 0.44/( ) = (nail ) : Overhang The screw is considered to provide adequate resistance to uplift. The nail is inadequate. 6.2 Compressive bearing pressures The maximum force before yielding during the compressive force tests is taken to be 450 N. This is equivalent to 180 kpa on the 50 x 50 mm specimens. If ISOBOARD panels are to be limited to this compressive stress, then typical limits for spacing of rafters and battens can be calculated. The limits presented here are based on the following : - Assuming a material factor of 1.15 (strength reduction factor) on the compressive strength (i.e. limit = 450/1.15 = 390N) - Roof tiles with mass of 60 kg/m 2 - Roof sheeting with mass 10 kg/m 2 - Imposed load of 0.5 kpa - Imposed load factor Dead load factor 1.2. The calculated limits for rafter and batten spacing are presented in Tables 2 and3 for sheeted and tiled roofs. Table 2 : Spacing limits for battens and rafters of tiled roofs Member sizes Battens on rafter (mm on mm) Maximum allowed Supporting area (m 2 ) Examples of limits Batten x rafter (mm x mm) 38 x x x x x x x x 1100 Table 3 : Spacing limits for battens and rafters of sheeted roofs Member sizes Battens on rafter (mm on mm) Maximum allowed Supporting area (m 2 ) Examples of spacing limits Batten x rafter (mm x mm) 38 x x x x x x x x x x x Lateral restraint to truss chords and rafters The lateral strength and stiffness tests enabled the analyses to be performed as described under Section 5 above. 9
11 Top chords in trusses : From the analyses it is clear that when battens are fixed to top chord members in trusses using screws (or nails), the connection does not provide inadequate lateral support to the member. Battens used in conjunction with ISOBOARD panels in an over truss application as studied in this report can therefore not be relied upon to provide lateral restraint to top chord members in trusses. Rafters : A maximum span of 8m was investigated using a rafter of 50 x 225mm. It is found that screw connections with ISOBOARD panels in an over rafter application can provide adequate lateral restraint in bending to the top of the rafter under gravity loads. This is valid for battens at a maximum spacing of 600mm. Rafters with a maximum size of 50 x 255mm and a maximum span of 8m are therefore considered to be adequately retrained laterally by the screw connection for bending under gravity loads. Sketches are shown in Annexure F to explain the above concepts of systems which may or may not be sufficiently braced against lateral buckling. 6.4 Construction The tests in this series were performed with material prepared and fixed in laboratory conditions. It is however important to realize that construction conditions on site may be significantly different. For this reason, it is imperative that the following be taken into account when ISOBOARD panels are used in an over rafter application : - Contractors need to have a suitable method to ensure that screws can be fixed through battens and ISOBOARD panels into rafters in such a manner that adequate edge distances are maintained in both batten and rafter. Pre-drilling of screw guide holes is considered to be the only manner suitable. - Contractors need to have well monitored quality procedures in place to ensure that the method statements are correctly followed. Recommendations for battens to provide adequate restraint is based on the assumption that battens are fixed in such a manner elsewhere that they are prevented form lateral movement themselves. 7. Conclusions and recommendations An investigation was carried out to evaluate the structural performance of the ISOBOARD system in an over rafter and an over truss application. The investigation consisted of a series of tests to determine strength and stiffness properties of ISOBOARD panels and of typical connections. Furthermore, theoretical analyses were performed to study lateral restraint provided by the batten connections to top chord members and for rafters. The range of ISOBOARD panel thickness and connector sizes (screw and nail) which were investigated are described in the report. The following recommendations are presented for ISOBOARD used in an over TRUSS application: - Guide holes must be pre drilled in truss members and battens before fixing of screws. - Nails are not considered an adequate method of fixing battens to the truss.. - ISOBOARD panels and timber battens fixed with either nails or screws in an over chord application, do not provide sufficient lateral restraint to top chord members in trusses. The 10
