DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: IKO INDUSTRIES LIMITED
|
|
- Brianne Matthews
- 5 years ago
- Views:
Transcription
1 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) (562) ESR-3532 Reissued 01/2017 This report is subject to renewal 01/2019. DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: IKO INDUSTRIES LIMITED 40 HANSEN ROAD SOUTH BRAMPTON, ONTARIO L6W 3H4 CANADA EVALUATION SUBJECT: IKO THREE-TAB SHINGLES: MARATHON 20, MARATHON 25, MARATHON 25 AR AND MARATHON ULTRA AR; IKO LAMINATED SHINGLES: CAMBRIDGE, CAMBRIDGE HD, BILTMORE AR, CAMBRIDGE AR AND ARMOURSHAKE; ACCESSORIES: LEADING EDGE PLUS STARTER STRIP AND HIP & RIDGE Look for the trusted marks of Conformity! 2014 Recipient of Prestigious Western States Seismic Policy Council (WSSPC) Award in Excellence A Subsidiary of ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2016 ICC Evaluation Service, LLC. All rights reserved.
2 ICC-ES Evaluation Report ESR-3532 Reissued January 2017 This report is subject to renewal January (800) (562) A Subsidiary of the International Code Council DIVISION: THERMAL AND MOISTURE PROTECTION Section: Asphalt Shingles REPORT HOLDER: IKO INDUSTRIES LIMITED 40 HANSEN ROAD SOUTH BRAMPTON, ONTARIO L6W 3H4 CANADA (800) EXT EVALUATION SUBJECT: IKO THREE-TAB SHINGLES: MARATHON 20, MARATHON 25, MARATHON 25 AR, AND MARATHON ULTRA AR IKO LAMINATED SHINGLES: CAMBRIDGE, CAMBRIDGE HD, BILTMORE AR, CAMBRIDGE AR AND ARMOURSHAKE ACCESSORIES: LEADING EDGE PLUS STARTER STRIP AND HIP & RIDGE 1.0 EVALUATION SCOPE Compliance with the following codes: 2012 and 2009 International Building Code (IBC) 2012 and 2009 International Residential Code (IRC) Properties evaluated: Weather resistance Fire classification Wind resistance 2.0 USES The IKO asphalt shingles described in this report comply with IBC Section and IRC Section R905.2 and are Class A roof coverings when installed as described in this report. 3.0 DESCRIPTION 3.1 General: The products are available as three-tab shingles and as laminated shingles. See Table 1 for product names, overall dimensions, maximum exposure to the weather, location of nail line and classification per or ASTM D3161, as applicable. See Table 2 for accessory products. See Figures 1 and 2 for typical installation details. 3.2 Three-tab Shingles Marathon 20, Marathon 25, Marathon 25 AR and Marathon Ultra AR are three-tab shingles manufactured with a single fiberglass mat, coated on both sides with asphalt and surfaced with ceramic mineral granules. The shingles are self-sealing and have 0.24-inch-by-2.24-inch (6.1 mm by 56.9 mm) thermal sealing adhesive buttons spaced 1 inch (25 mm) apart and located at the centerline of the shingle, 6 5 / 8 inches (168 mm) up from the butt edge of the shingle. 3.3 Laminated Shingles: Cambridge, Cambridge HD, Biltmore AR, Cambridge AR, and Armourshake are laminated shingles manufactured with a double layer of fiberglass mat coated with asphalt on all sides and surfaced with mineral granules. The shingles are self-sealing with thermal sealing adhesive buttons located 1 inch (25.4 mm) above the shingle butt on the unexposed side of the shingle. (Exception: The self-sealing thermal adhesive for the Armourshake shingle is located on the back of the shingle.) 3.4 Accessory Shingles: Leading Edge Plus Starter Strips: These are factory-made shingles used under the first course of shingles being installed or applied on the roof. The shingles are perforated in the middle for separation into two starter pieces Hip and Ridge Shingles: Hip and Ridge is a single-layer fiberglass shingle impregnated with asphalt and having a mineral algae-resistant granular exposed surface. The shingles are scored for separation into four pieces. 3.5 Fasteners: Fasteners must comply with ASTM F1667 and must be minimum No. 12 gage [0.105-inch-diameter (2.67 mm) shank], 3 / 8-inch-diameter-head (9.5 mm), galvanized, stainless steel, aluminum or copper, barbed-, deformed-, or smooth-shank roofing nails. Fasteners must be of sufficient length to penetrate 3 / 4 inch (19.1 mm) into the sheathing, or through the sheathing, whichever is less. 3.6 Underlayment: Underlayment must comply with ASTM D226 Type I or Type II, ASTM D4869 Type I or Type II, or ASTM D6757. In areas where there has been a history of ice forming along the eaves causing a backup of water, an ice dam barrier in accordance with IBC Section or IRC Section R must be provided. 3.7 Asphalt Cement: Asphalt roofing cement used for hand-sealing the shingles must comply with ASTM D4586, Type I, Class I, or Type II, Class I. ICC-ES Evaluation Reports are not to be construed as representing aesthetics or any other attributes not specifically addressed, nor are they to be construed as an endorsement of the subject of the report or a recommendation for its use. There is no warranty by ICC Evaluation Service, LLC, express or implied, as to any finding or other matter in this report, or as to any product covered by the report. Copyright 2016 ICC Evaluation Service, LLC. All rights reserved. Page 1 of
