Associated Documents

Size: px
Start display at page:

Download "Associated Documents"

Transcription

1 Tiger 320 Series SETOINTS & RELAYS SULEMENT This document is designed to supplement the information on the meter s programmable setpoints and optional relay output modules described in the Tiger 320 Series user manual. Associated Documents The following documents must be read together with this supplement: Relevant Tiger 320 Series User Manual The users manual provides general information on the relevant Tiger 320 Series meter. Tiger 320 Series rogramming Code Sheet (NZ0) The programming code sheet provides all meter programming codes including setpoint programming codes. Registers Supplement (NZ209) This supplement provides a detailed list of all registers available for setpoint source activation and reset functions. Advanced Calibration & On Demnad Mode Supplement (NZ203) This supplement provides detailed descriptions on all calibration related topics. rogramming Tip This document has been written using a DI-50 7-segment, 5-digit display meter. When programming meters with other display options, some display readings may vary to the diagrams shown. Note: All examples used throughout this document are for relays with NMALLY OEN contacts. 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age

2 General Notices & Tips The range of Tiger 320 Series supplements contain three graphic symbols to aid you: WARNING Symbol The WARNING symbol is generic to all Tiger 320 Series documents and indicates that if the instruction is not heeded, the action may result in loss of life or serious injury. NOTE Symbol The NOTE symbol is generic to all Tiger 320 Series user manual supplements and indicates important or helpful information on the topic being discussed. ROGRAMMING TI Symbol The programming tip symbol is generic to all Tiger 320 Series documents and indicates useful tips when programming the instrument. Definitions The following definitions are relevant to this document: X If an X appears in the description of a 3-digit programming code or in a configuration procedure, this means that any number displayed in that digit is not relevant to the function being explained, or more than one choice can be made. Meter Controller The term meter, as used throughout this document, is a generic term for all Tiger 320 Series signal processors and controllers age 2 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

3 Contents Table of Contents Setpoint Functional Overview Technical Specifications Technical Description Setpoint rogramming Mode Setpoint Activation Values Mode Setpoint and Control Settings Mode Electromechanical s Options Solid State s Opto-isolators Options GI-50 & GI-50B0 Meter s FI-B0D50 Bargraph s Level Basic Mode Level and Setpoint Configuration Sequence Level Functions Level 2nd Digit: Setpoint Activation Source Level st Digit: Energize Functions Level 3rd Digit: Latching and Reset Level Example Configuration rocedures Example Setpoint Activation Values Example Setpoint Control Settings LEVEL Setpoint Activation Values: Example rocedure LEVEL Energize, Latching, & Activation Source: Example rocedure Level 2 Intermediate Mode Level 2 and Setpoint Configuration Sequence Level 2 Functions Level 2 st Digit: Energize Functions Level 2 3rd Digit: Hysteresis, Deviation, and ID Level 2 3rd Digit: Latching and Reset Level 2 2nd Digit: Setpoint Activation Source Level 2 3rd Digit: Timers Example Setpoint Activation Values Example Setpoint Control Settings Level 2 Example Configuration rocedures LEVEL 2 Hysteresis Mode: Example rocedure LEVEL 2 ID Mode: Example rocedure LEVEL 2 Timer Mode: Example rocedure LEVEL 2 Select Setpoint Activation Source: Example rocedure5 Level 3 Advanced Mode Level 3 and Setpoint Configuration Sequence Level 3 Functions Level 3 st Digit: Energize Functions Level 3 3rd Digit: Latching and Reset Level 3 2nd Digit: Setpoint Activation Source Level 3 3rd Digit: Advanced Functions Mode Level 3 3rd Digit: Hysteresis, Deviation, ID, & Timers Example Setpoint Activation Source Example Setpoint Control Settings Level 3 Example Configuration rocedures LEVEL 3 Advanced Reset and Trigger Functions : Example rocedure Other Setpoint Related Functions Data Logging & Data rinting from a Setpoint Setpoint Time Control and Logging Data rinting from a Setpoint to a Serial rinter or C Data Logging from a Setpoint Local Distributor Address List of Figures Figure Setpoint Mode Functional Block Diagram Figure 2 Meter rogramming Digits for Setpoint and Control Functions Figure 3 Setpoint rogramming Mode Logic Diagram Figure 4 Tiger 320 Series Options Figure 5 NO Latching Figure 6 Setpoint Latching Figure 7 Manual Reset Figure 8 Latching & Manual Reset Figure 9 Latched Figure 0 Example : energize functions without hysteresis or deviation Figure Hysteresis Delay Figure 2 Example : energize functions with hysteresis Figure 3 Deviation Delay Figure 4 Example 2: energize functions with deviation Figure 5 ID Controls Figure 6 ID Control Settings Figure 7 Examples 3 and 4: ID mode with the relay energized above and below Figure 8 Example of Setpoint Tracking Figure 9 Normal Mode Figure 20 NMAL Mode Time Control Figure 2 Repeat ON Mode Figure 22 REEAT ON Mode Time Control Figure 23 ulse ON Mode Figure 24 ULSE ON Mode Time Control Figure 25 -Shot ON Mode Figure 26 -SHOT ON Mode Time Control Figure 27 -Shot Mode Figure 28 -Shot Mode Time Control Figure 29 ulse Mode Figure 30 ULSE Mode Time Control Figure 3 Repeat Mode Figure 32 REEAT Mode Time Control Figure 33 Make Edge Mode Figure 34 Break Edge Mode Figure 35 Both Edges Mode Figure 36 Level Mode March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 3

4 This age intentionally left blank age 4 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

5 Setpoint Functional Overview 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 5

6 The Tiger 320 Series signal processor and controller has six setpoints individually programmable to operate within the total span range of the meter and the selected input module. A relay output module provides the instrument with up to six relay outputs using a combination of 5 amp Form A and 0 amp Form C, or 5 volt solid state relays (SSRs). See Options for further details Individually programmable setpoints All six setpoints are available for relay activation or internal control functions such as register reset and counting functions. Each setpoint can be individually programmed to energize a relay or reset a register. The setpoint can be activated from any input channel, a selected register, or from the rear input pins. All six setpoints are individually programmable for sophisticated time control applications using the following features. Above ACTIVATION Energize Functions All setpoints activate at the setpoint value. All relays/setpoints are programmable to energize above or below the setpoint value. Below Input Channels External Switched Inputs Setpoint Activation Source Setpoints activate from any input channel, selected meter register, or external switched inputs (digital input pins) LATCH LATCH ON Setpoint Latching Setpoints can be programmed in relay latching modes. TRIGGER OERATES ON: MAKE EDGE BREAK EDGE MAKE & BREAK EDGE EVERY SAMLE ERIOD RESET SELECTED REGISTER TRIGGER RINT TRIGGER LOG DATA Setpoint Reset Setpoints can be programmed to reset selected registers, or be manually reset. RESET -B SETOINT TRACKING -A Setpoint Tracking Any setpoint can be programmed to track any other setpoint Real-time Clock Option Any setpoint can be programmed to operate from the real-time clock option. age 6 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

7 r i n t * * Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data Data * * Data Logging Data Logging Any setpoint can be programmed to log data within the meter (up to 4000 samples). r i n t r i n t * *********** E SON TM-U20 * *********** 24:07: 0 0 J o b J o b Data rinting to Serial rinter Any setpoint can be programmed to send data directly to a serial printer. Data rinting to C Any setpoint can be programmed to send data directly to a connected C. Hysteresis Deviation Hysteresis or Deviation Each relay can operate in a hysteresis or deviation mode. DUAL ID ID s and 2 can be programmed for ID operation TIMER 30 Timer Control Modes Each setpoint can be programmed to operate the relay in one of the following seven resident time control modes: Normal Mode Timer Single actuation, delay-on-make (DOM) and delay-on-break (DOB). Normally /ulsed ON Timers Repeat ON Mode Timer multiple actuation, programmable offand on-time. ulse ON Mode Timer single actuation, programmable DOM and maximum on-time. -Shot ON Mode Timer single actuation, programmable DOM and minimum on-time. Normally ON/ulsed Timers Repeat Mode Timer multiple actuation, programmable offand on-time. ulse Mode Timer single actuation, programmable DOB and maximum off-time. -Shot Mode Timer single actuation, programmable DOB and minimum off-time. 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 7

8 Setpoint Activation Source Any analog input signal on any channel. Any digital input signal on any channel. Digital input pins at rear of meter. An external switch closure. Result of math performed on input signal. An internal register. Serial input. Setpoints tracking other setpoints. Setpoint Activation Functions Activate ABOVE setpoint. Activate BELOW setpoint. Hysteresis. Deviation. Dual ID Control. Initial Start-up Inhibit. Window Comparator. Setpoint Timer Modes Normal Mode. Delay-on-make (DOM), delay-on-break (DOB) settings. Repeat ON Mode. rogrammable on and off time settings. ulse ON Mode. rogrammable DOM and on time settings. -Shot ON Mode. rogrammable DOM and minimum on time settings. Repeat Mode. rogrammable off and on time settings. ulse Mode. rogrammable off time and DOB. -Shot Mode. rogrammable minimum off time and DOB settings. Setpoints & s Setpoint Activation Results FLASH Display. Turn relay ON. Turn relay. Latch relay ON. Latch relay. Count setpoint activations. Reset any internal register. Increment any internal register. Activate another relay. rint any selected register contents. Turn ON front panel annunciators. Transfer contents of any register to another register. Log data to internal memory. Activate a custom macro. Send a pulse to an external device. Control ID output. Setpoint Timer Results Single and multiple actuation, normally / pulsed ON or normally ON / pulsed modes second resolution settings for setpoints and 2 in both ULSE and both REEAT timer modes. 0. second resolution settings for setpoints 3 to 6 in all timer modes. Delay-on-make, Delay-on-break (Normal timer). Turn relay ON//ON/ (Repeat timer). Turn relay /ON//ON ( Repeat timer). ulse ON for guaranteed on-time (ulse timer). ulse for guaranteed off-time ( ulse timer). Stay ON for guaranteed minimum on-time (Shot timer). Stay for guaranteed minimum off-time ( Shot timer). Technical Specifications Types: 5 A, 240 VAC Form A, electromechanical relay. 0 A, 240 VAC Form C, electromechanical relay. 400 V, 20 ma DC, independent normally open solid state relay (SSR). 400 V, 40 ma AC / DC, independent normally open SSR. All Tiger 320 Series meters, except the FI-B0D50, can be configured with a maximum of six electromechanical or four solid state relays (SSRs) using one of the following relay output modules: Output Module 37: Maximum six 5 A, Form A relays grouped in three using a single common per group. Output Module 38: Maximum four relays. Two groups of one 5 A, Form A and one 0 A, Form C relays using a single common per group. Output Module 56: Maximum four 5 A, Form A isolated relays. SSR Output Module 237: SSR Output Module 24: Maximum four independent 400 V, 20 ma DC SSRs. Maximum four independent 400 V, 40 ma AC / DC SSRs. GI & FI Meter Main Board: Maximum four relays. Two groups of one 0 A, Form C and one 5 A, Form A relays sharing a single common per group. FI Meter Carrier Board: Maximum two independent 400 V, 20 ma DC SSRs. For further information on relay options for individual meter types, see the specific meter user manual. age 8 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