12 limitation is due to the fact that connection does not possess sufficient lateral stiffness between the batten and the top chord truss member. Other means are necessary to provide lateral restraint to top chords in trusses if ISOBOARD is used in an over truss application. - If other elements are provided in a roof system to provide lateral restraint to the top chord of trusses, then ISOBOARD panels can be used in an over truss application. In such a case, there is a limitation on the spacing of battens and trusses which needs to be adhered to, and which is a function of the roof material type, being either roof sheets or roof tiles. These limitations are provided in Tables 2 and 3. - Battens and truss top chord members shall be SA Pine Grade 4 or better. - Contractors must have a well prepared method statement to ensure correct placement and fixing of battens over trusses to ensure that screws will be placed within SABS 1200 tolerance specifications. - Contractors must have an approved quality control procedure to monitor the correct placement of ISOBOARD panels and screws. The following recommendations are presented for ISOBOARD used in an over RAFTER application: - When used in an over rafter application, ISOBOARD panels must be fixed between the rafter and batten using 150mm screws with a diameter of 4.4mm tying the battens to timber rafters. - Timber rafters shall have a minimum width of 50mm - Guide holes must be pre drilled in rafters and battens before fixing of screws. - Nails are not considered an adequate method of fixing battens to rafters. - Screw connections fixing battens to rafters with ISOBOARD panels in an over rafter application can be considered to provide sufficient lateral restraint to the top of the timber beam under gravity load with the following limitations : o Maximum rafter span length is 8m (longer span lengths were not investigated). o Maximum spacing between battens is 600mm. o o Maximum rafter size 75 x 225mm (larger rafters were not investigated) Maximum imposed (live) load on the roof is 0.5 kpa (higher loads were not investigated). - The above limitations can be exceeded if other elements are provided in a roof system to provide lateral restraint to the top of rafters. - There is a limitation on the spacing of battens and rafters which needs to be adhered to, and which is a function of the roof material type, being either roof sheets or roof tiles. These limitations are provided in Tables 2 and 3. - Battens and rafters shall be SA Pine Grade 4 or better. - Contractors must have a well prepared method statement to ensure correct placement and fixing of battens over rafters to ensure that screws will be placed within SABS 1200 tolerance specifications. - Contractors must have an approved quality control procedure to monitor the correct placement of ISOBOARD panels and screws. 8. References ASTM D : Standard test methods for mechanical fasteners in word. ASTM Standards, Philadelphia, USA SABS 0160 (1989) : The general procedures and loadings to be adopted in the design of buildings. South African Bureau of Standards, Pretoria. As amended SABS :1994 : The structural use of timber Part 1 : Limit-states design. South African Bureau of Standards, Pretoria. As amended SABS : Expanded polystyrene thermal insulation boards. South African Bureau of Standards, Pretoria
13 ANNEXURE A : COMPRESSIVE STRENGTH TEST TABLE A1. Compressive strength tests force at yield Specimen thickness (mm) Force at yield (N) Stress at yield (kpa) Deformation at yield TABLE A2 Compressive strength tests force at 90% of original thickness Specimen number Thickness Loading rate Force at 90% of thickness mm mm/min N Thickness 40mm average Thickness 30mm average Thickness 25mm average
14 Compressive Graphs Force (N) mm Thickness 30mm Thickness 40mm Thickness Displacement (mm) FIGURE A1 : Force vs displacement behaviour of ISOBOARD specimens. 25 mm Force [N] Displacement [mm] FIGURE A2 : Force vs displacement behaviour of ISOBOARD specimens (25 mm) 13
15 30mm ISOBOARD Force [N] Displacement [mm] FIGURE A3 : Force vs displacement behaviour of ISOBOARD specimens (30 mm) 40mm ISOBOARD Force [N] Displacement [mm] FIGURE A4 : Force vs displacement behaviour of ISOBOARD specimens (40 mm) 14
16 FIGURE A5 : ISOBOARD specimen in Zwig testing machine for compressive strength test 15
17 ANNEXURE B : DEFORMATION UNDER SCREW LOAD SCREW/NAIL ISOBOARD BATTEN (PURLIN) Rafter INDENT MEASURED (Table B1) FIGURE B1 : Measurement of indent TABLE B1: Deformation under screw tightening loads ISO Board Thickness Thickness before (mm) Thickness after (mm) Deformation Equivalent force (from Fig. A2- A4) mm mm mm mm N
18 ANNEXURE C : SCREW PULL OUT CAPACITY A SCREW/NAIL ISOBOARD BATTEN (PURLIN) Rafter A 0.5 mm gap SCREW/NAIL ISOBOARD BATTEN (PURLIN) Angle irons Moved 7 mm Rafter (fixed against movement) SECTION A-A FIGURE C1 : Set-up for repetition loads 17
19 FIGURE C2: Test frame for repetition loads FIGURE C3: Specimen in test frame for repetition loads 18
20 FIGURE C4: Specimen in test frame for repetition loads FIGURE C5: Specimen in test frame for repetition loads 19
21 FIGURE C6: Pull-out test after repetitive loads 20
22 TABLE C1 : Pull out capacity of SCREWS without load repetition and after load repetition. Frame Connection nr ISO Board Thickness Purlin Thickness Pullout capacity without repetition Purlin Thickness Pullout capacity after repetition mm mm N mm N Screws Screws Screws
23 TABLE C2 : Pull out capacity of NAILS with load repetition. Frame Connection nr ISO Board Nail Purlin Pullout Thickness length Thickness capacity mm mm mm N Nails Nails Nails 13 no Isoboard no Isoboard no Isoboard no Isoboard
24 ANNEXURE D : LATERAL STIFFNESS AND STRENGTH TESTS TABLE D1 : Range of tests performed with lateral strength values Fmax Screw Length Nail Length ISO board thickness N mm mm mm Screw Screw Screw Nail Nail Nail Nail Nail Nail Nail FIGURE D1 : Lateral stiffness test on specimen with ISOBOARD 23