3 ESR-3532 Most Widely Accepted and Trusted Page 2 of Installation: 4.1 New Construction: General: When installed on new construction in accordance with this section and the IKO Industries Limited installation instructions, the shingles are a Class A roof covering. The shingles, underlayment and flashings must be installed in accordance with IBC Section or IRC Section R905.2 except as noted in this report. The shingles must be installed over roof decks of codecomplying, minimum 3 / 8-inch-thick (9.5 mm) exterior-grade plywood; 7 / 16-inch-thick (11.1 mm) oriented strand board (OSB); or nominally 1-inch-by-6-inch lumber installed as solid sheathing conforming to IBC Sections and and underlayment specified in Section 3.6. Minimum roof slope must be 2:12 (16.7 percent). See Figures 1 and 2 for typical installation details. A starter course of Leading Edge Plus or shingles consisting of three-tab shingles, cut off at the top of the cut-out, is attached to the eave and rake edges using fasteners located 3 to 4 inches (76 to 102 mm) from the eave edge and spaced 1 inch (25.4 mm) and 12 inches (305 mm) from each end, for a total of four fasteners per shingle. The starter strip must overhang the eave and rake edges by a at least a nominal 1 / 4 inch. The first course of field shingles is then installed over the starter course. The shingles are located with vertical joints in three-tab shingles offset a minimum of one quarter of the tab width from adjacent courses; in laminated shingles the vertical joints must be offset a minimum of 4 inches (102 mm) Application: Fastening: Fasteners are as described in Section 3.5. For roof slopes of 2:12 to 21:12, each shingle is fastened to the roof deck using a minimum of four fasteners, spaced as shown in Figures 1 and 2. For roof slopes over 21:12, six fasteners are used, spaced as shown in Figures 1 and 2. Fasteners must be placed on the fastener line. Maximum exposure to the weather is 5 5 / 8 inches (143 mm) for three-tab shingles, and 5 3 / 4 inches (146 mm) for laminated shingles Shingle Sealing: In colder climates or wind regions where it is questionable whether the thermalsealing adhesive will activate and seal the shingles, the shingles must be hand-sealed. For three-tab shingles, each tab is sealed to the roof deck with a 1-inch-diameter (25.4 mm) spot of asphalt cement, placed at the center of the tab, 1 1 / 2 inches (38 mm) up from the bottom edge. For laminated shingles, three 1-inch-diameter (25.4 mm) spots are applied per shingle, spaced equally along a line 6 1 / 4 inches (159 mm) below the top edge of the previous course of shingles. Overlying shingles are sealed by having them embedded in the cement spots. For applications on slopes greater than 21:12, hand-sealing is required. Refer to the hand-sealing guidelines in the report holder s published installation instructions. The shingles must be hand-sealed to the satisfaction of the code official Hip and Ridge Shingles: Hip and ridge shingles are placed evenly over hips and ridges, and are fastened to the roof deck using two fasteners, one located on either side of the shingle, 6 1 / 8 inches (mm) from the exposed end and 1 inch (25.4 mm) up from the edge. Hip and ridge shingles are installed with a maximum 5 5 / 8-inch (143 mm) exposure to the weather. Hips and ridges for laminated shingle roofs may be double thickness Valleys: Valleys must be constructed as required by IBC Section or IRC Section R except as follows: Metal valley flashing used in open valleys must extend 12 inches (305 mm) from the centerline, each way. Underlayment placed directly under the valley flashing or beneath closed-cut valleys must be 36 inches wide (914 mm), and either minimum 50-pound-per-100-squarefoot (2.4 kg/m 2 ) felt underlayment or a membrane complying with ASTM D Reroofing: When installed over existing Class A or Class C asphalt shingle roofs in accordance with this section, the shingles described in this report are recognized as a Class A roof covering. The existing asphalt