Transformer Measurement & Verification Report

Size: px
Start display at page:

Download "Transformer Measurement & Verification Report"

Transcription

1 Transformer Measurement & Verification Report Delaware Legislative Mall Prepared for: Rick Howard, P.E., LEED AP Project Development Manager Powersmiths International Corp.

2 M&V Methodology ECM Technology Category Transformer Retrofits Parameter Type Project Phase Parameter Transformer Loading, Performance Losses & Efficiency Annual operating Operational hours & times Baseline Post-Installation One-time measurement of representative transformer loading, losses & efficiencies One-time measurement of representative transformer loading, losses & efficiencies Based on interview data Same as baseline Approach for Establishing Baseline Powersmiths used the steps listed below to establish the baseline. 1. Develop the baseline transformer inventory, as shown in the Appendix 1, based upon on-site audit. 2. Determine the baseline and proposed loading, losses and efficiency based on actual testing data and a cross section of manufacturers data. These losses and efficiencies are detailed in the Transformer Findings section. 3. Establish the hours of operation through interviews with facility owners and personnel. 4. Develop a spreadsheet model of the transformers with the above information and the current electric rate schedule. 5. Measure the baseline loading, losses and efficiencies prior to construction and adjust, if needed, as proposed in step 6 below. Post-Installation M&V Activities Powersmiths used the steps listed below to establish the post-installation performance for this ECM. 1. Develop the post-installation Measurement & Verification data based upon on-site audit. 2. Determine the post-installation loading, losses and efficiency based on actual testing data. These loading, losses and efficiencies are detailed in the Transformer Findings section. 3. Use the same hours of operation as baseline. 4. Develop a spreadsheet model of the transformers with the above information and the current electric rate schedule. 5. Measure the post-installation loading, losses and efficiencies following construction and adjust, if needed, as proposed in step 6 below. 6. Powersmiths measured the retrofitted transformers in the same locations that were measured during the baseline sampling. Page 2 of 20

3 Transformer Measurements & Findings On January 26th 2011 baseline measurements were taken on five (5) existing transformers at various locations throughout the Delaware Legislative Mall Complex. The measured loading, efficiency and losses of the replacement Powersmiths E-Saver-C3L transformers were measured on December 5th 2012 and compared to the old transformers (see tables below for each transformer). Measurements were taken using the Cyberhawk EP-300 portable meter; see Appendix 1 for information regarding the Cyberhawk meter capabilities and setup. Figure 1: Square D 225T3HB Transformer Figure 2: Powersmiths E-Saver-C3L-A Transformer End User Location Tag Number Manufacturer Model Nominal kva Biggs Museum Basement 5007 Square D Powersmiths 225T3HB E-Saver-C3L-A Measurement Period (HH:MM) Sampling Interval 0:14 1 Minute Parameter % Loading (kva) - Average % Efficiency - Average Losses (kw) - Average Reduction in Avg Losses Average Energy Lost per Year (kwh) Average Annual Savings (kwh) Square D 10.6% 91.6% Representative Output Voltage THD (%) Representative Output Current THD (%) 17, % 12.5% Calculated Powersmiths 10.6% 97.8% % 4,319 13, % 24.3% Page 3 of 20

4 Page 4 of 20

5 Page 5 of 20

6 Figure 3: Square D 75T23H Transformer Figure 4: Powersmiths E-Saver-C3L-A Transformer End User Location Tag Number Manufacturer Model Nominal kva Public Archives Room Square D Powersmiths 75T3H E-Saver-C3L-A Measurement Period (HH:MM) Sampling Interval 0:14 1 Minute 0:14 1 Minute Parameter % Loading (kva) - Average % Efficiency - Average Losses (kw) - Average Square D 0.2% 16.8% Powersmiths 0.2% 33.7% Reduction in Avg Losses Average Energy Lost per Year (kwh) 60.6% 4,739 Average Annual Savings (kwh) 1,866 2,873 Representative Output Voltage THD (%) 3.3% 2.4% Representative Output Current THD (%) 60.9% 52.5% Page 6 of 20

7 Page 7 of 20

8 Page 8 of 20

9 Figure 5: Square D 75T3H Transformer Figure 6: Powersmiths E-Saver-C3L-A Transformer End User Location Tag Number Manufacturer Model Nominal kva Townsend Building 1st Floor Storage - Elec Room 5021 Square D Powersmiths 75T3H E-Saver-C3L-A Measurement Period (HH:MM) Sampling Interval 0:14 1 Minute 0:14 1 Minute Parameter % Loading (kva) - Average % Efficiency - Average Losses (kw) - Average Square D 9.1% 88.5% Powersmiths 11.6% 98.0% Reduction in Avg Losses Average Energy Lost per Year (kwh) 79.7% 7,569 Average Annual Savings (kwh) 1,533 6,036 Representative Output Voltage THD (%) 2.7% 2.1% Representative Output Current THD (%) 24.0% 23.0% Page 9 of 20

