ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE
|
|
- Corey Conley
- 5 years ago
- Views:
Transcription
1 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and commissioning procedures for compact and micro substations. Author: John Mason Approver: Paul Williams Date: 23/04/2018 This document forms part of the Company's Integrated Business System and its requirements are mandatory throughout UK Power Networks. Departure from these requirements may only be taken with the written approval of the Director of Asset Management. If you have any queries about this document please contact the author or owner of the current version. Circulation UK Power Networks External Asset Management UK Power Networks Services Capital Programme Contractors Connections ICPs/IDNOs Health & Safety Meter Operators Legal G81 Website Network Operations Procurement Strategy & Regulation Technical Training THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE
2 Revision Record Version 3.0 Review Date 23/04/2023 Date 21/03/2018 Author John Mason Reason for update: Periodic review What has changed: Alfresco file paths updated Version 2.0 Review Date 31/03/2018 Date 01/05/2013 Author Stephen Tucker Reviewed for G81 website Version 1.0 Review Date Date 04/11/2011 Author Original Stephen Tucker / Sinéad Hogan UK Power Networks 2018 All rights reserved 2 of 7
3 Contents 1 Introduction Scope References Abbreviations and Definitions Equipment Inspection Tap Changer Checks Winding Insulation Resistance Earthing Energisation Asset Data Test Equipment Certification... 7 UK Power Networks 2018 All rights reserved 3 of 7
4 1 Introduction 1.1 This procedure details the testing and commissioning procedures for compact substations that shall be satisfied before the compact substation can be accepted as fit for service and energisation. 1.2 This procedure shall be carried out by the Commissioning Engineer or his appointed representative, who shall be an Authorised Person having appropriate training and experience. 1.3 This procedure shall be carried out in accordance with the requirements of the UK Power Networks Distribution Safety Rules. 1.4 This procedure shall be carried out having regard to the requirements and recommendations of the manufacturer. If conflict exists between the requirements of the manufacturer and those of UK Power Networks the matter shall be referred to Asset Management (or your UK Power Networks nominated contact). 1.5 This procedure assumes that the unit has been installed in accordance with the appropriate procedures and that the equipment is isolated from the network. 1.6 The results of all observations, tests, adjustments and all relevant remarks shall be recorded on the associated test form. 2 Scope 2.1 This procedure applies to all compact substations, previously known as micro substations, padmounts and mini substations. 2.2 This procedure is intended for use by UK Power Networks field staff, contractors and external connection providers. 3 References 3.1 This procedure should be read in conjunction with the following references: UK Power Networks Distribution Safety Rules. EOS Compact Substations 11kV and 6.6kV. Manufacturer's installation and operation instructions (available from Intranet > PPF > Engineering > Reference Library > Manufacturers > CG Power Systems). 3.2 This procedure should be used with the following procedures and test forms: ECP a Compact Substation Test Form. ECP Earthing Commissioning. ECP a Earthing Test Form. ECP Secondary Substation Energisation. UK Power Networks 2018 All rights reserved 4 of 7
5 4 Abbreviations and Definitions 4.1 The following abbreviations are used throughout this procedure. Term ART PPF Definition UK Power Networks Asset Registration Team Policies, s & Forms 5 Equipment 5.1 The following test equipment is required to carry out the tests detailed in this procedure: 1kV insulation resistance tester (Megger). 