9 Technical Description Each setpoint can be individually configured for basic to advanced operations in the following three levels. Each operational level is designed to provide only the required relevant setpoint and relay functions. The modes at Level 2 and Level 3 can be set to for each individual setpoint, ensuring that no other functions are programmed to influence the setup. Figure is a block diagram showing the functional blocks that comprise the setpoint mode. Level Setpoint & Basic Mode This is an easily programmable mode for users who require the following basic setpoint and relay functions: First Digit Energize Functions s programmed to energize above or below the setpoint value. Second Digit Activation Source Setpoints programmed to activate from selectable meter registers or one of six external switched inputs. Third Digit Setpoint Latching s programmed with latching and manual reset options. Level 2 Setpoint & Intermediate Mode Level 2 uses all Level functions and is further extended by the following programmable modes. The functionality of the relay energize functions are extended by allowing the relays to be programmed with or without initial start-up inhibit. rogramming Tip If you do not require any of the functions in this mode, ensure it is set to: Hysteresis, Deviation & ID Mode This mode adds extra functionality to the basic mode by providing programmable hysteresis or deviation settings for all setpoints, or ID control from setpoints and 2. rogramming Tip If you do not require any of the functions in this mode, ensure it is set to: Timer Modes These modes add even more functionality to the basic and intermediate mode by providing each setpoint with a choice of one of seven resident programmable timers. Level 3 rogramming Tip If you do not require any of the functions in this mode, ensure it is set to: Setpoint & Advanced Mode Level 3 uses all Level and Level 2 functions combined with reset and trigger functions to provide an extremely powerful advanced mode. Level 3 enables you to program all setpoints individually for operations normally requiring sophisticated controllers. 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 9

10 SETOINTS S 6 _Source x_delay_tye MODE x_data_source Normal Value Hysteresis Deviation Hysteresis Deviation x_control Invert Logic ON / x_hyst Setpoint Comparison x_tracking SETOINT_x Setpoint Value SETOINT VALUE ON T+SETOINTx x_tracking T = T = 2 T = 3 T = 4 T = 5 T = 6 rogramming Tip By y switching g to remote,, the macro can take control of setpoint output by writing g to x. The x status is still valid when in remote mode ALARM STATUS x_control Setpoint NMAL x_status x Shows status of setpoint comparison ON REMOTE Latching Latch ON Latch x_trigger TRIG = = = = = TRIGGERx x_delay_tye TIMER MODES _ (D.O.M.) (D.O.B.) ulse ulse Repeat Repeat _Shot _Shot x_make_delay x_break_delay x_trigger TRIGGER FUNCTIONS Reset Value Input_x + Reset Value Reset Destination + Reset Value Reset Source Register x_reset_value x_reset_source x_reset_destination x_trigger Log on Trigger No Log x_trigger rint on Trigger No rint RELAY_DE_ENERGISE_FLAGS Deenergise ON / RELAYx in to drive circuit Figure Setpoint Mode Functional Block Diagram age 0 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

11 Setpoint rogramming Mode All Tiger 320 Series meter setpoint and relay functions for Levels, 2, and 3 are configured in the meter s setpoint programming mode. During configuration, the last three digits on the meter display are used to select the setpoint and relay functions. See Figure 2. Alternately, if the meter is connected to a C through the serial port, the setpoints can be configured using the Meter Configuration rogram. See Meter Configuration Utility rogram Tutorial (NZ206) for details. To enter the setpoint programming mode press the meter s and buttons at the same time. See Figure 3 Setpoint rogramming Mode Logic Diagram for menu details. Setpoint Activation Values Mode On entering the setpoint programming mode, the meter display toggles between [_] and [8000]. This is the Setpoint Activation Values Mode. Using the button, step through each setpoint and set the activation value required using the and buttons. Setpoint activation values can be set within the total span range of the meter and the selected input module. Setpoint and Control Settings Mode ing the button after setting the activation value for 6 enters the Setpoint and Control Settings Mode. The meter display toggles between [C_] and [XXX]. This is the menu for setting setpoint control functions for. Using the button, step through each setpoint control menu and set the control functions for the required setpoints using the and buttons. The setpoint and relay control settings mode provides access to the following setpoint and relay functions by setting the st, 2nd, and 3rd digits on the meter display: First Digit Energize Functions. Allows you to select the required relay energize functions. Second Digit Setpoint Activation Source. Allows you to select the setpoint activation source. Third Digit Setpoint Delay, Timer, and Reset and Trigger Functions. Allows you to select from a range of delays, timers, and reset functions. Figure 2 shows the front panel of a Tiger 320 Series DI-50 meter. FIRST DIGIT SECOND DIGIT THIRD DIGIT U Button rogram Button DOWN Button Setpoint Annunciators Figure 2 Meter rogramming Digits for Setpoint and Control Functions 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age

12 rog. Operational Display To enter press and buttons at the same time Setpoint rogramming Mode Setpoint Activation Values Mode Enter these menus to set setpoint () activation values [_] Setpoint Default setting = 8000 [_2] [_3] [_4] [_5] [_6] Setpoint 2 Setpoint 3 Setpoint 4 Setpoint 5 Setpoint 6 Default setting = 8000 Default setting = 5000 Default setting = 5000 Default setting = 0000 Default setting = 0000 Setpoint & Control Settings Mode Enter these menus to configure control values [C_] [C_2] [C_3] [C_4] [C_5] [C_6] Setpoint Setpoint 2 Setpoint 3 Setpoint 4 Setpoint 5 Setpoint 6 See age 9 for a Level Setpoint & Control Settings diagram. See age 29 for a Level 2 Setpoint & Control Settings diagram. See age 55 for a Level 3 Setpoint & Control Settings diagram. Operational Display rog. Figure 3 Setpoint rogramming Mode Logic Diagram age 2 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

13 Options Tiger 320 Series DI, FI, and GI meters use the following electromechanical and solid state relays: 5 A, 240 VAC Form A, electromechanical relay. 0 A, 240 VAC Form C, electromechanical relay. 400 V, 20 ma DC, independent normally open solid state relay (SSR). 400 V, 40 ma AC / DC, independent normally open SSR. Electromechanical s There are three standard electromechanical relay output modules available that use a combination of 5 and 0 A electromechanical relays to make a total of twelve relay options: Output Module with Six Non-isolated 5 A Form A s. Output Module with Two Non-isolated 5 A Form A and 2 Non-isolated 0 A Form C s. Four Isolated 5 A Form A s Six Non-isolated 5 A Form A s This relay output module has a maximum of two groups of three 5 A Form A relays using a common pin. There are a total of two relay combinations available. 6 DI Series Order Code Options A 5A 5A 5A 5A 46 5A 5A 5A 5A 5A 5A Two Non-isolated 5 A Form A & Two Non-isolated 0 A Form C s This relay output module has a maximum of two groups of two relays. Each group can have a 0 A Form C and 5 A Form A relay using a common pin. There are a total of six relay combinations available. 2 DI Series 4 3 Order Code Options A - 2 0A - 0A A 5A 0A - 4 0A 5A 0A 5A 5-5A 0A 5A 6-5A 0A - 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 3

14 Four Isolated 5 A Form A s This relay output module has a maximum of four isolated 5 A Form A relays. There are a total of four relay combinations available. 4 3 DI Series 2 Order Code Options A A 5A 33-5A 5A 5A 34 5A 5A 5A 5A Solid State s There are two standard solid state relay (SSR) output modules available that provide a total of eight relay options: Four Independent 400 V, 20 ma (DC Only) SSR Output Module. Four Independent 400 V, 40 ma (AC/DC) SSR Output Module. Four Independent 400 V, 20 ma (DC Only) SSR Output Module This SSR output module has a maximum of four independent, normally open output, solid state relays. They are suitable for maximum 400 V, 20 ma DC inputs only. DI Series Order Code Options mA mA 20mA - 20mA 20mA 20mA 20mA 20mA 20mA 20mA Four Independent 400 V, 40 ma (AC/DC) SSR Output Module This SSR output module has a maximum of four independent, normally open output, solid state relays. They are suitable for maximum 400 V, 40 ma AC/DC inputs. DI Series Order Code Options mA mA 40mA - 40mA 40mA 40mA 40mA 40mA 40mA 40mA age 4 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