10 Page 10 of 20

11 Page 11 of 20

12 Figure 7: Powerformer Transformer End User Location Tag Number Manufacturer Model Nominal kva Figure 8: Powersmiths E-Saver-C3L-A Transformer Townsend Building 1st Floor Storage - Elec Room 5022 Powerformer Powersmiths E-Saver-C3L-A :14 1 Minute 0:14 1 Minute Powerformer 21.4% 97.4% Powersmiths 12.6% 98.1% Measurement Period (HH:MM) Sampling Interval Parameter % Loading (kva) - Average % Efficiency - Average Losses (kw) - Average Reduction in Avg Losses Average Energy Lost per Year (kwh) 55.6% 3,653 Average Annual Savings (kwh) 1,621 2,032 Representative Output Voltage THD (%) 2.4% 2.0% Representative Output Current THD (%) 15.7% 29.7% Page 12 of 20

13 Page 13 of 20

14 Page 14 of 20

15 Figure 9: Heavi-Duty T2B Series A Transformer End User Location Tag Number Manufacturer Model Nominal kva Figure 10: Powersmiths E-Saver-C3L-A Transformer Townsend Building 3rd Floor Middle Elec Room 5027 Heavi-Duty Powersmiths T2B Series A E-Saver-C3L-A Measurement Period (HH:MM) Sampling Interval Parameter % Loading (kva) - Average % Efficiency - Average Losses (kw) - Average 0:14 1 Minute 0:14 1 Minute Heavi-Duty 21.9% 96.5% Powersmiths 15.6% 98.5% Reduction in Avg Losses Average Energy Lost per Year (kwh) 70.6% 5,028 Average Annual Savings (kwh) 1,480 3,548 Representative Output Voltage THD (%) 2.3% 2.1% Representative Output Current THD (%) 24.0% 16.0% Page 15 of 20

16 Page 16 of 20

17 Page 17 of 20

18 Conclusions Reduction in Average Losses with Powersmiths E-Saver-C3 Transformer: 68.5% on average. Replacement of the existing transformers with Powersmiths E-Saver-C3 transformers will pay for themselves many times over during the decades of expected service life. Excessive voltage distortion can impact the operating reliability of connected equipment. However, the voltage distortion levels measured are below the IEEE recommended limit of 5% for general purpose and electronic equipment loads. Current THD levels are greater than 5% and therefore general purpose transformers would not be UL listed for this application. Powersmiths E-Saver Transformers carry the required K rating to supply the measured load profile. Upgrading to Powersmiths transformers provides significant environmental benefits. Reduced transformer losses result in reductions in greenhouse gas emissions and carbon footprint due to reductions in fossil-fuel consumption at the power-generating station feeding transformer losses. See the complete description of Powersmiths E-Saver-C3 transformer benefits in Appendix 2 Page 18 of 20

19 Appendix 1 Cyberhawk Portable Meter Cyberhawk Portable is a practical instrument for the field measurement of energy efficiency and power quality. With the unique capability of SIMULTANEOUSLY measuring up to three 3phase ports, Cyberhawk Portable can be used to quantify losses and efficiency of transformers, UPS s and other multiport devices with near revenue class accuracy. TYPICAL TRANSFORMER SET-UP A Typical hookup configuration to the input and output of the transformer is illustrated in the figure below, which uses the 2Wattmeter method on the input and the 3-Wattmeter method on the output Page 19 of 20