shingle roof covering must be inspected in accordance with the provisions and limitations of Section 1510 of the IBC or Section R907 of the IRC. Prior to the reroofing, hip and ridge covering must be removed. Except as noted in this section, the shingles must be installed in accordance with Section 4.1 of this report. Fasteners must be of sufficient length to penetrate 3 / 4 inch (19.1 mm) into the sheathing, or through the sheathing, whichever is less. Flashing and edging must comply, as applicable, with IBC Sections and and/or IRC Sections R907.5 and R CONDITIONS OF USE The IKO Industries Limited asphalt shingles described in this report comply with, or are suitable alternatives to what is specified in, those codes listed in Section 1.0 of this report, subject to the following conditions: 5.1 The products must be manufactured, identified, and installed in accordance with the applicable codes, this report, and the manufacturer s published installation instructions. In the event of a conflict between this report and the manufacturer s published installation instructions, this report governs. 5.2 Application must be in accordance with Section of this report. 5.3 The products are manufactured in Sumas, Washington, under a quality control program with inspections by ICC-ES. 6.0 EVIDENCE SUBMITTED 6.1 Data in accordance with ASTM D Reports of wind resistance testing in accordance with. 6.3 Reports of testing in accordance with FM 4475, including wind resistance testing in accordance with. 6.4 Reports of testing in accordance with ASTM E Quality documentation. 7.0 IDENTIFICATION Each bundle of shingles must bear a label with the name and address of the IKO manufacturing plant location; the product name; the roof classification (Class A); the installation instructions; the evaluation report number (ESR-3532); a reference to compliance with ASTM D3462, and,, or,, as applicable. Additionally, in accordance with ASTM D3462, each bundle of shingles must be marked with the area of roof surface covered and the style, type and color of the product.
4 ESR-3532 Most Widely Accepted and Trusted Page 3 of 5 TABLE 1 IKO SHINGLES AND PRODUCT DESCRIPTIONS TYPE PRODUCT NAME 2 [height width] DIMENSIONS Three-tab shingles Laminated shingles For SI: 1 inch = 25.4 mm MAXIMUM EXPOSURE LOCATION OF NAIL LINE 1 Marathon / 4 x 39 3 / / / 8 Marathon / 4 x 39 3 / / / 8 Marathon 25 AR 13 1 / 4 x 39 3 / / / 8 Marathon Ultra AR 13 1 / 4 x 39 3 / / / 8 Cambridge Biltmore AR 13 3 / 4 x 40 7 / / / 4 Cambridge HD 13 3 / 4 x 40 7 / / / 4 Cambridge AR 13 3 / 4 x 40 7 / / / 4 Armourshake 18 1 / 2 x 37 3 / / / 4 1 Nail line = distance from lowermost edge of shingle to target nail location. See Figures 1 and 2. 2 Products may have AR added to their product names to designate shingles produced with algae-resistant granules. CLASS TABLE 2 ACCESSORY PRODUCTS AND PRODUCT DESCRIPTIONS PRODUCT 1 DIMENSIONS [width x length] MAXIMUM EXPOSURE Leading Edge Plus Starter Strip 6 5 / 8 X 39 3 / 8 N/A Hip and Ridge 13 1 / 4 X 39 3 / / 8 For SI: 1 inch = 25.4 mm 1 Products may have AR added to their product names to designate shingles produced with algae-resistant granules.
5 ESR-3532 Most Widely Accepted and Trusted Page 4 of 5 DO NOT NAIL INTO OR ABOVE SEALING STRIP DO NOT NAIL INTO OR ABOVE SEALING STRIP FIGURE 1 THREE-TAB SHINGLES
6 ESR-3532 Most Widely Accepted and Trusted Page 5 of 5 OPEN VALLEY: A. Underlayment applied over entire deck. B. Valley Flashing: metal, minimum 28 gauge, minimum 24 width. C. Chalk Lines: 6 apart at the top and increasing in width 1 / 8 per foot towards the bottom. D. Shingle: cut a 2 triangle off the corner to direct water into the valley. E. Asphalt cement. FIGURE 2 LAMINATED SHINGLES
DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: GAF 1 CAMPUS DRIVE PARSIPPANY, NEW JERSEY 07054
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1475 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 07 00
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1717 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 07 00
More informationTECHNICAL BULLETIN NEW ICC ES EVALUATION REPORT
TECHNICAL BULLETIN NEW ICC ES EVALUATION REPORT [March 25, 2015] Malarkey recently received our new, updated ICC ES Evaluation Report (ESR 3150) which includes the additions of Windsor shingles and all
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: GAF EVALUATION SUBJECT:
0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-1475 Reissued 10/2017 Revised 12/12/2018 This report is subject to renewal 10/2019.
