Design Specifications Low Voltage Active Harmonic Filter

Size: px
Start display at page:

Download "Design Specifications Low Voltage Active Harmonic Filter"

Transcription

1 Design Specifications Low Voltage Active Harmonic Filter 1.0 General Description This section contains the design standards, general equipment type and configuration, components, product description, warranty and installation requirements for active harmonic mitigation and power factor correction, as provided by an active harmonic filter. Such equipment shall be utilized for the improvement of harmonic rich environments, along with the improvement of power factor, in AC electrical power systems. The manufacturer shall have been engaged in the engineering and production of electrical power equipment for a minimum of ten years. The finished product shall be designed, assembled, tested and shipped as a complete system by the manufacturer. Equipment finished in any other manner is not acceptable. 2.0 System and Environment Active filter equipment and systems shall be suitable for environments of either indoor or outdoor, intended as either stand-alone or integrated with other equipment, such as motor control centers, switchboards, switchgear and static switches, UPS or distributed generation. Equipment is intended for use with voltage classifications from 208 to 480vac. A step-up transformer shall be used for voltages above 480vac. Equipment shall be used on three phase, 3 wire, grounded wye, ungrounded wye, or delta wire systems at 50hz or 60hz. Equipment is designed for reliable operation in ambient temperatures of 0 degrees C to 40 degrees C, up to 3250 feet (1000 meters) above sea level, with relative humidity of 95%. The finished Electrotek / Enersine ESD33 equipment shall be listed to UL508, C-UL. 3.0 Basic Equipment Type The Electrotek / Enersine ESD33 active harmonic filter is an assembly intended to monitor the non-linear load and dynamically correct a wide spectrum of harmonic orders. Active filter technology shall utilize power electronics for its operation and functions such as switching, cancellation, injection, monitoring and controlling AC and DC power. Power semi- conductors shall switch the AC power to modulate and control output, which cancels detrimental harmonic and/or reactive currents. DC bus power shall provide storage for semiconductor switching. Semi-conductors shall have current limiting protection. A microprocessor shall provide control, monitoring and operational functions for the complete active harmonic filter apparatus. When installed, the active filter shall provide 5% (Total Demand Distortion) TDD; 5% (Total Harmonic Distortion-Voltage) THDv; and specific power factor correction value at the load, where applicable, while not affecting the load in the form of a resonance condition. Corrected current distortion shall include all odd orders from the 3rd through the 51 st harmonic order. Each harmonic order shall maintain a consistent and maximum level of performance. 1

2 A resonant condition occurring within the electrical power system between the active filter and the load shall not cause the active filter to stop functioning properly. Equipment which cannot correct a wide harmonic spectrum and be capable to operate in a resonance condition to a minimum of the 51 st harmonic order is not acceptable. A constant, proportional value of power factor correction compensation shall be inherent in the design of the active filter, along with the capability to allow for the use of separate, additional power factor correction capacitor modules. Active filters shall operate in full compensation mode without shut-down, should additional loads be added (no overload). Heat loss (watts) shall be at a minimum. Active harmonic filter apparatus that derates harmonic cancellation performance when a power factor correction mode is operational is not acceptable. The expandable design of the active filter shall allow for additional (up to six) active filters to be installed in a parallel arrangement, and also allow use of existing active filters on the electrical system. Placement of the equipment shall be to mitigate single, or multiple loads, or a complete facility load. The active harmonic filter shall be installed at either the load or source location. Individual ampere ratings shall be provided at 25 ampere, 50 ampere, 100 ampere, 150 ampere and 200 ampere. The power electronics of the active filter shall be designed to operate well within the tolerance of the intended environment, utilize fan cooling and be properly ventilated. Power fuses (Class J), rated at 200kaic, shall be provided for protection of the power electronic IGBT (switched at 20 khz) modules. When initially energized, the active filter DC capacitor charge - soft start time shall be 10 seconds. Steady state at 100% step load (zero amperes to rated compensation amperes) shall be <40ms. Equipment shall allow for wall mounting (to 50 amperes) and free-standing (100 amperes and above) configurations. In addition, and where integration is required, equipment shall provide incoming, active filter, capacitor, motor control, or switchgear sections, where applicable. Compartments or sections shall be segregated as required. The active filter shall be available as a three wire apparatus. The active filter shall include two current transformers (CT s), for connection during installation (phases A and C), for a three wire connection. Standard split-core type CT size shall be 2000:1, 20va, 400 hz, with <1ms transient response time to detect load current. A DSP controller, with Discrete Fourier Transform (DFT) algorithm topology and analysis/calculate performance response time of minimum <20ms shall be provided. Controller shall allow for global or specific harmonic order settings (such as 3 rd, 5 th, 7 th, 9 th, 11 th simultaneously). Controller shall be positioned on the front panel of the enclosure with display and keypad as part of the active filter system and shall be easily viewed. The graphic display shall be an LCD type, with multiple functions for operation and maintenance control, with 16 line and 40 character capability. Management and control access to the load, source and Electrotek / Enersine ESD33 data shall be provided to the user. 2

