FINAL - EST Electrical Service Technician Answer Schedule
|
|
- Louise Pope
- 5 years ago
- Views:
Transcription
1 FINAL - EST Electrical Service Technician Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker can exercise their discretion and decide on the overall accuracy of any answer that is presented in the candidate s own words. 3. Symbols and terms - alternatives Power W or P Voltage V or E or U Phase Active Question 1 Marks Reference Marking notes (a) I = V R = = 9.58A (b) Any ONE of: A landlord of residential premises must not provide any fittings or appliances under or in connection with a residential tenancy if the fittings or appliances are electrically unsafe. A landlord of residential premises must not allow any person to use any fittings or appliances provided by the landlord under or in connection with a residential tenancy if the fittings or appliances are electrically unsafe. A landlord of residential premises must provide the occupier with adequate instructions for the safe use of any fittings or appliances provided under or in connection with a residential tenancy. ESR 15A(1) ESR 15A(2) ESR 15A(3) (c) Correct circuit connections (polarity) Continuity of conductors (d) Low voltage is any voltage between 50V and 1000V. Standard low voltage is a nominal voltage of 230V between phase and neutral ESR 4 ESR 4 FINAL - EST 2069 ANSWERS 25 JUNE
2 Question 1 Marks Reference Marking notes (e) One pole of the isolating switch has failed to open. (f) (i) 1 MΩ (ii) 1Ω (g) Any TWO of: When the appliance is double insulated When the appliance is supplied from an isolating transformer When connected to a generator supply (h) Open circuited centrifugal switch Open start winding circuit (i) Other equipment could fail or stop during an essential operation (lift or elevator control circuit) (j) Category of duty (Rupturing Capacity) Current rating FINAL - EST 2069 ANSWERS 25 JUNE
3 Question 2 Marks Reference Marking notes (a) Earth continuity test * An ohmmeter * Test between the earth conductor of the flexible cord and the frame of the press. * A test result of 1Ω or less Insulation resistance test * Insulation resistance tester * 500V d.c. * Bridge the phase and neutral on the flexible cord * Test between the bridge and the frame of the press * A test result of 1MΩ or more (b) The description has to show: Taking a voltage test on the load side of the isolator. Using the prove-test-prove method Locking the isolator Attaching a danger tag to the isolator. (c) By testing the resistance between the frame of the printing press and another earth. FINAL - EST 2069 ANSWERS 25 JUNE
4 Question 3 Marks Reference Marking notes (a) (i) 1. Phase 2. Neutral 3. Fuse 4. Start button 5. Hold-in contact 6. Coil 7. Stop button 8. Thermal overload (4 marks) (ii) 24V or 110V or 230V (b) (i) Detects an overload and opens the control circuit. When the current exceeds a pre-determined level. (ii) Detects a rise in temperature in the motor windings. Opens the control circuit when the temperature exceeds a pre-set level. (c) The motor s original direction of rotation will be reversed. FINAL - EST 2069 ANSWERS 25 JUNE
5 Question 4 Marks Reference Marking notes (a) Only the protective device nearest the fault operates. (b) 60A Is the maximum current the fuse can carry continuously 440V is the maximum operating voltage of the fuse AC40. 40,000A is the maximum prospective short circuit current the fuse can safely interrupt (c) To provide short-circuit protection for the motor final subcircuit (d) (i) As current through a protective device increases, the time taken to operate decreases. (ii) FINAL - EST 2069 ANSWERS 25 JUNE
6 Question 5 Marks Reference Marking notes (a) A short-circuit will be created which will operate the meter protection. (b) The voltmeter will show a 0 volt reading even though the circuit being measured is live. (c) Cord extension sets AS/NZS 3760: Appendix F (d) Any TWO of: Ensure the correct instrument for the conditions is used. Inspect instrument, clips, leads and probes to ensure they are in good condition. Ensure correct function is selected on the instrument. Ensure correct range is selected on the instrument. Ensure leads are correctly connected. (e) (i) Any ONE of: Clamped around the phase (active) conductor. Clamped around the neutral conductor. (ii) The current flowing in the phase and neutral are balanced so no reading can be obtained. (f) The output voltage of the ohmmeter is insufficient to stress the insulation. FINAL - EST 2069 ANSWERS 25 JUNE