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: GAF 1 CAMPUS DRIVE PARSIPPANY, NEW JERSEY 07054
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3267 Reissued 12/2017 This report is subject to renewal 12/2019. DIVISION: 07 00
More informationES Report GAF-Elk Shingle Roof Covering Systems ESR-1475
ES Report GAF-Elk Shingle Roof Covering Systems ESR-1475 Product Evaluation Updated: 4/08 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer ESR-1475 Reissued April 1,
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: CERTAINTEED CORPORATION EVALUATION SUBJECT:
0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-3537 Reissued 06/2018 Revised 08/2018 This report is subject to renewal 06/2019.
More informationREPORT HOLDER: ISAIAH INDUSTRIES, INC. EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1360 Reissued 08/2018 This report is subject to renewal 08/2019. DIVISION: 07 00
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES SECTION: METAL ROOF PANELS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3564 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00
More informationICC-ES Evaluation Report Reissued September 1, 2012 This report is subject to renewal September 1, 2013.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1790 Reissued September 1, 2012 This report is subject to renewal September 1, 2013. A Subsidiary of the International Code Council
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ASPHALT SHINGLES REPORT HOLDER: CERTAINTEED CORPORATION
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1389 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 07 00
More informationESR-1129 Reissued June 1, 2011 This report is subject to renewal in two years.
ICC-ES Evaluation Report ESR-1129 Reissued June 1, 2011 This report is subject to renewal in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
More informationICC-ES Evaluation Report Issued February 1, 2011 This report is subject to re-examination in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-3098 Issued February 1, 2011 This report is subject to re-examination in one year. A Subsidiary of the International Code Council
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES SECTION: METAL ROOF TILES REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1754 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00
More informationDIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL SHINGLES SECTION: METAL ROOF TILES REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1754 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 07 00
More informationWOODSTART STARTER SHINGLE, STARTER STRIP PLUS, STARTER STRIP SHINGLE, AND TRI BUILT STARTER STRIP
UL Evaluation Report UL ER2453-02 Issued: April 5, 2017 Visit UL s On-Line Certifications Directory: www.ul.com/erdirectory for current status of Report. UL Category Code: ULEZ CSI MasterFormat DIVISION:
More informationPROJECT INSTRUCTIONS Roofing
PROJECT INSTRUCTIONS Roofing This handout outlines some basic regulations contained within the 2015 Minnesota State Building Code, as well as other good building practices. However, this handout is not
More informationICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.
ICC-ES Evaluation Report ESR-2648 Reissued June 1, 2010 This report is subject to re-examination in one year. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council
More informationREPORT HOLDER: JAACO CORPORATION NORTHEAST 68 TH STREET, SUITE C-130 REDMOND, WASHINGTON EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2961 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 05 00
More informationTrusted ICC ES PASLODE, Evaluation. report, or as to any. ICC-ES Evaluation
0 ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg Most Widely Accepted and Trusted ESR 3072 Reissued 09/2018 Revised 10/2018 This report is subject to renewal 09/2020.
More informationESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.
ICC-ES Evaluation Report ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
More informationCambridge English Application Instructions
Cambridge English Application Instructions ROOF SLOPE: Never apply asphalt shingles to roof slopes less than 2:12. For slopes 2:12 to 4:12 (LOW SLOPE), see special underlayment requirements outlined below.
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: ASTROTECH STEELS PRIVATE LIMITED
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3507 Reissued 03/2018 This report is subject to renewal 03/2020. DIVISION: 06 00
More informationA P P L I C A T I O N I N S T R U C T I O N S
1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: SCREW PRODUCTS, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3654 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 06 00
More informationROOFING City of Grand Rapids Building Safety Division
ROOFING City of Grand Rapids Building Safety Division 218-326-7601 www.cityofgrandrapidsmn.com This handout is intended only as a guide and is based in part on the 2015 Minnesota State Building Code, Grand
More informationJoint Evaluation Report
0 Joint Evaluation Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 ESR-2909 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 06 00 00 WOOD, PLASTICS AND COMPOSITES SECTION:
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: NAILS REPORT HOLDER: MiTek USA, INC.