15 Opto-isolators An opto-isolated I/O plug-in module is a combination of two boards that provide a total of six digital status inputs and 6 digital status outputs using opto-isolators. The standard board mounts six inputs and six outputs. The six outputs are controlled by the meter s six programmable setpoints. The six inputs operate via a macro. An add-on board mounts onto the standard board and provides a further 0 outputs. These also operate via a macro. The opto-isolators have the following specifications: Isolation Voltage: 3.7 kv. Collector Emitter: 80 V. Collector Current: 50 ma. The opto-isolated I/O module comes complete with a 3M IDC cable connected to a DIN rail terminal block. The setpoint external pinouts to the terminal block are as follows: Add-on Board 0 Digital Outputs 2 in Function Meter setpoints 7 to 6 require a macro in Function M IDC Cable DIN Rail Terminal Block Options Standard Board 6 Digital Inputs/6 Digital Outputs All Tiger 320 Series DI and GI meters use plug-in relay output modules. The GI range can also mount up to four relays in six combinations on its main processor board. The FI bargraph meter can have up to four electromechanical relays mounted on its main board and two solid state relays (SSRs) on its output carrier board. See Figure 4. DI Meter Options GI Meter Options FI Meter Options Output Module Carrier Board Output Module Carrier Board Output Module Carrier Board Max Six 5 A Form A Max Six 5 A Form A Max Two 5 A Form A Max Two 0 A Form C Max Two 5 A Form A Max Two 0 A Form C Max Four 5 A Form A Max Four 5 A Form A Max Four 20 ma (DC Only) Max Four 40 ma (AC/DC) Max Four 20 ma (DC Only) Max Four 40 ma (AC/DC) Main rocessing Board Main rocessing Board Figure 4 Tiger 320 Series Options 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 5

16 GI-50 & GI-50B0 Meter s The GI-50 and GI-50B0 support the standard electromechanical and solid state relay output modules on their output carrier board. They can also support up to four electromechanical relays on the main processing board. The relay combination selected for the main processing board use setpoints to 4. If a plug-in relay output module with more than two relays is also selected for the output carrier board, then both sets of relays designated to 4 share setpoints to 4. GI-50 or GI-50B0 Main / rocessor Board Maximum 2 groups of x0 A Form C & x5 A Form A s using one common pin per group IN Numbers: Order Code R R2 R Options A 0A 0A 0A A 0A R4 5A 0A 5A 0A R5 5A 0A 5A - R6 5A 0A - - FI-B0D50 Bargraph s The FI-B0D50 bargraph combines up to two 5 A Form A and two 0 A Form C electromechanical relays on its main / processor board. An optional output carrier board combines two solid state relays. The solid state relays are normally open outputs and are suitable for maximum 400 V, 20 ma DC inputs only. Carrier Board (DC ONLY) SSR 5 6 Maximum 2 x 20 ma 400 V DC ONLY ALL INS ISOLATED IN Numbers: Order Code R R Options mA - 20mA 20mA FI-B0D50 Main / rocessor Board Maximum 2 groups of x0 A Form C & x5 A Form A s using one common pin per group IN Numbers Order Code R R2 R23 R4 R5 R Options A A 5A 5A 5A 0A 0A 0A 0A 0A A 5A - 2 0A 0A 0A - - age 6 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

17 Level Basic Mode 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 7

18 Level and Setpoint Configuration Sequence When configuring each setpoint for Level settings, the following programming sequence must be followed to ensure that all configuration settings are correctly entered and saved: STAR ART T HERE 2 3 Enter the Setpoint rogramming Mode the and buttons at the same time. This enters the setpoint programming mode. The display toggles between [_] and [8000]. Adjust Setpoint Activation Values Use the and buttons to adjust the setpoint () activation value. If not, press the button to move to the required setpoint and adjust. Adjust all other applicable setpoint activation values as required (2 to 6). Select Setpoint Control Function Settings After all required setpoint activation values have been adjusted, press the button until [C_] appears. C_ is the setpoint control function programming menu for setpoint. Set the three digits in the following order: LEVEL BASIC FUNCTIONS ) 3rd Digit Turn Intermediate and Advanced Level Modes Set display to [XX5] the button to enter the Hysteresis, Deviation, & ID Mode submenu. Display toggles between [ModE] and [off]. If not set to [off], use the or button to select [off]. Set display to [XX6] the button to enter the Timer Mode sub-menu. Display toggles between [timr] and [off]. If not set to [off], use the or button to select [off]. Set display to [XX7] the button to enter the Advanced Functions Mode sub-menu. Display toggles between [trig] and [off]. If not set to [off], use the or button to select [off]. When complete, reset the third digit to [XX0] to prevent cycling through the mode. 2) 2nd Digit Select Setpoint Activation Source Set to [XX] the button to enter the sub-menu and select the setpoint activation source for from any channel or selected register. When complete, reset back to [000]. If the source is from an external switched input (digital input pin), set to one of either [X2X] to [X7X] to select the setpoint activation source from one of six digital inputs (2 to 7). rogramming Tip As a final setting, combine Steps 3 and 4 to select the relay energize mode and the latching and manual reset functions into a single step. 3) st Digit Select Energize Mode Select the relay energize mode for from either [0XX] or [XX]. 4) 3rd Digit Latching & Manual Reset Functions Select the 3rd digit setpoint relay latching and manual reset functions either [XX0] to [XX4] as required. age 8 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

19 4 Record All Setpoint rogramming Code Settings Record all activation and control values in the Table: Customer Code Settings Setpoint rogramming Mode on age 5 of the Tiger 320 Series rogramming Code Sheet (NZ0). 5 6 Repeat Setpoint Control Function Settings for all Applicable Setpoints the button to move to [C_2]. C_2 is the setpoint control function programming menu for setpoint 2 (2). Repeat Steps 3 and 4 for all applicable setpoints. Exit the Setpoint rogramming Mode the button to save a setpoint programming mode setting and then press the and buttons at the same time to return to the operational display. END HERE Level Setpoint & Control Settings Diagram The following diagram shows the setpoint and relay three digit control function settings for operational Level. FIRST DIGIT SECOND DIGIT THIRD DIGIT Energize Function 0 Energized ABOVE setpoint value. Energized BELOW setpoint value Activation Source 0 Activate Setpoint Source from Selected Register Select Source for Setpoint from Selected Register Note: [XX] is a register selection procedure only. To finish, reset to [X0X] to activate the selection, or reset to 2-7 as required for digital input selection. Delay & Timing Functions 0 No Latching Latched 2 Manual Reset 3 Latched with Manual Reset 4 Latched Off Digital Input Capture in 3 Digital Input D 4 Digital Input D2 5 Digital Input D3 6 HOLD in 7 LOCK in Select Source for Setpoint Functions Use the buttons to cycle through the menu [di] [reslt] [Ch] Use the or button to select a register as the data source for the setpoint [ to 244] [tare] [Ch2] [Ch3] [VALEY] [EAK] [Ch4] [tot_] [tot_2] 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 9

20 Level Functions Level st Digit: Energize Functions The st digit of the setpoint and relay control mode allows you to configure relay energize functions. Above ACTIVATION Below Energize Function 0 Energized ABOVE setpoint value. Energized BELOW setpoint value FIRST DIGIT All setpoints activate at the setpoint activation value. At Level, the st digit allows you to program the setpoint relay to energize above or below the setpoint value. Level 2nd Digit: Setpoint Activation Source The 2nd Digit of the setpoint and relay control mode allows you to configure the setpoint activation source. The settings and functionality of the 2nd digit remain the same for Levels, 2, and 3. The activation source must be programmed for all required setpoints. The 2nd digit allows you to individually program the activation source for setpoints to 6 from one of eight selections. Setpoints activate from any input channel, selected meter register, or an external switched input (via digital input pin). Input Channels External Switched Inputs Note: The setpoint activation source of any unused setpoints can be set to off. This improves efficiency and stops unused setpoint activation values being displayed. SECOND DIGIT Activation Source 0 Activate Setpoint Source from Selected Register (select in 3rd digit) To 3rd digit Select Source for Setpoint Functions Select Source for Setpoint from Selected Register Note: [XX] is a register selection procedure only. To finish, reset to [X0X] to activate the selection, or reset to 2-7 as required for digital input selection. 2 Digital Input Capture in 3 Digital Input D 4 Digital Input D2 5 Digital Input D3 6 HOLD in 7 LOCK in [di] Use the buttons to cycle [ to 244] through the menu [reslt] Use the or button to select a register as the data source for [tare] [Ch] the setpoint [Ch2] [Ch3] [VALEY] [EAK] [Ch4] [tot_] [tot_2] [X0X] Activate Setpoint Source from Selected Register Setting the 2nd digit to 0 [X0X] means that the source selected for the setpoint when the 2nd digit is set to [XX] is now active for that setpoint. When selection of the setpoint activation source in [XX] is complete, reset back to [X0X]. Also, setting the 2nd and 3rd digits to [X05] to [X07] is the easiest method of entering Level 2 or Level 3 function setup modes. age 20 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

21 [XX] Select Source for Setpoint Selecting [XX] allows you to select the activation source for setpoints to 6 from any operational channel or meter register (# to 244). This is a register selection menu only. To leave this menu and activate the selection, reset the display [C_X] to [X0X]. [X2X] Digital Input Capture in Selecting [X2X] allows you to program setpoint activation from a switched input via the meter s capture pin. [X3X] Digital Input D Selecting [X3X] allows you to program setpoint activation from a switched input via the D pin on selected smart input modules. See Advanced Input Module Supplement for further information on smart input modules. [X4X] Digital Input D2 Selecting [X4X] allows you to program setpoint activation from a switched input via the D2 pin on selected input modules. See Advanced Input Module Supplement for further information on smart input modules. [X5X] Digital Input D3 Selecting [X5X] allows you to program setpoint activation from a switched input via the D3 pin on selected input modules. See Advanced Input Module Supplement for further information on smart input modules. [X6X] Digital Input Hold in Selecting [X6X] allows you to program setpoint activation from a switched input via the meter s hold pin. [X7X] Digital Input Lock in Selecting [X7X] allows you to program setpoint activation from a switched input via the meter s lock pin. Note: When a digital input pin is selected as a setpoint source, the setpoint activation value for that setpoint becomes irrelevant and is not displayed. Level 3rd Digit: Latching and Reset The 3rd digit allows you to configure the latching functionality of the setpoints and relays. LATCH LATCH ON Selecting [XX0] to [XX4] allows you to program the setpoint for one of five relay latching and manual reset modes. THIRD DIGIT Delay & Timing Functions 0 No Latching Setpoints Latched 2 Manual Reset 3 Setpoints Latched with Manual Reset 4 Setpoints Latched Off March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 2