20 Appendix 2 Powersmiths E-Saver-C3 Transformer Benefits The E-Saver-C3 transformer is the ideal transformer for government environments where energy efficiency is a priority. The E-Saver-C3 is a practical and affordable solution for buildings where lowest life-cycle cost and energy savings are a priority. Characteristics The E-Saver-C3 sets new benchmarks for environmental protection, energy efficiency and reliability. Designed to provide the lowest life cycle cost, the E-Saver-C3 goes beyond US DOE Candidate Level 3 efficiency ensuring lower operating losses than standard off-the-shelf transformers. To provide superior performance and reduce environmental impact, the E-Saver-C3 comes with a superior Nomex based insulation system impregnated with an organic epoxy adhesive. Custom Design E-Saver-C3 transformers are designed and manufactured to match the footprint and terminal configuration of the existing transformers. Custom design and manufacturing allows for faster installation and lower installation costs. Quiet Operation Educational environments can be degraded or disrupted when noisy transformers are located close to people. To meet this challenge, the E-Saver-C3 has embedded structural and acoustic treatments that combine to reduce ambient noise generated by the transformer. To ensure quiet operation, noise tests are part of our ISO 9001 procedures for every transformer. Environmental The E-Saver-C3 is built in an ISO 9001 (quality management) and ISO (environmental management) certified facility. Throughout the manufacturing process, Powersmiths takes steps to ensure that waste is eliminated and hazardous materials are avoided. Because Powersmiths transformers generate lower losses, they reduce power drawn from generating stations resulting in less smog and lower greenhouse gas emissions. Testing E-Saver-C3 transformers are subjected to rigorous testing to ensure efficiency under various load profiles and loading conditions, quiet operation, and insulation integrity and production tests with actual computer power loading. Powersmiths' test facility has been certified to ISO for efficiency testing by Canadian Standards Association International (CSA). Warranty The E-Saver-C3 s long life and dependable performance is backed up by Powersmiths industry leading 25 year pro-rated warranty. Page 20 of 20

Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems

Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems Alternative Designs to Support Electronic Loads in Extensive UPS Distribution Systems Philip J.A. Ling, P.Eng. Powersmiths International Corp. Toronto, Canada M1H 2X1 philip.ling@powersmiths.com Cyril

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Power-Sure 700. Technical Data TD158001EN. Contents

Power-Sure 700. Technical Data TD158001EN. Contents Technical Data TD158001EN Power-Sure 700 Supersedes August 2015 Contents Description Page General description... 2 Power-Sure 700 benefits.... 2 Specifications... 3 Industry standards and certifications...

More information

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads

Fluke 345. Power Quality Clamp Meter. The ideal meter for commissioning and troubleshooting modern electrical loads Fluke 345 Power Quality Clamp Meter Technical Data The ideal meter for commissioning and troubleshooting modern electrical loads With a bright color display to analyze the harmonic spectrum, a low-pass

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005

ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005 ASSOCIATION OF ENERGY ENGINEERS NORTHERN OHIO CHAPTER APRIL 21, 2005 Two Types of Electrical Loads Linear Non-Linear INCANDESCENT LIGHTING COMPUTERS INDUCTION MOTORS VARIABLE FREQUENCY DRIVES FLUORESCENT

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

5 kva Isolation Transformer - 115V Primary Voltage - 230V Secondary Voltage - Single Phase - NEMA 3R

5 kva Isolation Transformer - 115V Primary Voltage - 230V Secondary Voltage - Single Phase - NEMA 3R 5 kva Isolation Transformer - 115V Primary Voltage - 230V Secondary Voltage - Single Phase - NEMA 3R Part #: MT-ISX-FP-1P-115V-5KVA-230V-N3R Page: 1 The MT-ISX-FP-1P-115V-5KVA-230V-N3R 115V 1 Phase Energy

More information

Standby Power. Primer

Standby Power. Primer Standby Power Primer Primer Table of Contents What is Standby Power?...3 Why is Standby Power Important?...3 How to Measure Standby Power...4 Requirements for a Measurement...4 Standby Measurement Challenges...4

More information

European producers of glass beads for industrial products are aware of their impact on climate change.

European producers of glass beads for industrial products are aware of their impact on climate change. European producers of glass beads for industrial products are aware of their impact on climate change. Exploring the possibilities of reducing CO2 emission and improving energy efficiency, Euroadbead (see

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

SF6 Gas Management Australia

SF6 Gas Management Australia Dr B. Alexander; ABB Australia Pty Limited, Moorebank, Australia SF6 Gas Management Australia May 3, 2012 Slide 1 SF 6 Presentation Overview Clean Energy Future Legislation Power industry problem Significance

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

New power tools provide quality and efficiency By

New power tools provide quality and efficiency By Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment

More information

Programmable Grid Simulator THE POWER TEST EXPERTS

Programmable Grid Simulator THE POWER TEST EXPERTS PAS-F Series 45kVA to 1.6MVA Programmable Grid Simulator THE POWER TEST EXPERTS PAS-F Series 45kVA to 1.6MVA Product Overview The PAS-F Series is a broad line of programmable three phase output regenerative

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

15 kva Isolation Transformer - Single Phase - 208V Primary - 120/240V Secondary - NEMA 3R