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3768 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 06 00
More informationSG-30 A P P L I C A T I O N I N S T R U C T I O N S. Directions For Application
1 2 3 General Instructions NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE
More informationStormMaster Slate General Instructions 1.) GENERAL INSTRUCTIONS 2.) ROOF DECK VENTILATION 3.) ROOF DECK
StormMaster Slate General Instructions IMPORTANT: THE STATEMENTS EXPRESSED ON THIS PAGE ARE THE RECOMMENDATIONS FOR THE APPLICATION OF THE ROOFING PRODUCTS AS OUTLINED AND ILLUSTRATED. ANY DEVIATION FROM
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationDIRECTIONS FOR APPLICATION
Instructions 1 General NOTICE: THESE SHINGLES MUST BE APPLIED TO CONFORM WITH ALL APPLICABLE BUILDING CODES. THESE DIRECTIONS REPRESENT COMMON AND ACCEPTED ROOFING PRACTICES. DEVIATIONS FROM THESE DIRECTIONS
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 87 () 99 0 www.icc es.org ESR 9 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 WOOD, PLASTICS AND COMPOSITES
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC AND COMPOSITE FASTENINGS REPORT HOLDER: EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3201 Reissued 07/2018 This report is subject to renewal 07/2019. DIVISION: 06 00
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2442 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 06 00
More informationREPORT HOLDER: INTERCORP DBA OF U.S. NITTO 641 NORTH POPLAR ORANGE, CALIFORNIA EVALUATION SUBJECT: STRONG POINT SCREWS
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3528 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 05 00
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 2442 Reissued 0/208 This report is subject to renewal 0/209. DIVISION: 06 00 00 WOOD,
More informationB. Related Sections: The following Sections contain requirements that relate to this Section:
SECTION 07311 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: DEWALT EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3042 Reissued 09/2018 This report is subject to renewal 09/2019. DIVISION: 06 00
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationeco-shake INSTALLATION INSTRUCTION
1 eco-shake INSTALLATION INSTRUCTION NOTE: Shuffling the eco-shakes during installation may be necessary to obtain a uniform color throughout the roof. Due to the natural wood content in the ecoshakes,
More informationDIVISION: METALS SECTION: METAL FASTENINGS DIVISION: FINISHES SECTION: FASTENERS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1408 Reissued 12/2017 This report is subject to renewal 12/2018. DIVISION: 05 00
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC AND COMPOSITE FASTENINGS REPORT HOLDER: DEWALT
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3164 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 06 00
More informationESR-1271* Reissued September 1, 2013 This report is subject to renewal July 1, 2015.
ICC-ES Evaluation Report www.icc-es.org (800) 4-6587 (56) 699-054 ESR-7* Reissued September, 0 This report is subject to renewal July, 05. A Subsidiary of the International Code Council DIVISION: 05 00
More informationDIVISION: CONCRETE SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 6587 (562) 699 054 www.icc es.org ESR 279 Reissued 08/2018 This report is subject to renewal 08/2020. DIVISION: 0 00 00 CONCRETE
More informationREPORT HOLDER: SENCO BRANDS INC IVY POINTE BOULEVARD CINCINNATI, OHIO EVALUATION SUBJECT: SENCO SELF-DRILLING AND SELF-PIERCING SCREWS
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3558 Reissued 06/2017 This report is subject to renewal 06/2019. DIVISION: 05 00
More information1 Exam Prep NRCA Roofing Manual: Steep-Slope Roof Systems 2013 Tabs and Highlights
1 Exam Prep NRCA Roofing Manual: Steep-Slope Roof Systems 2013 Tabs and s These 1 Exam Prep Tabs are based on the National Roofing Contractors Association (NRCA) manual listed below: Steep-Slope Roof Systems
More information1.04 QUALITY ASSURANCE
SECTION 07312 ARCHITECTURAL ASPHALT SHINGLES PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
More informationREPORT HOLDER: SFS INTEC 1045 SPRING STREET WYOMISSING, PENNSYLVANIA EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3870 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 05 00
More informationESR-1799 Reissued April 2014 This report is subject to renewal June 1, 2015.