25 FIGURE D2 : Lateral stiffness test on specimen without ISOBOARD Lateral Stiffness Graphs Force (N) Nail150mmISO40mm#1 Nail150mmISO40mm#2 Nail150mmISO40mm#3 Nail150mmISO40mm#3 Nails120mm#1 Nails120mm#2 Nails120mm#3 Screws140mmISO40mm#1 Screws140mmISO40mm#2 Screws140mmISO40mm# Displacement (mm) FIGURE D3 : Results of tests to determine lateral stiffness of connections 24
26 ANNEXURE E : THEORETICAL EVALUATION OF LATERAL RESTRAINT PROVIDED BY BATTENS WHEN ISOBOARD IS USED IN AN OVER RAFTER APPLICATION. Table E1 : Lateral displacement of rafter under various restraint conditions Case Bending moment Restraint at top of rafter Displacement (mm) knm No restraint knm Screw + ISOBOARD at 307mm knm Nails at 614 mm knm Screw + ISOBOARD at 614mm knm Nails at 307 mm knm Screw + ISOBOARD at 307mm 0.57 FIGURE E1 : Case 1 : Rafter with no lateral restraint (M = 0.93 knm) 25
27 FIGURE E2 : Case 2 : Rafter with battens fixed with screws at 307mm (M =0.93 knm) FIGURE E3 : Case 3 : Rafter with battens NAILED on at 614mm (M =5.61 knm) 26
28 FIGURE E4 : Case 4 : Rafter with battens fixed with screws at 614mm (M =5.61 knm) FIGURE E5 : Case 5 : Rafter with battens fixed with nails at 307mm (M =5.61 knm) 27
29 FIGURE E6 : Case 6 : Rafter with battens fixed with screws at 307mm (M =5.61 knm) FIGURE E7 : Truss top chord with battens fixed with nails at 750mm 28
30 FIGURE E8 : Truss top chord with battens fixed with screws at 375mm 29
31 ANNEXURE F : BRACING SYTEMS 30
32 31
33 32
2.3 SPECIFIC DESIGN DHS PURLINS
2.3 SPECIFIC DESIGN DHS PURLINS 2.3.1 INTRODUCTION Dimond Hi-Span (DHS) Purlin Systems have been designed to comply with AS/NZS 4600:1996, based on physical testing and analysis carried out by the University
More informationAttach Trusses and Rafters Faster
Attach Trusses and Rafters Faster SDWC TRUSS Screw Truss-to-Plate Connections For Truss-to-Plate Connections The Strong-Drive SDWC TRUSS screw provides a truss- and rafter-to-top-plate connection. The
More informationCCFSS Technical Bulletin
CCFSS Technical Bulletin Vol. 12, No. 1 February 2003 FREQUENTLY ASKED QUESTIONS CONCERNING THE AISI BASE TEST METHOD AND THE USE OF THE AISI ANCHORAGE EQUATIONS Answers Provided by the AISI Task Committee
More informationStructural Strength of Lapped Cold-Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes
Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2014) - 22nd International Specialty Conference on Cold-Formed Steel Structures
More informationBRACING BRACING SECTION 7 SECTION 7
If we are to learn from the past, it is clear that there is generally a lack of understanding of the purpose of roof bracing and who should be responsible for it. This has led to disputes, claims and,
More information3.1 General Provisions
WOOD FRAME CONSTRUCTION MANUAL 107 3.1 General Provisions 3.1.1 Prescriptive Requirements The provisions of this Chapter establish a specific set of resistance requirements for buildings meeting the scope
More informationLVL8 H1.2 GENERAL FRAMING. Eco Friendly Revolutionary H1.2 Treatment Azotek by Zelam
LVL8 H1.2 GENERAL FRAMING Eco Friendly Revolutionary H1.2 Treatment Azotek by Zelam NPIL/MARCH2015 Introduction to NelsonPine LVL8 H1.2 NelsonPine LVL is an engineered wood composite made from rotary peeled
More informationTechnical Data Sheet. T E C H N I C A L D A T A S H E E T Superprop. Mass 25 Mass 50 M AT 125 Superprop. MU Bridging
Technical Data Sheet Mass 25 Mass 50 M AT 125 Hydraulics Quickbridge MU Falsework MU Bridging Compact Bridging BarrierGuard 800 Instrumentation Mabey Hire Ltd. Structural Support & Bridging Bridge House,
More informationSturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models
Sturdi-Wall Design Manual for SW46, SW66, SW63, SW64, SW60, SW83, SW84, and SW80 Models Project Number ME086-05 by Brent Leatherman, P.E. Timber Tech Engineering, Inc E-Mail: bl@timbertecheng.com January
More informationTOPSPAN 22 / 40 LYSAGHT TOPSPAN 22 / 40. Steel roof and ceiling battens for non cyclonic applications
TOPSPAN 22 / 40 LYSAGHT TOPSPAN 22 / 40 Steel roof and ceiling battens for non cyclonic applications Our TOPSPAN 22 ceiling batten and TOPSPAN 40 roof battens are the economical alternative to timber battens.
More informationIntroducing AJSTM INSTALLATION GUIDE USA. 8 th Edition USA
The SIMPLE FRAMING SYSTEMSM INSTALLATION GUIDE USA for Floors This Installation Guide is intended to provide general information for the designer and end-user. For further information, please refer to
More informationEurocode EN Eurocode 3: 3 Design of steel structures. Part 1-1: General rules and rules for buildings
Eurocode EN 1993-1-1 Eurocode 3: 3 Design of steel structures Part 1-1: General rules and rules for buildings Eurocode EN 1993-1-1 Eurocode 3 applies to the design of buildings and civil engineering works
More informationLoad-carrying capacity of timber frame diaphragms with unidirectional support
Load-carrying capacity of timber frame diaphragms with unidirectional support Jørgen Munch-Andersen, Danish Timber Information, 2012-06-26 Introduction The rules for determining the load-carrying capacity
More informationLP SolidStart LSL. LP SolidStart LSL Prescriptive Roof Framing Technical Guide 2500F b-1.75e, 2360F b -1.55E and 1730F b -1.