15 kva Isolation Transformer - Single Phase - 208V Primary - 120/240V Secondary - NEMA 3R 15 kva Isolation Transformer Single Phase 208V Primary 120/240V Secondary NEMA 3R Part #: MT20815KVA240.120 Page: 1 The MT20815KVA240.120 208V 1 Phase Energy Efficient Isolation Transformer from Larson

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power

More information

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner conditioning products Electronic voltage regulator -Sure 700 & 800 -Suppress T7 & 100 Harmonic correction unit Sag ride-through power conditioner The power to work Basics of power quality The partner you

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information

Technical Series Edition 5

Technical Series Edition 5 Totally Integrated Power Technical Series Edition 5 Load Impact in the Feed-in Circuit on Life Cycle Energy Costs Answers for infrastructure. Contents Introduction 4 Power Loss Calculation 5 Determining

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS.

3/29/2012 MAIN TOPICS DISCUSSED ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K ELECTRIC RATES POWER COMPUTATION FORMULAS. MAIN TOPICS DISCUSSED Electric Rates Electrical system utilization ELECTRICAL SYSTEMS AND ELECTRIC ENERGY MANAGEMENT SECTION K Power quality Harmonics Power factor (Cos phi) improvement Section K - 2 ELECTRIC

More information

ENA33LCD. Power line analyzer. User and service manual. Obrezija 5 SI-1411 Izlake

ENA33LCD. Power line analyzer. User and service manual.   Obrezija 5 SI-1411 Izlake ENA33LCD Power line analyzer User and service manual version 2.9 (FW version 6.8 and newer) ETI, d.o.o. Obrezija 5 SI-1411 Izlake www.etigroup.eu/products-services 1. Front control panel and terminal plate

More information

Strategies for design 600V large modular UPS for critical power applications

Strategies for design 600V large modular UPS for critical power applications White Paper Markets Served Data centers Strategies for design 600V large modular UPS for critical power applications Executive summary Today s transformerless UPS systems are significantly smaller and

More information

BRIDGEABLE FOUR-CHANNEL POWER AMPLIFIER GM-A6604 GM-A4604. Owner s Manual

BRIDGEABLE FOUR-CHANNEL POWER AMPLIFIER GM-A6604 GM-A4604. Owner s Manual BRIDGEABLE FOUR-CHANNEL POWER AMPLIFIER GM-A6604 GM-A4604 Owner s Manual Section 01 Before you start Thank you for purchasing this PIONEER product To ensure proper use, please read through this manual

More information

PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer

PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer PowerFlex Medium Voltage Drives with Direct-to-Drive Technology Eliminating the Isolation Transformer Transformerless drives help industry reduce the cost of motor control while using standard motors.

More information

Hazardous area LED lighting Pauluhn Summit linear LED luminaires. Pauluhn Summit. Linear, high bay LED luminaires designed for hazardous areas

Hazardous area LED lighting Pauluhn Summit linear LED luminaires. Pauluhn Summit. Linear, high bay LED luminaires designed for hazardous areas Hazardous area lighting Pauluhn linear luminaires Pauluhn Linear, high bay luminaires designed for hazardous areas Pauluhn Safe. Reliable. Efficient. Featuring the industry's broadest range of luminaires

More information

Fluke Fluke-Direct.ca. Three-Phase Power Logger. Technical Data

Fluke Fluke-Direct.ca. Three-Phase Power Logger. Technical Data Fluke 1735 Three-Phase Power Logger Technical Data Electrical load studies, energy consumption testing, and general power quality logging The Fluke 1735 Three-Phase Power Logger is the ideal electrician

More information

General Description & Features Selection Charts Definition of Terms... 42

General Description & Features Selection Charts Definition of Terms... 42 SECTION NON-LINEAR LOAD ISOLATION TRANSFORMERS Special winding techniques minimize eddy current losses. A double sized neutral handles excessive neutral currents. UL Listed for K Factor Loads 4, 1 & 20.

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi Features Special relay for alternating loads, for applications with pumps, compressors, air conditioning or refrigeration units 2 independent NO output, 12 A 4 functions 2 independent control signals,

More information

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM

ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM ENERGY SAVINGS THROUGH POWER CONDITIONING WITH THE PowerGUARD SYSTEM Abstract Efficient operation of the electrical system of any facility is essential to controlling operational costs while maximizing

More information

BFM136 THE PERFECT SOLUTION FOR MULTI-CIRCUIT, MULTI-CLIENT METERING

BFM136 THE PERFECT SOLUTION FOR MULTI-CIRCUIT, MULTI-CLIENT METERING BFM136 BRANCH FEEDER MONITOR THE PERFECT SOLUTION FOR MULTI-CIRCUIT, MULTI-CLIENT METERING Multi-client billing Multi-circuit energy reading Built-in communication platforms Time-of-Use (TOU) metering