ICC-ES Evaluation Report www.icc-es.org (800) 42-6587 (562) 699-054 ESR-799 Reissued April 204 This report is subject to renewal June, 205. A Subsidiary of the International Code Council DIVISION: 0 00
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2761 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 06 00
More informationICC-ES Evaluation Report Reissued June 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 42-658 (562) 699-054 ESR-99* Reissued June, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION: 0 00
More informationHatteras Shingles. CertainTeed Shingle Applicator s Manual. YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles
CertainTeed Applicator s Manual Hatteras s 14 YOUR OBJECTIVE: To learn the correct procedures for installing Hatteras shingles HATTERAS SHINGLES Hatteras shingles are a premium oversize (18" x 36") roofing
More informationICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.
ICC-ES Evaluation Report www.icc-es.org (800) -6587 (56) 699-05 ESR-0 Reissued March, 0 This report is subject to renewal in two years. A Subsidiary of the International Code Council DIVISION: 06 00 00
More informationDIVISION: METALS SECTION: METAL FASTENINGS REPORT HOLDER: ELCO CONSTRUCTION PRODUCTS 1032 KERR DRIVE DECORAH, IOWA 52101
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-87 (2) 99-043 www.icc-es.org ESR-3332 Reissued 09/207 This report is subject to renewal 09/208. DIVISION: 0 00 00 METALS
More informationStormMaster Shake GENERAL INSTRUCTIONS For Spanish Instructions Click Here (Para las Instrucciones Españolas Haga Clic Aquí)
StormMaster Shake GENERAL INSTRUCTIONS For Spanish Instructions Click Here (Para las Instrucciones Españolas Haga Clic Aquí) IMPORTANT: THE STATEMENTS EXPRESSED ON THIS PAGE ARE THE RECOMMENDATIONS FOR
More information3-Tab Shingle Instructions DURA-SEAL 20 DURA-SEAL 25
3-Tab Shingle Instructions DURA-SEAL 20 DURA-SEAL 25 1 Directions For Applying Malarkey 3-Tab Shingles GENERAL INSTRUCTIONS Install Malarkey 3-tab shingles according to building code and local amendments.
More informationESR-1799 Reissued June 1, 2009 This report is subject to re-examination in one year.
ICC-ES Evaluation Report ESR-799 Reissued June, 009 This report is subject to re-examination in one year. www.icc-es.org (800) -87 () 99-0 A Subsidiary of the International Code Council DIVISION: 0CONCRETE
More informationRED DIAMOND SHINGLES Roof Installation Introduction:
RED DIAMOND SHINGLES Roof Installation Introduction: The guidelines set forth in this manual are intended for use with the application of Red Diamond shingles. Wallaba specie (Eperua Falcata) shingles
More informationTurada Hardwood Shingles and Shakes Installation instructions
1. General 1.1 Maximum Exposure: Maximum exposure for wood shingles and shakes shall comply with Table 1 herein, unless specifically specified in the roof assemblies Product Approval. 1.2 Solid and Spaced
More informationSECTION ASPHALT SHINGLES
SECTION 073110 - ASPHALT SHINGLES PART 1 - GENERAL 1.1 SUMMARY A. This Section includes the following: 1. Asphalt shingles. 2. Felt underlayment. 3. Self-adhering sheet underlayment. 4. Ice Shield Underlayment
More informationGlassMaster General Instructions - Ardmore, OK & Hampton, GA <br /> Atlas Roofing
GlassMaster General Instructions - Ardmore, OK & Hampton, GA (For Metric Size Franklin, OH Instructions Click Here) IMPORTANT: THE STATEMENTS EXPRESSED ON THIS WRAPPER ARE THE RECOMMENDATIONS FOR THE APPLICATION
More informationThe proposal includes the replacement of the roof on the entire house (historic massing and later additions) and detached garage.
The proposal includes the replacement of the roof on the entire house (historic massing and later additions) and detached garage. LANDMARK SERIES DESIGNER ROOFING SHINGLES Landmark, shown in Silver
More informationF-WAVE REVIA SYNTHETIC ROOFING SHINGLES
F-WAVE REVIA SYNTHETIC ROOFING SHINGLES Installation Manual for Steep-Slope Residential Installations For support with all other Steep-Slope Installations, please call F-Wave Technical Support at 888-GO-FWAVE.