3 The display shall provide man-machine interface, and analyzer, operating data status and alarm information, while functioning, and allow the operator to utilize keypad/scrolling utilities. Parameters available for display, at a minimum shall include: Graphics display with wave form, measurements and spectrum data to the 31 st order, four LED indicator and eight control/keypad utilities for On/Off, Reset (Alarm-Reset), Power On indicator, Filtering indicator, Full Correcting indicator, Error indicator, Confirmation (keypad), Direction Scrolling (keypad), Escape/Cancel (keypad). At a minimum, AC line voltage, total rms current, harmonic current, reactive current, output harmonic and reactive current of power correction shall be displayed values. A total of (5) five dry contacts (250vac/2amp) shall be provided for remote monitoring. Communications via RS 232 shall be provided as standard. Additional communications for RS 422, RS 485, USB, TCP/IP and Ethernet RJ45 shall be included where applicable. Controllers without capabilities as described above are not acceptable. The active harmonic filter shall meet specific performance standards for harmonic mitigation, surge immunity, electromagnetic compatibility, design and safety: IEEE519 / EN Harmonic Mitigation Guidelines IEEE587/ANSI C62.41/ EN Surge Immunity FCC Part 15 / EN55011 Electromagnetic compatibility UL508, C-UL / EN60146 Safety/Design EN50178 Vibration Testing, Safety/Design 4.0 Equipment Specifications and References A. Low voltage power distribution equipment, motor control centers, switches switchboards, switchgear, static switches, fixed motor load and switched power factor correction capacitors and harmonic mitigation systems B. Medium voltage switchgear, switches and static transfer switches C. Medium voltage metal enclosed capacitors and harmonic filters D. Engine-generator control, distributed generation systems, paralleling switchgear E. Energy management and other power quality equipment and components A. American National Standards Institute (ANSI) B. Institute of Electrical and Electronic Engineers (IEEE) C. National Electrical Manufacturers Association (NEMA) D. Underwriters Laboratories, Inc (UL) E. Canadian Standards Association (CSA) F. International Electromechanical Commission (IEC) G. European Standards (EN) H. National Electric Code (NEC) 3

4 5.0 Submittals Documentation for approval or reference shall be submitted in a CAD format. Common information, where applicable, shall include equipment plan view and outline dimensions, active filter sections, incoming locations, cable entry, main bus, fuse and active filter ratings, and where applicable capacitor ratings, mounting locations, and component technical descriptions. 6.0 Construction Guidelines Equipment design shall follow the most recent applicable standards and guidelines and shall serve to meet the intended application requirements. Installation and operation of equipment is for general business, commercial, industrial, government and energy or utility service providers. The enclosure assembly shall be from 14-gauge sheet steel, with wall mounted enclosure and freestanding enclosure construction of bolted design, to allow for ease of expansion, where applicable. Enclosures shall be finished with a texture and painted light gray, or other color as specified. The complete assembly shall be painted using electrostatically applied polyester powder coated paint, or a liquid enamel application, both, which provides for enhanced durability and extended protection. The finished enclosure shall provide both front and rear access via hinged doors or bolted, removable panels. Wall mounted enclosures shall allow for front access to internally mounted components. Doors shall be equipped with a latch-close system and include a key lockable feature, where applicable. Hardware shall be environmentally sound; either zinc plated or stainless steel, for optimum corrosion resistance. The entire assembly shall provide adequate personnel safety and component security. Cable entry shall be from the bottom with a grounding termination point included within the enclosure. A separate disconnect means may be required by NEC. Lifting lugs shall be provided for transport and to facilitate ease of installation of the finished equipment. Such removable lugs shall be located at the top of the equipment. Equipment manufactured in accordance to Electrotek / Enersine. Enclosures shall be rated as NEMA 1 or NEMA 12 (indoor) and NEMA 3R (outdoor). Where applicable, louvers shall be included for proper ventilation. For specific indoor or outdoor applications, aluminum mesh filters, fan(s) and heater(s)/thermostat(s) shall be incorporated in the assembly. The design and construction integrity of the finished assembly shall allow for the equipment to be lifted, or slid into place. The ready to ship equipment shall meet stringent, applicable engineering and design standards and be neatly constructed and finished, meeting all Electrotek / Enersine ESD33 quality and production control standards, prior to shipment. 4

5 7.0 Systems Integration The active filter shall be compatible to allow other power quality related components and devices to be incorporated, allowing for maximum equipment provisions. Where applicable, the equipment shall be designed in such a manner for system and physical integration or match and line with new or existing power distribution equipment. The active filter itself shall be suitable for mounting in other power distribution or control equipment, where applicable. AC or DC variable frequency drive applications shall utilize a 3% (minimum impedance) line reactor/isolation transformer, where applicable. 8.0 Testing and Safety The equipment shall be production tested, prior to shipment. This will include, at a minimum, mechanical functional operation, electrical functional operation, control wiring and circuit continuity, and polarity verification. Major electrical, electronic, and mechanical components and devices integral to the equipment shall include testing reports and technical information and other such data, where applicable. A manual for the purpose of operation and maintenance instruction shall be included with the finished equipment. The finished equipment shall include nameplates, labels, and other decals, providing applicable safety and general operation instruction. Such markings shall be visually accessible and conveniently located both internally and externally. 9.0 Equipment Documentation The finished equipment shall be provided with design and construction documentation as a minimum: Physical dimension data, outline/plan elevation drawings, general component layout and technical information, weight and installation detail. Single line and three line drawings (where applicable) Control schematic and control program (where applicable) Component Bill of Materials Operations and Maintenance Instructions 10.0 Equipment Installation Correct installation is required for proper performance and function of the Electrotek / Enersine ESD33 active filter. Physical inspection of equipment for damage is recommended, prior to any installation. Indoor storage for indoor and outdoor rated equipment should be in a clean, dry environment, and where recommended, may require removal of packaging materials. 5