22 rog. rog. rog. [XX0] No Latching Selecting [XX0] means that no latching is applied to the setpoints. See Figure 5 for an example. X EXAMLE: NO Latching Input Signal ON ON Figure 5 NO Latching [XX] Setpoint Latching Selecting [XX] means that latching is applied to the setpoints. See Figure 6 for an example. X EXAMLE: Latching Unlatch using the and button Input Signal ON ON Figure 6 Setpoint Latching [XX2] Manual Reset Selecting [XX2] means that the relay can be de-energized (reset) manually by the operator. The relay does not energize again until the setpoint reactivates. ing the and buttons on the meter s front panel at the same time manually resets the relay setpoint by the operator. Or it can be reset from a remote switch (Code 9 set to [X7X] or [XX7]). See Figure 7 for an example. X EXAMLE: Manual Reset De-energize using the and button Input Signal ON ON De-energized Figure 7 Manual Reset Note: A setpoint can be reset from a remote switch in any of the latching modes (Code 9 set to [X7X] or [XX7]). age 22 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

23 rog. rog. [XX3] Setpoint Latched with Manual Reset Selecting [XX3] means that setpoint latching is applied and the relay can be de-energized (reset) manually by the operator. The relay does not energize again until the next setpoint activation. See Figure 8 for an example. X EXAMLE: Latching & Manual Reset Input Signal ON Unlatch using the and button De-energize using the and button ON De-energized Figure 8 Latching & Manual Reset [XX4] Setpoint Latched Selecting [XX4] means that latching is applied to the setpoint but in the latched mode. See Figure 9 for an example. Input Signal X EXAMLE: Latched Unlatch using the and button ON Latched Latched ON Figure 9 Latched Level Example Configuration rocedures Configure the setpoint activation values and the required setpoint control settings for Level. Example Setpoint Activation Values See Level Setpoint Activation Values: Example rocedure. This example describes how to adjust the setpoint activation value for setpoint to 0,000 counts. All other setpoint activation values are adjusted in the same way. Example Setpoint Control Settings See Level Energize, Latching, & Activation Source Settings: Example rocedure. This example describes how to configure setpoint for the following Level (basic) setpoint control operations: st Digit Energize. Configure the relay to energize above the setpoint value. 2nd Digit Activation Source. Select channel as the activation data source for setpoint. 3rd Digit Setpoint Latching. Configure the setpoint to latch with manual relay reset. 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 23

24 LEVEL Setpoint Activation Values: Example rocedure Adjust the setpoint activation value for setpoint. Example rocedure Adjust setpoint to activate at 0,000 counts. Using Steps 2 and 3 adjust all other applicable setpoint activation values. STAR ART T HERE Configure Setpoint Activation Value Settings Step Enter the Setpoint rogramming Mode at same time Setpoint Activation Values Mode Operational Display at same time rogramming Tip Record the values in the Table: Customer Code Settings Setpoint rogramming Mode on age 5 of the Tiger 320 Series rogramming Code Sheet. Step 2 Adjsut the setpoint to the required activation value Example rogramming Tip To save and exit the setpoint programming mode at any time, press the button to save the setpoint settings you are currently programming. Then, press the and buttons at the same time to return to the operational display. Step 3 Save the settings and proceed to adjust all required setpoint activation value settings Step 4 Repeat Steps 2 and 3 for all applicable setpoints (2 thru 6) Example rogramming Tip Configuring the setpoint activation values and levels, 2, and 3 setpoint control functions can either be carried out individually, or as one complete procedure. Configuring as one complete procedure means there is no need to leave the setpoint programming mode until the procedure is complete. For a description of the sequence to configure a setpoint through all setpoint and relay functions in one complete procedure, see and Setpoint Configuration Sequence at the beginning of Level, Level 2, and Level 3. Step 5 After all setpoints X have been adjusted, save the setpoint values in the meter by pressing the ROGRAM button repeatedly until [C_6] appears Step 6 Exit C_6 and return to the operational display Setpoint and Control Functions Mode Continue rogramming Operational Display Enter the Setpoint and Control Functions Mode and program the control settings for each setpoint relay in turn (C_ thru C_6) See Level Setpoint Control Setting Example rocedure for an example procedure to configure Level functions age 24 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

25 LEVEL Energize, Latching, & Activation Source: Example rocedure STAR ART T HERE Configure Level Settings Operational Display From Step 5 Example Step Enter Setpoint rogramming Mode at same time at same time Step 6 Save control settings Step 2 ass thru to 6 and enter C_ 6 X Step 7 Reset 2nd digit to 0 (This activates the setpoint source from the selected register). If the 2nd digit is not reset to 0, the meter will constantly cycle thru C_ Step 3 Set C_ to [03]: st Digit = 0 Energize above value 2nd Digit = Select data source for 3rd Digit = 3 latching with manual reset Example Step 8 Save control settings Step 4 Enter source sub-menu Step 9 Exit C_2 and return to operational display at same time at same time Step 5 Select [Ch] as the activation source. See Select Data Source diagram below To Step 6 Operational Display Select Data Source Use the buttons to cycle through the options [di] [reslt] [Ch] [Ch2] [Ch3] [Ch4] [tot_] [tot_2] [EAK] Use the buttons to select register number as data source for setpoint. [VALEY] [ to 244] [tare] 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 25

26 This age intentionally left blank age 26 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

27 Level 2 Intermediate Mode 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 27

28 Level 2 and Setpoint Configuration Sequence When configuring each setpoint for Level 2 settings, the following programming sequence must be followed to ensure that all configuration settings are correctly entered and saved: STAR ART T HERE Enter the Setpoint rogramming Mode the and buttons at the same time. This enters the setpoint programming mode. The display toggles between [_] and [8000]. 2 Adjust Setpoint Activation Values Use the and buttons to adjust the setpoint () activation value. If not, press the button to move to the required setpoint and then adjust. Adjust all other applicable setpoint activation values as required (2 to 6). 3 Select Setpoint Control Function Settings After all required setpoint activation values have been adjusted, press the button until [C_] appears. C_ is the setpoint control function programming menu for setpoint. Set the three digits in the following order: LEVEL 2 INTERMEDIATE FUNCTIONS ) Third Digit Configure Hysteresis, Deviation & ID Settings [XX5] If hystersis, deviation, or ID is required, set to [XX5]. the button to enter the Hysteresis, Deviation & ID Mode sub-menu and program the hysteresis, deviation, or ID settings as required. When complete, reset back to [XX0]. 2) Third Digit Configure Timers [XX6] If a timer is required, set to [XX6]. the button to enter the Timer Modes sub-menu, select and program one of seven time control modes as required for. When complete, reset back to [XX0]. 3) Second Digit Select Setpoint Activation Source Set to [XX] the button to enter the sub-menu and select the setpoint activation source for from any channel or selected register. When complete, reset back to [000]. If the source is from an external switched input (digital input pin), set to one of either [X2X] to [X7X] to select the setpoint activation source from one of six digital inputs (2 to 7). rogramming Tip As a final setting, combine Steps 4 and 5 to select the relay energize mode and the latching and manual reset functions into a single step. 4) First Digit Select Energize Mode Select the relay energize mode and initial start-up setting for from either [0XX] to [3XX]. 5) Third Digit Latching & Manual Reset Functions Select the relay latching and manual reset functions from either [XX0] to [XX4] as required. age 28 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

29 4 Record All Setpoint rogramming Code Settings Enter all activation and control values in the Table: Customer Code Settings Setpoint rogramming Mode on age 5 of the Tiger 320 Series rogramming Code Sheet (NZ0). 5 6 Repeat Setpoint Control Function Settings for all Applicable Setpoints the button to move to [C_2]. C_2 is the setpoint control function programming menu for setpoint 2 (2). Repeat Steps 3 and 4 for all applicable setpoints. Exit the Setpoint rogramming Mode the button to save a setpoint programming mode setting and then press the and buttons at the same time to return to the operational display. END HERE Level 2 Setpoint & Control Settings Diagram The following diagram shows the setpoint and relay three digit control function settings for operational Level 2. FIRST DIGIT SECOND DIGIT THIRD DIGIT Energize Function 0 Energized ABOVE setpoint value. Energized BELOW setpoint value. 2 Energized ABOVE setpoint value with FALLING INUT SIGNAL INI- TIAL START-U INHIBIT. 3 Energized BELOW setpoint value with RISING INUT SIGNAL INI- TIAL START-U INHIBIT. Activation Source 0 Activate Setpoint Source from Selected Register Select Source for Setpoint from Selected Register Note: [XX] is a register selection procedure only. To finish, reset to [X0X] to activate the selection, or reset to 2-7 as required for digital input selection. 2 Digital Input Capture in 3 Digital Input D 4 Digital Input D2 5 Digital Input D3 6 HOLD in 7 LOCK in Delay & Timing Functions 0 No Latching Setpoint Latched 2 Manual Reset 3 Setpoint Latched with Manual Reset 4 Setpoint Latched Off 5 Hysteresis, Deviation & ID Mode (includes Tracking) 6 Timer Modes: Normal Delay. Repeat ON. ulse ON. -Shot ON. Repeat. ulse. -Shot. Go to age 3 Go to age 38 Note: In ID mode, all functions on set in [XX6] are not functional. Note: [XX5] and [XX6] are set up procedure settings only. To finish, reset to 0-4 as required for setpoint latching and relay reset modes. Select Source for Setpoint Functions [di] Use the buttons to cycle through the menu [reslt] Use the or button to select a register as the data source for [Ch] the setpoint [ to 244] [tare] [Ch2] [Ch3] [VALEY] [EAK] [Ch4] [tot_] [tot_2] 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 29

