LCL VSC Converter for High-Power Applications

Size: px
Start display at page:

Download "LCL VSC Converter for High-Power Applications"

Transcription

1 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY LCL VSC Converter for High-Power Applications Dragan Jovcic, Senior Member, IEEE, Lu Zhang, Student Member, IEEE, and Masood Hajian, Member, IEEE Abstract This paper studies an inductor-capacitor-inductor (LCL) voltage-source converter (VSC) ac/dc converter concept which can be employed as high-power static converter. The converter is designed to have fault current near or below the rated value under the dc-side short circuits. This is very important for applications with HVDC and, in particular, with high-power dc transmission networks. This converter is composedofanac/dcinsulated-gate bipolar transistor-based VSC converter and a passive LCL circuit. A transformer is not required since LCL circuit can achieve voltage stepping. The converter parameters are designed to have optimal response during the faults, good controllability, and to minimize converter losses. A detailed model is developed on the PSCAD platform for a 500-MW test system. The simulation confirms capability to independently control active and reactive power and demonstrates favorable fault responses. The transient fault current peaks are not significant and can be overcome with slight overrating. Index Terms AC DC power conversion, dc grids, high-voltage dc transmission, HVDC converter, insulated-gate biploar transistor (IGBT) converter. I. INTRODUCTION T HE VSC HVDC represents a significant advance over the traditional thyristor HVDC. It generates fewer harmonics, enables controllable reactive power exchange, and even achieves operation with passive ac grids [1]. On the downside, VSC converters are vulnerable to dc faults. A dc voltage depression causes overcurrents in IGBTs, and system protection will trip IGBTs. Consequently, the converter becomes an uncontrollable diode bridge, discharging the ac grid into the dc fault. This is a serious problem with HVDC since: the VSC converter becomes uncontrollable; the fault current magnitude can reach extreme values; it is only limited by the impedance on the ac side; diodes have good overcurrent capability and typically may sustain 10-p.u. current for a 10-ms ( rating from manufacturer s sheets); however, the ac protection operating time is typically longer than 10 ms, and the current magnitude frequently exceeds 10 p.u.; the high fault current implies that ac-side voltage will also be depressed, and the fault is propagated to the ac system. Manuscript received November 04, 2011; revised August 02, 2012; accepted September 09, Date of publication December 13, 2012; date of current version December 19, This work was supported by the Engineering and Physical Sciences Research Council U.K. (EPSRC) under Grant EP/H010262/1. Paper no. TPWRD The authors are with the Electrical Engineering Department, University of Aberdeen, Aberdeen, AB24 3UE, U.K. ( d.jovcic@abdn.ac.uk; r02lz0@abdn.ac.uk; m.hajian@abdn.ac.uk). Color versions of one or more of the figures in this paper are available online at Digital Object Identifier /TPWRD A two-terminal VSC HVDC will clear the dc faults using ac CBs. The clearing time is limited by the speed of mechanical CBs to ms. In order to limit the fault current magnitude, series reactors are introduced on both ac and dc sides. Since the entire HVDC system (two VSC converters and dc line)is tripped for a dc fault, the recovery is slow and may take 5 10 s. The VSC converters are being extensively studied for multiterminal HVDC and dc grids [2]. They are suitable for paralleling, can change power direction by reversing only current, andtheyarenotvulnerabletoacgriddisturbances. Nevertheless,thedcfaultsbecomeamuchmoreserious issue with dc grids. It will not be acceptable to clear dc faults by opening all ac CBs. The dc grids will need dc CBs, practically on each dc cable [3]. However, it has proven very challenging to develop dc CBs that can interrupt extreme currents (of the order of 50 ka) in very fast time (of the order of a few milliseconds) [4]. The semiconductor dc CBs can be combined with mechanical switches to achieve good operation speed and low losses, and they are becoming commercially available [5]. However, they have limitations in fault current magnitude, and the operating time is extended when protecting long transmission systems. The alternative approachtomanagingdcgridfaultsistocontrol dc fault current at the VSC converters. The fault currents can only be supplied from ac grids through ac/dc converters since there will be no other power sources in dc grids. If the fault level in the entire dc grid is reduced, the performance demand on dc CBs becomes less stringent in terms of peak current and operating time. In addition, the impact of dc faults on the ac grid is reduced. One method to achieve dc fault control in VSC converters is to use full H-bridge multilevel converters [6]. This converter retains full control under ac faults and under dc faults. On the downside, a full H-bridge converter has four times the number of switches compared with an ordinary two-level VSC converter. Another method recently studied is the topology with an alternate arm multilevel converter [7]. Similarly, this topology suffers from an excessive number of switches. The LCL passive circuits have some interesting properties under faults, which have been explored for developing highpower dc/dc converters [8], [9]. An adequately designed LCL filter can automatically regulate the power in such a way that voltage depressionononesideleadstocurrentreductiononthe opposite side. This approach has three important advantages: 1) the power reduction is inherent and does not rely on any protection circuits; 2) the cost of LCL components is considerably lower than semiconductors; and 3) the converter control is retained even during the most severe faults. This paper studies an ac/dc converter topology that employs apassive LCL circuit. The goal of the research is to develop a high-power VSC ac/dc converter that inherently limits the fault current and retains full control under ac or dc faults. The con /$ IEEE