6 Inspection 6.1 Record the compact substation details on the test form. 6.2 Carry out a visual inspection of the compact substation as detailed below referring to the manufacturer s manual where appropriate. If possible the Commissioning Engineer shall rectify any non-conformances. However, all equipment defects shall be referred to Asset Management (or your UK Power Networks nominated contact). Check that the compact substation is undamaged and is correctly positioned on the plinth. Check that all external surface finishes are undamaged and any damaged paintwork has been repaired. Check that the earthing terminal(s) are securely connected directly to the substation earth electrodes and that the HV and LV earths are separated or combined as required. Check all earth straps are securely fitted. Check that there are no oil leaks. Check that the transformer oil level is satisfactory (if applicable). Check that all valves are securely closed. Check that the pressure relief device is not blocked and remove any packing if labelled adjacent to device. Check that the HV bushings are satisfactory. Check that the LV bushings are satisfactory. Check that the LV fuse arrangement is undamaged. Check that the HV bay-o-net fuses are pushed in fully (if applicable). Check the transformer ID labels are fitted (if applicable). UK Power Networks 2018 All rights reserved 5 of 7
6 7 Tap Changer Checks 7.1 Carry out the following tap changer checks referring to the manufacturer s manual where appropriate: Operate the tap changer through all positions while off-circuit. Set the desired tap position. Lock the tap changer only if it is not located in the HV cable box (200kVA and above). Tap changers located in the HV cable box (100kVA and less) can not be interfered with since the lock would interfere with the HV insulation. 7.2 Record the tap position on the test form. 8 Winding Insulation Resistance 8.1 Measure HV winding insulation resistance as follows: Connect the LV windings together and to earth via the neutral-earth link and substation earth. Connect a 1kV insulation tester between the transformer HV winding and earth. The insulation resistance should be greater than the values shown in the table below. The transformer should be discharged after the measurement. 8.2 Measure LV winding insulation resistance as follows: Connect the HV windings together and to earth via the substation earth. Connect a 1kV insulation tester between the transformer LV winding and earth. The insulation resistance should be greater than the values shown in the table below. The transformer should be discharged after the measurement. Replace the neutral-earth link if it has been removed previously. Ambient Oil Temperature ( C) Insulation Resistance (MΩ) Insulation Resistance with Secondary Auxiliary Wiring (e.g socket, ammeter, RCD etc) (MΩ) UK Power Networks 2018 All rights reserved 6 of 7
7 9 Earthing 9.1 The earthing shall be tested and commissioned in accordance with commissioning procedure ECP Energisation 10.1 Energisation including phasing checks shall be carried out in accordance with ECP Asset Data 11.1 Complete the asset data form and send it to the Asset Registration Team (ART). This can be done via the Intranet (Asset Management > Asset Information > Asset Registration) or through SAP ESS. Ensure that the form is sent to the correct ART department: 12 Test Equipment 12.1 Record the purpose, make, type and serial number of all test equipment used during commissioning on the test form. 13 Certification 13.1 When the commissioning has been satisfactorily completed, sign and date the test form. Place a copy of the test form on-site in a plastic wallet and in a secure location. UK Power Networks 2018 All rights reserved 7 of 7
ECP DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE
Document Number: ECP 11-0506 ENGINEERING COMMISSIONING PROCEDURE ECP 11-0506 DISTRIBUTION TRANSFORMER COMMISSIONING PROCEDURE Network(s): Summary: EPN, LPN, SPN This procedure details the testing and commissioning
More informationECP HV METERING EQUIPMENT COMMISSIONING PROCEDURE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: ECP 11-0515 ENGINEERING COMMISSIONING PROCEDURE ECP 11-0515 HV METERING EQUIPMENT COMMISSIONING PROCEDURE
More informationECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE
ENGINEERING COMMISSIONING PROCEDURE ECP 11-0512 GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE Network(s): Summary: EPN, LPN, SPN This procedure details the testing and commissioning
More informationECP GROUND-MOUNTED SWITCHGEAR COMMISSIONING PROCEDURE
Document Number: ECP 11-0511 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0511 GROUND-MOUNTED SWITCHGEAR COMMISSIONING PROCEDURE EPN, LPN, SPN This procedure details the testing and
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: All ENGINEERING COMMISSIONING PROCEDURE ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing of new and
More informationECP HV INSULATION TESTING