30 rog. rog. rog. rog. Level 2 Functions Level 2 st Digit: Energize Functions At Level 2, the st digit also allows you to program the setpoint relay to energize above or below the setpoint value, but this is further controlled by the mode selected when the third digit is set to [XX5]. This can be either: Hysteresis. See age 32 for further details. Deviation. See age 34 for further details. ID. See age 35 for further details. The hysteresis and deviation modes can also be programmed to energize the relay with or without initial start-up inhibit. Above ACTIVATION FIRST DIGIT Energize Function 0 Energized ABOVE setpoint value. Energized BELOW setpoint value. Below 2 Energized ABOVE setpoint value with FALLING INUT SIGNAL INITIAL START-U INHIBIT. 3 Energized BELOW setpoint value with RISING INUT SIGNAL INITIAL START-U INHIBIT. Initial Start-up Inhibit On switch-on when set to either [0XX] or [XX], initial start-up inhibit prevents the relay from energizing on the first setpoint activation cycle. When set to [2XX] initial start-up inhibit only functions during a falling input signal. When set to [3XX] initial start-up inhibit only functions during a rising input signal. The signal must activate then deactivate the setpoint, and only when the setpoint activates for the second time does the relay energize. Figure 0 Example shows the relay energize functions without hysteresis or deviation applied, but with and without initial start-up inhibit. EXAMLES Energize Functions WITHOUT Hysteresis or Deviation XX SETOINT Input Signal Energizes ABOVE Setpoint Activated Time in Seconds ENERGIZED DE-ENERGIZED Setpoint Activated ENERGIZED DE-ENERGIZED Setpoint Activated ENERGIZED XX Energizes BELOW DE-ENERGIZED ENERGIZED DE-ENERGIZED ENERGIZED DE-ENERGIZED With START U INHIBIT Meter switched ON BELOW Energizes BELOW XX with INITIAL START U INHIBIT (provided meter switched ON when input signal below ) SETOINT Meter switched ON ABOVE Energizes ABOVE XX with INITIAL START U INHIBIT (provided meter switched on when input signal above ) NOTE: All examples used throughout this document are for a relay with NMALLY OEN contacts. DE-ENERGIZED Input Signal ENERGIZED DE-ENERGIZED ENERGIZED DE-ENERGIZED METER OWER ON OINT Time in Seconds DE-ENERGIZED ENERGIZED Figure 0 Example : energize functions without hysteresis or deviation DE-ENERGIZED 65 ENERGIZED age 30 Texmate Inc. Tel. (760) March, 2003 Setpoints & s (NZ20)

31 Level 2 2nd Digit: Setpoint Activation Source The settings and functionality of the 2nd digit remain the same for Levels, 2, and 3. The activation source must be programmed for all required setpoints. See Level 2nd Digit: Setpoint Activation Source for further details. Level 2 3rd Digit: Latching and Reset The settings and functionality of the 3rd digit latching and reset functions remain the same for Levels, 2, and 3. LATCH LATCH ON Selecting [XX0] to [XX4] allows you to program the setpoint for one of five relay latching and manual reset modes. THIRD DIGIT Delay & Timing Functions 0 No Latching Setpoints Latched 2 Manual Reset 3 Setpoints Latched with Manual Reset 4 Setpoints Latched Off See Level 3rd Digit: Latching and Reset for further details. Level 2 3rd Digit: Hysteresis, Deviation, and ID Selecting [XX5] and pressing the button enters the Level 2 setpoint control mode and makes the following modes available for further programming: Hysteresis. Deviation. ID on setpoints and 2. Individual settings can be programmed for all required setpoints. Setpoints not required in this mode can be set to. Hysteresis Deviation DUAL ID THIRD DIGIT Delay & Timing Functions 0 No Latching Setpoint Latched 2 Manual Reset 3 Setpoint Latched with Manual Reset 4 Setpoint Latched Off 5 Hysteresis, Deviation & ID Mode (includes Tracking) Note: In ID mode, all functions on set in [XX6] are not functional. Note: [XX5] is a set up procedure setting only. To finish, reset to 0-4 as required for setpoint latching and relay reset modes. 2 March, 2003 Setpoints & s (NZ20) Texmate, Inc. Tel. (760) age 3

DUAL RTD INPUT. State-of-the-art Electromagnetic Noise Suppression Circuitry. Ensures signal integrity even in harsh EMC environments.

DUAL RTD INPUT. State-of-the-art Electromagnetic Noise Suppression Circuitry. Ensures signal integrity even in harsh EMC environments. DUAL RTD INUT Fits Tiger 320 Series 8-pin Input Connector. Dual 4-wire RTD inputs. State-of-the-art Electromagnetic Noise Suppression Circuitry. Ensures signal integrity even in harsh EMC environments.

More information

Fits Tiger 320 Series UNIVERSAL FREQ/COUNTER INPUT MODULE

Fits Tiger 320 Series UNIVERSAL FREQ/COUNTER INPUT MODULE Fits Tiger 320 Series UNIVERSAL /ER INPUT MODULE Sensor. Magnetic, Namur, Source, Sink. De-coupling. 0.02 Hz high pass filter. Signal Type., (mv) or digital logic. Input Connector. Freq. Input (CH) Up/Down

More information

Fits Tiger 320 Series 16-BIT SMART 4-CHANNEL LOAD CELL MODULE

Fits Tiger 320 Series 16-BIT SMART 4-CHANNEL LOAD CELL MODULE Fits Tiger 320 Series 16-BIT SMART 4-CHANNEL LOAD CELL MODULE IDC ed Cable. In user selectable lengths 16-pin Terminal Block. Din rail mount. Up to 8 load cells, 6-wire configuration. Ultra-low noise 16-bit

More information

leopard Series transmitter and Controller

leopard Series transmitter and Controller FAMILY tl leopard Series transmitter and Controller An economically smart programmable transmitter relay with isolated 4 to 20 ma retransmission or control loop output capability for measurementand control

More information

TABLE OF CONTENTS. Keypad Programming Manual 1

TABLE OF CONTENTS. Keypad Programming Manual 1 TABLE OF CONTENTS How To Program Radios...2 Keypad Programming...2 A. Navigation...3 1. Group Parameters (CH 00)...4 2. Channel Parameters (CH 01 - CH20)...4 3. Global Parameters (GRP 00)...5 B. Group

More information

BATCHMATE 1500 Batch Control Computer Technical Bulletin

BATCHMATE 1500 Batch Control Computer Technical Bulletin TS-5(C) BATCHMATE 5 Batch Control Computer Technical Bulletin DESCRIPTION The BATCHMATE features an 8 digit.55-in. alphanumeric LED display. The pulse input model will accept up to 2, pulses per second

More information

Controllers for Vibratory Feeder Engineering REOVIB MTS 440/442. REO-USA, Inc. Thyristor controllers for vibratory feeders With digital settings

Controllers for Vibratory Feeder Engineering REOVIB MTS 440/442. REO-USA, Inc. Thyristor controllers for vibratory feeders With digital settings Operating Instructions REOVIB MTS 0/ Thyristor controllers for vibratory feeders With digital settings REO-USA, Inc 850 E 7th Street Indianapolis, IN 66 USA hone + (7) 899-95 ax + (7) 899-96 http://www.reo-usa.com

More information

MFJ ENTERPRISES, INC.

MFJ ENTERPRISES, INC. TM Model MFJ-1924 INSTRUCTION MANUAL CAUTION: Read All Instructions Before Operating Equipment! MFJ ENTERPRISES, INC. 300 Industrial Park Road Starkville, MS 39759 USA Tel: 662-323-5869 Fax: 662-323-6551

More information

Virtual Measurements & Control. Packaging Controller 7/8/99

Virtual Measurements & Control. Packaging Controller 7/8/99 Virtual Measurements & Control Packaging Controller 7/8/99 OVERVIEW... 2 HARDWARE... 2 CONTROL... 3 OPERATIONAL SEQUENCE SINGLE FILL MODE... 6 OPERATIONAL SEQUENCE BATCH FILL MODE... 8 EXITING SMARTS...

More information

TECHNICAL NOTES MT-4 Radio Systems TN182 Battery Level Reporting and Remote P25 Test Tone

TECHNICAL NOTES MT-4 Radio Systems TN182 Battery Level Reporting and Remote P25 Test Tone Battery Level Reporting is a method of activating a repeater remotely to have it transmit a signal that reports the battery voltage level over RF. The Remote P25 Test Tone is a remotely activated Standard

More information

The LEBOW 7554 Operator's Manual 7.2

The LEBOW 7554 Operator's Manual 7.2 The LEBOW 7554 Operator's Manual 7.2 This manual covers operating version 7.2 of the LEBOW 7554. 11 February 1999 Lebow Products Inc Lebow Products Inc 1728 Maplelawn Rd Troy, MI 48084 1 (800) 803-1164

More information

High Performance Process & Temperature Controllers

High Performance Process & Temperature Controllers C22 C62 C82 C83 High Performance Process & Temperature Controllers C72 C42 R22 01. Multi Color LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. 200 msec Sampling Rate 04. True Universal

More information

Excellent low-cost Process & Temperature Controllers

Excellent low-cost Process & Temperature Controllers C22 C62 C82 C83 Excellent low-cost Process & Temperature Controllers C72 C42 R22 01. High Quality LCD Display 02. High Accuracy 18 Bit A-D Input and 15 Bit D-A Output 03. The Fast Sampling Rate in 200

More information

Installation, Operation and Maintenance Manual

Installation, Operation and Maintenance Manual M518 Rev. B Model 1030F Indicator-Totalizer Model 1030F Indicator-Totalizer Installation, Operation and Maintenance Manual Table of Contents General... 1 Installation... 1 Operation... 7 Programming...