2 138 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013 (5) (6) where are - components of the PWM modulated control signal and is pole dc voltage. The basic circuit equations are Fig. 1. Proposed ac/dc converter. (7) (8) (9) verter should retain low cost/losses and good control in nominal operation. II. ANALYSIS OF CONVERTER TOPOLOGY A. Converter Topology The proposed three-phase ac/dc converter topology is shown in Fig. 1. The converter is comprised of a passive LCL circuit and a VSC converter. We assume a simple two-level three-phase sinusoidal pulsewidth modulation (SPWM)-controlled VSC, but any other topology (like Modular Multilevel Converter) is suitable. The point of connection with the grid (PCC) is at the voltage. Under normal conditions, we should have controllable and at and we should try to minimize converter current to reduce losses. Under faults, the converter can control current unless the gradient is very high. Under dc faults, we aim to have converter current within the rated values and the grid voltage closetotheratedvalue. B. LCL Circuit Equations and Controllability The LCL circuit is viewed as a power network with input connection ( and ) and output connection ( and ). The ac voltage vectors and are expressed as (1) (2) where are the voltage phasors, are the magnitudes, and are the phase angles of respective voltages. The subscripts and denote corresponding phasor components. We can position the coordinate frame arbitrarily and without loss of generality, is located on the -axis where,and 50 Hz. From (7) (9), we can express the capacitor voltage and the currents We will conveniently rewrite (11) (12) as where (10) (11) (12) (13) (14) (15) (16) (17) The above variables,and are conveniently introduced to study converter behavior. Ultimately, we need to determine the three parameters:,and, which can be obtained from the three equations (15) (17). The coefficient is a positive nonzero constant that is fully determined by the power transfer level as is explained later. Coefficients and are manipulated in the design stage, as will be discussed in Section III. Since,from (15) (17), we have (18) is control- In this topology, only the converter voltage lable, and the converter line-neutral rms voltage is (3) C. LCL Circuit for Case Replacing in (13) (14), we obtain (19) (4) (20)

3 JOVCIC et al.: LCL VSC CONVERTER FOR HIGH-POWER APPLICATIONS 139 Considering the normal operating conditions, there are several important conclusions from (19) (20) as follows. Grid current depends only on the converter voltage (not on the grid voltage). This implies very simple control and immunity to ac grid faults. The aforementioned conclusion also implies that the LCL circuit can achieve any stepping ratio and keep zero reactive power at and.wecan change the current sign and, therefore, change power direction (active and reactive) just by changing the sign of. As a consequence, we may not need transformers. Converter current depends only on the grid voltage. This current is on the axis and converter voltage is also on the axis (assuming a typical condition of ). This implies minimal current through the converter and low loss. Since depends only on the grid voltage, it cannot be controlled by the converter. This is a major disadvantage, since at partial loading, we will still have high current and losses in the converter. Unless the converter is always operated at full power, we cannot use case 0. Considering a dc fault condition, we have in (19) (20) and the following conclusions emerge: Grid current will be reduced to zero. This is a very much desired response since the ac grid sees an open circuit for dc faults. Converter current is not affected and remains at the rated value. This is a circulating reactive current between the converter and ac capacitor C. Therefore, the converter can sustain a dc fault indefinitely without damage. III. CONVERTER DESIGN The aforementioned case 0 shows excellent fault responses and controllability. The principal issue is the lack of direct control of converter current, which implies that relative converter losses will be high at low loading. In this section, we aim to reduce losses while retaining good fault responses by varying 0and 0. Dividing (23) with (24) and replacing (4) (5) (25) At rated power, we assume in (6) and replacing (25), we can obtain a quadratic equation that enables us to obtain for assumed and given,and (rated values). Once and are determined, we replace in (23) and calculate. B. Converter Operation Under Faults We assume that the converter is operating at full power just prior to the fault. We study inherent converter response and assume that the controller is inactive during faults ( and remain at rated values). In order to simplify the study and without loss of generality, we assume that the converter is designed for 0. From (24), we obtain the rated component of the converter voltage (26) where subscript denotes rated values. 1) Faults on : The converter currents under the extreme fault on can be obtained from (13) and (14) by replacing. Therefore, the magnitude of the grid fault current is (27) The magnitude of fault current relative to the rated current can be obtained by dividing (27) with (13) where the stepping ratio is introduced as (28) (29) A. Calculating In the general case be calculated as, the PCC complex power can (21) The singularity case of is not feasible in (28) since this would imply that in (23). This condition poses the following general limit on : (30) The magnitude of fault current is from (14): where is the number of phases ( in Fig. 1). Replacing (1) (2) in (21), we will have (22) (23) (24) (31) Dividing (31) with (14), the magnitude of fault current relative to the rated current will be (32) Equating (32) with 1, we obtain the condition where fault current exceeds the rated current

4 140 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013 for for (33) 2) Faults on DC Voltage : The converter currents under the most extreme pole-pole dc fault 0 can be obtained from (13) and (14) by replacing 0. The magnitude of grid fault current is (34) Dividing (34) with (13), the magnitude of fault current relative to the rated current will be (35) Equating (35) with 1, we obtain the condition where fault current exceeds the rated current Fig. 2. Ratio of fault current over rated current for faults on and on, versus the stepping ratio Traces labeled , traces labelled (36) The magnitude of converter fault current in (14) is (37) Dividing (37) with (14), the magnitude of the converter dc fault current relative to the rated current will be (38) Equating (38) with 1, we obtain the condition where fault current exceeds the rated current (39) The maximum value of (38) corresponds to the minimal rated current which occurs for. Figs. 2 and 3 show the aforementioned relative fault current magnitudes in (28), (32), (35), and (38) for a range of stepping ratios. Two different sets of values for and are shown in Figs. 2 and 3, with curves labeled a and b. Fig. 2 considers the case where the converter voltage is higher than the ac grid voltage. This case would be most commonly encountered with practical HVDC since high dc voltage is desired for long distance transmission. It is seen that the converter fault current will be close to or below the rated value for most and values. The worst case occurs with a stepping ratio close to 1 and very high and. In such cases, the fault current can approach 2 times the rated value, but this fault current can be readily controlled by the converter. The current on grid side also stays close to the rated value for or faults. Fig. 3 shows the case where converter voltage is lower than grid voltage 4). In this case, can only assume very low values since it is bounded by in (30). In practical HVDC systems, lower converter voltage may be adopted with monopolar cable dc systems where dc voltage is limited by the cable ratings. We can observe even more favorable fault Fig. 3. Ratio of fault current over rated current for faults on and on, versus the stepping ratio. Traces labelled , traces labelled responses than in Fig. 2, since, in most cases, the fault current magnitude stays below the rated values. Note that is very low in both cases and. As a general conclusion, lower values are best for fault responses but the fault responses are still good (below 2 p.u.) even for very high values for and. By restricting values for and, we can keep fault currents below rated values. C. Selection of and In this section, we study the influence of and on LCL parameter values and on converter losses. A 500-MW test system is selected and parameters are given in Table I. Fig. 4 shows the system variables considering the case with 0.9 and with varied. It is seen that and are reducing as is increasing, but is increasing. It is convenient that the peak capacitor voltage is also reducing as is in-