More informationSECTION SLATE SHINGLES. 1.1 SUMMARY A. Section Includes: 1. Slate shingles over underlayment nailed to roof sheathing.
SECTION 07 31 26 SLATE SHINGLES SPEC WRITER NOTES: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Slate shingles
More informationROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION
ROOFING APPLICATION STANDARD (RAS) No. 130 INSTALLATION CRITERIA FOR WOOD SHINGLES AND SHAKES APPLICATION 1. 2. 3. Scope 1.1 This application standard provides the minimum installation criteria for wood
More informationA201 3 PROPOSED SOUTH ELEVATION SCALE: PROPOSED EAST ELEVATION SCALE: EXISTING EAST ELEVATION EXISTING SOUTH ELEVATION WEST WORKSHOP
WEST WORKSHOP Residential Designer Kurt West P: 202-957-0933 E: kurt@westworkshop.com NOTE: INSTALL NEW ROOFING -REPLACE ALUM DRIP EDGES -REPLACE ICE/WATER SHIELD AT EAVES AND VALLEYS -INSTALL SYNTHETIC
More informationSECTION PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY
SECTION 07312 PVC THATCH SHINGLE ROOFING SYSTEM PART 1 GENERAL 1.01 SUMMARY A. This Section Includes the following: 1. Endureed Dominica PVC thatch shingles. 2. Self- adhering sheet underlayment. B. Related
More informationNEMO etc. Certificate of Authorization # Christian Street, Unit #13 Oxford, CT (203)
Certificate of Authorization #32455 353 Christian Street, Unit #13 Oxford, CT 06478 (203) 262-9245 ENGINEER EVALUATE TEST CONSULT CERTIFY CertainTeed Corporation 20 Moores Road Malvern, PA 19355 (610)
More informationTimberline and Sovereign Expanded Fastener Placement Area
Timberline and Sovereign Expanded Fastener Placement Area Information Sheet Updated: 2004 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer Less Fastening Hassles! Announcing
More informationROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION
ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive
More informationROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION
ROOFING APPLICATION STANDARD (RAS) No. 115 STANDARD PROCEDURES FOR ASPHALTIC SHINGLE INSTALLATION 1. Scope 4. Underlayment 2. 1.1 This roofing application standard has been developed to provide a responsive
More informationROOFING APPLICATION STANDARD (RAS) No. 130
ROOFING APPLICATION STANDARD (RAS) No. 130 1. Scope 1.1 This application Standard provides the minimum installation criteria for wood shingles and shakes. 2. Definitions 2.1 For definitions of terms used
More informationICC-ES Evaluation Report
ICC-ES Evaluation Report ESR-6 Reissued April, 009 This report is subject to re-examination in two years. www.icc-es.org (800) 4-6587 (56) 699-054 A Subsidiary of the International Code Council DIVISION:
More informationSTORMMASTER SHAKE GENERAL INSTRUCTIONS
STORMMASTER SHAKE GENERAL INSTRUCTIONS IMPORTANT: THE STATEMENTS EXPRESSED ON THIS PAGE ARE THE RECOMMENDATIONS FOR THE APPLICATION OF THE ROOFING PRODUCTS AS OUTLINED AND ILLUSTRATED. ANY DEVIATION FROM
More informationESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013.
ICC-ES Evaluation Report ESR-2024* Reissued September, 20 This report is subject to renewal September, 20. www.icc-es.org (800) 42-68 (62) 699-04 A Subsidiary of the International Code Council DIVISION:
More informationREPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI SELF-DRILLING AND SELF-PIERCING SCREWS
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2196 Reissued 10/2017 This report is subject to renewal 10/2019. DIVISION: 05 00
More informationHip & Ridge Shingles Installation Instructions
Hip & Ridge Shingles Installation Instructions WWW.MALARKEYROOFING.COM Directions for Applying Malarkey Hip & Ridge Shingles MALARKEY HIP AND RIDGE SHINGLE SPECIFICATIONS Malarkey Roofing Products manufacture
More informationSECTION WOOD SHINGLES
SECTION 07 31 29.13 WOOD SHINGLES SPEC WRITER NOTES: 1. Delete text between // // not applicable to project. Edit remaining text to suit project. 2. This guide specification does not include requirements
More informationSECTION ASPHALT SHINGLES
(Specifier Note: The purpose of this guide specification is to assist the specifier in correctly specifying glass-fiber-reinforced asphalt shingle products for sloped roofing applications. The specifier
More informationCapstone Application Instructions
Capstone Application Instructions Information Sheet Updated: 2007 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer L IFETIME D ESIGNER S HINGLES APPLICATION INSTRUCTIONS
More informationESR-3042* Reissued August 1, 2012 This report is subject to renewal September 1, 2014.