Document Number: ECP 11-0006 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE EPN, LPN, SPN ECP 11-0006 HV INSULATION TESTING This standard details the policy for the on-site insulation testing
More informationEDS LV ELECTRICAL SERVICE DRAWINGS
Document Number: EDS 08-2110 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 08-2110 LV ELECTRICAL SERVICE DRAWINGS EPN, LPN, SPN This standard details the drawings for service positions and connection
More informationEDS LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS
ENGINEERING DESIGN STANDARD EDS 08-2109 LV SUPPLIES TO MOBILE PHONE BASE STATIONS MOUNTED ON TRANSMISSION TOWERS Network(s): Summary: EPN, LPN, SPN This standard provides guidance on the installation of
More informationEDS LV WAVEFORM MAINS CABLE RATINGS
Document Number: EDS 02-0033 Network(s): Summary: ENGINEERING DESIGN STANDARD EDS 02-0033 LV WAVEFORM MAINS CABLE RATINGS EPN, LPN, SPN This standard details the technical and practical information required
More informationEI HIGH VOLTAGE INSULATION TESTING POLICY
Network(s): Summary: ENGINEERING INSTRUCTION EI 09-0001 HIGH VOLTAGE INSULATION TESTING POLICY EPN, LPN, SPN This engineering instruction details the policy for the on-site insulation testing of new and
More informationEDS GRID AND PRIMARY SUBSTATION CIVIL DESIGN STANDARDS
Document Number: EDS 07-0105 ENGINEERING DESIGN STANDARD EDS 07-0105 GRID AND PRIMARY SUBSTATION CIVIL DESIGN STANDARDS Network(s): Summary: EPN, LPN, SPN This design standard details the current civil
More informationUK Power Networks OPERATIONAL BULLETIN
Document No: HSS 406 OB 160 Issue Date: 10 July 2018 Type: Operational Safety Subject: Changes to DSR procedures 2018/1 Applicable Areas: All Applicable Job Roles: All DSR holders Issued By: Dudley Sparks
More informationEDS FAULT LEVELS
Document Number: EDS 08-1110 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-1110 FAULT LEVELS This standard provides guidance on the calculation, application and availability of
More informationEDS KV TRIPLEX CABLE RATING
Document Number: EDS 02-0027 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE RATING This engineering design standard provides the cable ratings and important
More informationEquipment Description Quantity as per drawings Actual quantity
NOTE: SAFETY: Tests must be carried out after the installation, alteration or repair and before putting back to service. At all times maintain suitable clearance to all other electrical equipment and verify
More informationEDS KV SINGLE CORE XLPE CABLES
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0034 ENGINEERING DESIGN STANDARD EDS 02-0034 33KV SINGLE CORE XLPE CABLES Network(s): EPN, LPN,
More informationPRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer
PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer
More informationCONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationUNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1
GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers
More informationSPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)
SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor
More informationNSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation
Version:- 1.0 of Issue:- March 2016 Page 1 of 7 NSP/ 007 / 006 Guidance on Substation Design: Transformer Transport, Delivery and Installation 1. Purpose The purpose of this document is to provide guidance
More informationDistribution transformers Part 2 Ground mounted transformers not closecoupled
PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationField Instruction Switching Activities. Purpose. Scope. Objective. Safety
8.22 Switching Activities Purpose This instruction provides a safe system for switching on Horizon Powers Low Voltage, High Voltage and or Transmission electrical apparatus/network, where switching operations
More informationMESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER
Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationCONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS
CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased
More informationMV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer
PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with
More informationCommissioning Manual Distribution Transformers - Three-phase Oil Filled
1LPL000006A2110 rev. 1 Commissioning Manual Distribution Transformers - Three-phase Oil Filled 1LPL000006A2110 rev. 1 2 / 7 Table of contents 1 Commissioning and start-up... 3 1.1 Transformer survey...