5 JOVCIC et al.: LCL VSC CONVERTER FOR HIGH-POWER APPLICATIONS 141 TABLE I TEST SYSTEM DATA (TWO-LEVEL CONVERTER) creasing. The max and min labels correspond to maximum active power of 500 MW and minimum active power of 0, assuming 100 MVAr. As is increasing, the current at minimal power is reducing which reduces partial loading losses. The rated current curve is a parabola and is simplified further with 0; from (14), it can be shown that the minimum occurs at. Therefore, the drawback of high and is that the losses at high power will increase. It is evident that in the region , both the maximum and minimum currents are reasonably low. The frequency graph shows the operating frequency ( 50 Hz), the global resonance,thefirst local resonance, and the second local resonance. A proximity to global resonance indicates poorly damped modes. The last two graphs show the magnitude of and for faults on and on. These graphs confirm the study in Fig. 2 but note that 100 MVAr in Fig. 4. D. Converter Losses In order to finalize the values for and, the test converter losses are calculated. The losses in this converter include: conduction losses and switching losses, for IGBT and diodes (inductor and capacitor losses are not considered). The losses are calculated as [10] (40) (41) where is the peak current through the switches, and is the switch test voltage given in the manufacturer s datasheets. The PWM modulation index and phase angle can be obtained from the simulation at a particular power level. All circuit variables at the 500-MW power level that are used in (40) (41) areshownintableii.thevaluesofon-stateresistance, Fig. 4. System variables as is varied, with 0.9. TABLE II VARIABLES FOR LOSS CALCULATION AT 500 MW threshold voltage, voltage and are taken from the manufacturer s sheets for IGBTs switches. Fig. 5 shows the converter losses with different, fixed, and considering three power levels (Full power 100%, 50%, and 20%). Note that case of at full power would be a benchmark value for comparison with a conventional 2-level HVDC VSC converter. At full power, as is increasing, the losses are increasing. When the converter operates at lower power levels, the relative losses are higher comparing with full power case. Nevertheless, we believe that the loss of 3% 4% at 50% power and 6% 7% at 20% power level would be acceptable. For comparison, Fig. 6 shows the losses when is varied with fixed at three power levels also. The final selection of parameters will depend on the operating

6 142 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013 Fig. 5. Total converter losses based on respective power level as is varied. Fig. 6. Total converter losses based on respective power level as is varied. Fig. 7. Controller for the ac/dc converter. regime. Placing more emphasize on high power operation, we finally selected parameters as. E. Summary Design Steps The converter design procedure is summarized as follows. 1) Given data are,and. 2) Assume values for and, by observing the allowed range. 3) and are calculated using (25). 4) Calculating using (23). 5) Determine inductance, and capacitance C by using Fig. 8. Converter operation in steady state. (43) (42) (44)

7 JOVCIC et al.: LCL VSC CONVERTER FOR HIGH-POWER APPLICATIONS 143 Fig. 9. Converter response after a 0.1-s three-phase fault on. Fig. 10. Converter response after a dc fault on. 6) Plot graphs in Fig. 4 to determine the converter-rated currents and fault currents. 7) Select switches and switching frequency and using (40) (41), calculate losses for given parameters. 8) Repeat the above steps for different and until optimum values are selected. IV. PSCAD SIMULATION A. Controller System Design In order to demonstrate the feasibility of this topology, a simple controller is designed based on (13) and (14). This is