LP SolidStart LSL LP SolidStart LSL Prescriptive Roof Framing Technical Guide 2500F b-1.75e, 2360F b -1.55E and 1730F b -1.35E LSL Please verify availability with the LP SolidStart Engineered Wood Products
More informationBolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy
Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy steel: 4, 5, 6, 8, 10, 12 2- Bolts made of stainless
More informationDowel connections in laminated strand lumber
Dowel connections in laminated strand lumber Cranswick, Chad J. 1, M c Gregor, Stuart I. 2 ABSTRACT Laminated strand lumber (LSL) is a relatively new structural composite lumber. As such, very limited
More informationMAT105: Floor Framing
MAT105: Copyright 2007 American Forest & Paper Association, Inc. Because the common applications for wood framing are in residential construction, the details of this program will be based on the IRC which
More informationConnection and performance of two-way CLT plates
Connection and performance of two-way CLT plates by Chao (Tom) Zhang George Lee Dr. Frank Lam Prepared for Forestry Innovation Investment 1130 W Pender St, Vancouver BC V6E 4A4 Timber Engineering and Applied
More informationZ and C - sections ZED PURLIN SYSTEMS. Design tables according to Eurocodes. For secondary steel structures. Large range of. Z and C - sections
ZED PURLIN SYSTEMS Large range of Z and C - sections System solution Purlins and side rails Eaves beams Floor beams Framing Easy design in software MetSPEC 12 Z and C - sections For secondary steel structures
More informationFASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S. Which FERO Tie Systems Require Fasteners?
FASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S Which FERO Tie Systems Require Fasteners? Structural Actions: Fastener,, or Both? With the exception of FERO tie systems that are directly
More informationLightweight purlins. Technical Manual.
CFI.001E/08.2011/PR Ruukki is a metal expert you can rely on from start to finish, when you need materials, components, systems or total solutions. e continuously develop our operating model and product
More informationWHY YOU SHOULD USE TUFFLOOR. components
Tuffloor DESIGN GUIDE WHY YOU SHOULD USE TUFFLOOR Strong and Easily Installed Tuffloor is a steel floor framing system designed for strength and ease of installation, and is an easy and economical alternative
More informationROOF-CEILING CONSTRUCTION
CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings. R801.2
More informationGeneral Layout. Eng. Maha Moddather
General Layout Eng. Maha Moddather mahamoddather@eng.cu.edu.eg Introduction Concrete Beam subjected to Bending Moment around Major Axis M x Compression d Concrete tensile strength is neglected A S Tension
More informationICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.
ICC-ES Evaluation Report www.icc-es.org (800) -6587 (56) 699-05 ESR-0 Reissued March, 0 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION: 06 00 00
More informationFastener Schedule. a, b, c. FASTENER Roof 3-8d (2 1 / ) / ) 3-10d. 3-10d ( ) 3-16d box nails. (3 1 2 toe nails on one side
ITEM 1 DESCRIPTION OF BUILDING ELEMENTS Blocking between joists or rafters to top plate, toe 2 Ceiling joists to plate, toe 3 4 5 6 Ceiling joists not attached to parallel rafter, laps over partitions,
More informationSECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION
SECTION R507 DECKS R507.1 Application. The provisions of this section shall provide prescriptive requirements for the design and construction of all uncovered, wood-framed, single-span exterior decks.
More informationTwo basic types of single
Designing with Single Plate Connections M. Thomas Ferrell M. Thomas Ferrell is president of Ferrell Engineering, Inc., of Birmingham, AL. He is a member of the AISC Committee on Manuals and Textbooks,
More informationTension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite.
Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite. Tracy Hummer, Research Assistant J. Daniel Dolan, Professor Michael Wolcott, Professor Wood Materials
More informationPV System Structural Criteria
PV System Structural Criteria Town of Atherton Building Department 91 Ashfield Road Atherton, California 94027 Phone: (650) 752-0560 STRUCTURAL CRITERIA FOR RESIDENTIAL ROOFTOP FLUSH-MOUNTED SOLAR ARRAYS
More informationDesign Guide Pryda Connectors for Steel Framing
Pryda Connectors for Steel Framing Copyright: (c) Pryda Australia A Division of ITW Australia November 2012 November 2012 Design Guide Pryda Connectors for Steel Framing INDEX General Notes General information
More informationSTRUCTURAL TIMBER DESIGN
STRUCTURAL TIMBER DESIGN to Eurocode 5 2nd Edition Jack Porteous BSc, MSc, DIC, PhD, CEng, MIStructE, FICE Director lack Porteous Consultancy and Abdy Kernlani BSc, MSc, PhD, CEng, FIStructE, FIWSc Professor
More informationConnection and Tension Member Design
Connection and Tension Member Design Notation: A = area (net = with holes, bearing = in contact, etc...) Ae = effective net area found from the product of the net area An by the shear lag factor U Ab =
More informationTECH SHEET PEM - REF / TESTING CLINCH PERFORMANCE. SUBJECT: Testing clinch performance of self-clinching fasteners.