6 Outdoor storage of outdoor equipment shall require installation of any materials shipped for site assembly, such as fans and bus ducts and the mating of equipment shipping splits. Where recommended, packaging materials may be required to be removed. Equipment includes removable lifting lugs, for transport and site installation handling. As a cautionary note, placement of the active filter shall be at a level and solid location, for correct operation. National Electrical Code (NEC), electric utility company or service provider codes shall be adhered to during the installation. Electrical connections shall also be in compliance with required codes. Installer/Contractor shall inspect and verify proper alignment, anchorage and ground, proper connections and tightness of connections, prior to any start-up functions. Appropriate personnel shall start-up and operate equipment upon installation approval. This may also include use of portable measuring devices or analyzers to verify performance of the Electrotek / Enersine ESD33 active filter. Section Operational Guidelines Electrotek / Enersine ESD33 is a solid-state power converter that brings about the following advantages: Eliminate all harmonic currents from non-linear loads. Compensate reactive power factor of lagging loads. Act as a virtual damping resistor to prevent possible harmonic resonance. Electrotek / Enersine ESD33 behaves like a harmonics current generator. E l e c t r o t e k / Enersine ESD33 will measure the harmonics generated from the non-linear loads and cancel these harmonics with a newly generated, opposite phase shifted harmonics current of the same amplitude. By cancelling the harmonic currents in the circuit, there will be (1) No risk of harmonic resonance; (2) Significantly reduce the voltage waveform distortion; (3) Reduced voltages drop on transformers & cables; (4) Reduced temperatures rise on transformers & cables; (5) Improved power factor Components of Electrotek / Enersine ESD33 Electrotek / Enersine ESD33 provides 3 phase harmonic current compensations, and the main components of the APF are as follow: 1 set of Ripple Current Filter module. Its main function is to absorb the high frequency ripple current and compensate specific amount of reactive power. 1 set of Electromagnetic Contactor module for soft-starting. It helps to limit the amplitude of the inrush current when DC capacitor set is charging. 6

7 1 set of High Frequency Inductor-Capacitor module. It acts as the power transmission interface component between power converter and power system. 1 set of IGBT Power Converter module. This is to transform the harmonics energy from the connected power system and re-generate an equal but opposite phase shifted harmonic current back to the power system. This re-generated energy will cancel the harmonics produced by the power system. 1 set of DC Capacitor module which store energy taken from the power system before the IGBT Converter can use it to re-generate the opposite phase shifted compensating harmonic current. c d c Power Breaker-Switch d High-Speed Fuse 3 Ripple Current Filter Module 4 Soft-start Electromagnetic Contactor Module 5 High Frequency Inductor-Capacitor Module 6 IGBT Power Converter Module 7 DC Capacitor Module 7

8 2-3. Brief Description of Components This section describes the working principles of the main components inside Electrotek / Enersine ESD Ripple Current Filter Module The Ripple Current Filter is shunt-connected at the output terminals of the Electrotek / Enersine ESD33. Its main function is to absorb high frequency ripple current and provide specific amount of reactive power compensation. Its main components consist of the following: (1) Parallel/Series link resonance filter. (2) Over-current protection relay (OL1). (3) Abnormal trip control device. Under the normal working condition, Ripple Current Filter will also provide partial reactive power factor to improve lagging power factor. The Over-Current Protection Relay (OL1) is incorporated to protect the Electrotek / Enersine ESD33. In the event when the IGBT Power Converter is malfunction, it may generate a large amount of high frequency current drifting into the Ripple Current Filter. This will cause the Over- Current Protection Relay to trip, thus shutting down the APF system to prevent further damage to the entire APF system. 2-5 Soft Start Electromagnetic Contactor Module The main function of this module is to inhibit inrush current when DC capacitor module is charging. When the voltage of the DC capacitor reaches its default value, the Electrotek / Enersine ESD33 will then be switched on to its normal operating mode. The main components for Soft Start Electromagnetic Contactor are as followings: (1) Current-limiting Resistor. (2) Electromagnetic Contactor. This module inhibits the inrush current going through the IGBT Power Converter into the DC capacitor module within a certain level, while closing the power break-switch. After switching on the Electrotek / Enersine ESD33, the Electromagnetic Contactor will close to make the IGBT Power Converter truly connected with the power system and bypasses the current-limiting resistor. 2-6 High Frequency Inductor-Capacitor Module The Inductor & Capacitor are the power transmission interface components between the IGBT Power Converter and the connected power system. It also compensates the reactive power for the lagging power factor. The main components of the High Frequency Inductor-Capacitor Module are: (1) High frequency response inductor. (2) High frequency response capacitor. (3) Current transformer. 10