More information

B9000 FXS kVA B9600 FXS kVA

B9000 FXS kVA B9600 FXS kVA OF CONTINUOUS SERVICE YEARS WARRANTY B9000 FXS 60-300kVA B9600 FXS 400-800kVA BORRI B9000 FXS B9600 FXS With disturbances to the electrical supply being one of the major causes of IT downtime, the UPS

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated

Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Premium 30 Energy Efficient, Low Voltage Transformers General Purpose, Harmonic Mitigating, and K-Rated Catalog 7400CT1001 2010 Class 7400 CONTENTS Description.............................................

More information

Category: ELECTRICITY Requirement: EL-ENG Page: 1 of 13. Document(s): S-E-01, S-E-04 Issue Date: Effective Date:

Category: ELECTRICITY Requirement: EL-ENG Page: 1 of 13. Document(s): S-E-01, S-E-04 Issue Date: Effective Date: Requirements for Certification Category: ELECTRICITY Requirement: EL-ENG-11-02 Page: 1 of 13 Requirements for Certification and Use of Portable Measuring Apparatus for Reverification and Dispute Meter

More information

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics Power Quality Monitor Individual Harmonics measurement upto 56th Harmonics True representation of Voltage & Current waveforms. Phasor Representation of All 3 phases for system analysis Real Time Clock

More information

Technical data ESA614 Electrical Safety Analyzer

Technical data ESA614 Electrical Safety Analyzer Technical data ESA614 Electrical Safety Analyzer The ESA614 Electrical Safety Analyzer brings fast and simple automated testing in the form of a portable analyzer to healthcare technology professionals

More information

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits CS 36 HOSP 14 36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the

More information

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,

More information

Submerged Arc Welding Equipment

Submerged Arc Welding Equipment Submerged Arc Welding Equipment Miller Submerged Arc Solutions Built for you to build with you. Miller develops high-quality, reliable welding solutions that deliver exceptional performance for our customers.

More information

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection

More information

10 kva Transformer - 480V Primary Voltage - 208V Secondary Voltage - Single Phase - NEMA 3R

10 kva Transformer - 480V Primary Voltage - 208V Secondary Voltage - Single Phase - NEMA 3R 10 kva Transformer 480V Primary Voltage 208V Secondary Voltage Single Phase NEMA 3R Part #: MTATX1P480V10KVA208VN3R Page: 1 The MTATX1P480V10KVA208VN3R 480V 1 Phase Energy Efficient Encapsulated Transformer

More information

Improving Safety Culture and Systems at Americas Ports

Improving Safety Culture and Systems at Americas Ports June 8, 2011 Improving Safety Culture and Systems at Americas Ports Improving Safety Plan for the Future Pete M. Diana Project Manager Copyright 2011 DuPont. All rights reserved. The DuPont Oval Logo,

More information

OMA PLA SMA BEVE LER The reliable, easy-to-use, and compact system

OMA PLA SMA BEVE LER The reliable, easy-to-use, and compact system DMX DMX AUTOMATED PLASMA BEVELLER AUTOMATED PLASMA BEVELLER The reliable, easy-to-use, and compact system for safe, high-quality plasma bevel cutting. THE FUTURE OF BEVEL CUTTING IS HERE. DMX is the next

More information

Harmonic Analysis and Power Factor Correction For Food Processing Industry

Harmonic Analysis and Power Factor Correction For Food Processing Industry International Journal of Computational Engineering Research Vol, 03 Issue, 6 Harmonic Analysis and Power Factor Correction For Food Processing Industry Rupali Shinde 1, Amit Pathak 2, Bhakti Chaughule

More information

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation

Power supply circuit Through an external power supply unit V ac / 12 V dc. Operating temperature ºC. Humidity of operation Portable Description Features Measures all of the main electrical parameters of an electricity network Measurement in true root mean square Built-in energy meter With 4 voltage channels and 4 current channels

More information

Installation requirements

Installation requirements Installation requirements for SUNNY CENTRAL 500U 1 Contents This document describes the requirements which have to be observed for the installation site of the Sunny Central 500U. The installation and