More information

Operating Instructions

Operating Instructions CMYX Color mark sensor Operating Instructions CAUTIONS AND WARNINGS SET-UP DISTANCE ADJUSTMENT: As a general rule, the sensor should be fixed at a 15 to 20 angle from directly perpendicular to the target

More information

Interfacing Clockaudio microphones with the Logic Box

Interfacing Clockaudio microphones with the Logic Box Interfacing Clockaudio microphones with the INTRODUCTION One popular application for the is to interface with conferencing microphones that feature mute switches and LED indicators, and Clockaudio is a

More information

DC Voltage Hawk II H235 Series Advanced Digital Panel Meter

DC Voltage Hawk II H235 Series Advanced Digital Panel Meter % DC Voltage Hawk II H35 Series Advanced Digital Panel Meter Easily Programmed from the Front Panel User-Friendly Software Functions Include: Password Display Scaling Decimal Point Selection Set Point

More information

RUN MAN OUT1 OUT2 FL40

RUN MAN OUT1 OUT2 FL40 MAN RUN OUT1 OUT2 FL40 Iso 5167 mass flow computer Installation and user manual rev. 12/2015 PRELIMINARY INFORMATION This document haves copyright reserved, C Arian. Referred trademarks are of property

More information

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater

Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater Mate Serial Communications Guide This guide is only relevant to Mate Code Revs. of 4.00 and greater For additional information contact matedev@outbackpower.com Page 1 of 20 Revision History Revision 2.0:

More information

LAUREL ELECTRONICS, INC.

LAUREL ELECTRONICS, INC. LAUREL ELECTRONICS, INC. Laureate True RMS AC Voltage & Current Meter with 1 Cycle Update at 50/60 Hz Features True AC or AC plus DC RMS measurement with crest factor of 3.0 at FS Fast response: reading

More information

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2

MICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2 PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features

More information

Installation Notes. SCR Single Channel

Installation Notes. SCR Single Channel Installation Notes SCR Single Channel Receiver Part No. 100-187 Receives ARM / Disarm / PANIC / Low Batt channels from Ness Radio Keys or Radio PIRs / Radio Reeds. Supports up to four transmitters. Simple

More information

WHEN A PLC IS TOO MUCH, AND SPACE FOR

WHEN A PLC IS TOO MUCH, AND SPACE FOR WHEN A PLC IS TOO MUCH, AND SPACE FOR A RELAY SEQUENCE CIRCUIT IS TOO LITTLE Pattern Selector 59 2.33 66 2.6 70 2.75 No programming required Select from among 15 preset patterns Wiring far simpler than

More information

User Manual Solenoid Controller BI-SC1001

User Manual Solenoid Controller BI-SC1001 User Manual Solenoid Controller BI-SC1001 NOTICE Brandstrom Instruments, 2017 85 Ethan Allen Highway Ridgefield, CT 06877 (203) 544-9341 www.brandstrominstruments.com No part of this document may be photocopied,

More information

Model cpci-75ld1 3U. Eight (8) LVDT/RVDT-to-Digital Channels

Model cpci-75ld1 3U. Eight (8) LVDT/RVDT-to-Digital Channels Model cpci-75ld1 3U Eight (8) LVDT/RVDT-to-Digital Channels Eight (8) LVDT Measurement Channels 2-Wire or 3/4-Wire LVDT to Digital Converters Auto-ranging; Optional On-Board Excitation Commercial & Military

More information

Data Acquisition Modules/ Distributed IO Modules

Data Acquisition Modules/ Distributed IO Modules User Manual Data Acquisition Modules/ Distributed IO Modules Future Design Controls, Inc. 7524 West 98 th Place / P.O. Box 1196 Bridgeview, IL 60455 888.751.5444 - Office: 888.307.8014 - Fax 866.342.5332

More information

F2A3X Frequency to Analog Converter Module

F2A3X Frequency to Analog Converter Module the professional s choice F2A3X Frequency to Analog Converter Module Instruction Manual MONARCH INSTRUMENT 15 Columbia Drive Amherst, NH 03031 USA Phone: (603) 883-3390 Fax: (603) 886-3300 E-mail: support@monarchinstrument.com

More information

AMERITRON SDC-102 Screwdriver Antenna Controller

AMERITRON SDC-102 Screwdriver Antenna Controller AMERITRON SDC-102 Screwdriver Antenna Controller INSTRUCTION MANUAL PLEA S E REA D T H IS M A NU A L BEFORE OP ERA T I N G T H IS EQU IP M EN T! 116 Willow Road Starkville, MS 39759 USA 662-323-8211 Version

More information

PROCESS & TEMPERATURE CONTROLLERS

PROCESS & TEMPERATURE CONTROLLERS PROCESS & TEMPERATURE CONTROLLERS NOVA PD54 Series Thermocouple, RTD, & Process Inputs High Accuracy Auto-Tuning PID Heating & Cooling Models Universal Power Supply 1-24 VAC Up to 3 Relays & 2 Analog Outputs

More information

THE APOLLO INTELLIGENT METER SERIES MODEL IMD1 INSTRUCTION MANUAL

THE APOLLO INTELLIGENT METER SERIES MODEL IMD1 INSTRUCTION MANUAL THE APOLLO INTELLIGENT METER SERIES MODEL IMD1 INSTRUCTION MANUAL INTRODUCTION The Intelligent Meter for Decade Volt (DC) Inputs (IMD1) is another unit in our multi-purpose series of industrial control

More information

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide 14/11/2006 V10 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: +27 (031) 7028033 Fax: +27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com

More information

MFJ ENTERPRISES, INC.

MFJ ENTERPRISES, INC. Screwdriver Antenna Controller Model MFJ-1926 INSTRUCTION MANUAL CAUTION: Read All Instructions Before Operating Equipment! MFJ ENTERPRISES, INC. 300 Industrial Park Road Starkville, MS 39759 USA Tel:

More information

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22. USER MANUAL - Intelligent Positioner Control Unit 1/22 Table of contents: 1 General... 3 1.1 Safety instructions... 3 2 Application... 4 3 Electrical specifications and terminals... 5 3.1 Control loop...

More information

7SD/7SH/7SM Temperature Controllers

7SD/7SH/7SM Temperature Controllers 7SD/7SH/7SM Temperature ADVANTAGE EZ Series 7SD, 7SH, 7SM 1/16 DIN Temperature 3Digit LED Display Thermocouple and RTD Input Autotuning NEMA 4X Field onfigurable 100 to 40 Vac Switching Power Supply Programmable

More information

C u t l e r- H a m m e r. IQ Analyzer START Q U I C KS TA RT G U I D E

C u t l e r- H a m m e r. IQ Analyzer START Q U I C KS TA RT G U I D E C u t l e r- H a m m e r IQ Analyzer START Q U I C KS TA RT G U I D E C O N T E N T S Introduction 4 Mounting 9 IMPORTANT NOTICE Use this Guide to begin performing basic metering functions quickly, without

More information

Kurz Instruments Inc. December 27, 2007

Kurz Instruments Inc. December 27, 2007 BUILT-IN ZERO-MIDSPAN-SPAN DRIFT CHECK/CALIBRATOR Introduction Continuous Emissions monitoring systems (CEMS) have a long term stability verification requirement. Most of the equipment is verified using

More information

CHAPTER 1 INTRODUCTION...

CHAPTER 1 INTRODUCTION... GSE 460 and 465 Technical Reference Manual Manual TABLE OF CONTENTS CHAPTER 1 INTRODUCTION...1-1 INTRODUCTION...1-2 About This Manual...1-2 Conventions...1-2 CHAPTER 2 INSTALLATION...2-1 INSTALLATION...2-1

More information

SNZA TRIPLE LEVEL CONTROL FOR CONDUCTIVE LIQUIDS

SNZA TRIPLE LEVEL CONTROL FOR CONDUCTIVE LIQUIDS / TRILE LEVEL CONTROL FOR CONDUCTIVE LIQUIDS! Field of application Difference Operating principle Leds indication ower supply V/A in probes line robes connection cables Connection of the common electrode

More information

Heliotrack Programmable Wind Alarm Switch V1.0 Developed in partnership with Inspeed.com, LLC

Heliotrack Programmable Wind Alarm Switch V1.0 Developed in partnership with Inspeed.com, LLC Heliotrack Programmable Wind Alarm Switch V1.0 Developed in partnership with Inspeed.com, LLC IMPORTANT DISCLAIMER: Niether Heliotrack,LLC nor Inspeed assume any responsibility for damages caused by the

More information

1-7. Product information Temperature Monitoring. Type: TMS U. Thermal control module:

1-7. Product information Temperature Monitoring. Type: TMS U. Thermal control module: - Basic information The electronic module protects, in combination with temperature sensors, the winding from electrical machines (motors, generators, transformers ) and liquid or gaseous media. Used properly,

More information

C Series Functional Safety

C Series Functional Safety SAFETY MANUAL C Series Functional Safety This document provides information about developing, deploying, and running Functional Safety systems using C Series Functional Safety modules. C Series Functional

More information

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE)

ATS-I USER MANUAL. Tecnoelettra srl Dal Via Vioni Dimo, S.Rocco di Guastalla (RE) USER MANUAL ATS-I Tel.+39.0522.832004 P1/17 ATS-I User manual Fax.+39.0522.832012 Tecnoelettra_EN.doc P.1/17 Index General description...3 Electrical specifics...3 Device operative logic...4 Manual mode...4

More information

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional) Temperature Controller with Built-in SSR SB SB General Description SB is a channel temperature controller with Built-in SSR (Solid state relay) designed for flexible heating solutions such as heat trace

More information

User guide. Revision 1 January MegaPoints Controllers

User guide. Revision 1 January MegaPoints Controllers MegaPoints Servo 4R Controller A flexible and modular device for controlling model railway points and semaphore signals using inexpensive R/C servos and relays. User guide Revision 1 January 2018 MegaPoints