PEM - REF / TESTING CLINCH PERFORMANCE SUBJECT: Testing clinch performance of self-clinching fasteners. A self-clinching fastener s performance can be divided into two major types. The first is self-clinching
More informationENGINEERED BUILDING PRODUCTS. SplitHanger. mitek.com.au
ENGINEERED BUILDING PRODUCTS SplitHanger mitek.com.au S p l i t H a n g e r SUITABLE FOR VARIOUS WIDTHS OF TIMBER BEAM APPLICATION: SplitHangers are versatile hangers that provide a heavy duty connection
More informationEXAMPLE 1-4 EXAMPLE 1-5
EXAMPLE 1- Calculate the maximum shear stress τmax in a simply supported wood beam carrying a uniform load of (w=18 kn/m) if the length is 1.75 m and the cross section is rectangular with width 150 mm
More informationVERSA-LAM. An Introduction to VERSA-LAM Products
44 VERSA-LAM An Introduction to VERSA-LAM Products VERSA-LAM is one of the strongest and stiffest engineered wood products approved in the UK. 241 302 356 406 VERSA-LAM products are excellent as floor
More informationKorean standards of visual grading and establishing allowable properties of softwood structural lumber
Korean standards of visual grading and establishing allowable properties of softwood structural lumber Park, Moon-Jae 1, Shim, Kug-Bo 1 ABSTRACT Korean standards related to wood products such as "Sizes
More informationStructural Behaviour of Lapped Cold- Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes
Structural Behaviour of Lapped Cold- Formed Steel Z-Shaped Purlin Connections with Vertical Slotted Holes by Jingnan Liu A thesis presented to the University of Waterloo in fulfillment of the thesis requirement
More informationLawrence A. Soltis, M. and Robert J. Ross, M. 1
REPAIR OF WHITE OAK GLUED-LAMINATED BEAMS Lawrence A. Soltis, M. and Robert J. Ross, M. 1 Abstract Connections between steel side plates and white oak glued-laminated beams subjected to tension perpendicular-to-grain
More informationTech. Bulletin. Spacing. Positioning. Tile Brackets 6.1
created JM Tech. Bulletin Rev. Nr. 6.1 Tile Brackets checked JL valid from 28/02/13 Tile brackets are part of the SunLock mounting system for solar photovoltaic (PV) modules. The new SLTB005 adjustable
More informationUL Construction No. 254
UL Construction No. Wind-Uplift - Class 90 (See Item No. ) / Fire Not Investigated Metal Roof Deck Panels* Snap-Clad No. MSG or No. MSG min. thickness coated steel panels. Panels in. wide max., 0 in. wide
More informationAbout Everite and Nutec 2. Nutec Bigsix Tiles : Compsition and Product Quality 4. Installation Guide 5. Support Structure 6
c o n t e n t s About Everite and Nutec 2 Nutec Bigsix Tiles : Compsition and Product Quality 4 Installation Guide 5 Support Structure 6 Light Weight Steel Sections 4 Timber Supports 5 Mitre Details 5
More informationStructural Criteria for Residential Flush-Mounted Solar Arrays
Structural Criteria for Residential Flush-Mounted Solar Arrays Planning and Development Building & Safety Division 1. ROOF CHECKS A. Visual Review/Contractor s Site Audit of Existing Conditions: 1) Is
More informationROOF-CEILING CONSTRUCTION
CHAPTER 8 ROOF-CEILING CONSTRUCTION SECTION R801 GENERAL R801.1 Application. The provisions of this chapter shall control the design and construction of the roof-ceiling system for all buildings (see Section
More informationSteeline X-SPAN purlins
Steeline X-SPAN purlins DESIGN MANUAL F y y L R5 t D 2 Origin x x x x y D L steeline.com.au y y E CONTENTS IMPORTANT NOTES... 1-1 DISCLAIMER... 1-1 INTRODUCTION... 1-2 HOW TO USE THE X-SPAN purlins DESIGN
More informationStructural Criteria for Residential Rooftop Solar Energy Installations
TOOLKIT DOCUMENT #5 Structural Criteria for Residential Rooftop Solar Energy Installations CRITERIA FOR RESIDENTIAL FLUSH-MOUNTED SOLAR ARRAYS STRUCTURAL 1. ROOF CHECKS A. Visual Review/Contractor s Site
More informationAnti-check bolts as means of repair for damaged split ring connections
Anti-check bolts as means of repair for damaged split ring connections Quenneville, J.H.P. 1 and Mohammad, M. 2 ABSTRACT There are numerous large span timber hangars dating back to the Second World War.