7 Question 6 Marks Reference Marking notes (a) (i) A degree of protection in accordance with AS AS/NZS 3000: Appendix: G1 (ii) The degree of protection against solid objects Protection of persons against access to hazardous parts. AS/NZS 3000: Appendix: G1 AS/NZS 3000: Appendix: G1 (iii) A degree of protection against entry of water with harmful effects. AS/NZS 3000: Appendix: G1 (b) 5 Limited ingress of dust permitted (no harmful deposit). AS/NZS 3000: Table G1(a) X No degree of protection specified. AS/NZS 3000: Appendix G1 (c) Protection by means of obstacles in accordance with clause Protection by placing out of reach in accordance with clause AS/NZS 3000: (a) AS/NZS 3000: (b) (d) Any TWO of: IPX8 AS/NZS (a) Provided with the required degree AS/NZS 3000 of protection (a)(ii) Designed and constructed specifically for use in a swimming pool Be rated at a nominal voltage not exceeding 12V a.c. AS/NZS (a)(i) AS/NZS (a)(iii) FINAL - EST 2069 ANSWERS 25 JUNE
8 Question 7 Marks Reference Marking notes (a) The maximum current a fuse-link can carry continuously. (b) (i) The fuse is under-rated for the circuit. (ii) Any ONE of: The fuse is over-rated for the circuit. The rupturing capacity of the fuse is too small (c) Any TWO of: It prevents the fuse element from bulging out the side of the carrier and being accessible to touch. Under overload conditions the heat produced in the element is confined to the tunnel area. Under short-circuit conditions the arc and molten element is confined within the fuse carrier and base. (d) (i) Detects the loss of voltage on a phase Opens the control circuit and trips out the motor. (ii) Detects the reversal of any two phases of the supply. Prevents the motor from starting (e) The overload causes a bi-metal to heat up and bend, operating a trip mechanism (f) It is the maximum current an MCB can interrupt under fault conditions. FINAL - EST 2069 ANSWERS 25 JUNE
9 Question 8 Marks Reference Marking notes (a) Maintaining contact L O/L M Stop Start Timer Auxiliary Delta S N Timer Auxiliary Star D T Fuse protects entire circuit Overload protects entire circuit Correctly connected stop button Correctly connected start button and hold-in contacts Correctly connected timers Correctly connected delta auxiliary contact Correctly connected star auxiliary contact Correctly connected main contactor coil Correctly connected star contactor coil Correctly connected delta contactor coil Working circuit (b) Any ONE of: The motor ventilation is restricted in some manner. The cooling fan has become detached from the motor shaft FINAL - EST 2069 ANSWERS 25 JUNE
10 (c) (i) Thermistor (ii) In the windings of the motor (d) Interchange two phases on the motor terminal block FINAL - EST 2069 ANSWERS 25 JUNE
11 Question 9 Marks Reference Marking notes (a) R = R 2 x R 3 R 2 + R 3 = 20 x = 14.29Ω R t = = 64.29Ω I = V R = = 3.58A (b) P = V 2 R = 230 x = W P = V 2 R = 230 x = W = = 67.12W FINAL - EST 2069 ANSWERS 25 JUNE
EAS Electrical Appliance Serviceperson Answer Schedule
EAS 1083- Electrical Appliance Serviceperson Answer Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.
More informationEASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)
EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE Notes: 1. (1mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination
More informationET 51 - Electrician Theory Examination Marking Schedule
ET 51 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationFINAL - ET 60 - Electrician Theory Examination Marking Schedule
FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.
More informationELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationET 40 - Electrician Theory Examination Marking Schedule
ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationET 61 - Electrician Theory Examination Marking Schedule
ET 61 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker
More informationFINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes
FINAL - ER 70 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions.
More informationFINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2
FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination
More informationELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET51 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)
ER 87 Electrician Regulations Answer Schedule Notes:1. (1 mark) means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the expected answers to the examination questions. The
More informationELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET37 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Given Names: Date: Time: Location: Assessment Time (includes reading and preparation time): At the end of this time you will be asked to stop.
More informationLicensed Electricians Practical Assessment (LEP)
Licensed Electricians Practical Assessment (LEP) Surname: Date: Given Names: Time: Assessment Time (includes 10 minutes reading time): At the end of this time you will be asked to stop. 4 hours Have you
More informationELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET
Candidate Code No. ET 60 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 19 November 2016 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three
More informationNational Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56
1. Two Electrical Technicians are discussing markings that are required for AC wiring. Tech A says that AC conductors must be rated for 600 volts and must have their jackets and individual conductors marked
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationSAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS
SAUDI STANDARD NO. SASO IEC 60669-2-2: 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS Part 2-2: Particular requirements Electromagnetic remote-control switches (RCS) SAUDI ARABIAN
More information2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation
2394 EXAM PAPER 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation 2. There are various documents that are relevant to the Inspection and
More informationInstruction Manual for Digital Grounding Resistance Meter. Table of Contents
I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4 IV. Work Principle...7 V. Appearance Description...9 VI. Technical Characteristics 10 VII. Resistance Measurement Method..12 VIII.Battery
More informationELECTRICAL MAINTENANCE SKILLS
ELECTRICAL MAINTENANCE SKILLS FOR INSTRUMENTATION PERSONNEL COURSE 120: 7 DAYS: Max 8 Candidates The end objectives are identical to those of the Electrical maintenance skills (Course 110) but this starts
More informationSINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL
SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly
More informationL O V A G. T E S T I N S T R U C T I O N I E C / E N E d C O N D I T I O N S F O R T E S T I N G
LTI IEC/EN 60947-4-1 Ed.3.1 L O V A G T E S T I N S T R U C T I O N I E C / E N 6 0 9 4 7-4 - 1 E d. 3. 1 C O N D I T I O N S F O R T E S T I N G C O N T A C T O R S A N D M O T O R - S T A R T E R S This
More informationAC/DC CLAMP METER USER S MANUAL
AC/DC CLAMP METER USER S MANUAL CONTENTS PAGE SAFETY INFORMATION SYMBOL EXPLANATION SAFETY PRECAUTIONS 1 1 2 MAINTENANCE 3 GENERAL DESCRIPTION 4 PANEL DESCRIPTION 4 OPERATING INSTRUCTIONS... 7 SPECIFICATIONS
More informationreturned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.
1. This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions. KYORITSU will not accept liability for any damage or injury caused by misuse
More informationNOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.
City & Guilds Fundamental Inspection & Testing 30 Question Test Sheet (2392-10 Paper No1.) NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes
More informationModule Title: Electrical Installation II Laboratory Sheet:
Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date:
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationAX-C Introduction. 2. Safety Information
AX-C708 1. Introduction Read Safety Information before using the meter. ProcessMeter ( referred to as the meter )is a handheld, battery-operated tool for measuring electrical parameters. It has all the
More informationC&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations
C&G 2395-01 Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations Phase rotation and verification of voltage drop 1 Outcomes of this Session describe how to assess
More informationInstruction Manual for Digital Grounding Resistance Meter
Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4
More information, Power Industries and Communications Industry Training Board
, Power Industries and Communications Industry Training Board Suite 3 Level 22185 187 Boundary Boundary Rd Rd North Melbourne VIC 3051 Phone VIC 3051 (03) 9654 1299 Phone (03) 9654 1299 Facsimile (03)
More informationE X A M I N A T I O N S C O U N C I L SECONDARY EDUCATION CERTIFICATE EXAMINATION ELECTRICAL AND ELECTRONIC TECHNOLOGY TECHNICAL PROFICIENCY
TEST CODE 01317031/SBA FORM TP 2012069 JUNE 2012 C A R I B B E A N E X A M I N A T I O N S C O U N C I L SECONDARY EDUCATION CERTIFICATE EXAMINATION ELECTRICAL AND ELECTRONIC TECHNOLOGY TECHNICAL PROFICIENCY
More informationTesters: / Ohmmeters Insulation Measuring Instruments. n Compact and rugged for service calls and laboratory use. Scope of delivery:
Table of Contents Testers: / Ohmmeters Insulation Measuring Instruments 51 METRAOHM 413 Article: M630A Digital Low-Resistance Measuring Instrument for Measuring Protective Conductors, Equipotential Bonding
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationNATIONAL SENIOR CERTIFICATE GRADE 12
NATIONAL SENIOR CERTIFICATE GRADE 12 ELECTRICAL TECHNOLOGY NOVEMBER 2008 MEMORANDUM This memorandum consists of 12 pages. Electrical Technology 2 DoE/November 2008 QUESTION 1: TECHNOLOGY, SOCIETY AND THE
More informationAC/DC DIGITAL CLAMP METER OPERATION MANUAL
AC/DC DIGITAL CLAMP METER OPERATION MANUAL HYS005661 A0 ACCESSORIES 6. ACCESSORIES 1) Test Leads: Electric Ratings 1000V 10A 1 pair (set) 2) Operating Manual 1 copy 3) 1.5V AAA Battery 3 piece - - 55 -
More informationSection 3. Test Procedures
Section 3. Information contained within this section shall be read in conjunction with all sections of this manual Non - Compliant Test Results Where acceptable results are not attained in accordance with
More informationDigital Clamp Meter. User Manual
Digital Clamp Meter User Manual CM240 WWW.OWON.COM.CN Mar. 2016 edition V1.2 Copyright LILLIPUT Company. All rights reserved. The LILLIPUT's products are under the protection of the patent rights, including
More informationELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL
ELECTRONIC SHEAR PIN MODEL ESP 1 & 2 INSTRUCTION MANUAL ESP Product Warranty Zener Electric warrant the Electronic Shear Pin against defective workmanship and materials for a period of 24 months from the
More informationMM700. True RMS ENGLISH. INSTRUCTION MANUAL Auto-Ranging. Measurement Technology
INSTRUCTION MANUAL Auto-Ranging Digital Multimeter er True RMS Measurement Technology MM700 DATA & RANGE HOLD LOW IMPEDANCE AUDIBLE CONTINUITY MIN / MAX / RELATIVE TEMPERATURE DIODE TEST CAPACITANCE &
More informationCatalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009
Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred
More informationDIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS
CONTENTS CONTENTS CONTENTS 1. SAFETY INFORMATION...1 1.1 Preliminary...1 1.2 Dos and don ts...2 1.3 Symbols...3 1.4 Precautions...4 2. DESCRIPTION...5 2.1 Names of parts...6 2.2 Switches, buttons and input
More informationSRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS
ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase
More informationTN, TT & IT Earthing Arrangements
TN, TT & IT Earthing Arrangements In IT and TN-C networks, residual current devices are far less likely to detect an insulation fault. In a TN-C system, they would also be very vulnerable to unwanted triggering
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More informationMM V 10A ENGLISH. INSTRUCTION MANUAL Auto-Ranging DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE
INSTRUCTION MANUAL Auto-Ranging Digital Multimeter MM400 DATA HOLD AUDIBLE CONTINUITY MIN / MAX TEMPERATURE DIODE TEST CAPACITANCE 600V 10A 40MΩ 2 GENERAL SPECIFICATIONS Klein Tools MM400 is an auto-ranging
More informationPEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D
PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D T8211D 1 1. SAFETY INFORMATION BE EXTREMELY CAREFUL IN THE USE OF THIS METER. Improper use of this device can result in electric shock or destroy of
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More information1650 Series Multifunction Installation Testers
1650 Series Multifunction Installation Testers New RCD Type B Compatibility Extra functionality, faster testing, and as rugged as ever Fluke 1654B Fluke 1653B Fluke 1652C Safer, easier installation testing.
More informationNATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009
NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009 (12041013) 3 November (X-Paper) 09:00 12:00 This question paper consists of 5 pages. (12041013) -2- NC740(E)(N3)V TIME:
More informationArticle 225: Outside Branch Circuits And Feeders
Part C: Code Book Questions Article 225: Outside Branch Circuits And Feeders 1.! Open (individual) aerial overhead conductors shall be insulated or covered when within! feet of a building.! (a) 10! (c)
More informationINSTALLATION, OPERATION AND MAINTENANCE GUIDE
INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation
More informationAlternating Current Power
Chapter 4 Alternating Current Power MElec-Ch4-1 Overview What is Alternating Current AC Hazards AC Power Requirements Shoreside Utility System On-Board Generators MElec-Ch4-2 What is Alternating Current
More information1 SAFETY INSTALLATION OPERATION COMPONENTS FAULT DIAGNOSTICS FUNCTIONS TECHNICAL SPECIFICATIONS...
1 SAFETY... 2 1.1 Troubleshooting... 2 1.2 The microwave oven warnings... 2 1.3 Inverter circuit warnings... 2 1.4 Leak test (leak measurement)... 3 2 INSTALLATION... 4 3 OPERATION... 4 4 COMPONENTS...
More informationAgilent U1253B True RMS OLED Multimeter. Quick Start Guide
Agilent U1253B True RMS OLED Multimeter Quick Start Guide The following items are included with your multimeter: Silicone test leads 4 mm probes Alligator clips Printed Quick Start Guide Rechargeable 8.4
More informationpage 2 of 86 Report reference No:
articulars: test item vs. test requirements 3. Classification 3.1. Utilization category: (A or B)... : A 3.2. Interruption medium: (air, vacuum, gas Break)... : Air 3.3. Design: (open construction, moulded
More informationChapter 6. WIRING SYSTEMS Safe Electrical Design
Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous
More informationKeysight U1461A Insulation Multimeter/ U1453A Insulation Tester
Keysight U46A Insulation Multimeter/ U453A Insulation Tester Quick Start Guide Standard Accessories Included In Your Purchase Standard Accessories Included In Your Purchase The following accessories are
More informationElectrical IP Red Seal Practice Exam
Electrical IP Red Seal Practice Exam PRACTICE EXAM-3 1. What size 2 pole breaker must you use on a 3HP, 115V single phase motor? A. 40A B. 50A C. 80A. D. 100A. 2. An electrical equipment approved for use
More information312, 316, 318. Clamp Meter. Users Manual
312, 316, 318 Clamp Meter Users Manual PN 1989445 July 2002 Rev.2, 2/06 2002, 2006 Fluke Corporation. All rights reserved. Printed in China. All product names are trademarks of their respective companies.
More informationPSSI 27 Work or Testing On or Near to High Voltage Direct Current (HVDC) Plant and Apparatus
1. SCOPE This Safety Instruction applies the principles established by the ScottishPower Safety Rules (Electrical and Mechanical) and the Company Safety Instructions to achieve Safety from the System for
More informationpower Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.