More informationElectrical Switchgear & Power Transformer Testing. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
Electrical Switchgear & Power Transformer Testing H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: This will provide you with practical knowledge
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationIntroduction. Centrado leading-edge transformer. Introduction
Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,
More informationSingle-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL
Single-Phase Mini Pad-Mounted Transformer Specification: Energy+ MPDL Issued by: Approved by: Engineering Department Energy+ Inc. September 2016 Shawn Jackson, P.Eng. Approval is given in accordance with
More informationSUBJECT HEADING: Switching Programmes ISSUE: 18
SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme
More informationManual: Distribution Substation Manual (DSM) Section D: Substation Drawing Revision List
Manual: Distribution Substation Manual (DSM) Section D: Substation Drawing Revision List Standard Number: HPC-5DA-07-0011-2012 Document Control Author Name: Viswa Easwaran Position: Standards Engineer
More informationINSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION
TITLE: RECOMMENDED: P. Lemay NO: APPROVED: C. Malone, P.Eng. REV. DATE: 2015-11-02 Working Procedure GCG0001 REV: 3 INSTALLATION & TESTING OF UNDERGROUND PRIMARY AND SECONDARY POWER CABLES PRIOR TO ENERGIZATION
More informationFAQ ON EARTHING STANDARDS 16/08/2018
FAQ ON EARTHING STANDARDS 16/08/2018 This document has been updated to include changes made to substation earthing layouts that have been made necessary due to copper theft. The main changes to be aware
More informationPower Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.
Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the
More informationECP TESTING AND COMMISSIONING GUIDANCE NOTES
Document Number: ECP 11-0003 Network(s): Summary: ENGINEERING COMMISSIONING PROCEDURE ECP 11-0003 TESTING AND COMMISSIONING GUIDANCE NOTES EPN, LPN, SPN This document provides guidelines and preferred
More informationS. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013)
S. C. Electric Cooperative s Specification for a Single-Phase, Single Bushing Overhead Distribution Transformer (Revised 10/2013) 1.0 GENERAL 1.1 This specification covers the electrical and mechanical
More informationTitle Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control
More informationGreenlining and Bluelining of Ergon Energy Substation Drawings
Greenlining and Bluelining of Ergon Energy Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 General... 1 Requirements... 3 Testing
More informationEarthing Requirements for HV Transmission Structures
Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationC&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests
C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Earth Fault Loop Impedance Tests 1 Revision Inspections are made to verify that the installed
More informationModule Title: Electrical Installation II Laboratory Sheet:
Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date:
More informationON-SITE TESTING OF SPECIAL TRANSFORMERS
ON-SITE TESTING OF SPECIAL TRANSFORMERS Simanand GANDHI JEYARAJ, Megger Ltd, UK, Simanand.gandhi@megger.com, Robert MILNE, UK Power Networks, UK, robert.milne83@googlemail.com Grant MITCHELL, Transmag
More informationNOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.
City & Guilds Fundamental Inspection & Testing 30 Question Test Sheet (2392-10 Paper No1.) NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes
More informationGroup F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A
Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating
More informationELECTRIC NETWORK DESIGN APPROVAL APPLICATION
Please complete all sections of the application form and return to newconnections@ukpowerdistribution.co.uk Section 1 Site Details UKPD Reference Number: Energisation Date: Site Name/Address/Postcode:
More informationSchedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK
2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK PO Box 25876 Safat 13119 Kuwait Contact: Mr Atul Madhukar Vaidya Tel: +965 1822600 Fax: +965 24761963 E-Mail: factory@ahleiasg.com Website:
More informationBe on guard for effective testing: Introduction
Be on guard for effective testing: Introduction The development of the insulation tester by Evershed and Vignoles is part of our electrical history, with insulation testers produced by Megger Instruments
More informationTECHNICAL SPECIFICATION FOR POWER TRANSFORMER