9 The current transformer is use to feedback the harmonic compensating current to a control circuit, this will allow the Electrotek / Enersine ESD33 to performance a high-speed compensation and ensure a current-limit if the harmonics energy exceeded its capacity. 2-7 IGBT Power Converter Module The IGBT Power Converter is the major architecture of the Electrotek / Enersine ESD33 in the cancellation of the harmonic current (ILh) generated by the connected non-linear load. The IGBT Power Converter make use of this harmonic energy (ILh) as an initial power, to produce an opposite phase shifted harmonic current waveform (IE). This waveform is then re-injected into the connected power system to cancel the existing harmonics distortions (ILh), ensuring a near perfect sine waveform (Is) returning to the Power Mains. The main components of the IGBT Power Converter Module are: (1) IGBTs bridge (2) Driver circuit (3) Snubbers The electronics bridge of the power converter is made up of Isolated Gate Bipolar Transistor (IGBT) and utilizes Pulse Width Modulation (PWM) technology to drive the IGBTs to produce compensating current waveform. Built-in Snubbers are use with the IGBT for protection from spikes when the Power Converter is in operation. 2-8 DC Capacitor Module DC Capacitor Module stores the energy (ILh ) generated by the connected power system, to be use by the IGBT Power Converter for re-generation of the opposite phase shifted compensating harmonic current waveform (IE). The storing and releasing of energy of the DC Capacitor Module is electrically control by the IGBT Power Converter. The DC Capacitor Module is made up of a specific numbers of similar rating DC capacitors connected electrically in parallel. 11

10 1-4. System Structure Schematic Diagrams Drawing 1-1 Electrotek / Enersine ESD33 System Structure Schematic Diagram 12

11 3-0 Characteristics & Specifications General Characteristics Equipment storage temperature -20ºC to +70ºC Operating Temperature +12ºC to +25ºC (Recommend Range), + 0ºC to +40ºC (Tolerate Range) Relative Humidity < 95% Operating Altitude < 1000 m Reference Harmonic Standard EN , IEEE Reference Design Standard EN60146 Safety Standard EN50178 Electromagnetic Compatibility EN55011, EN , EN , EN , EN , EN , EN , EN Electrical Specification Category Unit 25A 50A 100A 150A 200A Line Voltage V 208/380/400/480 ±15% Phase/Wires ES33 series for 3 phase 3 wires Frequency Hz 50/60 ±3 Compensating Current in Phase Arms (2) Transient Response Time msec < 1 Inrush Current Less than rated current Current Limitation Yes, at full correcting Soft Start Sec 10 Heat-losses Watt Audible Noise from 1 Meter dba Mechanical Specification Category Unit 25A 50A 100A 150A 200A Color RAL9001 Protection Index IP20 Dimensions (W x D x H) Weight ES33 series ES33 series mm kg 410 x 390 x x 810 x x 810 x (1) It is the total time from detection to steady compensation at 100% step load is less than 40 msec. 13

12 4-0 Compensation Ability The Compensation ability of the Electrotek / Enersine ESD33 is defined in term of Harmonic Attenuation Ratio (HAR). HAR = ILh / ISh HAR : Harmonic attenuation ratio ILh : Harmonic current at load side ISh : Harmonic current at power source side ISh IE ESD Equipment Warranty The manufacturer shall provide its standard warranty for equipment of this type. The warranty shall provide for repair of replacement of the equipment, should it be found to be defective within twelve months from the date shipment. Approved Supplier: Electrotek Ltd AV SE Calgary, AB T2G 1V4 Tel: ( )

13

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned Part 1 - General Scope and Product Description 1.0 This specification contains the minimum design

More information

Type AHF Active Harmonic Filter

Type AHF Active Harmonic Filter Type AHF Active Harmonic Filter User s Manual 16964 West Victor Road New Berlin, WI 53151 (262) 754-3883 Fax: (262) 754-3993 Web site: www.artechepq.com 2008 October Form No. M3-2001 Form No. M3-2001 CONTENTS

More information

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

APQline Active Harmonic Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) APQline Active Harmonic Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Power electronic equipment and AC-DC power conversion equipment contribute

More information

Active Harmonic Filter

Active Harmonic Filter Reactive Power and Harmonic Compensation Active Harmonic Filter The new StacoSine Plus active harmonic filter is available in 100, 150, 200 and 300 amp assemblies. Modules can be paralleled for a maximum

More information

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED

SECTION LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED SECTION 16280 LOW VOLTAGE ACTIVE HARMONIC FILTER SYSTEM NEMA 1 ENCLOSED PART 1 - GENERAL 1.1 SUMMARY This specification defines the requirements for active harmonic filter systems in order to meet IEEE-519-2014

More information

S11 Adjustable Speed Drive Engineering Specification

S11 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3- phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC. 1.1 References A. National

More information

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters

DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters Section [26 35 26][16280] Active Harmonic Filters (Low Voltage) Part 1 General 1.1 Summary A. Scope: Provide design and engineering, labor,

More information

TOSHIBA International Corp

TOSHIBA International Corp TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification

More information

VF-nC1 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba VF-nC1 AC Variable Frequency Drives, 6 pulse for 100V single-phase 0.1 to 0.75kW, 200V single-phase 0.2 to 2.2kW and 200V threephase 0.1

More information

E3 Adjustable Speed Drive Engineering Specification

E3 Adjustable Speed Drive Engineering Specification E3 Adjustable Speed Drive Engineering Specification PART 1 - GENERAL 1.0 Scope This specification shall cover Toshiba E3 AC Variable Frequency Drives, 6 pulse for 230V and 460V. 1.1 References A. National

More information

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors.