ICC-ES Evaluation Report www.icc-es.org (800) -687 (6) 699-0 ESR-0* Reissued August, 0 This report is subject to renewal September, 0. A Subsidiary of the International Code Council DIVISION: 06 00 00
More informationICC-ES Evaluation Report
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-2608 Reissued January 2016 This report is subject to renewal January 2017. A Subsidiary of the International Code Council DIVISION:
More informationC e r t a i n T e e d S h i n g l e A p p l i c a t o r s M a n u a l. and Carriage House STEEP. Slope Application. (over 21/12)
C e r t a i n T e e d S h i n g l e A p p l i c a t o r s M a n u a l Grand Manor 16 and Carriage House YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products. These shingles
More informationPREMIUM LAMINATED ASPHALT SHINGLES Dallas, TX Tuscaloosa, AL Phillipsburg, KS
Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: OMG, INC.
0 ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org Most Widely Accepted and Trusted ESR-1078 Reissued 01/2018 Revised 09/2018 This report is subject to renewal 01/2019 DIVISION:
More informationRESIDENTIAL ROOFS ADDENDUM NUMBER ONE. August 28, 2017
RESIDENTIAL ADDENDUM NUMBER ONE August 28, 2017 The following additions to, deletions from, and clarifications of the Contract Documents govern insofar as they apply and shall take precedence over those
More informationESR-1254 * DELETED BY CITY OF LOS ANGELES. Reissued April 1, 2006 This report is subject to re-examination in one year.
ESR-1254 Reissued April 1, 2006 This report is subject to re-examination in one year. www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional
More informationREPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:
0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2024 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 03 00
More informationPREMIUM LAMINATED ASPHALT SHINGLES Frederick, MD
Application Instructions for FORMERLY 50 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationOAKRIDGE R SUPER TM Shingles Installation Instructions
Shingles Installation Instructions CAUTION DO NOT REMOVE THE RELEASE TAPE The release tape on the top of the OAKRIDGE SUPER TM is designed to prevent adhesion between the shingles, so please do not remove
More informationMIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
More informationHERITAGE LAMINATED ASPHALT SHINGLES Frederick, MD
Application Instructions for FORMERLY 30 THESE ARE THE MANUFACTURER S APPLICATION INSTRUCTIONS FOR THE ROOFING CONDITIONS DESCRIBED. TAMKO BUILDING PRODUCTS, INC. ASSUMES NO RESPONSIBILITY FOR LEAKS OR
More informationTrusted ICC ES. Issued 06/2018 HILTI, INC. Evaluation. report, or as to any. ICC-ES Evaluation
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg ESR 4185 Issued 06/2018 This report is subject to renewal 06/2019. SECTION: 05 05 23
More informationDIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: OMG, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1078 Reissued 01/2018 This report is subject to renewal 01/2019. DIVISION: 06 00
More informationROYAL ESTATE LIMITED LIFETIME ARCHITECTURAL SHINGLES
ROYAL ESTATE LIMITED LIFETIME ARCHITECTURAL SHINGLES Royal Estate 130 mph (210 km/h) 1,2 1 See Limited Warranty for complete terms, conditions, restrictions and application requirements. 2 High Wind Application
More informationGrand Manor Carriage House and Centennial Slate 16 YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products.
CertainTeed Shingle Applicator s Manual Grand Manor Carriage House and Centennial Slate 16 YOUR OBJECTIVE: To learn the correct method of installing each of these roofing products. 90 STEEP Slope Application
More informationARMORTAB R SUPER TM Shingles Installation Instructions
ARMORTAB R SUPER Shingles Installation Instructions ARMORTAB SUPER DO NOT REMOVE THE RELEASE TAPE The release tape on the top of the ARMORTAB SUPER is designed to prevent adhesion between the shingles,
More informationROYAL ESTATE LIMITED LIFETIME ARCHITECTURAL SHINGLES
ROYAL ESTATE LIMITED LIFETIME ARCHITECTURAL SHINGLES Royal Estate 130 mph (210 km/h) 1,2 1 See Limited Warranty for complete terms, conditions, restrictions and application requirements. 2 High Wind Application
More information