More information

+GF+ SIGNET Temperature Transmitter Instructions

+GF+ SIGNET Temperature Transmitter Instructions GF SIGNET 80- Temperature Transmitter Instructions ENGLISH -80.090- B-/00 English CAUTION! Remove power to unit before wiring input and output connections. Follow instructions carefully to avoid personal

More information

20 CHANNELS DIGITAL DELAY GENERATOR

20 CHANNELS DIGITAL DELAY GENERATOR NUT 063 Ed. 2.2 September 2015 User's Manual MODEL 745-20C 20 CHANNELS DIGITAL DELAY GENERATOR 20 independent delay channels 100 ps delay resolution (1 ps option) 10 seconds delay range Adjustable output

More information

THE APOLLO INTELLIGENT METER SERIES MODEL IMS INSTRUCTION MANUAL

THE APOLLO INTELLIGENT METER SERIES MODEL IMS INSTRUCTION MANUAL THE APOLLO INTELLIGENT METER SERIES MODEL IMS INSTRUCTION MANUAL INTRODUCTION The Intelligent Meter for Strain Gage Inputs (IMS) is another unit in our multipurpose series of industrial control products

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D2C Part 2: Adjustment and Operation, Measured Variables ph/chlorine dioxide ProMinent D2C2-001-pH/CIO2-GB ph/clo 2 7.20 ph 0.45 ppm DULCOMETER STOP STAR T ph/clo 2 7.20

More information

DIGITAL INTELLIGENT POWER FACTOR REGULATOR

DIGITAL INTELLIGENT POWER FACTOR REGULATOR An ISO 9001:2008 Comany DIGITAL INTELLIGENT POWER FACTOR REGULATOR Model - KM-PFR-9-06 / KM-PFR-9-12 The ioneers & leaders in high quality ower factor controllers & maximum demand controllers, now introduce

More information

V a l - C o. People. Products. Solutions. Model BE-SSC-401 DUAL HOG SCALE CONTROL User Manual. Version 7.0.1

V a l - C o. People. Products. Solutions. Model BE-SSC-401 DUAL HOG SCALE CONTROL User Manual. Version 7.0.1 V a l - C o People. Products. Solutions. www.valcompanies.com Model BE-SSC-401 DUAL HOG SCALE CONTROL User Manual Version 7.0.1 01 GENERAL SETTINGS 01 system on/off 0> off 2 INTRODUCTION Congratulations

More information

Blue Point Engineering

Blue Point Engineering Blue Point Engineering Instruction I www.bpesolutions.com Pointing the Way to Solutions! Animatronic Wizard - 3 Board (BPE No. WAC-0030) Version 3.0 2009 Controller Page 1 The Wizard 3 Board will record

More information

FLOMID-MX Control unit for electromagnetic flowmeters USERS MANUAL. instrumentación para fluidos. Realitzat: Revisat R+D Electrònic: Aprovat: Data:

FLOMID-MX Control unit for electromagnetic flowmeters USERS MANUAL. instrumentación para fluidos. Realitzat: Revisat R+D Electrònic: Aprovat: Data: instrumentación para fluidos FLOMID-MX Control unit for electromagnetic flowmeters USERS MANUAL Realitzat: Data: Revisat R+D Electrònic: Data: Revisat Of. Comercial: Data: Aprovat: Data: R-MI-Flomid-MX

More information

B & D Enterprises 1P repeater controller pg 1 INTRODUCTION:

B & D Enterprises 1P repeater controller pg 1 INTRODUCTION: B & D Enterprises 1P repeater controller pg 1 INTRODUCTION: The 1P is a basic repeater controller. The controller uses low power devices and stores all commands and system status in non-volatile EE prom.

More information

BS-3520 Digital Indicator

BS-3520 Digital Indicator BS-3520 Digital Indicator The Better Way for Weighing & easurements Table of Contents. Introduction...3 - Trait... 3-2 Warning... 4 2. Specification...5 3. External Size...6 4. Description on Front Panel...7

More information

8003 1/8 DIN Temperature Controller

8003 1/8 DIN Temperature Controller 8003 1/8 DIN Temperature Controller Issue Date April 1994 USER S MANUAL 0037-75212 Contents Model Identification... Page ii Dimensions and Panel Cutout...1 Wiring...2 Hardware Setup...3 Configuration Mode...4

More information

PC-OSCILLOSCOPE PCS500. Analog and digital circuit sections. Description of the operation

PC-OSCILLOSCOPE PCS500. Analog and digital circuit sections. Description of the operation PC-OSCILLOSCOPE PCS500 Analog and digital circuit sections Description of the operation Operation of the analog section This description concerns only channel 1 (CH1) input stages. The operation of CH2

More information

PM 305 Operating Guide

PM 305 Operating Guide PM 305 Operating Guide Northern Design PREFACE PM305 Operating Guide Revision 2.05 October 2000 This manual represents your meter as manufactured at the time of publication. It assumes standard software.

More information

Jet Central Sequencer Plus

Jet Central Sequencer Plus Jet Central Sequencer Plus Features The Jet Central Sequencer Plus is a multipurpose electronic device, the capabilities of the unit include: Three part sequencer, operating landing gear and two independent

More information

YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS

YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS Supersedes: 160.69-PW2 (815) Form 160.69-PW2 (116) WIRING DIAGRAM CONTRACTOR ORDER NO. JCI CONTRACT NO. JCI ORDER NO. YD (MOD A-C) WITH OPTIVIEW CONTROL CENTER FIELD CONTROL MODIFICATIONS PURCHASER JOB

More information

DC1000 (120VAC) Theory of Operations

DC1000 (120VAC) Theory of Operations DC1000 (120VAC) Theory of Operations The DC1000 is a dynamic DC treadmill designed for a wide range of applications that vary from the medical market to the sports performance market. This theory of operation

More information

Alemite FCS Fluid Control System

Alemite FCS Fluid Control System 343000 343000-1 Alemite FCS Fluid Control System Installation and Operation Guide 670996 TABLE OF CONTENTS DISCLAIMER... 3 BEFORE YOU BEGIN........................................................ 4 1.0

More information

Preset counters, electronic

Preset counters, electronic The Codix 716 / 717 can be used universally. These preset pulse, tachometers or preset timers with up to 2 presets can solve a wide variety of control and monitoring tasks in every application. With their

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 905U Wireless Solutions for Process Applications New Products... New Solutions The ELPRO 905U range of telemetry modules provide remote monitoring

More information

MODEL P-1400 OPERATION MANUAL. Four Loop Inputs, Two Vital Outputs, and One Vital Input

MODEL P-1400 OPERATION MANUAL. Four Loop Inputs, Two Vital Outputs, and One Vital Input Reno A & E 4655 Aircenter Circle Reno, NV 89502-5948 USA Telephone: (775) 826-2020 Facsimile: (775) 826-99 Website: www.renoae.com E-mail: contact@renoae.com MODEL P-400 OPERATION MANUAL Four Loop Inputs,

More information

Standard Configuration

Standard Configuration Radiant Technologies, Inc. 2835D Pan American Freeway NE Albuquerque, NM 87107 Tel: 505-842-8007 Fax: 505-842-0366 e-mail: radiant@ferrodevices.com 9 April, 2009 From: Scott P. Chapman Radiant Technologies,

More information

This document is not copyrighted. This document may be reproduced, in part or in whole, for any purpose. Ray Montagne - W7CIA

This document is not copyrighted. This document may be reproduced, in part or in whole, for any purpose. Ray Montagne - W7CIA 33-centimeter Kenwood TK-941 Conversion The following documentation is largely based on a set of separate documents that are already available on the internet. While performing a conversion of two Kenwood

More information

HOMANN DESIGNS. DigiSpeed. Instruction manual. Version 1.0. Copyright 2004 Homann Designs.

HOMANN DESIGNS. DigiSpeed. Instruction manual. Version 1.0. Copyright 2004 Homann Designs. HOMANN DESIGNS DigiSpeed Instruction manual Version 1.0 Copyright 2004 Homann Designs http://www.homanndesigns.com Table of Contents Introduction...3 Features...3 DigiSpeed Operation Description...5 Overview...5

More information

BATCHtrol II. Software Versions 8.x & 12.x Installation and Operating Manual. Kessler-Ellis Products Co. Description. Features.

BATCHtrol II. Software Versions 8.x & 12.x Installation and Operating Manual. Kessler-Ellis Products Co. Description. Features. BATCHtrol II Software Versions 8.x & 12.x Installation and Operating Manual Kessler-Ellis Products Co. escription The Batcher is a programmable, microprocessor based unit which provides batch control,

More information

THE APOLLO INTELLIGENT METER SERIES MODEL IMP INSTRUCTION MANUAL

THE APOLLO INTELLIGENT METER SERIES MODEL IMP INSTRUCTION MANUAL THE APOLLO INTELLIGENT METER SERIES MODEL IMP INSTRUCTION MANUAL INTRODUCTION The Intelligent Meter for Process Inputs (IMP) is another unit in our multi-purpose series of industrial control products that

More information

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224

T6+ Analog I/O Section. Installation booklet for part numbers: 5/4-80A-115 5/4-90A-115 5/4-80A /4-90A-1224 T and T+ are trade names of Trol Systems Inc. TSI reserves the right to make changes to the information contained in this manual without notice. publication /4A115MAN- rev:1 2001 TSI All rights reserved

More information

ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide

ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide ACT-3X Tachometer / Totalizer / Ratemeter User Manual and Reference Guide Rev 1.0, 021110 Safeguards and Precautions 1. Read and follow all instructions in this manual carefully, and retain this manual

More information

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application RWD44U Controller Installation and Commissioning Guide Document No. 129-408 Function RWD44U controllers are intended for HVAC and Refrigeration systems including Heat Pumps. They are suitable for 1-, 2-,