8 144 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 1, JANUARY 2013 a PQ controller with inner current control loops as shown in Fig. 7. B. PSCAD Simulation The PSCAD model includes detailed switch models and all parasitic resistances. Fig. 8 shows the PSCAD simulation in steady-state operation. We simulate the positive and negative step on active power at 0.85 s and 1.05 s, and positive and negative step on reactive power at 1.2 and 1.4 s. The converter controllability and transient stability are confirmed. In this figure, we can observe that the magnitude of is reduced as active power is reducing, which is a consequence of selecting 0. Fig. 9 shows the PSCAD simulation of the worst case threephase 0.1-s fault on at PCC. It is seen that the currents and only marginally transiently increase during the fault. There is no overvoltage on the LCL circuit capacitor. The converter normally operates during the fault and the recovery is fast. Fig. 10 shows the worst case pole-pole fault at the dc capacitors 0). It is observed that the converter current settles at close to the rated value as predicted in theoretical analysis. There is, however, a transient overcurrent which cannot be predicted with phasor modeling. The magnitude and duration of this overcurrent are not significant (2.7-p.u. negative peak and fully decaying after 700 ms) and may require only modest diode overrating. Alternatively, a small dc-side inductor can remove this transient peak. The voltage at PCC stays close to the rated value, and the dc fault is not transferred to the ac side. The small depression in is the result of reactive power circulation. The grid current is close to the rated value but active power is not drawn from the grid. [2] G.Asplund,B.Jacobson,B.Berggren,andK.Lindén, Continental overlay HVDC-grid, in Proc, CIGRÉ Session, Paris, France, [3] L. Tang and B. T. Ooi, Protection of VSC-multi-terminal HVDC against DC faults, in Proc. IEEE 33rd Annu. Power Electron. Specialists Conf., Jun. 2002, vol. 2, pp [4] D. Van Hertem, M. Ghandhari, J. B. Curis, O. Despouys, and A. Marzin, Protection requirements for a multi-terminal meshed DC grid, presented at the CIGRÉ Bologna Symp., Bologna, Italy, 2011, paper 282. [5] J. Häfner and B. Jacobson, Proactive hybrid HVDC breakers A key innovation for reliable HVDC grids, in Proc., CIGRÉ 2011 Bologna Symp., Bologna, Italy, paper 264. [6] C. C. Davidson and D. R. Trainer, Innovative concepts for hybrid multi-level converters for HVDC power transmission, in Proc. 9th Inst. Eng. Technol. Int. Conf. AC DC Power Transm., London, U.K., Oct. 2010, pp [7]M.M.C.Merlin,T.C.Green,P.D.Mitcheson,D.R.Trainer,D. R. Critchley, and R. W. Crookes, A new hybrid multi-level voltagesource converter with DC fault blocking capability, in Proc. 9th Inst. Eng. Technol. Int. Conf. AC DC Power Transm., London, U.K., Oct. 2010, pp [8] D. Jovcic, Bidirectional high power DC transformer, IEEE Trans. Power Del., vol. 24, no. 4, pp , Oct [9] D. Jovcic and B. T. Ooi, Theoretical aspects of fault isolation on highpower DC lines using resonant DC/DC converters, Proc. Inst. Eng. Technol. Gen., Transm. Distrib., vol. 5, no. 2, pp , Feb [10] B. Backlund, R. Schnell, U. Schlapbach, R. Fischer, and E. Tsyplakov, Applying IGBTs, Apr. 2009, Tech. Note ABB Switzerland Ltd., 5SYA Dragan Jovcic (S 97 M 00 SM 06) received the D.Eng. degree in control engineering from the University of Belgrade, Belgrade, Serbia, in 1993 and the Ph.D. degree in electrical engineering from the University of Auckland, Auckland, New Zealand, in Currently, he is a Professor with the University of Aberdeen, Aberdeen, U.K., where he has been since He was also a Lecturer with the University of Ulster,Ulster,U.K.,from2000to2004andasaDesign Engineer in the New Zealand power industry from 1999 to His research interests are flexible ac transmission systems, HVDC, as well as integration of renewable sources and control systems. V. CONCLUSION A novel LCL VSC converter concept is presented which is recommended for use with HVDC transmission. Analytical modeling concludes that this topology has very favorable responses for either ac or dc faults. The fault currents will be below the rated values for a very wide range of design parameters. A model of the 500-MW 220-kV ac- to 600-kV dc converter is developed in PSCAD/EMTDC software and tested for normal operation and faults. The simulation confirms the ability to control active and reactive power independently. The dc-line and ac-line faults are tested, and responses indicate that currents are below rated values. The calculation of losses concludes that the converter has comparable efficiency to conventional VSC ac/dc converters. REFERENCES [1] G. Asplund, K. Eriksson, and K. Svensson, DC transmission based on voltage source converters, CIGRE SC14 Colloq. South Africa, Lu Zhang (S 11) received the B.Sc. and M.Sc. degrees in control engineering from the Harbin Institute of Technology, Harbin, China, in 2006 and 2008, respectively, and is currently pursuing the Ph.D. degree in electrical engineering at the University of Aberdeen, Aberdeen, U.K. His research interests are in control engineering and power electronics. Masood Hajian (M 10) received the B.Sc. degree in control engineering from Sharif University of Technology, Tehran, Iran, and the M.Sc. and Ph.D. degrees in power electronics from Isfahan University of Technology, Isfahan, Iran. Currently, he is a Research Fellow at the University of Aberdeen, Aberdeen, U.K.Hismainresearch interests include power electronics, electrical machines, nonlinear control, and variable-speed electrical drives.

DC Transmission Grid with Low Speed Protection using Mechanical DC Circuit Breakers

DC Transmission Grid with Low Speed Protection using Mechanical DC Circuit Breakers 1 DC Transmission Grid with Low Speed Protection using Mechanical DC Circuit Breakers M. Hajian, Member, IEEE, L. Zhang, Student Member, IEEE, and D. Jovcic, Senior Member, IEEE Abstract--This paper introduces

More information

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage

More information

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems A New Network Proposal for Fault-Tolerant HVDC Transmission Systems Malothu Malliswari 1, M. Srinu 2 1 PG Scholar, Anurag Engineering College 2 Assistant Professor, Anurag Engineering College Abstract:

More information

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling

A cost effective hybrid HVDC transmission system with high performance in DC line fault handling 2, rue d Artois, F-758 PARIS B4-7 CIGRE 28 http : //www.cigre.org A cost effective hybrid HVDC transmission system with high performance in DC line fault handling Mats Andersson, Xiaobo ang and ing-jiang

More information

WITH THE increasing size of offshore power parks and

WITH THE increasing size of offshore power parks and IEEE TRANSACTIONS ON POWER DELIVERY 1 Multiport High-Power LCL DC Hub for Use in DC Transmission Grids Dragan Jovcic, Senior Member, IEEE, and Weixing Lin, Member, IEEE Abstract This paper proposes an

More information

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults

Partial Power Operation of Multi-level Modular Converters under Subsystem Faults Partial Power Operation of Multi-level Modular Converters under Subsystem Faults Philip Clemow Email: philipclemow@imperialacuk Timothy C Green Email: tgreen@imperialacuk Michael M C Merlin Email: michaelmerlin7@imperialacuk

More information

Using Fault Current Limiting mode of a Hybrid DC Breaker

Using Fault Current Limiting mode of a Hybrid DC Breaker Using Fault Current Limiting mode of a Hybrid DC Breaker M. Wang, W. Leterme, J. Beerten, D. Van Hertem Department of Electrical Engineering (ESAT), Division ELECTA & Energyville, University of Leuven

More information

ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER

ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER ZERO PHASE SEQUENCE VOLTAGE INJECTION FOR THE ALTERNATE ARM CONVERTER F J Moreno*, M M C Merlin, D R Trainer*, T C Green, K J Dyke* *Alstom Grid, St Leonards Ave, Stafford, ST17 4LX Imperial College, South