More informationStructural Criteria for Residential Rooftop Solar Energy Installations
DOCUMENT #5 Structural Criteria for Residential Rooftop Solar Energy Installations STRUCTURAL CRITERIA FOR RESIDENTIAL FLUSH-MOUNTED SOLAR ARRAYS 1. ROOF CHECKS A. Visual Review/Contractor s Site Audit
More informationA Study On Bracing Systems On High Rise Steel Structures Jagadish J. S [1], Tejas D. Doshi [2]
Abstract A Study On Bracing Systems On High Rise Steel Structures Jagadish J. S [1], Tejas D. Doshi [2] 1-Post Graduate Student, Department of Civil Engineering, KLE Dr. MSSCET, Belgaum, Karnataka, India,
More informationSite Installation Guide
Site Installation Guide Site Checklist Stop and read this now. Tick box when checked. Floor Joist Layout If a floor joist design/layout was done, was a site copy of the layout provided with the joists,
More informationHECO-TOPIX -CombiConnect HECO-TOPIX -Therm HCS-Calculation software
HECO-TOPIX -CombiConnect HECO-TOPIX -Therm HCS-Calculation software THE WOOD SCREW FOR THE PROFESSIONAL The HECO-Calculation software (HCS) and HECO-TOPIX Woodscrews for easy estimation and safe assembling
More informationSCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS
SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS Prof. Dr.-Ing. H. J. Blaß, Dipl.-Ing. I. Bejtka Universität Karlsruhe (TH), Germany Abstract Screws, bolts and dowels loaded perpendicular to the fastener
More informationLYSAGHT FIRMLOK. Identification The format of the number code is: Material specifications
LYSGHT FIRMLOK W = 47 W = 47 2t W = 47 2t D = 200 2t D = 150 D = 100 t t t F100 F150 F200 Sizes Section Dimensions Metal thickness Section area Mass (Colorbond) D x W t ( mm) ( mm) 2 ) ( mm (kg/m) 100
More informationTHE ENGINEERED WOOD ASSOCIATION
D A T A F I L E APA Performance Rated Rim Boards A rim board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top
More informationGlobal Roofing Solutions Klip-Tite
GRS Klip-Tite Global Roofing Solutions Klip-Tite www.globalroofs.co.za marketing@globalroofs.co.za GRS Klip-Tite GRS Klip-Tite 09/18 Typical Specification Materials The roofing shall be Klip-Tite profile,
More informationStructural Calculations
Structural Calculations Project Project Number 14 266 Napier Girls High School Performing Arts Building (Arthur Building) Document Control Date Version Extent of Revision Status 21 September 2015 A Original
More informationHazlan Abdul Hamid* & Mohammad Iqbal Shah Harsad
Malaysian Journal of Civil Engineering 28(1):59-68 (2016) BEHAVIOUR OF SELF-DRILLING SCREW UPON SINGLE SHEAR LOADING ON COLD FORMED STEEL Hazlan Abdul Hamid* & Mohammad Iqbal Shah Harsad Faculty of Civil
More informationADDENDUM (February 2014) 2012 NDS Changes John Buddy Showalter, P.E., Bradford K. Douglas, P.E., Philip Line, P.E., and Peter Mazikins, P.Eng.
ADDENDUM (February 2014) 2012 NDS Changes John Buddy Showalter, P.E., Bradford K. Douglas, P.E., Philip Line, P.E., and Peter Mazikins, P.Eng. 1) Add to section on Dowel-type Fasteners as follows: Section
More informationBeam & Header Technical Guide. LP SolidStart LVL. 2900F b -2.0E. U.S. Technical Guide U.S. TECHNICAL GUIDE
U.S. Technical Guide U.S. TECHNICAL GUIDE LP SolidStart LVL & Header Technical Guide 2900F b -2.0E Please verify availability with the LP SolidStart Engineered Wood Products distributor in your area prior
More information1. Enumerate the most commonly used engineering materials and state some important properties and their engineering applications.
Code No: R05310305 Set No. 1 III B.Tech I Semester Regular Examinations, November 2008 DESIGN OF MACHINE MEMBERS-I ( Common to Mechanical Engineering and Production Engineering) Time: 3 hours Max Marks:
More informationAPA Performance Rated Rim Boards
D a t a F i l e APA Performance Rated Rim Boards A Rim Board is the wood component that fills the space between the sill plate and bottom plate of a wall or, in second floor construction, between the top
More informationCast-in Ferrule Connections Load/Displacement Characteristics in Shear
Cast-in Ferrule Connections Load/Displacement Characteristics in Shear Ian Ferrier 1 and Andrew Barraclough 2 1 Product Manager - Connections, ITW Construction Systems ANZ. 2 Research and Development Manager,
More informationPlease do not open this exam until you are told to do so.
Seat # Name a General examination rules: 1) Do not put your completed work anywhere that it can be seen. If any part of your work can be seen by others it will be confiscated and you will not be permitted
More informationNailed Structural-Use Panel and Lumber Beams
D A T A F I L E Nailed Structural-Use Panel and Lumber Beams When roof load or span requirements are too great to allow use of commonly available dimension lumber or timbers, a box beam constructed of
More informationLoad application in load cells - Tips for users
Load application in load cells - Tips for users Correct load application on the load cells is a prerequisite for precise weighing results. Be it load direction, support structure or mounting aids load
More informationHanger bolts and solar fasteners in sandwich panels
Hanger bolts and solar fasteners in sandwich panels Helmut Krüger 1, Thomas Ummenhofer 2, Daniel C. Ruff 3 Abstract For the energetic use of sunlit roofs, photovoltaic and solar thermal elements are mounted
More informationEuropean Technical Assessment. ETA-16/0902 of 17 March English translation prepared by DIBt - Original version in German language.