These true on-line inverters incorporate pulse width modulation (PWM) control combined with high frequency igbt power transistors. Industrial Inverter The Gentec inverter systems, OND2 SERIES, provide safe, pure sine wave, reliable power to critical control equipment. These inverters are online type, usually the load is fed by the

More information

Power Processor - Series 700F 10KVA to 150KVA

Power Processor - Series 700F 10KVA to 150KVA Power Processor - Series 700F 10KVA to 150KVA Power Conditioning and Regulation for Commercial & Industrial Equipment General Specifications PART 1 - GENERAL 1.1 DESCRIPTION This specification defines

More information

Phoenix DX Clean Power (18 Pulse) AC Drive

Phoenix DX Clean Power (18 Pulse) AC Drive PHOENIX DX Phoenix DX Clean Power (18 Pulse) AC Drive Poor power quality can be costly. Nonlinear loads, including AC Drives, introduce undesirable harmonic currents into the power system that can damage

More information

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian) 1.0 General This specification covers the electrical characteristics and

More information

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation

Variable Frequency Drive Packages with Harmonic Mitigation. Low Harmonic Drive Packages Engineered by Rockwell Automation Variable Frequency Drive Packages with Harmonic Mitigation Low Harmonic Drive Packages Engineered by Rockwell Automation What Do I Need to know About Harmonics? What are Harmonics? Harmonics are deviations

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse

ADJUSTABLE SPEED DRIVES. HX7 Series. 18-Pulse ADJUSTABLE SPEED DRIVES HX7 Series 18-Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Power IT LV Active Filters PQFA - PQFL - PQFT

Power IT LV Active Filters PQFA - PQFL - PQFT Power IT LV Active Filters PQFA - PQFL - PQFT The ABB comprehensive solution for active filtering of harmonics Pst Harmonics and Power Quality Harmonics caused by non-linear electrical loads such as variable

More information

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web: -

ADJUSTABLE SPEED DRIVES. HX7 Series. 18 Pulse. Phone: Fax: Web:  - ADJUSTABLE SPEED DRIVES HX7 Series 18 Pulse Toshiba HX7 In some industrial applications, users need reliable and efficient adjustable speed drives that do not contribute significant harmonic distortion

More information

Harmonic Correction Unit NEMA 1 Enclosure

Harmonic Correction Unit NEMA 1 Enclosure ffective: June 2001 Page 1 New Information Harmonic orrection Unit ontents Description Page Harmonic orrection Unit Specifications.......... 2 Sizing and Selection.............................................

More information

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics

Power IT LV Active Filters PQFI PQFM PQFK. The ABB comprehensive solution for active filtering of harmonics Power IT LV Active Filters PQFI PQFM PQFK The ABB comprehensive solution for active filtering of harmonics Harmonics and Power Quality Power Quality relates to the amplitude, frequency and distortion of

More information

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS 1.0 SCOPE The following specification describes the features, design, and application of the Series 7200A

More information

StatiVolt. Inverter UPS Systems. Features. Contents

StatiVolt. Inverter UPS Systems. Features. Contents Redundant, clean, sine-wave AC power ensures a high availability of mission-critical safety devices, instrumentation, alarms, controls and computers. Robust, StatiVolt UPS Systems are designed and built

More information

INTELLIMETER REGISTER

INTELLIMETER REGISTER INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products

More information

Power-Sure 700. Technical Data TD158001EN. Contents

Power-Sure 700. Technical Data TD158001EN. Contents Technical Data TD158001EN Power-Sure 700 Supersedes August 2015 Contents Description Page General description... 2 Power-Sure 700 benefits.... 2 Specifications... 3 Industry standards and certifications...

More information

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse

ADJUSTABLE SPEED DRIVES. W7 Series. 18 Pulse ADJUSTABLE SPEED DRIVES W7 Series 18 Pulse Meets or Exceeds Your Specifications Standard Specifications Item Voltage Class 460V Maximum HP 60 75 100 125 150 200 250 300 400 500 600 700 800 Drive Rating

More information

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors.

These true online inverters integrate pulse width modulation (PWM) control combined with high frequency IGBT power transistors. Three-phase Industrial Inverter OND4 SERIES The new OND4 SERIES inverter provides safe, pure sine wave, single-phase or three-phase reliable power to critical control equipment. These inverters are of

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS)

WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) WAVEFORM CORRECTOR (WAVEFORM CORRECTORS) REPLACES SURGE PROTECTION DEVICES (SPD) PREVIOUSLY KNOWN AS (TVSS) 1 PART 1: GENERAL This section describes materials and installation requirements for low voltage

More information

SECTION AUTOMATIC TRANSFER SWITCH

SECTION AUTOMATIC TRANSFER SWITCH SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.

More information

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing.