Knowledge is power The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits. Written by: Paul Sayer Technical Standards Manager for Hager Contents 2 Conductor
More informationSingle & Three Phase Transformers SAMPLE. Learner Workbook. Version 1. Training and Education Support Industry Skills Unit Meadowbank
Single & Three Phase Transformers Learner Workbook Version 1 Training and Education Support Industry Skills Unit Meadowbank Product Code: 5634 Table of Contents Introduction... 5 Section 1. Transformer
More informationCurrent Probes. User Manual
Current Probes User Manual ETS-Lindgren Inc. reserves the right to make changes to any product described herein in order to improve function, design, or for any other reason. Nothing contained herein shall
More informationIndustrial Electrician Level 3
Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide
More informationAgilent U1211A, U1212A, and U1213A Clamp Meter. Quick Start Guide U1211A U1212A U1213A
Agilent U1211A, U1212A, and U1213A Clamp Meter U1211A U1212A U1213A The following items are included with your clamp meter: Standard test leads with 19 mm probes Soft carrying case and 4 mm probes Certificate
More informationSnap Action Switches Technical Guide
These basic principles apply to all our precision switches. The specific characteristics of each model are given in more detail in the relevant production sections. Switch construction Single-pole changeover
More information2014 NEC Changes Part 1
www.garyklinka.com Page 1 of 8 Instructions: Fee $20 1. Print these pages. 2. Circle the correct answers and transfer them to the answer sheet. 3. Page down to the last page for the verification forms
More informationINDEX. Micro-ohmmeter MH-10 Page 3. MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4
Micro-ohmmeter MH-10 Page 3 MI (5, 10, 15, 20 kv) Page 4 Mega-ohmmeter MD (5 kv) Page 4 Earth resistance meter TL-5 Page 5 Indirect earth contact simulator MPC (5, 20, 50 A) Page 6 Trip time tester CR
More informationUser Manual Digital Multimeter
User Manual Digital Multimeter model no.: MSR-R500 Questions or Concerns? support@etekcity.com visit etekcity.com for more products Safe and Proper Usage Thank you for purchasing the Etekcity MSR-R500
More informationBlock Contactors. Contents. Panorama 3-pole Contactors... 2/2 4-pole Contactors... 2/4
/0 Block Contactors Contents Panorama -pole Contactors... / 4-pole Contactors... /4 -pole Contactors: Description and Ordering Details A 9... A 0 Contactors (a.c. Operated)... /6 A 4... AF 60 Contactors
More informationINSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.
INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD. CONTENTS 1. SAFE TESTING... 1 2. PROCEDURE OF REMOVING COVER... 4 3. FEATURES... 5 3.1 Instrument Layout...
More informationInstallation and Operational Instructions for ROBA -switch Type 017._00.2
OBA -switch Type 017._00.2 Guidelines on the Declaration of Conformity A conformity evaluation has been carried out for the product in terms of the EC Low Voltage Directive 2014/35/ EC and the EMC Directive
More informationPortable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No
Portable Appliance Testers OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver. 1.2. Code No. 20 750 684 Distributor: Producer: METREL d.d. Ljubljanska 77 SI-1354 Horjul E-mail: metrel@metrel.si http://www.metrel.si
More informationMAHARASHTRA STATE BOARD OF TECHNICAL EDUCATION
Important Instructions to examiners: 1) The answers should be examined by key words and not as word-to-word as given in the model answer scheme. 2) The model answer and the answer written by candidate
More informationIGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards
APPROVED IGS Iranian Gas Standards Contactors. Fax:(9821)-8131-5679 --. /012 34-52673892 :;395- 8? /@A7 B;CD /E FGH 34-52673892I2
More informationMIT415 Insulation tester
MIT415 Insulation tester General features o 10V & 100V ESD testing o 25V, 50V, 250V & 500V additional ranges o Insulation testing up to 50Gohms (500V) o Continuity testing at 200mA or 20mA from 0.01ohms
More informationMFT1800 series. Multifunction testers. User manual
M MFT1800 series Multifunction testers User manual 1 Contents X.1 SAFETY WARNINGS 4 1. Introduction 5 2. Overview 6 2.1 Front panel and controls 6 2.2 Waste electrical and electronic equipment 9 2.3 Battery
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationNZQA registered unit standard version 2 Page 1 of 8. Demonstrate knowledge of theory for registration of electrical installers
Page 1 of 8 Title Demonstrate knowledge of theory for registration of electrical installers Level 3 Credits 3 Purpose This unit standard covers the theory assessment required for registration as an electrical
More informationMS8250A/B OPERATION MANUAL MS8250A. Hz% FUNC REL RANGE REL HOLD OFF 10A. Hz% A NCV. Hz% COM. A ma 10A FUSED 600V CAT IV.