European Technical Assessment ETA-16/0902 of 17 March 2017 - Original version in German language General Part Technical Assessment Body issuing the European Technical Assessment: Trade name of the construction
More informationENGINEERED BUILDING PRODUCTS. CycloneTie CT1200 CT900 CT600 CT400 CT180. mitek.com.au
ENGINEERED BUILDING PRODUTS yclonetie T1200 T900 T600 T400 T180 mitek.com.au Ti e FOR ROOF SEURITY UNDER EXTREME WIND ONDITIONS APPLIATION: ycloneties are used to secure purlins, rafters and trusses to
More informationPryda Timber Connectors
Pryda Timber Connectors Pryda Lintel Guide Engineered Steel Wall Lintels March 2014 ESSENTIAL NOTES PRYDA PRODUCT GUIDES INTRODUCTION The information in this Product Guide is provided for use in Australia
More informationENGINEERED BUILDING PRODUCTS. I-Beam HANGERS. NEW Enhanced Capacity with YELLOW MiTek 40 x 3.75mm nails
ENGINEERED BUILDING PRODUCTS I-Beam HANGERS NEW Enhanced Capacity with YELLOW MiTek 40 x 3.75mm nails I - B e a m H a n g e r s - F a c e & T o p F i x e d FOR FACE AND TOP FIXING OF I-BEAMS TO BEAMS APPLICATION:
More informationENGINEERED BUILDING PRODUCTS. Boomerang CONNECTOR
ENGINEERED BUILDING PRODUCTS Boomerang CONNECTOR B o o m e r a n g C o n n e c t o r FOR FIXING JACK/CUT-OFF TRUSSES TO HIP/BOOMERANG TRUSSES APPLICATION: The Boomerang Connector has been developed to
More informationPOST FRAME CONSTRUCTION MANUAL
POST FRAME CONSTRUCTION MANUAL www.pole-barn.info www.apbbuildings.com TABLE OF CONTENTS 3. Jobsite Preparation 4. Setting Foundation Posts 5. Setting Corner Posts 6. Sidewall & Endwall Posts 7. Grade
More informationMoment-Resisting Connections In Laminated Veneer Lumber (LVL) Frames
Moment-Resisting Connections In Laminated Veneer Lumber (LVL) Frames Andy van Houtte Product Engineer-LVL Nelson Pine Industries Nelson, NZ Andy Buchanan Professor of Civil Engineering Peter Moss Associate
More informationExpressed Hardwood Structures
Expressed Hardwood Structures Introduction This guide provides ideas and design information to assist in the development of expressed native timber structures in buildings. Basic information on how to
More informationSecuAnch Roof Anchor System
Height Safety Products Email: marketing@fallprotec.com SecuAnch Roof Anchor System 1 Presentation The SecuAnch lifeline is designed to be permanently installed on buildings and other structures where maintenance
More informationInstallation Guide. Please read before installing SIPs Kit. 1 Method Statement for the erection of a SIPS Industries Kit Materials...
30a Renewable Chase Bibra Lake WA 6163 Tel: (08) 9494 2211 Fax: (08) 9494 2202 Email: info@sipsindustries.com.au Web: www.sipsindustries.com.au Installation Guide Please read before installing SIPs Kit.
More informationWood Roof Framing Common Design and Construction Defects Concurrent Session #5.3, Friday April 28, 2017, 9:45 AM-10:30 AM
Wood Roof Framing Common Design and Construction Defects Concurrent Session #5.3, Friday April 28, 2017, 9:45 AM-10:30 AM William J. Dery, PE Sr. Structural Engineer Outline 1. Wood Roof Framing 101 the
More informationbolts: G Cr-1/5Mo (A193 B7) 16 x M20 (EN ISO 4014) MPR GASKET 'SP' PETRO 4,0mm 363 x 323 x 4,5 mm (2 pieces)
test condition: 20 C 44 bar load condition 1: 206 C 18 bar load condition 2: 210 C 26 bar bolts: G41400 1Cr-1/5Mo (A193 B7) 16 x M20 (EN ISO 4014) gasket: MPR GASKET 'SP' PETRO 4,0mm 363 x 323 x 4,5 mm
More informationTechnical Data Sheet. Eurocode Compliant. T E C H N I C A L D A T A S H E E T Superprop. Mass 25 Mass 50 MAT 125 Superprop
Technical Data Sheet Eurocode Compliant Mass 25 Mass 50 MAT 125 Hydraulics Quickbridge MU Falsework MU Bridging Compact Bridging BarrierGuard 800 Instrumentation Mabey Hire Ltd. Structural Support & Bridging
More informationTensile strength of ASSY plus VG screws wood-wood (softwood)
Tensile strength of ASSY plus VG screws wood-wood (softwood) STRENGTHENS THE WOOD - INSTEAD OF SPLITTING IT 23.05.2017 Table of contents for tensile strength Determining the tensile strength - Table values
More informationPosi-Joist Installation Guide. A guide for storage, handling and installation of the MiTek Posi-Joist floor system
Posi-Joist Installation Guide A guide for storage, handling and installation of the MiTek Posi-Joist floor system Posi-Joist Installation Details A B C D F E A Masonry Wall Connection Details Blockwork
More informationAcceptable Standards of Domestic Construction
Truss or Rafter Roof Batten Triple grip fastener (for roof trusses) Foil lined Insulation blanket Top plate Sprocket Brick tie Top plate strapping at 1200mm max. cts. Note: Holding down straps should be
More informationAmerican Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/