2.1 Performance Standards The UPS is designed with the applicable sections of UL, CUL, and ISO The UPS has UL and CUL listing. 1.0 Scope This document describes the specification for Toshiba 1000 Series On-Line Uninterruptible Power System (UPS). The UPS will supply a computer grade AC output sine wave which is unaffected by the

More information

PowerGard Series C 18-Pulse Enclosed Drive Controllers

PowerGard Series C 18-Pulse Enclosed Drive Controllers PowerGard Series C 18-Pulse Enclosed Drive Controllers Combining adjustable speed drive and power quality solutions PowerGard Series C 18-Pulse Enclosed Drive Controllers Combining adjustable speed drive

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM SECTION 263353 - THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM PART 1 GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

High Frequency SineWave Guardian TM Filter

High Frequency SineWave Guardian TM Filter High Frequency SineWave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL WARNING High Voltage! Only a qualified electrician can carry out the electrical installation of this filter. Quick Reference

More information

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V

Technical Data Sheet. Uninterruptible Power Supply On-line VH Series UPS. Critical Power UL / 208V Technical Data Sheet Uninterruptible Power Supply On-line VH Series UPS 2000-3000 UL / 208V GE Consumer & Industrial SA General Electric Company CH 6595 Riazzino (Locarno) Switzerland T +41 (0)91 / 850

More information

High Frequency Sinewave Guardian TM Filter

High Frequency Sinewave Guardian TM Filter High Frequency Sinewave Guardian TM Filter 380V 480V TECHNICAL REFERENCE MANUAL FORM: SHF-TRM-E REL. April 2015 REV. 001 2015 MTE Corporation Caution Prior to start up; confirm the drive operation mode

More information

Low Pass Harmonic Filters

Low Pass Harmonic Filters Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power

More information

Gutor PxW AC UPS Designed for North American Market

Gutor PxW AC UPS Designed for North American Market Gutor PxW AC UPS Designed for North American Market PEW 5 200 kva single phase PDW 10 220 kva three phase Higher ratings upon request schneider-electric.com 2 schneider-electric.com schneider-electric.com

More information

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz

INSTRUCTION MANUAL. Type SWF. Sine Wave Filters 690 Volts, 50Hz POWER QUALITY INSTRUCTION MANUAL Type SWF Sine Wave Filters 690 Volts, 50Hz Page 2 of 24 Contents 1. Introduction & SAFETY 2. Theory of operation 3. Typical results of the Sine Wave Filters 4. Transportation,

More information

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control. Section 16680 VARIABLE SPEED DRIVE SYSTEMS OR AFD Part I - GENERAL I.01 Description A. This specification is to cover a complete adjustable frequency motor drive consisting of a pulse width modulated (PWM)

More information

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK

SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK SPECIFICATION FOR HORIZONTAL AIRFLOW OUTDOOR RESISTIVE LOAD BANK PART 1.0 GENERAL 1.1 SCOPE A. This specification contains the minimum requirements for the design, manufacture and testing of a UL listed,

More information

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, and withstand

More information

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS

NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS NGS INVERTER REPLACEMENT SCOPE OF WORK & SPECIFICATIONS TABLE OF CONTENTS Section 1.0 General... 3 1.1 Work Included... 3 1.2 Related Work... 3 1.3 System Description... 3 1.4 System Operation... 4 1.5

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers

Power Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers EPCOS Product Brief 2017 Power Quality Solutions of Active Harmonic Filters and Power Optimizers EPCOS has been offering a comprehensive range of key components for power factor correction (PFC) and power

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Frequency Converter SFX 10kVA - 10MVA Static Frequency Converter SFX 10kVA - 10MVA A Concept Thycon Static Frequency Converters (SFX) convert supply frequency to load requirement frequency.

More information

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING 1.0 General This specification covers the electrical characteristics and general

More information

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL 1.1 SUMMARY Liebert NX UPS GUIDE SPECIFICATIONS 40-80kVA, 80-120kVA and 160-200kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL This specification defines the electrical and mechanical

More information

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems SECTION 26 33 53 - STATIC UNINTERRUPTIBLE POWER SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. This specification defines the electrical and mechanical characteristics and requirements for a continuous-duty three-phase,

More information

SECTIONS , (15040, 15767, 15950, 16269) Guide Specification for VARIABLE SPEED DRIVES with Optional Bypass

SECTIONS , (15040, 15767, 15950, 16269) Guide Specification for VARIABLE SPEED DRIVES with Optional Bypass PART 1: GENERAL 1.01 SCOPE A. This specification describes the electrical, mechanical, environmental, agency and reliability requirements for three phase, variable speed drives as specified herein and

More information

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator)

PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) PRODUCT SPECIFICATION FOR A 15 THRU 500 kva, THREE PHASE, MODULAR POWER REGULATOR AND CONDITIONER PIRANHA 3 (3-phase, Power Conditioning Voltage Regulator) 1.0 General This specification covers the electrical

More information

Tap Changer Analyzer & Winding Ohmmeter RMO25TD

Tap Changer Analyzer & Winding Ohmmeter RMO25TD Tap Changer Analyzer & Winding Ohmmeter RMO25TD Test current 5 ma 25 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 9,5 kg Measuring range 0,1-2 k Two voltage sense channels

More information

Dry Type Transformers Full Line Catalog. jeffersonelectric.com

Dry Type Transformers Full Line Catalog. jeffersonelectric.com Dry Type Transformers Full Line Catalog jeffersonelectric.com The Transformer Authority PIONEER TRANSFORMERS: Why us? Scale We produce over 100,000 transformers every year. With this high level of production