More information

Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults

Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults 216 International High Voltage Direct Current Conference (HVDC 216) Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults Gen Li 1, Jun Liang 1, Carlos E Ugalde-Loo 1, Paul Coventry

More information

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System

Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System Improvement of Rotor Angle Stability and Dynamic Performance of AC/DC Interconnected Transmission System 1 Ramesh Gantha 1, Rasool Ahemmed 2 1 eee Kl University, India 2 AsstProfessor, EEE KL University,

More information

Alternate Arm Converter Operation of the Modular Multilevel Converter

Alternate Arm Converter Operation of the Modular Multilevel Converter Alternate Arm Converter Operation of the Modular Multilevel Converter M.M.C. Merlin, P.D. Judge, T.C. Green, P.D. Mitcheson Imperial College London London, UK michael.merlin@imperial.ac.uk Abstract A new

More information

Improving Passive Filter Compensation Performance With Active Techniques

Improving Passive Filter Compensation Performance With Active Techniques IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Copyright 2012 IEEE. Paper presented at 2012 IEEE Workshop on Complexity in Engineering 11 June, Aachen,

Copyright 2012 IEEE. Paper presented at 2012 IEEE Workshop on Complexity in Engineering 11 June, Aachen, Copyright 22 IEEE Paper presented at 22 IEEE Workshop on Complexity in Engineering June, Aachen, Germany 22 This material is posted here with the permission of the IEEE. Such permission of the IEEE does

More information

IN THE high power isolated dc/dc applications, full bridge

IN THE high power isolated dc/dc applications, full bridge 354 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 21, NO. 2, MARCH 2006 A Novel Zero-Current-Transition Full Bridge DC/DC Converter Junming Zhang, Xiaogao Xie, Xinke Wu, Guoliang Wu, and Zhaoming Qian,

More information

Transient system behaviour under DC fault conditions in meshed HVDC system

Transient system behaviour under DC fault conditions in meshed HVDC system Transient system behaviour under DC fault conditions in meshed HVDC system A. Yanushkevich, N.A. Belda Abstract-- Nowadays, development of multi-terminal HVDC systems is driven by aim to connect remote

More information

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter 1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560

More information

HARMONIC contamination, due to the increment of nonlinear

HARMONIC contamination, due to the increment of nonlinear 612 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 A Series Active Power Filter Based on a Sinusoidal Current-Controlled Voltage-Source Inverter Juan W. Dixon, Senior Member,

More information

Topology Assessment for 3+3 Terminal Offshore DC Grid considering DC fault management

Topology Assessment for 3+3 Terminal Offshore DC Grid considering DC fault management Topology Assessment for 3+3 Terminal Offshore DC Grid considering DC fault management Journal: IET Generation, Transmission & Distribution Manuscript ID: GTD-2013-0838.R1 Manuscript Type: Research Paper

More information

U I. HVDC Control. LCC Reactive power characteristics

U I. HVDC Control. LCC Reactive power characteristics Lecture 29 HVDC Control Series Compensation 1 Fall 2017 LCC Reactive power characteristics LCC HVDC Reactive compensation by switched filters and shunt capacitor banks Operates at lagging power factor

More information

Control and protection strategy for MMC MTDC system under converter-side AC fault during converter blocking failure

Control and protection strategy for MMC MTDC system under converter-side AC fault during converter blocking failure J. Mod. Power Syst. Clean Energy (4) (3):7 8 DOI.7/s4565-4-64- Control and protection strategy for MMC MT system under converter-side AC fault during converter blocking failure Puyu WANG, Xiao-Ping ZHANG

More information

Voltage Source Converter Modelling

Voltage Source Converter Modelling Voltage Source Converter Modelling Introduction The AC/DC converters in Ipsa represent either voltage source converters (VSC) or line commutated converters (LCC). A single converter component is used to

More information

High Voltage DC Transmission 2

High Voltage DC Transmission 2 High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion

More information

Internal DC Short-Circuit Fault Analysis and Protection for VSI of Wind Power Generation Systems

Internal DC Short-Circuit Fault Analysis and Protection for VSI of Wind Power Generation Systems April 2014, Volume 5, No.2 International Journal of Chemical and Environmental Engineering Internal DC Short-Circuit Fault Analysis and Protection for VSI of Wind Power Generation Systems M.Radmehr a,*,

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012 Aalborg Universitet Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin Publication date: 2012 Document Version Publisher's PDF, also known as Version of record Link to publication from

More information

Impact of VSC Converter Topology on Fault Characteristics in HVDC Transmission Systems

Impact of VSC Converter Topology on Fault Characteristics in HVDC Transmission Systems Impact of VSC Converter Topology on Fault Characteristics in HVDC Transmission Systems Dimitrios Tzelepis, Sul Ademi, Dimitrios Vozikis, Adam Dyśko, Sankara Subramanian, Hengxu Ha University of Strathclyde,

More information

Direct Harmonic Analysis of the Voltage Source Converter

Direct Harmonic Analysis of the Voltage Source Converter 1034 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 3, JULY 2003 Direct Harmonic Analysis of the Voltage Source Converter Peter W. Lehn, Member, IEEE Abstract An analytic technique is presented for

More information

29 Level H- Bridge VSC for HVDC Application

29 Level H- Bridge VSC for HVDC Application 29 Level H- Bridge VSC for HVDC Application Syamdev.C.S 1, Asha Anu Kurian 2 PG Scholar, SAINTGITS College of Engineering, Kottayam, Kerala, India 1 Assistant Professor, SAINTGITS College of Engineering,

More information

Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids

Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids Sequential Tripping of Hybrid DC Circuit Breakers to Enhance the Fault Interruption Capability in Multi-Terminal DC Grids J. SUN, Y. SONG, M. SAEEDIFARD, and A. P. MELIOPOULOS Georgia Institute of Technology