More information

EMERGING ISSUES IN SUSTAINABLE INDUSTRIAL DESIGN PRACTICE: IMPLICATIONS FOR DESIGNERS, MANUFACTURERS AND EDUCATORS

EMERGING ISSUES IN SUSTAINABLE INDUSTRIAL DESIGN PRACTICE: IMPLICATIONS FOR DESIGNERS, MANUFACTURERS AND EDUCATORS EMERGING ISSUES IN SUSTAINABLE INDUSTRIAL DESIGN PRACTICE: IMPLICATIONS FOR DESIGNERS, MANUFACTURERS AND EDUCATORS John Dennison Submitted for the degree of Master of Design by Research University of Technology,

More information

An introduction. Vision. Mission

An introduction. Vision. Mission An introduction Arzoo energy came into being on 15 august 2003. From there it has been a steady rise to where we are today. Driven by passion, we have stood the test of time and delivered on our promise

More information

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE

More information

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease

Fluke 1740 Series. Three-Phase Power Quality Loggers Memobox. Assess power quality and conduct long-term studies with ease Fluke 1740 Series Three-Phase Power Quality Loggers Memobox Technical Data Assess power quality and conduct long-term studies with ease Compact and rugged, the Fluke 1740 Series three-phase power quality

More information

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz

7.5 kva Isolation Transformer - 460V Primary - 230V Secondary - NEMA 3R - Single Phase - 50/60 Hz 7.5 kva Isolation Transformer 460V Primary 230V Secondary NEMA 3R Single Phase 50/60 Hz Part #: MTISX1P460V7.5KVA230VN3R50.60HZ Page: 1 The MTISX1P460V7.5KVA230VN3R50.60HZ 460V 1 Phase Energy Efficient

More information

ARCMASTER. Industrial Portable Welding Power Sources

ARCMASTER. Industrial Portable Welding Power Sources ARCMASTER Industrial Portable Welding Power Sources U.S. Customer Care: 800-426-1888 Canada Customer Care: 905-827-4515 International Customer Care: 940-381-1212 ARCMASTER Industrial Portable Welding Power

More information

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor

500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor 500 kva Dry-type Isolation Transformer - 13200V-Delta to 208Y/120V 3PH - NEMA 1/Indoor Part #: MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Page: 1 The MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Dry-type Isolation

More information

PLA 33. Power line analyzer. User and service manual. version 2.4

PLA 33. Power line analyzer. User and service manual. version 2.4 PLA 33 Power line analyzer User and service manual version 2.4 Content. Front control panel and terminal plate...3 7.2.2. System frequency setting...0 2. Device description...4 7.2.3. Password protection...0

More information

Reliable power onboard and offshore

Reliable power onboard and offshore Reliable power onboard and offshore AccuSine PCS+ Active Harmonic Filters For electrical network reliability and quality in Marine 2 What causes harmonics in Marine applications? Power electronics with

More information

Installation and Operating Instructions

Installation and Operating Instructions Energy Division Installation and Operating Instructions Quadratic Integra 1530 Digital Metering Systems Our commitment. Your advantage. Contents Page 1 Introduction 4 1.1 Measurement Capabilities 5 1.2

More information

Mr Gould was an adventurer with a great deal of passion for nature and energy

Mr Gould was an adventurer with a great deal of passion for nature and energy Mr Gould was an adventurer with a great deal of passion for nature and energy Gould is defined as: the discovery of an ideal wind region. But why is the name Gould associated with a wind region? Mr Gould

More information

Thyristorised Automatic Power Factor

Thyristorised Automatic Power Factor Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor

More information

AC Power Monitoring Application Brief

AC Power Monitoring Application Brief AC Power Monitoring Application Brief APPLICATION NOTE Managing and monitoring AC power usage at remote sites (cell sites, communication huts, controlled environment vaults {CEVs}, substations, cabinets,

More information

Operating Guide October 2006

Operating Guide October 2006 Operating Guide October 2006 Safety 1 Safety This manual represents your meter as manufactured at the time of publication. It assumes standard software. Special versions of software may be fitted, in which

More information

HARMONIC MITIGATIONCASE STUDY

HARMONIC MITIGATIONCASE STUDY HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study

More information

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance PRODUCT FOR HIGH VOLTAGE APPLICATION Current transformers for Gasinsulated switchgear type ELK Instructions for installation, use and maintenance 2 CURRENT TRANSFORMERS FOR GAS-INSULATED SWITCHGEAR TYPE

More information

WDBR Series (RoHS compliant)

WDBR Series (RoHS compliant) WDBR Series (RoHS compliant) This new range of thick film planar power resistors on steel, offering high pulse withstand capability, compact footprint and low profile, to many demanding applications including