TECHNICAL SPECIFICATION FOR POWER TRANSFORMER NOTE: Vendor to give their offer in line with this data sheet only. Any deviations/additions/deletions shall be brought out in a separate sheet. A TECHNICAL
More informationGUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT
GUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT COURSE CURRICULUM COURSE TITLE: MAINTENANCE OF TRANSFORMER AND CIRCUIT BREAKER (COURSE CODE:3360907) Diploma Programme in which this course is offered
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationSubstation Preventive Maintenance
Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS
More informationEarthing, HV Switching and Associated Operational Equipment. Approval: Chief Operating Officer
ACCESS PRACTICE AP 24 Earthing, HV Switching and Associated Operational Equipment Process Authority: Manager Operations Improvement Approval: Chief Operating Officer Version Date: 27/08/2013 Revision:
More informationNational Grid UK Electricity Transmission plc. NATIONAL SAFETY INSTRUCTION and Guidance
National Grid UK Electricity Transmission plc NATIONAL SAFETY INSTRUCTION and Guidance NSI 26 RAILWAY CONNECTION CIRCUITS Copyright National Grid plc 2016, all rights reserved. No part of this publication
More informationNSP/007/019 - Guidance on Substation Design: EHV Substation Drawing Policy
Version:- 1.1 Date of Issue:- Feb 2015 Page 1 of 13 NSP/007/019 - Guidance on Substation Design: EHV Substation Drawing Policy 1. Purpose The purpose of this document is to outline the Northern Powergrid
More informationCompany Directive ENGINEERING SPECIFICATION EE SPEC: 5/5. Relating to 11kV Distribution Transformers
Company Directive ENGINEERING SPECIFICATION EE SPEC: 5/5 Relating to 11kV Distribution Transformers Policy Summary This specification covers the requirements for Distribution Transformers from 16kVA single
More informationPOWER/DISTRIBUTION TRANSFORMER PERFORMANCE EVALUATION.
POWER/DISTRIBUTION TRANSFORMER PERFORMANCE EVALUATION. PROJECT INDEX: PRJ005 SUPERVISOR: MR. N.S WALKADE EXAMINER: DR.ABUNGU DONE BY: MWANIKI FREDRICK MUKUNDI F17/2120/04 INTRODUCTION A transformer is
More informationRING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL
RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS F.T.M. S. r. l. Fabbrica trasformatori di misura Via Po, 3 20090 Opera MI - Italy Tel : +39 (0)2 576814 Fax : +39 (0)2 57605296 E-mail: info@ftmsrl.it
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationPOWER TRANSFORMER. Failure Analysis & Troubleshooting. H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E
POWER TRANSFORMER Failure Analysis & Troubleshooting H.H. Sheik Sultan Tower (0) Floor Corniche Street Abu Dhabi U.A.E www.ictd.ae ictd@ictd.ae Course Introduction: Electricity is high-grade energy. Working
More informationConnection of Embedded Generating Plant up to 5MW
Engineering Recommendation No.3 of the Electricity Distribution Code Connection of Embedded Generating Plant up to 5MW Version 1.0 30th November 2005 Prepared by: Al Ain Distribution Company, Abu Dhabi
More information25kV A.C. Electrified Lines - Traction Bonding
Date:MAR 94 25kV A.C. Electrified Lines - Traction Page 1 of 6 Part A Synopsis This is issued by the to define the Boards requirements for continuity bonding on railway systems. This will ensure a continuous
More information500 kva Dry-type Isolation Transformer V-Delta to 208Y/120V 3PH - NEMA 1/Indoor
500 kva Dry-type Isolation Transformer - 13200V-Delta to 208Y/120V 3PH - NEMA 1/Indoor Part #: MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Page: 1 The MT-DOE16-3P-13200D-500KVA-208Y.120-N1 Dry-type Isolation
More informationPROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA
PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA Generally inspection of electrical installations is carried out under Regulation-30 (Periodical inspection & testing) & Regulation-43 (Approval
More informationCompany Directive STANDARD TECHNIQUE: TP14C. Distribution Business Provided Metering Facilities
Company Directive STANDARD TECHNIQUE: TP14C Distribution Business Provided Metering Facilities Summary This standard technique document details the metering facilities to be provided by the distribution
More information2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation
2394 EXAM PAPER 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2. There are various documents that are relevant to the Inspection and
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS
101135-ELE-CMOS-E-2001 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 14 years hands-on experience, including 13 years working in operation, maintenance, construction
More informationSPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.