More information

A NEW APPROACH FOR MODELING COMPLEX POWER SYSTEM COMPONENTS IN DIFFERENT SIMULATION TOOLS

A NEW APPROACH FOR MODELING COMPLEX POWER SYSTEM COMPONENTS IN DIFFERENT SIMULATION TOOLS A NEW APPROACH FOR MODELING COMPLEX POWER SYSTEM COMPONENTS IN DIFFERENT SIMULATION TOOLS Per-Erik Bjorklund Jiuping Pan Chengyan Yue Kailash Srivastava ABB Power Systems ABB Corporate Research ABB Corporate

More information

Assessment of Saturable Reactor Replacement Options

Assessment of Saturable Reactor Replacement Options Assessment of Saturable Reactor Replacement Options D.T.A Kho, K.S. Smith Abstract-- The performance of the dynamic reactive power compensation provided by the existing variable static compensation (STC)

More information

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )

Power System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light ) 21, rue d Artois, F-75008 PARIS SECURITY AND RELIABILITY OF ELECTRIC POWER SYSTEMS http : //www.cigre.org CIGRÉ Regional Meeting June 18-20, 2007, Tallinn, Estonia Power System Reliability and Transfer

More information

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION International Journal of Electrical, Electronics and Data Communication, ISSN: 23284 Volume, Issue-4, April14 INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION 1 V.S.VENKATESAN, 2 P.CHANDHRA

More information

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy

Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Multiconverter Unified Power-Quality Conditioning System: MC-UPQC T.Charan Singh, L.Kishore, T.Sripal Reddy Abstract This paper presents a new unified power-quality conditioning system (MC-UPQC), capable

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

PHASE locked loops (PLL) with all ac/dc converters take

PHASE locked loops (PLL) with all ac/dc converters take 1116 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 18, NO. 3, AUGUST 2003 Phase Locked Loop System for FACTS Dragan Jovcic, Member, IEEE Abstract This research addresses the special requirements of phase locked

More information

ISSN Vol.07,Issue.08, July-2015, Pages:

ISSN Vol.07,Issue.08, July-2015, Pages: ISSN 2348 2370 Vol.07,Issue.08, July-2015, Pages:1373-1379 www.ijatir.org Reactive Power Control in Multi-group IGBT Based Current-Sourced HVDC Interconnections K. USHA RANI 1, DHANNANI SURESH 2, J. NANDANA

More information

SEVERAL static compensators (STATCOM s) based on

SEVERAL static compensators (STATCOM s) based on 1118 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 35, NO. 5, SEPTEMBER/OCTOBER 1999 A New Type of STATCOM Based on Cascading Voltage-Source Inverters with Phase-Shifted Unipolar SPWM Yiqiao Liang,

More information

SERIES ACTIVE power filters have proved to be an interesting

SERIES ACTIVE power filters have proved to be an interesting 928 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 5, SEPTEMBER 1999 A Fault Protection Scheme for Series Active Power Filters Luis A. Morán, Senior Member, IEEE, Ivar Pastorini, Juan Dixon, Senior

More information

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator 66 JOURNAL OF ELECTRONIC SCIENCE AND TECHNOLOGY, VOL. 11, NO. 1, MARCH 213 Hybrid Simulation of ±5 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator Lei Chen, Kan-Jun

More information

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES Int. J. Engg. Res. & Sci. & Tech. 2015 xxxxxxxxxxxxxxxxxxxxxxxx, 2015 Research Paper MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES N Lakshmipriya 1* and L

More information

Testing Firing Pulse Controls for a VSC Based HVDC Scheme with a Real Time Timestep < 3 µs

Testing Firing Pulse Controls for a VSC Based HVDC Scheme with a Real Time Timestep < 3 µs Testing Firing Pulse Controls for a VSC Based HVDC Scheme with a Real Time Timestep < 3 µs P.A. Forsyth, T.L. Maguire, D. Shearer, D. Rydmell T I. ABSTRACT Under Sea DC Cable HE paper deals with the difficulties

More information

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

More information

A LC PARALLEL RESONANT CONVERTER FOR GRID-CONNECTED RENEWABLE ENERGY SOURCES

A LC PARALLEL RESONANT CONVERTER FOR GRID-CONNECTED RENEWABLE ENERGY SOURCES A LC PARALLEL RESONANT CONVERTER FOR GRID-CONNECTED RENEWABLE ENERGY SOURCES #1PATAN RIYASATH KHAN, PG STUDENT #2Mr. E.RAMAKRISHNA, Associate Professor & HOD #3Mr.S.SHAMSHUL HAQ,Associate professor & coordinator

More information

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013 A Statcom-Control Scheme for Power Quality Improvement of Grid Connected Wind Energy System B.T.RAMAKRISHNARAO*, B.ESWARARAO**, L.NARENDRA**, K.PRAVALLIKA** * Associate.Professor, Dept.of EEE, Lendi Inst.Of

More information

Robustness Evaluation of Fast Breaker Failure Backup Protection in Bipolar HVDC Grids

Robustness Evaluation of Fast Breaker Failure Backup Protection in Bipolar HVDC Grids Robustness Evaluation of Fast Breaker Failure Backup Protection in Bipolar HVDC Grids M. Wang, W. Leterme, J. Beerten, D. Van Hertem Department of Electrical Engineering (ESAT), Division ELECTA & Energyville,

More information

Importance of DC-DC Transformation in Grids of the Future

Importance of DC-DC Transformation in Grids of the Future 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Importance of DC-DC Transformation in Grids of the Future L. BARTHOLD 1, D. WOODFORD

More information

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage

A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage 21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant

More information

Intelligence Controller for STATCOM Using Cascaded Multilevel Inverter

Intelligence Controller for STATCOM Using Cascaded Multilevel Inverter Journal of Engineering Science and Technology Review 3 (1) (2010) 65-69 Research Article JOURNAL OF Engineering Science and Technology Review www.jestr.org Intelligence Controller for STATCOM Using Cascaded