More information

Tap Changer Analyzer & Winding Ohmmeter RMO60TD

Tap Changer Analyzer & Winding Ohmmeter RMO60TD Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels

More information

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL

Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power

More information

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.1 SUMMARY DISCONTINUED PRODUCT GUIDE SPECIFICATIONS 15-75 kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL These specifications describe requirements for a complete power conditioning and

More information

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN UNINTERRUPTIBLE POWER SYSTEMS PF >0.98 G8000MM Series 100 to 750 KVA UPS IGBT DESIGN 94% Efficiency Main Features State-of-the-Art Modular Design Provides Maximum Flexibility The Toshiba G8000MM Uninterruptible

More information

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1. TECHNICAL SPECIFICATIONS for Single Phase, 1 to 3 KVA Power Conditioner with Regulation and Distribution Constant Power 3 (CP3) CP36508A 7/15/04 1.0 General This specification covers the electrical characteristics

More information

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL SINGLE PHASE INSTRUCTION MANUAL DIAGRAM D This manual applies to all single-phase buck & boost transformers sold by Larson Electronics. Please refer to the connection diagram on pages 4-6 for properly

More information

PowerFlex 400 Submittal

PowerFlex 400 Submittal PowerFlex 400 Submittal Submittal Date: Project Name: Project Location: Consulting Engineer: Contractor: Contractor PO #: Distributor Name: Distributor Contact: Distributor Reference #: Note: This is general

More information

SHORE TO SHIP FREQUENCY

SHORE TO SHIP FREQUENCY POWER SYSTEMS INTERNATIONAL SHORE POWER POWER CONVERSION SYSTEMS 50Hz, 60Hz and 400Hz three phase and single phase There is a growing world focus on energy conservation with the drive towards reducing

More information

2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES

2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES 2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES Medium-voltage rack-mount power supplies Page 2 The MV2000 series high-performance, medium output

More information

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer

Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Lightweight 9,5 kg Test current 5 ma 40 A DC Measuring range 0,1-2 k Two voltage sense channels Extremely quick measurement Rapid automatic

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5

UBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS

More information

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans

LCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans LCL Series SIngle Output Industrial Supplies High Efficiency Low Cost 150 W Convection Cooled 300 W & 500 W with Internal Fans Outputs form 12 V to 48 V 3 Year Warranty The LCL series is a low cost chassis

More information

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL 1.1 SUMMARY GUIDE SPECIFICATIONS 100-200 kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL These specifications describe requirements for a complete power conditioning and distribution system,

More information

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS Copyright Mitsubishi Electric Power Products TABLE OF CONTENTS 1. SCOPE... 1 1.1 The System... 1 2. SYSTEM DESCRIPTION... 1 2.1 Components... 1 2.2 Modes

More information

TECHNICAL DATA SHEET B9600FXS kva

TECHNICAL DATA SHEET B9600FXS kva GENERAL INFORMATION TECHNICAL DATA SHEET B9600FXS 400-500-600-800 kva UPS Type ON LINE - Double Conversion Nominal output power (Cos 0.9) kva 400 500 600 800 Nominal output power (Cos 1.0) kw 360 450 540

More information

SECTION PANELBOARDS

SECTION PANELBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 16 PANELBOARDS SPEC WRITER NOTE: Delete between // --- // if not applicable to project. Also, delete any other item or paragraph not applicable in the section

More information

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD

RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES. Power Management Instruments ELECTRONIC STABILIZER FROM PMI & OES GROUP COMPANIES SUD RELIABLE SOLUTIONS in POWER ELECTRONICS VRST SERIES Power Management Instruments FROM PMI & OES GROUP COMPANIES SUD Today, as technology evolves, Electrical, Electronic and Electromechanical devices are

More information

SECTION DISTRIBUTION SWITCHBOARDS

SECTION DISTRIBUTION SWITCHBOARDS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 24 11 SPEC WRITER NOTES: Use this section only for NCA projects. Delete between // -- // if not applicable to project. Also delete any other item or paragraph

More information

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT

INPUT VOLTAGE STARTING MINIMUM NORMAL MAXIMUM MAXIMUM INPUT RANGE VOLTAFE VOLTAGE VOLTAGE VOLTAGE CURRENT RK-23/048RD100-7200 SPECIFICATION SCOPE This functional specification defines the performance characteristics of the switching mode regulated power supply, and also defines world wide safety requirements

More information

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION)

MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) GENERAL MANUFACTURING GUIDELINES FOR PLC (LEVEL-1 AUTOMATION) SUBMITTED BY SASHIKUMAR G BHARAT HEAVY ELECTRICALS LIMITED INDUSTRIAL SYSTEMS GROUP Prof. C. N. R. Rao Circle I. I. Sc. POST Malleswaram Bangalore

More information

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General Section 16621A - AUTOMATIC TRANSFER SWITCH Part 1 General 1.01 One 600 Amp, 3 Phase, 480 Volt Automatic Transfer Switch (ATS) shall be provided with gasketed enclosure. The ATS shall consist of an inherently

More information

INSTALLATION, OPERATION AND MAINTENANCE GUIDE

INSTALLATION, OPERATION AND MAINTENANCE GUIDE INSTALLATION, OPERATION AND MAINTENANCE GUIDE FOR INDOOR/OUTDOOR SINGLE PHASE ENCAPSULATED TRANSFORMERS Indoor/Outdoor Encapsulated Transformers The pictures used in this guide are only a representation