More information

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R

1.5 kva Single Phase Transformer - 120V Primary Voltage - 277V Secondary Voltage - NEMA 3R 1.5 kva Single Phase Transformer 120V Primary Voltage 277V Secondary Voltage NEMA 3R Part #: MT120V1.5KVA277V Page: 1 The MT120V1.5KVA277V 120V 1 Phase Energy Efficient Transformer from Larson Electronics

More information

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R

75 kva Isolation Transformer V Delta Primary Voltage - 480Y/277 Secondary Voltage - NEMA 3R 75 kva Isolation Transformer 4160V Delta Primary Voltage 480Y/277 Secondary Voltage NEMA 3R Part #: MTISX3P4160D75KVA480Y.277N3R Page: 1 The MTISX3P4160D75KVA480Y.277N3R 4160D 3 Phase Energy Efficient

More information

WDG 51 - Technical Data Sheet

WDG 51 - Technical Data Sheet MV 804 S WDG 51 - Technical Data Sheet FRAME MV 804 S SPECIFICATIONS & OPTIONS STANDARDS STAMFORD AC generators are designed to meet the performance requirements of IEC EN 60034-1. Other international

More information

6 FT LED Bulb - T8-36W Lumens - UL Listed - Fluorescent T8 LED Replacement/Retrofit Lamp

6 FT LED Bulb - T8-36W Lumens - UL Listed - Fluorescent T8 LED Replacement/Retrofit Lamp 6 FT LED Bulb - T8-36W - 4500 Lumens - UL Listed - Fluorescent T8 LED Replacement/Retrofit Lamp Part #: LEDT8-72-RP The Larson Electronics LEDT8-72-RP 36 watt T-series LED tube lamp is an excellent choice

More information

PORT WARATAH COAL SERVICES COMMUNITY NEWS

PORT WARATAH COAL SERVICES COMMUNITY NEWS PORT WARATAH COAL SERVICES COMMUNITY NEWS Edition One 2017 WELCOME TO THE PORT WARATAH COAL SERVICES COMMUNITY NEWSLETTER Welcome to the first edition of our Community News for 2017. As I look forward

More information

80 kva Isolation Transformer - 480V AC Primary - 20V AC Secondary - NEMA 3R - Single Phase

80 kva Isolation Transformer - 480V AC Primary - 20V AC Secondary - NEMA 3R - Single Phase 80 kva Isolation Transformer 480V AC Primary 20V AC Secondary NEMA 3R Single Phase Part #: MTDOE161P480V80KVA20VN3R The MTDOE161P480V80KVA20VN3R 480V AC 1 Phase Energy Efficient Isolation Transformer from

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

MAX Series Bass Amplifiers

MAX Series Bass Amplifiers MAX Series Bass Amplifiers Operating Manual www.peavey.com FCC Compliancy Statement This device complies with Part 15 of the FCC rules. Operation is subject to the following two conditions: (1) this device

More information

GANESH GBM-4020 Heavy-Duty CNC Bed Mill With Class-7 Super-Precision Spindle Bearings and Box Ways

GANESH GBM-4020 Heavy-Duty CNC Bed Mill With Class-7 Super-Precision Spindle Bearings and Box Ways 20869 Plummer St. Chatsworth, CA 91311 Toll Free: 888-542-6374 (US only) Phone: 818-349-9166 I Fax: 818-349-7286 www.ganeshmachinery.com GANESH GBM-4020 Heavy-Duty CNC Bed Mill With Class-7 Super-Precision

More information

Vector Network Analyzers ZVB

Vector Network Analyzers ZVB Specifications Version 05.00 Vector Network Analyzers ZVB September 2005 Specifications MEASUREMENT RANGE...3 MEASUREMENT SPEED...5 MEASUREMENT ACCURACY...6 EFFECTIVE SYSTEM DATA...8 TEST PORT OUTPUT...8

More information

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R

500 kva Isolation Transformer - 480V Delta Primary - 400Y/231 Wye Secondary - NEMA 3R 500 kva Isolation Transformer 480V Delta Primary 400Y/231 Wye Secondary NEMA 3R Part #: MTDOE163P480D500KVA400Y.231N3R Page: 1 The MTDOE163P480D500KVA400Y.231N3R 480 V Delta 3 Phase Energy Efficient Isolation

More information

Power Amplifier. Input Characteristics. SPECIFICATIONS NI PXIe-4610 Power Amplifier. Signal Range

Power Amplifier. Input Characteristics. SPECIFICATIONS NI PXIe-4610 Power Amplifier. Signal Range SPECIFICATIONS NI PXIe-4610 Power Amplifier This document lists specifications for the NI PXIe-4610 Power Amplifier. These specifications are typical at 25 ºC unless otherwise stated. The operating range