More information

Fault Current Characterisation in VSC-based HVDC Systems

Fault Current Characterisation in VSC-based HVDC Systems Fault Current Characterisation in VSC-based HVDC Systems Sul Ademi, Dimitrios Tzelepis, Adam Dyśko, Sankara Subramanian, Hengxu Ha University of Strathclyde, Glasgow, UK, sul.ademi@strath.ac.uk, dimitrios.tzelepis@strath.ac.uk,

More information

Operating DC Circuit Breakers with MMC

Operating DC Circuit Breakers with MMC > REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 Operating DC Circuit Breakers with MMC Oliver Cwikowski, Alan Wood, Member, IEEE, Allan Miller, Senior Member,

More information

MMC based D-STATCOM for Different Loading Conditions

MMC based D-STATCOM for Different Loading Conditions International Journal of Engineering Research And Management (IJERM) ISSN : 2349-2058, Volume-02, Issue-12, December 2015 MMC based D-STATCOM for Different Loading Conditions D.Satish Kumar, Geetanjali

More information

H-BRIDGE system used in high power dc dc conversion

H-BRIDGE system used in high power dc dc conversion IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 1, JANUARY 2008 353 Quasi Current Mode Control for the Phase-Shifted Series Resonant Converter Yan Lu, K. W. Eric Cheng, Senior Member, IEEE, and S.

More information

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation http: //www.cigre.org CIGRÉ A3/B4-009 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 Stress Analysis of HVDC Circuit Breakers for Defining Test

More information

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM Ehsan Behrouzian 1, Massimo Bongiorno 1, Hector Zelaya De La Parra 1,2 1 CHALMERS UNIVERSITY OF TECHNOLOGY SE-412

More information

THE ALTERNATE ARM CONVERTER: A NEW HYBRID MULTILEVEL CONVERTER WITH DC- FAULT BLOCKING CAPABILITY

THE ALTERNATE ARM CONVERTER: A NEW HYBRID MULTILEVEL CONVERTER WITH DC- FAULT BLOCKING CAPABILITY THE ALTERNATE ARM CONVERTER: A NEW HYBRID MULTILEVEL CONVERTER WITH DC- FAULT BLOCKING CAPABILITY Miss.Yashoda.R.Perkar 1, Mr.Santhosh Kumar Rayarao 2 1 P.G. Student, 2 Asst. Prof., Department of Electrical

More information

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India) ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin

More information

DC current interruption tests with HV mechanical DC circuit breaker

DC current interruption tests with HV mechanical DC circuit breaker http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit

More information

RECENTLY, the harmonics current in a power grid can

RECENTLY, the harmonics current in a power grid can IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 23, NO. 2, MARCH 2008 715 A Novel Three-Phase PFC Rectifier Using a Harmonic Current Injection Method Jun-Ichi Itoh, Member, IEEE, and Itsuki Ashida Abstract

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT Harshkumar Sharma 1, Gajendra Patel 2 1 PG Scholar, Electrical Department, SPCE, Visnagar, Gujarat, India 2 Assistant

More information

NOWADAYS, it is not enough to increase the power

NOWADAYS, it is not enough to increase the power IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 44, NO. 5, OCTOBER 1997 597 An Integrated Battery Charger/Discharger with Power-Factor Correction Carlos Aguilar, Student Member, IEEE, Francisco Canales,

More information

IEEE Transactions On Circuits And Systems Ii: Express Briefs, 2007, v. 54 n. 12, p

IEEE Transactions On Circuits And Systems Ii: Express Briefs, 2007, v. 54 n. 12, p Title A new switched-capacitor boost-multilevel inverter using partial charging Author(s) Chan, MSW; Chau, KT Citation IEEE Transactions On Circuits And Systems Ii: Express Briefs, 2007, v. 54 n. 12, p.

More information

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission

Introduction to HVDC Transmission. High Voltage Direct Current (HVDC) Transmission Lecture 29 Introduction to HVDC Transmission Series Compensation 1 Fall 2003 High Voltage Direct Current (HVDC) Transmission Update to Edison s Vision AC Power Generation at Relatively Lower Voltage» Step

More information

IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM

IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM M. JYOTHSNA M.Tech EPS KSRM COLLEGE OF ENGINEERING, Affiliated to JNTUA, Kadapa,

More information

Standards Developments for Fault Current Limiters

Standards Developments for Fault Current Limiters tandards Developments for Fault Current Limiters Dr. Michael Mischa teurer steurer@caps.fsu.edu Center for Advanced Power ystems (CAP) Florida tate University 2000 Levy Avenue, Building A, Tallahassee,

More information

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM

DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM DIGITAL SIMULATION OF MULTILEVEL INVERTER BASED STATCOM G.SUNDAR, S.RAMAREDDY Research Scholar, Bharath University Chenna Professor Jerusalam College of Engg. Chennai ABSTRACT This paper deals with simulation

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

A Series-Connected Multilevel Inverter Topology for Squirrel-Cage Induction Motor Drive

A Series-Connected Multilevel Inverter Topology for Squirrel-Cage Induction Motor Drive Vol.2, Issue.3, May-June 2012 pp-1028-1033 ISSN: 2249-6645 A Series-Connected Multilevel Inverter Topology for Squirrel-Cage Induction Motor Drive B. SUSHMITHA M. tech Scholar, Power Electronics & Electrical

More information

Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation

Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation Improvement Voltage Sag And Swell Under Various Abnormal Condition Using Series Compensation Sumit Borakhade #1, Sumit Dabhade *2, Pravin Nagrale #3 # Department of Electrical Engineering, DMIETR Wardha.