More information

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network

AccuSine PCS Active Harmonic Filter. Cruise through rough waves in your electrical network AccuSine PCS Active Harmonic Filter Cruise through rough waves in your electrical network How Can Active Harmonic Filters Solve Power Quality Issues in Your Facility? Power electronic devices that have

More information

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: 61-340 MODEL: 61-342 Multimeter Service Information The Service Information provides the following information: Precautions and safety information Specifications

More information

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262)

SWF DV/DT Solutions Sinewave Filters. N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI P. (262) F. (262) SWF DV/DT Solutions Sinewave Filters N52 W13670 NORTHPARK DR. MENOMONEE FALLS, WI 53051 P. (262) 754-3883 F. (262) 754-3993 www.apqpower.com Does your application use variable frequency drives for improved

More information

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives

2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives .0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is

More information

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS

UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS UNINTERRUPTIBLE POWER SUPPLY MODEL 9900B SPECIFICATIONS TABLE OF CONTENTS PART 1 GENERAL... 2 1.1 SUMMARY... 2 1.2 STANDARD... 2 1.3 SYSTEM DESCRIPTION... 2 1.3.1 Components... 2 1.3.2 Mode of Operation...

More information

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX SSE-N NEGATIVE FIELD FORCING SHUNT STATIC EXCITER/REGULATOR SYSTEM Control Chassis 6 SCR Power Chassis APPLICATION The SSE-N Negative Field Forcing Exciter/Regulator is used for both new and old installations

More information

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM

Liebert AF2 Next Generation Active Harmonic Filter. Power Protection for Business-Critical Continuity TM Liebert AF2 Next Generation Active Harmonic Filter Power Protection for Business-Critical Continuity TM LIEBERT AF2 You Need To Be Aware Of Harmonics During the last few years industries has witnessed

More information

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality. PART 1: GENERAL 1.01 Wiring Devices A. This section of the standard includes design requirements for wiring connections, including receptacles and switches to equipment specified in other sections. 1.02

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

W o r l d C l a s s P o w e r S o l u t i o n s Internal power supply UPS mains operation UPS battery operation Bypass operation Parallel operation Manual bypass Overload Inverter failure Mains failure

More information

USER MANUAL LDY CW Diode Driver Power Supplies

USER MANUAL LDY CW Diode Driver Power Supplies USER MANUAL LDY CW Diode Driver Power Supplies The LDY family of CW diode laser drivers is Lumina Power s second generation of high power laser diode drivers. As a laser diode driver, the LDY power supply

More information

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY -- D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial

More information

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS

GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS GENERAL PURPOSE DRY-TYPE DISTRIBUTION TRANSFORMERS Acme offers a large selection of Dry-Type Distribution Transformers. Ranging from 600 Volt and below, in both Single and Three Phase, you re sure to find

More information

EMI Installation Guidelines

EMI Installation Guidelines EMI Installation Guidelines Although Red Lion Controls Products are designed with a high degree of immunity to Electromagnetic Interference (EMI), proper installation and wiring methods must be followed

More information

Introduction: TAS PowerTek Ltd. MAVROS

Introduction: TAS PowerTek Ltd. MAVROS Introduction: Electrical supply system in today s scenario faces a major challenge due to Power Quality issues. Harmonics on supply system due to Electronics type of loads that are used extensively. Power

More information

Models 31120/31120A/31180/31180A Programmable AC Power Source

Models 31120/31120A/31180/31180A Programmable AC Power Source FEATURES: Power Rating: 31120/31120A: 12KVA 31180/31180A: 18KVA Voltage : 0-150V/0-300V/Auto Frequency: DC, 15Hz - 1500Hz 1-phase or 3-phase output selectable Programmable slew rate setting for changing

More information

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection: Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n

More information

BOP 1 KILOWATT 1000 WATTS OF FOUR-QUADRANT BIPOLAR POWER FROM KEPCO AN ISO 9001 COMPANY

BOP 1 KILOWATT 1000 WATTS OF FOUR-QUADRANT BIPOLAR POWER FROM KEPCO AN ISO 9001 COMPANY 146-1946 BOP 1 KILOWATT 1000 WATTS OF FOUR-QUADRANT BIPOLAR POWER FROM KEPCO KEPCO BOP 1 KILOWATT The BOP 1 Kilowatt has two primary control channels: and current. Either of these may be controlled from

More information

Est Static Frequency Converter. SFX 10kVA - 10MVA

Est Static Frequency Converter. SFX 10kVA - 10MVA Est.1968 Static Converter SFX 10kVA - 10MVA Concept Thycon Static Converters (SFX) convert supply frequency to load requirement frequency. Typical applications are 50 to 60Hz conversion for naval and 50

More information

Types VIS and CRE. A e. Compliance with Standards. Uses. Features

Types VIS and CRE. A e. Compliance with Standards. Uses. Features Fig. 1 Pure Sine Wave IGBT Controlled CCRs Types VIS and CRE Compliance with Standards FAA: AC 150/5345-10 (current edition), L-828, L-829 except for input voltage ICAO: Aerodrome Design Manual Part 5,

More information