American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO 80112 Phone: 303/792-9559 Fax: 303/792-0669 404.1. SCOPE STANDARD FOR RADIALLY REINFORCING CURVED GLUED LAMINATED
More informationMeva Guided Screens MGS Technical Instruction Manual
Meva Guided Screens MGS Technical Instruction Manual Product Characteristics: The MEVA Guided Screens (MGS) system encloses complete floors especially in high-rise construction independent of the height
More informationDYNAMIC PERFORMANCE EVALUATION OF BRACED SHEAR WALL WITH NEW BRACE FASTENER FOR WOODEN HOUSES
DYNAMIC PERFORMANCE EVALUATION OF BRACED SHEAR WALL WITH NEW BRACE FASTENER FOR WOODEN HOUSES Tomoki Furuta 1 and Masato Nakao 2 ABSTRACT: In Japanese Post and Beam construction wooden houses, diagonal
More informationBROCHURE COMPANY PRODUCTS AND SERVICES
BROCHURE COMPANY PRODUCTS AND SERVICES Manufacture and supply of NOVOTEXI 440 concealed-fix steel roof sheeting Manufacture and supply of rainwater goods and roofing accessories Manufacture Purpose made
More informationConnectors for Cold-Formed Steel Curtain-Wall Construction
The expiration date of this document has been extended until 2/3/3. Introducing Connectors for Cold-Formed Steel Curtain-Wall Construction Code Listed: IAPMO ES ER-238 (800) 999-5099 www.strongtie.com
More informationExperimental and numerical study of nailed laminated timber elements for in plane and transverse loading
Experimental and numerical study of nailed laminated timber elements for in plane and transverse loading Haller, Peer 1 SUMMARY Nailed laminated timber elements are used in housing construction for floor,
More informationReview of AISI Design Guide for Cold-formed Steel Purlin Roof Framing Systems-component Stiffness Method
Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2010) - 20th International Specialty Conference on Cold-Formed Steel Structures
More informationISO INTERNATIONAL STANDARD. Fasteners Torque/clamp force testing. Éléments de fixation Essais couple/tension. First edition
Provläsningsexemplar / Preview INTERNATIONAL STANDARD ISO 16047 First edition 2005-02-01 Fasteners Torque/clamp force testing Éléments de fixation Essais couple/tension Reference number ISO 16047:2005(E)
More informationInstruction Manual for installing
Instruction Manual for installing Preloaded (HSFG) Bolting with TurnaSure DIRECT TENSION INDICATORS TurnaSure LLC TABLE OF CONTENTS Introduction... 1 Theory of Preloaded Bolting Assemblies... 2 Tightening
More informationShinde Suyog Sudhakar, Galatage Abhijeet.A, Kulkarni Sumant.K, International Journal of Advance Research, Ideas and Innovations in Technology.
ISSN: 2454-132X Impact factor: 4.295 (Volume3, Issue5) Available online at www.ijariit.com Evaluating Seismic Efficiency of Combination of Bracing for Steel Building Suyog Sudhakar Shinde 1P. G. Student
More informationSeismic Performance of Brick Infill in RCC Structure
Seismic Performance of Brick Infill in RCC Structure Ms. Vaishnavi Battul, Mr. Rohit M. Shinde, Mr. Shivkumar Hallale, Ms. Tejashree Gulve Dr. D. Y. Patil Institute of Engineering, Management and Research,
More informationINSTALLATION INSTRUCTIONS for TB6.2,TB7.0, TB7.8 & TB8.4
the unique loft conversion & flooring system INSTALLATION INSTRUCTIONS for TB6.2,TB7.0, TB7.8 & TB8.4 Unit 6, Devizes Trade Centre, Hopton Park, Devizes, Wiltshire, SN10 2EH t 01380 739000 e info@telebeam.co.uk
More information1. Tile Roof Installation:!
1. Tile Roof Installation:! * Solar Roof Fan have a different base plate and ventilation opening size. This will require different measurements and allowances to those shown as pictures. Materials Needed:
More informationGlobal Roofing Solutions Klip-Lok 700
GRS Klip-Lok 700 Global Roofing Solutions Klip-Lok 700 www.globalroofs.co.za marketing@globalroofs.co.za GRS Klip-Lok 700 GRS Klip-Lok 700 09/18 Typical Specification Materials The roofing shall be Klip-Lok
More informationMetroll. Purlins & Girts. C Section Purlins. C Section Purlins are manufactured from Galvaspan steel and are roll formed into C Section.
C Section Purlins C Section Purlins are manufactured from Galvaspan steel and are roll formed into C Section. Metroll C Section Purlins are recommended for simple, non-continuous span construction. Structural
More informationPRODUCT EVALUATION Effective July 1, 2009 RC-204
TEXAS DEPARTMENT OF INSURANCE Engineering Services / MC 103-3A 333 Guadalupe Street P.O. Box 149104 Austin, Texas 78714-9104 Phone No. (512) 322-2212 Fax No. (512) 463-6693 PRODUCT EVALUATION Effective
More informationINFLUENCE OF PILES ON LOAD- SETTLEMENT BEHAVIOUR OF RAFT FOUNDATION
INFLUENCE OF PILES ON LOAD- SETTLEMENT BEHAVIOUR OF RAFT FOUNDATION BALESHWAR SINGH Department of Civil Engineering Indian Institute of Technology Guwahati Guwahati 78139, India NINGOMBAM THOIBA SINGH
More information