MS8250A/B DIGITAL MULTIMETER OPERATION MANUAL AUTO DC AC REL hfe PCLINK % C F kmωkz nµmfav MS8250A DIGITAL MULTIMETER Auto Power Off RANGE REL HOLD FUNC NCV A ma OFF 10A A ma 10A FUSED 600V CAT IV COM
More informationMFT1700 series. Multifunction testers. User manual
M MFT1700 series Multifunction testers User manual 1 Contents SAFETY WARNINGS...3 1. Introduction...4 2. Overview...4 2.1 Front panel and controls...6 2.2 Waste electrical and electronic equipment...6
More information1507/1503. Insulation Testers. Users Manual
1507/1503 Insulation Testers 1507/1503 Insulation Testers Introduction The Fluke model 1507 and model 1503 are battery-powered insulation testers (hereafter, "the Tester"). Although this manual describes
More informationAMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS
AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published
More informationCommercial Microwave Technical Information. CAUTION All safety information must be followed as provided in Service Manual
Commercial Microwave Technical Information 0 V, 0 Hz Models RCS0MPA P00M RCS0A P00M RCS0PBDA P00M RCS0MPSA P00M RFSMPSA P00M RFSSWA P00M RCS0SWA P0M RCS0MPA P0M Due to possibility of personal injury or
More informationMiniature circuit-breakers S 280 UC series. System pro M. Technical data
Technical data 11 Robbie Rd. / Avon, MA 02322 T:(508)513-1000 F:(508)513-1100 70 Ernest St. / Providence, RI 02905 T:(401)781-7100 www.controllerservice.com System pro M Prior to connection of aluminum
More informationGROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER
GROUNDED ELECTRICAL POWER DISTRIBUTION Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER .0 Conductors for Electrical Power Distribution For single-phase transmission of AC power or
More informationNo. 139 Jinghai Third Road, BDA, Beijing, China, Office TEL. +86 (10) Website
PONOVO POWER CO., LTD No. 139 Jinghai Third Road, BDA, Beijing, China, 100176 Office TEL. +86 (10) 5908 9666 E-Mail Info@relaytest.com Website www.relaytest.com T1000 Series Universal Tester VERSION: DATE:
More informationResidual Current Operated Circuit-Breakers (RCCBs)
Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted
More informationMFT1800 Series. Multifunction testers. User Manual
MFT1800 Series Multifunction testers User Manual Contents X.1 SAFETY WARNINGS... 4 1. Introduction... 5 2. Overview... 6 2.1 Front panel and controls 6 2.2 Waste electrical and electronic equipment 9 2.3
More informationMM700. INSTRUCTION MANUAL Auto-Ranging Digital Multimeter True RMS
INSTRUCTION MANUAL Auto-Ranging Digital Multimeter True RMS Measurement Technology MM700 DATA & RANGE HOLD LOW IMPEDANCE AUDIBLE CONTINUITY MIN / MAX / RELATIVE TEMPERATURE DIODE TEST CAPACITANCE & FREQUENCY
More informationMV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING
Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star
More informationElectronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards
Electronically Commutated (EC) Motor Control with Solo, Select and Sync PWM Boards The Solo, Select and Sync PWM boards provide a pulse-width modulated (PWM) signal to the EC motor to control fan speed.
More informationGRAAD 12 NATIONAL SENIOR CERTIFICATE GRADE 12
GRAAD 12 NATIONAL SENIOR CERTIFICATE GRADE 12 ELECTRICAL TECHNOLOGY EXEMPLAR 2014 MEMORANDUM MARKS: 200 This memorandum consists of 13 pages. Electrical Technology 2 DBE/2014 INSTRUCTIONS TO THE MARKERS
More informationCommon Sensors. Understand the following sensors: Pull Up sensor Pull Down sensor Potentiometer Thermistor
Common Sensors Understand the following sensors: Pull Up sensor Pull Down sensor Potentiometer Thermistor Pull Up Switch (sensor) VERY low current 12 volt Pull Up Switch (sensor) VERY low current 12 volt
More informationSection L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES
Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE The following is PG&E's procedure for pre-energization inspections. For PG&E to provide the Load
More informationA resistor adds resistance to a circuit. Describe what the effect of adding resistance would have on the current flowing in the circuit.
A. Current, Potential Difference and Resistance 1a A student builds a circuit. The circuit is shown in Figure 1. Label the components shown in Figure 1. (3) Figure 1 Voltmeter Power Supply Diode Resistor
More information