More information

60K(i) - 260K(i) THREE PHASE. SureImage IMAGING & TREATMENT SERIES

60K(i) - 260K(i) THREE PHASE. SureImage IMAGING & TREATMENT SERIES 60K(i) - 260K(i) THREE PHASE SureImage IMAGING & TREATMENT SERIES Power Conditioner MODEL ULTRA-K/M THREE PHASE ISOLATION TRANSFORMER Power Processor MODEL 700F/M THREE PHASE VOLTAGE REGULATOR, WITH ISOLATION

More information

R&S ZN-Z5x Calibration Units Specifications. Data Sheet V03.00

R&S ZN-Z5x Calibration Units Specifications. Data Sheet V03.00 R&S ZN-Z5x Calibration Units Specifications Data Sheet V03.00 CONTENTS Definitions... 4 Specifications... 6 Model description R&S ZN-Z5x... 6 Model description R&S ZN-Z15x... 7 Input power limits... 7

More information

R&S ZV-Z5x Calibration Units Specifications

R&S ZV-Z5x Calibration Units Specifications R&S ZV-Z5x Calibration Units Specifications Test & Measurement Data Sheet 09.01 Specifications apply under the following conditions: Sufficient warm-up time (approx. 15 minutes) at ambient temperature,

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

225 kva Autotransformer - 240V Delta Primary Voltage - 220V Delta Secondary Voltage - NEMA 3R

225 kva Autotransformer - 240V Delta Primary Voltage - 220V Delta Secondary Voltage - NEMA 3R 225 kva Autotransformer 240V Delta Primary Voltage 220V Delta Secondary Voltage NEMA 3R Part #: MTATX3P240D225KVA220DN3R Page: 1 The MTATX3P240D225KVA220DN3R 240D 3 Phase Energy Efficient Autotransformer

More information

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

Tap Changer Analyzer & Winding Ohmmeter RMO25TD Tap Changer Analyzer & Winding Ohmmeter RMO25TD Test current 5 ma 25 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 9,5 kg Measuring range 0,1-2 k Two voltage sense channels

More information

III CHAPTER. Analysis Methodology. regarding data sampling, benchmarking indices and overall program layouts.

III CHAPTER. Analysis Methodology. regarding data sampling, benchmarking indices and overall program layouts. III CHAPTER Analysis Methodology CHAPTER 3 ANALYSIS METHODOLOGY: Provides information on preliminary design aspects regarding data sampling, benchmarking indices and overall program layouts. 3.1 INTRODUCTION

More information

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734E - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734C - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT

PI734B - Winding 312. Technical Data Sheet APPROVED DOCUMENT - Winding 312 Technical Data Sheet SPECIFICATIONS & OPTIONS STANDARDS Stamford industrial generators meet the requirements of BS EN 60034 and the relevant sections of other national and international standards

More information

PRIMAX EXCEL THE NEW BENCHMARK IN PRIMERS FOR ENGINEERED WOOD POWDER COATING BREAKTHROUGH TECHNOLOGY

PRIMAX EXCEL THE NEW BENCHMARK IN PRIMERS FOR ENGINEERED WOOD POWDER COATING BREAKTHROUGH TECHNOLOGY PRIMAX EXCEL THE NEW BENCHMARK IN PRIMERS FOR ENGINEERED WOOD POWDER COATING BREAKTHROUGH TECHNOLOGY FOR AN INDUSTRY THAT SEEKS EFFICIENCY There is increasing pressure in the engineered wood industry to

More information

Energy Efficient Distribution Transformers

Energy Efficient Distribution Transformers Energy Efficient Distribution Transformers Established in 1917, Hammond Power Solutions Inc. (HPS), is an industry leader in magnetic transformer design and development. With our headquarters in Guelph,

More information

R&S ZN-Zxxx Calibration Units Specifications. Data Sheet V04.00

R&S ZN-Zxxx Calibration Units Specifications. Data Sheet V04.00 R&S ZN-Zxxx Calibration Units Specifications Data Sheet V04.00 Version 03.00, January 2019 CONTENTS Definitions... 4 Specifications... 6 Model description R&S ZN-Z5x... 6 Model description R&S ZN-Z15x...

More information

A new compact power modules range for efficient solar inverters

A new compact power modules range for efficient solar inverters A new compact power modules range for efficient solar inverters Serge Bontemps, Pierre-Laurent Doumergue Microsemi PPG power module Products, Chemin de Magret, F-33700 Merignac Abstract The decrease of

More information