More information

ULTRA RAPID POWER QUALITY ANALYZER

ULTRA RAPID POWER QUALITY ANALYZER ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with

More information

Exercise 8. Troubleshooting a Radar Target Tracker EXERCISE OBJECTIVE

Exercise 8. Troubleshooting a Radar Target Tracker EXERCISE OBJECTIVE Exercise 8 Troubleshooting a Radar Target Tracker EXERCISE OBJECTIVE When you have completed this exercise, you will be able to apply an efficient troubleshooting procedure in order to locate instructor-inserted

More information

Operation. Section 4. Additional Information. Operation 4-1

Operation. Section 4. Additional Information. Operation 4-1 4-1 Section 4 WARNING: Allow only personnel with appropriate training and experience to operate or service the equipment. The use of untrained or inexperienced personnel to operate or service the equipment

More information

MODEL C-1000 SERIES OPERATION MANUAL

MODEL C-1000 SERIES OPERATION MANUAL Reno A & E Telephone: (775) 826-2020 4655 Aircenter Circle Facsimile: (775) 826-99 Reno, Nevada 89502 Internet: www.renoae.com USA e-mail: contact@renoae.com MODEL C-000 SERIES OPERATION MANUAL Built-in

More information

GCX. Guitar Audio Switcher OWNER S MANUAL

GCX. Guitar Audio Switcher OWNER S MANUAL GCX Guitar Audio Switcher OWNER S MANUAL Please visit our web site at: www.voodoolab.com Copyright 1998 by Digital Music Corporation. This publication is protected by copyright and all rights are reserved.

More information

RCMS460 and RCMS490 Series

RCMS460 and RCMS490 Series 4 T M RCMS460 and RCMS490 Series Digital Multi-Channel Ground Fault Monitor / Ground Fault Relay Grounded and High-Resistance Grounded AC/DC Systems Technical Bulletin NAE1042060 / 04.2013 BENDER Inc.

More information

Single Channel Loop Detector

Single Channel Loop Detector Single Channel Loop Detector Model LD120T Series The LD120T is a series of single channel inductive loop detectors. The use of microprocessor and surface mount technology enables a large number of functions

More information

DIGEM f 96 x 48 EK. Applications. Description

DIGEM f 96 x 48 EK. Applications. Description 3-349-002-03 1/7.98 Front panel dimensions: 96 x 48 mm LED display: red or green, 14 mm high Max. display range: 19 999 to + 32 765 Modular connectors for flexible use Simple adjustments at front panel

More information

Programmable Process Temperature Controller

Programmable Process Temperature Controller Programmable Process Temperature Controller www.maxitrol.com INSTALLATION GUIDE Warnings Inappropriate and/or improper installation, adjustment, alteration, service or maintenance can cause property damage,

More information

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE

8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE 8000 SERIES PRECISION MULTIMETER VERIFICATION AND ADJUSTMENT GUIDE TRANSMILLE LTD. Version 1.1 : Apr 2015 TABLE OF CONTENTS PREPARING FOR CALIBRATION... 4 INTRODUCTION... 4 CALIBRATION INTERVAL SELECTION...

More information

No mark Time-limit SPDT (1c) A Time-limit DPDT (2c) B Time-limit SPDT (1c), Instantaneous SPDT (1c) S DIN W48 H48mm.

No mark Time-limit SPDT (1c) A Time-limit DPDT (2c) B Time-limit SPDT (1c), Instantaneous SPDT (1c) S DIN W48 H48mm. Series Digital LCD Timer DIN W48 H48mm Features Power supply : 4-4VAC 5/6Hz, 4-4VDC universal Easy to switch Up/Down mode programmable output modes and timing ranges () Selectable function by front digital

More information

BandMaster V Manual. Installation

BandMaster V Manual. Installation BandMaster V Manual Installation Installing and configuring the BM-5 BandMaster V is a simple process. All the configuration process is done from the front panel. Installation and configuration steps are

More information

MegaPoints Servo Controller

MegaPoints Servo Controller MegaPoints Servo Controller Covers Servo Controller boards 1.8 onwards A flexible and modular device for controlling model railway points and semaphore signals using inexpensive R/C servos and relays.

More information

MODBUS MULTIPLEXING I/O SYSTEM CATALOG AND DESIGN GUIDE

MODBUS MULTIPLEXING I/O SYSTEM CATALOG AND DESIGN GUIDE MODMUX MODBUS MULTIPLEXING I/O SYSTEM CATALOG AND DESIGN GUIDE 22/02/2008 V19 P.O.Box 24 Stanfield 3613 SOUTH AFRICA Tel: 27 (031) 7028033 Fax: 27 (031) 7028041 Email: proconel@proconel.com Web: www.proconel.com

More information

Process/Strain Gauge Controller

Process/Strain Gauge Controller Process/Strain Gauge Controller Operator s Manual NEWPORT Electronics,Inc. http://www.newportus.com/i Counters Frequency Meters PID Controllers Clock/Timers Printers Process Meters On/Off Controllers Recorders

More information

The operator interface consists of an LCD and eight keys. Use the interface to program and operate the triggering controller.

The operator interface consists of an LCD and eight keys. Use the interface to program and operate the triggering controller. Nordson Corporation OPERATOR S CARD P/N 1017461C Sure Coat Triggering Controller Operator Interface WARNING: Allow only qualified personnel to perform the following tasks. Follow the safety instructions

More information

Megacode Receiver. Multi-Frequency Four Channel Receiver 10:05:12 STD MON OFF OFF OFF OFF. Doc # _00 Part # Released 15/05/14

Megacode Receiver. Multi-Frequency Four Channel Receiver 10:05:12 STD MON OFF OFF OFF OFF. Doc # _00 Part # Released 15/05/14 Megacode Receiver Multi-Frequency Four Channel Receiver 10:05:12 STD MON OFF OFF OFF OFF Doc # 160046_00 Part # 13367 Released 15/05/14 WARNING: It is vital for the safety of persons to follow all instructions.

More information

Please enter the identity code of your device here!

Please enter the identity code of your device here! Operating Instructions DULCOMETER D1C Part 2: Adjustment and Operation, Measured Variable Conductive Conductivity ProMinent D1C2-Leit.-001-GB Conductivity 100 µs/cm DULCOMETER STOP START Conductivity 100

More information

ISOMAG UNIQUE PID REGULATOR + MAG CONVERTER THE FRIENDLY MAG METER

ISOMAG UNIQUE PID REGULATOR + MAG CONVERTER THE FRIENDLY MAG METER UNIQUE PID REGULATOR MAG CONVERTER ISOMAG THE FRIENDLY MAG METER CONVERTER ML 212 Integrate PID Regulator N 1 output (0/4 20mA; frequency; pulses variable duty cycle ) for the actuator N 2 inputs (0 5/10V

More information

Model 805 PWM Proportional Valve / Solenoid Driver with Peak and Hold Control Modes

Model 805 PWM Proportional Valve / Solenoid Driver with Peak and Hold Control Modes Applied Processor and Measurement, Inc. FEATURES Model 805 PWM Proportional Valve / Solenoid Driver with Peak and Hold Control Modes Proportional Valve Driver with PWM output 3.5A max proportional control,

More information

The wireless alternative to expensive cabling...

The wireless alternative to expensive cabling... The wireless alternative to expensive cabling... ELPRO 105U ISO 9001 Certified New Products... New Solutions The ELPRO 105 range of telemetry modules provide remote monitoring and control by radio or twisted-pair

More information

BCV-1203 Barcode Verification System Users Guide Version 1.2

BCV-1203 Barcode Verification System Users Guide Version 1.2 BCV-1203 Barcode Verification System Users Guide Version 1.2 6 Clock Tower Place Suite 100 Maynard, MA 01754 USA Tel: (866) 837-1931 Tel: (978) 461-1140 FAX: (978) 461-1146 http://www.diamondt.com/ Liability

More information

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A. 3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2 (Code 7 71 071 to 7 71 083) INSTRUCTION MANUAL ( M 981 200 / 00 A ) (c) CIRCUTOR S.A. ----- MKT- MKT2 - ELECTRONIC METERS -------- M-981 200 --- Page Nº 2 3

More information

Industrial Modbus I/O Modules

Industrial Modbus I/O Modules Industrial Modbus I/O Modules Modbus I/O Modules Introduction & Features Digital Input / Output Modules Analog Input / Output Modules Modbus I/O Modules The Best Choice For Your SCADA Applications Introduction

More information

MICRO-C MIGHTY-1C MIGHTY-4C MIGHTY-5C OWNERS MANUAL

MICRO-C MIGHTY-1C MIGHTY-4C MIGHTY-5C OWNERS MANUAL MICRO-C MIGHTY-1C MIGHTY-4C MIGHTY-5C OWNERS MANUAL ELECTRO-NUMERICS, INC. CONTENTS SECTION NO: PAGE NO: 1. INTRODUCTION... 1 2. RECEIVING AND UNPACKING... 2 3. SAFETY CONSIDERATIONS... 2 4. CONNECTOR

More information

Monitoring Relays 3-Phase Active power Types DWB02, PWB02

Monitoring Relays 3-Phase Active power Types DWB02, PWB02 Monitoring Relays 3-hase Active power Types DWB02, WB02 DWB02 roduct Description DWB02 and WB02 are precise TRMS active power monitoring relays for 3- phase balanced systems. They can be used for monitoring

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

LBI-31807D. Mobile Communications MASTR II REPEATER CONTROL PANEL 19B234871P1. Maintenance Manual. Printed in U.S.A.

LBI-31807D. Mobile Communications MASTR II REPEATER CONTROL PANEL 19B234871P1. Maintenance Manual. Printed in U.S.A. D Mobile Communications MASTR II REPEATER CONTROL PANEL 19B234871P1 Maintenance Manual Printed in U.S.A. This page intentionally left blank 13 PARTS LIST 12 PARTS LIST LBI-31807 11 PARTS LIST 10 SCHEMATIC

More information