1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified
More informationNZQA registered unit standard version 2 Page 1 of 8. Demonstrate knowledge of theory for registration of electrical installers
Page 1 of 8 Title Demonstrate knowledge of theory for registration of electrical installers Level 3 Credits 3 Purpose This unit standard covers the theory assessment required for registration as an electrical
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60076-21 Edition 2.0 2018-12 IEEE Std C57.15 Power transformers Part 21: Standard requirements, terminology, and test code for step-voltage regulators INTERNATIONAL ELECTROTECHNICAL
More informationCalculating and compensating for power transformer and cable (or line) losses - standard methods
Guidance Calculating and compensating for power transformer and cable (or line) losses - standard methods Foreword This guidance sets out basic standard methods for calculating electrical loss compensation
More informationinstallation guide For Oil and Synthetic Ester filled Transformers
installation guide For Oil and Synthetic Ester filled Transformers 02 CONTENTS : Introduction 03. : Cautionary note 03.2 : Health & Safety 03 2 : Transformer Components 04 3 : Receiving the transformer
More informationSECTION 5 TRANSFORMERS
SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established
More informationISSN: [IDSTM-18] Impact Factor: 5.164
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant
More informationDMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)
DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date
More informationReference Number PCP 02 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Reference Number PCP 02 (RIC Standard: EP 20 00 00 20 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards
More informationPRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS
PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Date: Given Names: Time: Assessment Time (includes 10 minutes reading time): At the end of this time you will be asked to stop. 4 hours Have you
More informationSTS Fully automatic. Large graphic display. Primary injection testing capabilities: up to 3000 A, with the optional module BUX 3000
STS 4000 Multifunction substation maintenance & commissioning test system for current, voltage and power transformers. Capacitance / Tan Delta diagnostic system with the optional module TD 5000. w w w.
More informationEDS LV NETWORK DESIGN
Document Number: EDS 08-2000 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-2000 LV NETWORK DESIGN This standard defines UK Power Networks policy with regard to all aspects of the
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationTHE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT
THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationMESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER
Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head
More informationFor the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.
Voltage transducer DV 42/SP3 V P N = 42 V For the electronic measurement of voltage: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Bipolar and insulated
More informationTransformer condition assessment with an integrated test van
Transformer condition assessment with an integrated test van 1 2012 SebaKMT Measuring and locating techniques MADE in GERMANY 2 Testing and Standards for Power Transformers CIGRE CIGRE Brochure 342 (SFRA-FRAX)
More informationEE188: Transformer Design, Construction, Testing & Maintenance
EE188: Transformer Design, Construction, Testing & Maintenance EE188 Rev.001 CMCT COURSE OUTLINE Page 1 of 5 Training Description: This intensive training covers the design, theory, operation, maintenance
More informationAutotransformer Condition Monitoring Systems
Autotransformer Condition Monitoring Systems The Bidders shall offer separately the following systems of par.1 Integrated Condition Monitoring System and par.2 UHF PD Monitoring System. Two systems following
More informationINSTALLATION WARNING: BEFORE COMMENCING INSTALLATION ISOLATE YOUR MAINS ELECTRIC SUPPLY
TT403- K (1000W) Wireless Inline Switch Product Description The TT403- K is a 1000W switchable wireless receiver and can be used to control a lighting system, extractor fan or other appliance. It does
More informationMETER - INSTALLATION Pad Mount Transformer
ER 1-210-C PAGE 1 OF 5 USE: Pad mount transformer secondary compartment LATEST REVISION: PREVIOUS REVISION 10-01-12 ORIGINATED 0-94 PREVIOUS NUMBER ER 700, 10-01-86 Added specification for placement and
More informationTECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS
TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) BIDDER s OFFER S. No. PARTICULARS BHEL SPECIFICATIONS 1.0 Area of Application The 300kV Constant potential
More informationBasic Principles and Operation of Transformer
Basic Principles and Operation of Transformer CONSTRUCTIONAL ASPECTS Cores In order to enhance core s magnetic properties, it is constructed from an iron and silicon mixture (alloy). The magnetic core
More informationCUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv
CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable
More information