More information

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331 PP 33-40 www.iosrjournals.org An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

DUAL BRIDGE LLC RESONANT CONVERTER WITH FREQUENCY ADAPTIVE PHASE-SHIFT MODULATION CONTROL FOR WIDE VOLTAGE GAIN RANGE

DUAL BRIDGE LLC RESONANT CONVERTER WITH FREQUENCY ADAPTIVE PHASE-SHIFT MODULATION CONTROL FOR WIDE VOLTAGE GAIN RANGE DUAL BRIDGE LLC RESONANT CONVERTER WITH FREQUENCY ADAPTIVE PHASE-SHIFT MODULATION CONTROL FOR WIDE VOLTAGE GAIN RANGE S M SHOWYBUL ISLAM SHAKIB ELECTRICAL ENGINEERING UNIVERSITI OF MALAYA KUALA LUMPUR,

More information

Power Flow Control/Limiting Short Circuit Current Using TCSC

Power Flow Control/Limiting Short Circuit Current Using TCSC Power Flow Control/Limiting Short Circuit Current Using TCSC Gannavarapu Akhilesh 1 * D.Raju 2 1. ACTS, JNTU-H, PO box 500035, Hyderabad, Andhra Pradesh, India 2. M.Tech (NIT Nagpur), Hyderabad, Andhra

More information

M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore

M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore Implementation of Five Level Buck Converter for High Voltage Application Manu.N.R 1, V.Nattarasu 2 1 M.Tech in Industrial Electronics, SJCE, Mysore, 2 Associate Professor, Dept. of ECE, SJCE, Mysore Abstract-

More information

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer C.GOPI*, M.KISHOR** *(Department. of Electrical and Electronics Engineering, SVPCET, Puttur)

More information

Reactive Power Compensation Technologies: State-of-the-Art Review

Reactive Power Compensation Technologies: State-of-the-Art Review Reactive Power Compensation Technologies: State-of-the-Art Review JUAN DIXON, SENIOR MEMBER, IEEE, LUIS MORÁN, FELLOW, IEEE, JOSÉ RODRÍGUEZ, SENIOR MEMBER, IEEE, AND RICARDO DOMKE Invited Paper This paper

More information

The Impact of Superconducting Fault Current Limiter Locations on Voltage Sag in Power Distribution System

The Impact of Superconducting Fault Current Limiter Locations on Voltage Sag in Power Distribution System Amirkabir University of Technology (Tehran Polytechnic) Vol. 47, No. 2, Fall 215, pp. 49-6 Amirkabir International Journal of Science& Research )AIJ-EEE) The Impact of Superconducting Fault Current Limiter

More information

ISSN Vol.03,Issue.11, December-2015, Pages:

ISSN Vol.03,Issue.11, December-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.11, December-2015, Pages:2020-2026 Power Quality Improvement using BESS Based Dynamic Voltage Restorer B. ABHINETHRI 1, K. SABITHA 2 1 PG Scholar, Dr. K.V. Subba

More information

A Comparative Study of Different Topologies of Multilevel Inverters

A Comparative Study of Different Topologies of Multilevel Inverters A Comparative Study of Different Topologies of Multilevel Inverters Jainy Bhatnagar 1, Vikramaditya Dave 2 1 Department of Electrical Engineering, CTAE (India) 2 Department of Electrical Engineering, CTAE

More information

Grounded HVDC Grid Line Fault Protection Using Rate of Change of Voltage and Hybrid DC Breakers. Jeremy Sneath. The University of Manitoba

Grounded HVDC Grid Line Fault Protection Using Rate of Change of Voltage and Hybrid DC Breakers. Jeremy Sneath. The University of Manitoba Grounded HVDC Grid Line Fault Protection Using Rate of Change of Voltage and Hybrid DC Breakers By Jeremy Sneath A thesis submitted to the Faculty of Graduate Studies of The University of Manitoba In partial

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Copyright 2010 IEEE. Reprinted from: IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 25, NO. 2, MAY 2010

Copyright 2010 IEEE. Reprinted from: IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 25, NO. 2, MAY 2010 Copyright 2010 IEEE. Reprinted from: IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 25, NO. 2, MAY 2010 This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 Introduction Power semiconductor devices constitute the heart of the modern power electronics, and are being extensively used in power electronic converters in the form of a

More information

PRECISION SIMULATION OF PWM CONTROLLERS

PRECISION SIMULATION OF PWM CONTROLLERS PRECISION SIMULATION OF PWM CONTROLLERS G.D. Irwin D.A. Woodford A. Gole Manitoba HVDC Research Centre Inc. Dept. of Elect. and Computer Eng. 4-69 Pembina Highway, University of Manitoba Winnipeg, Manitoba,

More information

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering

More information

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

THE demand for high-voltage high-power inverters is

THE demand for high-voltage high-power inverters is 922 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 62, NO. 2, FEBRUARY 2015 A Single-Phase Cascaded Multilevel Inverter Based on a New Basic Unit With Reduced Number of Power Switches Ebrahim Babaei,

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online): 2321-0613 Control and Analysis of VSC based High Voltage DC Transmission Tripti Shahi 1 K.P.Singh

More information

A Double ZVS-PWM Active-Clamping Forward Converter: Analysis, Design, and Experimentation

A Double ZVS-PWM Active-Clamping Forward Converter: Analysis, Design, and Experimentation IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 6, NOVEMBER 2001 745 A Double ZVS-PWM Active-Clamping Forward Converter: Analysis, Design, and Experimentation René Torrico-Bascopé, Member, IEEE, and

More information

ANEW, simple and low cost scheme to reduce transformer

ANEW, simple and low cost scheme to reduce transformer 950 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 A Sequential Phase Energization Technique for Transformer Inrush Current Reduction Part II: Theoretical Analysis and Design Guide Wilsun

More information

Review of HVDC Circuit Breakers Topologies.

Review of HVDC Circuit Breakers Topologies. IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 12, Issue 3 Ver. II (May June 2017), PP 109-117 www.iosrjournals.org Review of HVDC Circuit

More information

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS Chapter 1 : Power Electronics Devices, Drivers, Applications, and Passive theinnatdunvilla.com - Google D Download Power Electronics: Devices, Drivers and Applications By B.W. Williams - Provides a wide

More information